Johnson Controls YXV SERIES, 20 SEER SERIES, AL21 SERIES, AC21 SERIES Installation Manual

INSTALLATION MANUAL
R-410A VARIABLE CAPACITY OUTDOOR SPLIT-SYSTEM AIR CONDITIONING
MODELS: 20 SEER YXV, AC21, AL21 SERIES
2 – 5 TONS – 1 PHASE
LIST OF SECTIONS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
LIST OF FIGURES
Typical Installation Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Alternative Installation Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Installation of Vapor Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Outdoor Unit Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Typical Communicating Field Wiring (Air Handler / Furnace) . . . . . . .7
Demand Response Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
SYSTEM OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
OUTDOOR SCREEN OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . 10
INSTRUCTING THE OWNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
CHARGING CHARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
System Charging Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Main Outdoor Control and Display . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Outdoor Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2 Ton Inverter Drive LED Location . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3 & 4 Ton Inverter Drive LED Location . . . . . . . . . . . . . . . . . . . . . . . 19
5 Ton Inverter Drive LED Location . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Wiring Diagram - 2 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Wiring Diagram - 3-5 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
LIST OF TABLES
Minimum / Maximum Operating Limit Conditions . . . . . . . . . . . . . . . . .2
Allowable Vertical Linesets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
TEST Mode Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Same Priority Fault Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Status Code Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Outdoor Display Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
IMPORTANT
It is recommended before starting the system to connect the thermostat to Wi-Fi using a local network or portable hot-spot so the thermostat and system receive the latest software updates to optimize system performance.
!
CAUTION
The EEV is factory installed but shipped in the closed position. Prior to any brazing, power must be applied to the Indoor Unit. If installing a coil furnace match or multi-piece air handler system, the EEV harness must be plugged into the Comm port prior to applying power to the indoor unit. Allow open to allow proper nitrogen flow through the coil and lineset. If you are not able to power the indoor unit before brazing the line set, a tool to manually open the EEV is available through Source 1 under part number S1-02649686000.
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines. Sweat connect units are factory charged with refrigerant for a nominal sized matching indoor coil plus 15 feet of field-supplied lines.
1 minute for the EEV to
Outdoor Control Faults/Status Code Display . . . . . . . . . . . . . . . . . . 12
Inverter Drive Fault/Status Code Display . . . . . . . . . . . . . . . . . . . . . 16
Thermistor Resistance vs Temperature Table . . . . . . . . . . . . . . . . . 21
Sensor Connector Pin Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Low Suction Pressure Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION. DANGER indicates an imminently hazardous situation, which, if not
avoided, WARNING indicates a potentially hazardous situation, which, if not
avoided, CAUTION indicates a potentially hazardous situation, which, if not
avoided alert against unsafe practices and hazards involving only property dam­age.
will result in death or serious injury.
could result in death or serious injury.
may result in minor or moderate injury. It is also used to
!
WARNING
Improper installation may create a condition where the operation of the product could cause personal injury or property damage. Improper installation, adjustment, alteration, service or mainte­nance can cause injury or property damage. Refer to this manual for assistance or for additional information, consult a qualified con­tractor, installer or service agency.
Johnson Controls Unitary Products 5284792-UIM-D-1017
5284792-UIM-D-1017
!
CAUTION
This product must be installed in strict compliance with the enclosed installation instructions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical codes.
!
CAUTION
R-410A systems operate at higher pressures than R-22 systems. Do not use R-22 service equipment or components on R-410A equipment. Service equipment
Must Be Rated for R-410A.
INSPECTION
As soon as a unit is received, it should be inspected for possible dam­age during transit including copper distributor lines that may have shift­ing during transit, and are touching either copper lines or the cabinet. If damage is evident, the extent of the damage should be noted on the carrier’s delivery receipt. A separate request for inspection by the car­rier’s agent should be made in writing. See Local Distributor for more information.
Requirements For Installing/Servicing R-410A Equipment
• Gauge sets, hoses, refrigerant containers, and recovery system must be designed to handle the POE type oils, and the higher pressures of R-410A.
• Manifold sets should be high side and low side with low side retard.
• All hoses must have a 700 psig service pressure rating.
• Leak detectors should be designed to detect HFC refrigerant.
• Recovery equipment (including refrigerant recovery containers) must be specifically designed to handle R-410A.
LIMITATIONS
The unit should be installed in accordance with all National, State and Local Safety Codes and the limitations listed below:
1. Limitations for the indoor unit, coil, and appropriate accessories must also be observed.
2. The outdoor unit must not be installed with any duct work in the air stream. The outdoor fan is the propeller type and is not designed to operate against any additional external static pressure.
3. The maximum and minimum conditions for operation must be observed to ensure a system will give maximum performance with minimal service.
TABLE 1: Minimum / Maximum Operating
AIR TEMPERATURE AT OUTDOOR COIL, °F (°C)
Min. Max. Min. Max.
DB Cool DB Cool WB Cool WB Cool
35(2)* 125(52)* 57(14) 72(22)
Limit
Conditions
AIR TEMPERATURE AT
INDOOR COIL, °F (°C)
*Reference the NOTICE under the “Unit Reduced Capacity Conditions”
section.
4. The maximum allowable equivalent line length for this product is 80 feet.
Standard Lineset Applications
Maximum allowable lineset varies depending on the vertical separation between the evaporator and condenser. See Table 2 for allowable line set lengths and sizing.
TABLE 2:
Model
Unit Reduced Capacity Conditions
Allowable Vertical Linesets
Liquid
Suction
Line
Line
24 36 48 60
3/4”
3/8”
7/8”
Max Line
Length ­Units on
Equal Level
80 feet 25 feet 25 feet
Max Suction
Line Riser - If
OD Unit is
Above ID Unit
Max Liquid
Line Riser - If
OD Unit is
Below ID Unit
NOTICE
Inverter Temperature Protection
If excessive inverter temperatures are sensed, the compressor speed / capacity is reduced until an acceptable condition is reached. When the inverter temperature returns to an acceptable level, the system returns to normal operation. Over / Under Current Protection: If a low or high Current Condition is sensed, the compressor speed / capacity is reduced until an acceptable current level is reached. When the system reaches an acceptable current level, the compres­sor and fan return to normal operating conditions. Over / Under Voltage Protection: If a low or high supply Voltage Condition is experienced (below 187 VAC or above 265 VAC), the compressor speed / capacity is automatically reduced until an accept­able voltage level is sensed. When an acceptable voltage level is sensed, the system automati­cally returns to a normal state of operation. High Altitude Protection: If the unit is installed in Altitudes of 6,500 ft / 2,000 m above sea level or higher, the compressor and outdoor fan reduce speeds to protect the system. It is not recommended these units be installed at altitudes greater than 6,500 ft / 2,000 m above sea level.
Low Ambient Protection
Cooling Mode: The unit automatically adjusts to maintain cooling
operation in outdoor ambient conditions down to 35 °F (2 °C). The unit reduces capacity and Low Ambient Protection (cooling mode) or cycles off if asked to provide cooling when the outdoor temperature is at or below these conditions.
SECTION III: UNIT INSTALLATION
LOCATION
Before starting the installation, select and check the suitability of the location for both the indoor and outdoor unit. Observe all limitations and clearance requirements.
The outdoor unit must have sufficient clearance for air entrance to the condenser coil, air discharge, and service access. See Figure 1.
NOTICE
For multiple unit installations, units must be spaced a minimum of 24” (61 cm) apart (coil face to coil face).
If the unit is to be installed on a hot sun exposed roof or a paved ground area that is seasonally hot, the unit should be raised sufficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdoor unit (which can cause the unit to derate prematurely).
If the system is being installed during seasonally cold weather of 55°F or below, the preferred method is to weigh in the charge. For charging
or checking the system charge at 55 Cold Weather Charging” procedures near the end of SECTION VI: SYSTEM CHARGE. There is an “Optional Cold Weather Charging” accessory kit to prevent the outdoor unit from taking in cold air below 55°F. The kit part number can be found in the list of accessory kits on the UPGNET web site.
Provide adequate structural support for the unit.
°F or below, refer to the “Optional
2 Johnson Controls Unitary Products
5284792-UIM-D-1017
&$87,216SHFLDOFDUHPXVWEHWDNHQWRDYRLGUHFLUFXODWLRQRIGLVFKDUJHDLUWKURXJKRXWGRRUFRLO
127(
(QVXUHDPLQLPXPRI ´FOHDUDQFHEHWZHHQ DQ\WZRXQLWV
´&/($5$1&( $5281'3(5,0(7(5 ´FOHDUDQFH SHUPLVVLEOHRQRQH VLGHRQO\VHH $OWHUQDWLYH ,QVWDOODWLRQ &OHDUDQFHV
127(
$OORXWGRRUZLULQJ PXVWEHZHDWKHUSURRI
´29(5+($'&/($5$1&(
:($7+(53522) ',6&211(&7 6:,7&+
&21752/$&&(66 3$1(/:,7+6:,1* $:$<'225
0,1,080´6(59,&($&&(66&/($5$1&( 0DLQWDLQPLQLPXPFOHDUDQFHRQRQHVLGHRIDFFHVVSDQHO
1(&&/$66:,5,1*
7+(50267$7
1(&&/$66:,5,1*
1(&&/$66:,5,1*
6($/23(1,1*6 8VHSHUPDJXPRUHTXLYDOHQW
72)851$&(25 $,5+$1'/(5 7(50,1$/%/2&.
FIGURE 1: Typical Installation Clearances
%5$&(6 8VHIRUZDOOPRXQWZLWK FHQWHUEUDFHXQGHU FHQWHURIFRPSUHVVRU
612:3803836 8VHLQGHHSVQRZDUHDV ZLWK¿IWKSXPSXSXQGHU FHQWHURIFRPSUHVVRU
127(
(QVXUHDGHTXDWH ZDOOVXSSRUW
$
0,1,080&/($5$1&(%(7:((181,76
:$//
)(1&(
´
´
6(59,&(
´
´
81,7
7281,7
´
6(59,&(
´
´
81,7
7281,7
´
6(59,&(
´
127( &OHDUDQFHWRRQHVLGHRIWKH XQLWPD\EHUHGXFHGWR´SURYLGHG WKHFOHDUDQFHWRHDFKUHPDLQLQJVLGH LVLQFUHDVHGWR´PLQLPXPWKH VHUYLFHDFFHVVLVLQFUHDVHGWR´ PLQLPXPDQGWKHFOHDUDQFHVEHWZHHQ DQ\WZRXQLWVLVPDLQWDLQHGDW´ PLQLPXP
:$//
´
6(59,&(
&$87,21
6SHFLDOFDUHPXVWEHWDNHQWRDYRLGUHFLUFXODWLRQRIGLVFKDUJHDLUWKURXJKRXWGRRUFRLO
FIGURE 2: Alternative Installation Clearances
127( &OHDUDQFHEHWZHHQWZRXQLWVPD\EH UHGXFHGWR´PLQLPXPSURYLGHG WKHVHUYLFHDFFHVVFOHDUDQFHLV LQFUHDVHGWR´PLQLPXPDQGWKH FOHDUDQFHRQHDFKUHPDLQLQJVLGH LVPDLQWDLQHGDW´PLQLPXP
´
0,1,080&/($5$1&()520:$//
´
´
6(59,&(
$1'81,7
7281,7
´
´
´
)(1&(
´
$
Johnson Controls Unitary Products 3
5284792-UIM-D-1017
ADD-ON REPLACEMENT/RETROFIT
When this unit is being used as a replacement for an existing R-410A unit, these are matched systems and the indoor coil and outdoor unit must be replaced. The following steps should be performed in order to insure proper system operation and performance. Line-set change out is also recommended.
1. Change-out of the indoor coil to an approved R-410A coil / air han­dling unit combination with the appropriate metering device.
2. Change-out of the line-set when replacing an R-22 unit with an R410-A unit is highly recommended to reduce cross-contamination of oils and refrigerants.
3. If change-out of the line set is not practical, then the following pre­cautions should be taken.
• Inspect the line set for kinks, sharp bends, or other restrictions,
and for corrosion.
• Determine if there are any low spots which might be serving as oil
traps.
• Flush the line set with a commercially available flush kit to remove
as much of the existing oil and contaminants as possible.
• Install a suction line filter-drier to trap any remaining contami-
nants, and remove after 50 hours of operation.
4. If the outdoor unit is being replaced due to a compressor burnout, then installation of a 100% activated alumina suction-line filter drier in the suction-line is required, in addition to the factory installed bi­flow liquid-line drier. Operate the system for 10 hours. Monitor the suction drier pressure drop. If the pressure drop exceeds 3 psig, replace both the suction-line and liquid-line driers. After a total of 10 hours run time where the suction-line pressure drop has not exceeded 3 psig, replace the liquid line drier, and remove the suc­tion-line drier. Never leave a suction-line drier in the system longer than 50 hours of run time.
GROUND INSTALLATION
The unit may be installed at ground level on a solid base that will not shift or settle, causing strain on the refrigerant lines and possible leaks. The unit must be installed in as level a position as possible while main­taining the clearances shown in Figure 2.
Normal operating sound levels may be objectionable if the unit is placed directly under windows of certain rooms (bedrooms, study, etc.).
!
WARNING
The outdoor unit should not be installed in an area where mud or ice could cause personal injury.
Elevate the unit sufficiently to prevent any blockage of the air entrances by snow in areas where there will be snow accumulation. Check the local weather bureau for the expected snow accumulation in your area.
Isolate the unit from rain gutters to avoid any possible wash out of the foundation.
ROOF INSTALLATION
When installing units on a roof, the structure must be capable of sup­porting the total weight of the unit, including a pad, lintels, rails, etc., which should be used to minimize the transmission of sound or vibra­tion into the conditioned space.
WALL MOUNT INSTALLATION
Care must be taken to mount the outdoor unit on a solid base that is sloped to shed water, secure from settlement, and is isolated from the structural foundation or walls to prevent sound and vibration transmis­sion into the living space.
On occasion, site conditions may require direct wall mounted brackets to be used to locate and support the outdoor unit. In these applications, care must be taken to address unit base pan support, structural integ­rity, safe access and serviceability, as well as the possible sound and vibration transmission into the structure. Wall mounting requires 3 mounting brackets and best served by a properly engineered solution.
See price pages for specific part number for your application.
UNIT PLACEMENT
1. Provide a base in the pre-determined location.
2. Remove the shipping carton and inspect for possible damage.
3. Ensure that compressor tie-down bolts remain tightened.
4. Position the unit on the base provided.
LIQUID LINE FILTER-DRIER
The air conditioning unit's copper spun filter/dryer is located on the liq­uid line.
!
CAUTION
Failure to use the same as the original factory drier or using a substi­tute drier or a granular type may result in damage to the equipment.
NOTICE
Replacements for the liquid line drier must be exactly the same as marked on the original factory drier. See Source 1 for O.E.M. replace­ment driers.
R-410A Filter-Drier Source 1 Part No. Apply with Models
S1-02922195000 All
PIPING CONNECTIONS
The outdoor condensing unit must be connected to the indoor evapora­tor coil using field supplied refrigerant grade (ACR) copper tubing that is internally clean and dry. Units should be installed only with the tubing sizes for approved system combinations as specified in tabular data sheet. The charge given is applicable for total tubing lengths up to 15 feet (4.6 m).
NOTICE
Using a larger than specified line size could result in oil return prob­lems. Using too small a line will result in loss of capacity and other problems caused by insufficient refrigerant.
!
WARNING
Never install a suction-line filter drier in the liquid line of an R-410A system. Failure to follow this warning can cause a fire, injury or death.
!
CAUTION
This system uses R-410A refrigerant which operates at higher pres­sures than R-22. No other refrigerant may be used in this system. Gauge sets, hoses, refrigerant containers, and recovery system must be designed to handle R-410A. If you are unsure, consult the equip­ment manufacturer.
PRECAUTIONS DURING LINE INSTALLATION
Install the refrigerant lines with as few bends as possible. Care must be taken not to damage the couplings or kink the tubing. Use clean hard drawn copper tubing where no appreciable amount of bending around obstruction is necessary. If soft copper must be used, care must be taken to avoid sharp bends which may cause a restriction.
1. The lines should be installed so that they will not obstruct service access to the coil, air handling system, or filter.
2. Care must also be taken to isolate the refrigerant lines to minimize noise transmission from the equipment to the structure.
3. The vapor line must be insulated with a minimum of 1/2” foam rub­ber insulation (Armaflex or equivalent). Liquid lines that will be exposed to direct sunlight, high temperatures, or excessive humidity must also be insulated.
4. Tape and suspend the refrigerant lines as shown. DO NOT allow tube metal-to-metal contact. See Figure 3.
4 Johnson Controls Unitary Products
5284792-UIM-D-1017
5. Use PVC piping as a conduit for all underground installations as shown in Figure 4. Buried lines should be kept as short as possible to minimize the build up of liquid refrigerant in the vapor line during long periods of shutdown.
Sheet Metal Hanger
Liquid Line
Incorrect
TE
Tape
A0151-001
OUTDO
OR
NI
CA
T
U
P
TO
D
Correct
Insulated Vapor Line
FIGURE 3: Installation of Vapor Line
6. Pack fiberglass insulation and a sealing material such as permagum around refrigerant lines where they penetrate a wall to reduce vibra­tion and to retain some flexibility.
TO IND
OOR C
OI
LI
QU
PVC CO
ID
ND
LIN
U
E
IT
L
LA
IN
SU
VAPOR LINE
PRECAUTIONS DURING BRAZING SERVICE VALVE
Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Figure 5. Also, protect all painted surfaces, insulation, and plastic base during brazing. After braz­ing, cool joint with wet rag.
!
WARNING
This is not a backseating valve. The service access port has a valve core. Opening or closing valve does not close service access port. If the valve stem is backed out past the chamfered retaining wall, the O-ring can be damaged causing leakage or system pressure could force the valve stem out of the valve body possibly causing personal injury.
Valve can be opened by removing the service valve cap and fully insert­ing a hex wrench into the stem and backing out counter-clockwise until valve stem just touches the chamfered retaining wall.
Connect the refrigerant lines using the following procedure:
1. Remove the cap and Schrader core from both the liquid and vapor service valve service ports at the outdoor unit. Connect low pres­sure nitrogen to the liquid line service port, allow nitrogen to flow.
2. Braze the liquid line to the liquid service valve at the outdoor unit. Be sure to wrap the valve body with a wet rag. Allow the nitrogen to continue flowing.
3. Carefully remove the plugs from the evaporator liquid and vapor connections at the indoor coil.
A0152-001
FIGURE 4: Underground Installation
PRECAUTIONS DURING BRAZING OF LINES
All outdoor unit and evaporator coil connections are copper-to-copper and should be brazed with a phosphorous-copper alloy material such as Silfos-5, silver solder or equivalent. DO NOT use soft solder. The outdoor units have reusable service valves on both the liquid and vapor connections. The system refrigerant charge for 15 feet of lineset is retained within the outdoor unit during shipping and installation. The reusable service valves are provided to evacuate and charge per this instruction.
Serious service problems can be avoided by taking adequate precau­tions to assure an internally clean and dry system.
!
CAUTION
Dry nitrogen should always be supplied through the tubing while it is being brazed, because the temperature required is high enough to cause oxidation of the copper unless an inert atmosphere is provided. The flow of dry nitrogen should continue until the joint has cooled. Always use a pressure regulator and safety valve to insure that only low pressure dry nitrogen is introduced into the tubing. Only a small flow is necessary to displace air and prevent oxidation.
!
CAUTION
The EEV is factory installed but shipped in the closed position. Prior to any brazing, power must be applied to the Indoor Unit. If installing a coil furnace match or multi-piece air handler system, the EEV harness must be plugged into the Comm port prior to applying power to the indoor unit. Allow 1 minute for the EEV to open to allow proper nitrogen flow through the coil and lineset. If you are not able to power the indoor unit before brazing the line set, a tool to manually open the EEV is available through Source 1 under part number S1-02649686000.
:(75$*6 :UDSZHWUDJV DURXQGVHUYLFHYDOYH RUUHIULJHUDQWOLQHV SULRUWREUD]LQJ
FIGURE 5: Heat Protection
!
CAUTION
Do not install any coil with a furnace which is to be operated during the heating season without attaching the refrigerant lines to the coil. The coil is under pressure which must be released to prevent exces­sive pressure build-up and possible coil damage.
4. Power must be applied to the indoor unit.Allow 1 minute for the EEV to open to allow proper nitrogen flow through the coil and line-set.
5. Protect the vapor valve with a wet rag and braze the vapor line con­nection to the outdoor unit. The nitrogen flow should be exiting the system from the vapor service port connection. After this connection has cooled, remove the nitrogen source from the liquid fitting ser­vice port.
6. Braze the liquid line to the evaporator liquid connection. Nitrogen should be flowing through the evaporator coil.
7. Slide the grommet away from the vapor connection at the indoor coil and wrap with a wet rag as shown in Figure 5. Braze the vapor line to the evaporator vapor connection. After the connection has cooled, slide the grommet back into original position. After this con­nection has cooled, remove the nitrogen source from the liquid fit­ting service port.
$
Johnson Controls Unitary Products 5
5284792-UIM-D-1017
8. Replace the Schrader core in the liquid and vapor valves.
9. Leak test all refrigerant piping connections including the service port flare caps to be sure they are leak tight. DO NOT OVERTIGHTEN (between 40 and 60 inch - lbs. maximum).
NOTICE
Line set and indoor coil can be pressurized to 250 psig with dry nitro­gen and leak tested with a bubble type leak detector. Then release the nitrogen charge. Do not use the system refrigerant in the outdoor unit to purge or leak test.
10.Evacuate the vapor line, evaporator, and liquid line to 500 microns or less.
11.Replace cap on service ports. Do not remove the flare caps from the service ports except when necessary for servicing the system.
!
CAUTION
Do not connect manifold gauges unless trouble is suspected. Approx­imately 3/4 ounce of refrigerant will be lost each time a standard man­ifold gauge is connected.
12.Release the refrigerant charge into the system. Open both the liquid and vapor valves by removing the service valve cap and with an Allen wrench back out counter-clockwise until valve stem just touches the chamfered retaining wall. If the service valve is a ball valve, use a Crescent wrench to turn valve stem one-quarter turn counterclockwise to open. Do not overturn or the valve stem may break or become damaged. See “PRECAUTIONS DURING BRAZ­ING SERVICE VALVE”.
13.Replace service valve cap finger tight, then tighten an additional 1/2 turn (1/2 hex flat). Cap must be replaced to prevent leaks.
!
WARNING
Never attempt to repair any brazed connections while the system is under pressure. Personal injury could result.
14.See Section VI “System Charge” section for checking and recording system charge.
SECTION IV: EVACUATION
Evacuate the system to 500 microns or less. If a leak is suspected, leak test with dry nitrogen to locate the leak. Repair the leak and test again.
To verify that the system has no leaks, simply close the valve to the vacuum pump suction to isolate the pump and hold the system under vacuum. Watch the micron gauge for a few minutes. If the micron gauge indicates a steady and continuous rise, it’s an indication of a leak. If the gauge shows a rise, then levels off after a few minutes and remains fairly constant, it’s an indication that the system is leak free but still contains moisture and may require further evacuation if the reading is above 500 microns.
SECTION V: ELECTRICAL CONNECTIONS
GENERAL INFORMATION & GROUNDING
The control box cover is held in place with 5 screws (one screw near each lower corner, one each at the midpoint of each side and one at top middle). Check the electrical supply to be sure that it meets the values specified on the unit nameplate and wiring label. Power wiring, control (low voltage) wiring, disconnect switches and over current protection must be supplied by the installer. Wire size should be sized per NEC requirements.
!
CAUTION
All field wiring must USE COPPER CONDUCTORS ONLY and be in accordance with Local, National, Fire, Safety & Electrical Codes. This unit must be grounded with a separate ground wire in accordance with the above codes.
The complete connection diagram and schematic wiring label is located on the inside surface of the unit service access panel. An example of typical field connections can be found in Figure 7.
FIELD CONNECTIONS POWER WIRING
1. Install the proper size weatherproof disconnect switch outdoors and within sight of the unit, per local code.
2. Remove the screws at the top and sides of the corner cover. Slide the control box cover down and remove from unit.
3. Run power wiring from the disconnect switch to the unit.
4. Route wires from disconnect through power wiring exit provided and into the unit control box as shown in Figure 1 and view the openings in Figure 6.
5. Make the power supply connections to the supplied terminal block.
DO NOT connect the Rterminal of unit control board.
MAIN CONTROL BOARD
OUTDOOR DISPLAY
ACCESS PANEL SWITCH
OUTDOOR REACTOR/CHOKE
OUTDOOR FILTER CONTROLLER (May not be used on all units)
LOW VOLTAGE FIELD WIRING BOX
AMBIENT TEMPERATURE SENSOR
FIGURE 6: Outdoor Unit Control Box
TRANSFORMER
INVER
DR
TERMINAL
BLOCK
GROUND LUG FIELD WIRING
HIGH VOLTAGE CONDUITPLATE
HIGH VOLTAGE
FIELD WIRING
IVE
TER
A0770-001
FIELD CONNECTIONS CONTROL WIRING
1. Route low voltage wiring into bottom of control box through the hole inside the low voltage box. Connect low voltage wiring inside the low voltage box by clipping and discarding the connector plug and strip­ping the low voltage wires. See Figure 6.
2. The complete connection diagram and schematic wiring label is located on the inside surface of the unit service access panel.
3. Replace the control box cover removed in Step 2 of the FIELD CONNECTIONS POWER WIRING procedures.
4. All field wiring to be in accordance with national electrical codes (NEC) and/or local-city codes.
5. Mount the thermostat about 5 ft. above the floor, where it will be exposed to normal room air circulation. Do not place it on an outside wall or where it is exposed to the radiant effect from exposed glass or appliances, drafts from outside doors or supply air grilles.
6. Route the 24-volt control wiring (NEC Class 2) from the outdoor unit to the indoor unit and thermostat. Keep the low voltage wiring 4" or more away from the high voltage wires that are leaving the control box. If this isn't possible, install shielded low voltage wiring to reduce EMI risk.
6 Johnson Controls Unitary Products
5284792-UIM-D-1017
NOTICE
To eliminate erratic operation, seal the hole in the wall at the thermo­stat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat.
$//),(/':,5,1*72%(,1$&&25'$1&(:,7+(/(&75,&&2'(1(&$1'25/2&$/
287'22581,7
:+7
%
&21752/ %2$5'
*1' /8*
32:(5:,5,1*
'2127FRQQHFWWKH³5´WHUPLQDOIURPWKHWKHUPRVWDW WRWKHXQLWFRQWUROERDUG
7(50,1$/
%/2&.
$
*51
%/.
&
92/7&21752/:,5,1* 0,1,080*$:,5( 1(&&/$66
$//287'225:,5,1*0867%(:($7+(53522)86(&233(5&21'8&725621/<
FIGURE 7: Typical Communicating Field Wiring (Air Handler / Furnace) Demand Response (Load Shedding)
The main outdoor control has a conventional 24VAC input (DR) for util­ity demand response signals. When a 24VAC signal is present on the DR input the HX point by the user selected setting. For further details on available set­tings, please refer to the HX
TM
thermostat will adjust the indoor temperature set-
TM
thermostat installation and operation manual. The DR input terminal location can be found in Figure 10 and typical wiring is found in Figure 8.
87,/,7<
6833/,('5(/$<
$
& %
%
&
5
$
% & 5
'5&2
<
127(:RUNVZLWKQRUPDOO\ RSHQDQGQRUPDOO\FORVHG XWLOLW\FRQWUROUHOD\V 9HULI\FRQWUROUHOD\FRQWDFWVDUH UDWHGIRUDPLQLPXPRIP$WR HQVXUHDGHTXDWHZHWWLQJFXUUHQW
$
FIGURE 8: Demand Response Wiring
SECTION VI: SYSTEM CHARGE
After completion of system connections, apply power to the system, it is recommended before starting the system to connect the thermostat to Wi-Fi using a local network or portable hot-spot so the thermostat and system receive the latest software updates to optimize system perfor­mance. Utilize the Hx
TM
thermostat to “discover” the system compo-
32:(5:,5,1*
&21752/:,5,1*
)$&725<:,5,1*
)851$&(25$,5+$1'/(57(50,1$/%/2&.
%
$&
&
$
52207+(50267$7
5
%
5
$
nents and identify the Indoor and Outdoor Communicating Equipment. AVV air handler or MVC modular blower with electric heat. Inputs to air handler control board come from the thermostat which are communi­cated from the main control of the outdoor unit. This maintains proper sensible/latent balance during cooling and proper discharge tempera­ture during heating.
Proper indoor unit airflow is determined by the system and requires no initial set-up by the installing contractor unless using an AVV or MVC modular blower air handler with electric heat. If a unit is using electric heat, the unit must have the electric heat airflow set at the air handler control board.
After the system is started during the initial set-up process using the
TM
thermostat, additional fine tuning of the airflow is accomplished by
Hx selecting on of the three operating profiles. The three operating profiles include: humid, dry or normal. Select the one that best reflects the out­door environment where the conditioned space is located. This selec­tion adjusts the how the indoor blower and the compressor work together to manage temperature and humidity. Additional fine tune adjustments are available using the Hx
TM
thermostat. Refer to the Hx
TM
thermostat manual for additional detail. The proper airflow is determined by the main outdoor control in the out-
door unit.
!
CAUTION
If the outdoor temperature is below 55°F, an attempt to start the com­pressor without at least 2 hours of crankcase/stator heat can damage the compressor.
!
CAUTION
Refrigerant charging should only be carried out by a licensed quali­fied air conditioning contractor.
To ensure that your unit performs at the published levels, it is important that the indoor airflow is determined and refrigerant charge added accordingly.
Johnson Controls Unitary Products 7
5284792-UIM-D-1017
CHARGING THE UNIT
The factory charge in the outdoor unit includes enough charge for the unit, 15 ft. (4.6 m) of refrigerant piping, and the smallest indoor coil/air handler match-up. Some indoor coil / air handler matches may require additional charge.
/2: +,*+
´6$( 0,&521*$8*( 5HTXLUHGIRU HYDFXDWLRQ SURFHGXUHRQO\
)/$5(7((
%/8(
0$1,)2/' *$8*(6(7
5('
1,752*(1
9$&880
3803
FIGURE 9: System Charging Connections
!
CAUTION
Compressor damage will occur if system is improperly charged. On new system installations, charge system per tabular data sheet for the matched coil and follow guidelines in this instruction.
!
CAUTION
Do not leave the system open to the atmosphere. Unit damage could occur due to moisture being absorbed by the POE oil in the system. This type of oil is highly susceptible to moisture absorption.
<(//2:
5()5,*(5$17
',*,7$/
6&$/(
TOTAL SYSTEM CHARGE DETERMINED
1. Determine outdoor unit factory charge from Tabular Data Sheet.
2. Determine indoor coil adjustment (if any) from Tabular Data Sheet.
3. Calculate the additional charge for refrigerant piping using the Tabu­lar Data Sheet if line length is greater than 15 feet (4.6 m).
4. Total system charge = item 1 + item 2 + item 3.
5. The manifold gauge set is already installed on the unit for evacua­tion and charging. Use these gauges to initially charge the system using system pressures and subcooling. Before charging put the equipment into “Service Mode” at the outdoor control. You will find the charging information for charging mode printed on the bottom of the unit data tag. Charging data for cooling & heating mode is found on Page 21 of this manual or available in the “Service Data Applica­tion Guide”, available online. For subsequent annual maintenance visits the charge verification display can be used to quickly check overall system condition and the system charge without attaching a separate manifold gauge set or temperature sensors.
6. Permanently mark the unit data plate with the total amount of refrig­erant in the system.
7(03(5$785( ,1',&$725
&/$0372 /,48,'/,1(
It is unlawful to knowingly vent, release or discharge refrigerant into the open air during repair, service, maintenance or the final disposal of this unit.
/,1(6(7 7RLQGRRU &RLO
$
!
CAUTION
<
2
&
'5
67$786
)$8/76
!
WARNING
DO NOT attempt to pump “Total System Charge” into outdoor unit for maintenance, service, etc. This may cause damage to the compres­sor and/or other components. Recover and weigh “System Charge” into an appropriate recovery cylinder for any instances requiring evacuation.
8 Johnson Controls Unitary Products
$
FIGURE 10: Main Outdoor Control and Display
5284792-UIM-D-1017
CHARGE VERIFICATION MODE
The outdoor display will assist the installer with charging the system. Through interaction with the Outdoor Display the system will operate at predetermined nominal speed values. During this operation the system will monitor pressures and temperatures. When the subcooling is within the predetermined values set by the OEM, the outdoor display will indi­cate SYSTEM CHARGE VALIDATED. This mode is only available when the ID temperature is within 73 to 83°F and humidity is less than 73% as measured by the Hx charge will not be verified.
User Interaction/Operation:
1. Press Menu, press Arrow until Modes is displayed, press Select. Press Arrow until Charge Verification is displayed, press Select.
2. Press Select while in Charge Verification Mode. The system will detect the Unit Type and Unit Tonnage. The outdoor display will update and scroll text, see the example below.
Example: 4-TON AC FOUND * VERIFY CHARGE? * 4-TON AC FOUND * VERIFY CHARGE?
3. Press Select to verify charge, the outdoor display will update and scroll text, see the example below.
Example: VERIFYING CHARGE * PLEASE WAIT * VERIFYING CHARGE * PLEASE WAIT (5 minute wait time during initial charge calculation)
4. ADD CHARGE or REMOVE CHARGE will display on the banner with the appropriate response dependent upon the OEM's predeter­mined values, user may press Select when the banner displays ADD CHARGE or REMOVE CHARGE. The display will indicate ACCEPTED for 5 seconds and return to the example defined in Step 1. However, if the system does meet the charge requirements defined by the OEM, the outdoor display will indicate the below text example for 5 seconds and return to the text example in Step 2 until charge verification has fully completed.
Example: SYSTEM CHARGE VALIDATED
The system will repeat steps 1-3 until the subcooling has reached the predetermined values set by the OEM.
5. Once charge verification is fully complete the outdoor display will return to the Second Menu Layer.
TABLE 3:
Menu Options Operation
OPERATIONAL MODE (AC - HP) Display current system configuration (AC or HP) and unit capacity stored in memory. BYPASS ASCD TIMER
TEST Mode Option
TM
thermostat. Operation will continue but
TEST MODE OPTION
Bypass ASCD timer and initiate system operation if a call for space conditioning is present from the HXTM thermostat.
SECTION VII: SYSTEM OPERATION
SERVICE MODE
Service mode locks the system into maximum capacity operation based on ambient conditions. The unit will be locked into steady state condi­tions where operation and performance can be evaluated using the available service information. This function is outside of the charge ver­ification mode, available for all system component diagnostics and can only be access from the outdoor control.
ANTI SHORT-CYCLE DELAY
The control includes a five-minute anti short-cycle delay (ASCD) timer to prevent the compressor from short-cycling after a power or thermo­stat signal interruption. The ASCD timer is applied when the control is first powered and immediately following the completion of a compressor run cycle. The compressor and the outdoor fan will not operate during the five minutes that the timer is active.
LOW VOLTAGE DETECTION
The control monitors the outdoor transformer secondary (24 VAC) volt­age and provides low voltage protection for the heat pump and its com­ponents. If the voltage drops below approximately 22 VAC, the control continues to energize any outputs that are already energized. If the volt­age drops below approximately 19 VAC, the control immediately de­energizes the outputs and can no longer energize any outputs until the voltage level increases above 22VAC. The control stores and displays the appropriate fault codes when low voltage conditions occur.
TEST MODE OPERATION
Test mode operation provides the features found in Table 3 to assists in unit commissioning and troubleshooting. TEST MODE is accessed through the Outdoor Display. Please see Page 11 & Table 6 for detailed Outdoor Display operation. Test mode can only be accessed from the outdoor control.
FAULT AND STATUS CODE BEHAVIOR
Fault Code Storage
The main control stores the ten most recent fault codes for review by the service technician. These codes are stored even when power is removed from the control and will remain in memory until the control is powered for 30 consecutive days or manually cleared from the control. All codes are stored in order of occurrence and time stamped.
The control stores only one identical fault code during the same series of events. For example, if two or more high pressure switch (HPS) faults occur sequentially without another fault occurring in between the HPS faults, the control only stores the HPS fault once.
In addition, the main unit control stores the following unit sensor values when a fault and/or event occurs.
1. Suction Superheat
2. Liquid Subcooling
3. Liquid Temperature
4. Discharge Pressure
5. Suction Temperature
6. Suction Pressure
Johnson Controls Unitary Products 9
When a fault and/or event is present, the system will indicate the corre­sponding fault and/or event text on the Outdoor Display status banner.
NOTICE
The display will continue to indicate the above fault (saved) value(s) on the Outdoor Display with the active Fault and/or Event text, while the fault and/or event is still present. When the fault and/or event has cleared, the system will return to the General Display Operation.
Fault Code Display
The system will provide fault and/or event text, using the Outdoor Dis­play when CURRENT and/or STORED SYSTEM FAULT(s) are selected from the FAULT MODE category. Tables 7 & 8 describe the fault codes in more detail, giving potential causes and troubleshooting actions. If multiple faults and/or events are present at the same time, the Outdoor Display will show the most recent fault and/or event with the highest priority. In the event that multiple faults and/or events are populated at the same time, the Outdoor Display will indicate the most recent system fault and/or event that is stored in memory. The second system fault will not be displayed, but will be stored in memory. For example see Table 4.
Loading...
+ 19 hidden pages