A72 Series Cooling Tower or Evaporative Condenser Controls (Single-Stage Temperature Control with Outdoor Enclosure)

Description

The A72AE and A72CE are wide range temperature controls with heavy duty double-pole, single-throw (DPST) contacts and neoprene-coated sensing elements.

Refer to the A72 Series Temperature Controls for Cooling Towers and Evaporated Condensers with Weather Resistant Enclosure Product Bulletin (LIT-125165) for important product application information.

Selection Chart

Features

Open high or close high models are available.

Applications

Use for control of cooling tower fans; motorized valves or solenoid operated valves.

Repair Information

If the A72 Series Cooling Tower or Evaporative Condenser Control fails to

operate within its specifications, replace the A72 Series Temperature Control unit. For a replacement control, contact the

nearest Johnson Controls® representative.

Product

Switch

Range

Differential

Bulb and

Range

Code

Action

°F (°C)

F° (C°)

Capillary

Adjuster

Number

 

 

 

 

 

A72AE-1C

DPST; close high

25 to 90

4 to 25

11/16 in. x 6-3/4 in.

Internal

A72CE-1C

DPST; open high

(-5 to 30)

(2.2 to 14)

Neoprene-coated 6 ft cap.

screwdriver slot

Technical Specifications

ambient temperature limits: -65 to 150°F (-54 to 66°C)

maximum bulb temperature: 170°F (77°C)

Electrical Ratings

 

 

 

 

 

 

 

 

Motor Ratings VAC

120

 

2081

2401

2201

208

 

220

 

Single-

Single-

Single-

Two-

Three-

 

Three-

 

Phase

 

Phase

Phase

Phase

Phase

 

Phase

Horsepower

2

 

3

3

5

5

 

5

AC Full Load A

24.0

 

24.0

24.0

15.0

15.9

 

15.0

AC Locked Rotor A

144.0

 

144.0

144.0

90.0

95.4

 

90.0

AC Non-Inductive A

24.0

 

24.0

24.0

 

DC Non-Inductive A

3.0

 

0.5

 

Pilot Duty

 

125 VA, 120 to 600 VAC; 57.5 VA, 120 to 300 VDC

 

1. These full load and locked rotor ampere (not horsepower) ratings apply to hermetic compressors only.

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult th Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.