Johnson Controls A419ABG-3C Installation Instructions Manual

Installation Instructions
Issue Date June 16, 2003
A419ABG-3C Electronic Temperature Control
Application
IMPORTANT: Use this A419ABG-3C Electronic
Temperature Control only as an operating control. Where failure or malfunction of the A419ABG-3C Electronic Temperature Control could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of, or protect against, failure or malfunction of the A419ABG-3C Electronic Temperature Control.
The A419 Electronic Temperature Control is a single-stage, electronic temperature control. Pre-wired cords with plug and receptacle ends are provided for quick and simple installation.
The control features a lockable, three-button touchpad for setup and adjustment and a Liquid Crystal Display (LCD) which displays the sensed temperature and other control functions. A front panel Light-Emitting Diode (LED) indicates the output relay status. The control has a setpoint range of -30 to 212°F (-34 to 100°C) and is available in 120 VAC models. See the Technical Specifications section.
The A419 control has heating and cooling modes with adjustable setpoint and differential, an adjustable anti-short cycle delay, and a temperature offset (setback) function. The control provides remote sensing capability, and electronic accuracy in a Type NEMA 1 high-impact plastic enclosure suitable for surface or DIN rail mounting. The temperature sensor supplied with the control is interchangeable with compatible Johnson Controls/PENN® A99 temperature sensors.
FCC Compliance
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.
Canadian DOC Compliance
This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Installation
Refer to the following guidelines, procedures and illustrations when installing an A419 control.
Parts Included
Pre-wired cords with plug and receptacle ends are provided for quick and simple installation.
Each A419 control includes a Johnson Controls/PENN A99 temperature sensor. The sensor may be removed and replaced with any compatible Johnson Controls® A99 temperature sensor, or the wire leads on the sensor may be extended.
See the Mounting and Wiring sections for additional guidelines and restrictions when mounting and wiring the control.
© 2003 Johnson Controls, Inc. 1
Part No. 24-7664-2543, Rev. — www.johnsoncontrols.com
Dimensions
9/64 (3.7)
1/2
(13)
2-15/16
(75)
DIN Rail
2-3/8
(61)
2-3/8
(61)
MENU
(127)
4
(102)
A99 temperature sensors are not polarity sensitive. Wire the leads to (+) SEN and (-) COM on the sensor terminal block (TB3). See Figure 2. Keep the leads between the control and sensor as
5
short as possible/practical in your application. The additional resistance in long sensor leads creates error between the actual temperature and the displayed temperature. Refer to Table 1 when extending sensor leads.
1-9/16 (40)
6 ft (1.8 m)
Electrical Cords with
Male and Female Plugs
7/16
(11)
Sensor
2
(50)
1/4
(6)
Sensor
Wire Lead
6.6 ft
(2 m)
Figure 1: Dimensions, in. (mm)
Mounting
An A419 control has a standard high-impact plastic NEMA 1 enclosure. The A419 control is not position sensitive but should be mounted for convenient wiring and adjustment.
Wiring
!
WARNING: Risk of Electrical Shock
Disconnect each of multiple power supplies before making electrical connections. More than one disconnect may be required to completely de-energize equipment. Contact with components carrying hazardous voltage can cause electrical shock and may result in severe personal injury or death.
Table 1: Maximum Recommended Sensor Cable Lengths and Wire Sizes
Wire
Gauge
16 AWG
18 AWG
20 AWG
22 AWG
* At the listed maximum cable lengths, there is less
than 1F° (0.6C°) error in the actual temperature vs. displayed temperature.
Maximum Sensor Cable Length*
feet (meters)
500 (150)
300 (100)
200 (60)
125 (40)
(Optional)
Binary
Input
Switch
Cable
Shield
(if used)
A99
Sensor
120 VAC
Neutral
120 VAC Application
A419ABG-3
(+)
BIN
(–)
COM
(+)
SEN
TB3
TB1
Not
Used
TB2
120
Not
Used
AC COM
C
Load
NO
All wiring must conform to the National Electrical Code and local regulations.
Observe the following guidelines and refer to Figure 2 and Table 1 when wiring the sensor to the A419 control.
Wire insulation rating must be 90°C, minimum.
Temperature sensor signals may be affected by
electrical interference. When extending sensor cable beyond 50 ft (15.2 m), use a twisted-pair, shielded cable to reduce electrical interference.
2 A419ABG-3 Electronic Temperature Control Installation Instructions
Figure 2: Typical 120 VAC Application Wiring
C
Not
Used
A
COM
120
Not
Used
NO
C
TB1
Male Plug
TB2
Female Receptacle
Figure 3: Factory Power Wiring
Setup and Adjustments
!
WARNING: Risk of Electrical Shock
Disconnect each of multiple power supplies before making electrical connections. More than one disconnect may be required to completely de­energize equipment. Contact with components carrying hazardous voltage can cause electrical shock and may result in severe personal injury or death.
IMPORTANT: To ensure that the output relay operates as intended, verify that all three of the jumpers are positioned properly for the application before powering the A419 control.
A419ABG-3 Electronic Temperature Control Installation Instructions 3
IMPORTANT: The touchpad cannot be unlocked without a jumper installed across the P5 jumper pins. Do not discard jumpers in case they are required in the future. See Figure 4 and
Figure 5.
Positioning the Jumpers
The P5 jumper position determines if the touchpad is locked or unlocked.
The P4 jumper pin block has two pairs of jumper pins. The top pair of pins (JUMP1) determines if the control is set for Heating or Cooling mode. The bottom pair of pins, (JUMP2) establishes whether Setpoint is at cut-in or at cutout. See Table 2 and Figure 5.
The A419 Control Functions
To position a jumper in the Installed position, place the jumper on both pins, which closes the circuit between the pins. To position a jumper in the Removed position, place the jumper on one pin only. See Figure 4.
=
Jumper
(Jumper Positioned on Both Pins)
Pins
(Jumper Positioned on One Pin)
Figure 4: Positioning the Jumpers
Touchpad
Locked
JUMP2
P5
Installed
=
Removed
Heating Mode
Cut-in at Setpoint
Cooling Mode
Cut-in at Setpoint
P4
Heating Mode
Cut-out at Setpoint
Cooling Mode
Cut-out at Setpoint
Setpoint (SP) establishes the temperature value at which the equipment is switched on or off, depending on the user selected mode of operation. Setpoint range is -30 to 212°F or -34 to 100°C (in 1-degree increments).
If Setpoint mode is set to cut-in, setpoint is the temperature value at which the control closes the Normally Open (N.O.) contacts. If Setpoint mode is set to cutout, setpoint is the temperature at which the N.O. contacts open.
Differential (dIF) establishes the difference in temperature between the cut-in value and cutout value. The differential is set relative to Setpoint and may be set from 1 to 30 F° or C° (in 1-degree increments).
Anti-Short Cycle Delay (ASd) establishes the minimum time that the output relay remains de-energized before the next on-cycle. The ASd does not allow the output relay to re-energize until the programmed time delay has elapsed. The delay is activated when the control is first turned on and every time an on-cycle ends. When the delay is activated, the LCD alternately flashes the sensor temperature and ASd. The Anti-short Cycle Delay range is 0 to 12 minutes (in 1-minute increments).
Sensor Failure Operation (SF) establishes how the A419 control’s output-relay operates the equipment in the event of a sensor or sensor wiring failure. The user may select to run the equipment continuously or to shut it down. When the control detects a sensor circuit failure, the LCD flashes SF alternately with OP (if the sensor circuit is open), or SH (if the sensor circuit is shorted). Before indicating a failure, the control implements a 1-minute delay, which allows verification of failure condition and avoids nuisance failure indications.
Figure 5: Jumper Positions and Control Settings
Table 2: Jumper Designations, Jumper Positions, and Control Settings
Function
Cooling/Heating Operating Mode
Setpoint at
Cut-in or Cutout
Touchpad Lock P5
Jumper Pins Designation
on Control
JUMP1
(Top Pair of Pins on Block P4)
JUMP2
(Bottom Pair of Pins on Block P4)
4 A419ABG-3 Electronic Temperature Control Installation Instructions
Setting
Cooling Mode Removed
Heating Mode Installed
Setpoint at Cut-in
Setpoint at Cutout
Locked Removed
Jumper
Position
Removed
Installed
Factory Default Setting
(and Jumper Position)
Cooling Mode (Jumper Removed)
Cut-in (Jumper Removed)
Unlocked (Jumper Installed)
Temperature Offset (OFS) establishes a set secondary Setpoint and Differential values that may be invoked to control an application when a circuit is closed between the binary input (BIN) and common (COM) terminals (and BIN appears on the display). See Figure 6. Offset range is 0 to 50F° or C° (in 1-degree increments). A typical application might use a switching time clock to invoke night-setback temperature settings.
IMPORTANT: Make sure the Touchpad Lock jumper is installed (unlocked) before attempting to adjust the A419 control functions. See Figure 5.
If no setup entry is made for 30 seconds, the control reverts to the (normal) temperature display.
IMPORTANT: If MENU is not pressed after changing the setpoint value, the control reverts to the previously programmed setpoint value.
Temperature
Offset Indicator
Temperature
BIN
F
Units Indicator
Operating Mode
Indicator
Changing the A419 Control Temperature Units
The A419 control is factory set to display Fahrenheit temperature. To change to Celsius, press Up and Down (arrows) simultaneously. Press them again to display Fahrenheit units. Verify that the control is displaying the desired temperature units before setting the Setpoint.
Setting the A419 Control Setpoint Value
To view and adjust Setpoint, follow these steps:
1. Press and hold MENU (about 2 seconds) until the display flashes SP.
MENU
Figure 6: Liquid Crystal Display, Touchpad, and
LED Indicator
Liquid Crystal
Display
MENU
Button
DOWN
Arrow
Button
UP
Arrow
Button
Output Relay
Status Indicator
LED
2. Press MENU again to display the existing setpoint value.
3. Press Up or Down (arrows) to change the setpoint value.
4. Press MENU again to save the new value. The display returns to the sensed temperature.
Table 3: Display Symbols, Control Function, Ranges, Units, Values, and Factory Settings
Display Symbol
SP
dIF
ASd
OFS
SF
F or C
BIN
or
* The sum of the Setpoint and Differential values must be within the Setpoint range, or the control may not function
properly.
Control Function Range – Units/Value
Setpoint*
Differential*
Anti-short Cycle Delay 0 to 12 – (in 1-minute increments) 1
Temperature Offset
Sensor Failure Operation
Temperature Units
Temperature Offset Indicator
Cooling or Heating Mode of Operation
-30 to 212 – °F (-34 to 100 – °C)
1 to 30 – (F° or C° in 1-degree increments)
0 to 50 (F° or C° in 1-degree increments)
(No range) – 0 = output relay de-energized
1 = output relay energized
(No range) – F° or C°
(No range) – BIN is displayed and the A419 control operates on the secondary setpoints when the circuit between the BIN and COM terminals is closed.
(No range) – Jump1 jumper is removed. when the Jump1 jumper is installed.
(Cooling Mode) is displayed when the
(Heating Mode) is displayed
Factory Set Value
30
5
0
1
N/A
Cooling Mode
A419ABG-3 Electronic Temperature Control Installation Instructions 5
Setting the Other A419 Control Functions
To set the Differential, Anti-short Cycle Delay, Temperature Offset, or Sensor Failure operation, use the following method:
1. Press and hold MENU until the display changes to flashing SP. (This takes about 2 seconds.)
2. Press Up or Down (arrows) repeatedly until the desired function is displayed. (See Figure 6.)
3. Press MENU to display the function’s current value.
4. Press Up or Down (arrows) until the desired value is displayed.
5. Press MENU to save the new value. The display returns to the sensor temperature.
If the control system does not function properly, verify that the control is wired, and set up properly. If the problem persists, use the following procedures to determine the cause of the problem:
IMPORTANT: Follow these troubleshooting procedures in the order presented. Do not skip any of the steps in the procedures.
1. Check for proper voltage to the A419 control.
a. Remove the cover by loosening the four
captive cover screws.
b. Use a reliable AC voltmeter to check the
voltage between the COM and 120V terminals on terminal block TB1. Refer to Figure 2.
IMPORTANT: If MENU is not pressed after changing the settings, the new settings are not saved and the control reverts to the previously programmed setting values.
Note: If no setup entry is made for 30 seconds, the control reverts to the (normal) temperature display.
Note: Any saved A419 control settings are non-volatile and remain in the control’s memory
during power interruptions.
IMPORTANT: Do not set Setpoint and Differential values which (when totaled) fall out of A419 control’s Setpoint range (-30 to 212°F [-34 to 100°C]). The control will not function properly if Cut-in or Cutout values are outside of the control’s Setpoint range.
Checkout
Before applying power, make sure installation and wire connections are correct for your application. Then power, operate, and observe the system and A419 control for at least three complete operating cycles before leaving the installation.
Troubleshooting
c. The voltage must be between 102 and
132 VAC for 120 VAC applications.
d. If the voltage reading is not within the required
range, check the power source and input power wires for problems.
2. Check for proper sensor operation.
a. Disconnect all power sources to control.
b. Using an accurate thermometer, take a
temperature reading at the sensor location.
c. Disconnect the sensor from the control.
d. Using an ohmmeter, measure the resistance
across the two sensor leads while the sensor is at the temperature taken in Step 2b.
e. Consult Figure 7 to verify that the measured
temperature and resistance conform to established temperature and resistance values.
f. If the measured values conform to the values
in Figure 7, proceed to Step 3.
g. If the sensor’s measured resistance value is
substantially different from the expected value for that temperature, check the sensor wiring. If sensor wiring is okay, replace the sensor.
!
WARNING: Risk of Electrical Shock.
Do not touch any exposed metal parts with anything other than properly insulated tools or insulated probes of the digital voltage meter. Failure to use properly insulated tools and probes may result in severe personal injuries or death.
6 A419ABG-3 Electronic Temperature Control Installation Instructions
Temperature (°F)
260 240 220 200 180 160 140 120 100
80 60 40 20
0
-20
-40 500 700 900 1100 1300 1500 1700 1900 2100
Resistance in Ohms
Temperature (°C)
120
100
80
60
40
20
0
-20
-40
Figure 7: Temperature vs. Sensor Resistance
3. Check the A419 for proper operation.
Note: Perform Troubleshooting Steps 1 and 2 before
performing this step.
a. Disconnect the load from the output relay
terminals.
b. Ensure that the Touchpad Lock jumper is
installed, so that the touchpad is unlocked.
e. Check the control settings for proper values.
f. Press and hold MENU until Setpoint
appears. (This takes about 2 seconds.)
g. Press the Up and Down (arrows) to change
the Setpoint temperature above and below the sensor temperature until the relay energizes and de-energizes as shown in Figure 7.
Note: If the anti-short cycle delay has a set delay-time value greater than 0 minutes when the control is powered On, the relay does not energize until the time delay has elapsed.
h. If the output relay does not perform as
indicated in Figure 7, replace the A419 control.
i. If proper operation of the A419 control is
verified, reconnect the load and consult the equipment manufacturer’s instructions for troubleshooting the controlled equipment.
Fault Codes
If the LCD displays an alarm or fault code (SF or EE), consult Table 5 for explanation.
c. Reconnect the sensor leads and supply
power to the control.
d. Replace the cover.
Table 4: A419 Output Relay Operation in Different Operating Modes
Setpoint Mode
Cutout
Cut-in
Operating Mode
Cooling Setpoint plus differential Setpoint
Heating Setpoint minus differential Setpoint
Cooling Setpoint Setpoint minus differential
Heating Setpoint Setpoint plus differential
Output Relay Is Energized (closing the NO and COM contacts) at…
Output Relay Is De-Energized (opening the NO and COM contacts) at…
Table 5: Fault Codes Defined
Fault Code Definition System Status Solution
SF flashing alternately
OP
with
SF flashing alternately
with
SH
EE
Open temperature sensor or sensor wiring
Shorted temperature sensor or sensor wiring
Program failure Output is off
Output functions according to the selected sensor failure mode (SF setting)
Output functions according to the selected sensor failure mode (SF setting)
See Troubleshooting section.
Cycle power to reset the control.
See Troubleshooting section.
Cycle power to reset the control.
Reset the control by pressing MENU. If problems persist, replace the control.
A419ABG-3 Electronic Temperature Control Installation Instructions 7
Repairs and Replacement
Do not attempt to repair or recalibrate the A419 temperature control. In case of a defective or improperly functioning control, contact your nearest Authorized Johnson Controls/PENN distributor or sales representative.
Ordering Information
Refer to Table 6 to order sensors, mounting hardware and other accessories used to install A419 controls. Contact your nearest Johnson Controls/PENN distributor or sales representative to order these products.
When contacting your Johnson Controls/PENN distributor, have the model number of the control available. This number can be found on the label inside the cover of the control.
Table 6: A419 Controls Accessories
Product Code Number Description
A99BB-200 Temperature Sensor: PTC Sensor with 6-1/2 ft (2 m) Non-shielded 2-Wire Lead
BKT287-1R DIN Rail: 12 in. (305 mm) long
BKT287-2R DIN Rail: 36 in. (914 mm) long
PLT344-1R End Clamps for DIN Rail Mounting
CLK350-2C 7-Day Programmable Digital Clock for activating Binary Offset
WEL11A-601C Immersion Well for Mounting Sensor in Liquid Applications
Technical Specifications
Product
Setpoint Range
Differential Range
Supply Voltage
Power Consumption
SPST Output Relay
Contacts Electrical
Ratings
A419ABG-3C Electronic Temperature Control
-30 to 212°F (-34 to 100°C)
1 to 30F° (1 to 30C°)
120 VAC, 60 Hz
1.8 VA Maximum
Full Load Amperes N.O.: 12 A
Locked Rotor Amperes N.O. : 72 A
Non-inductive Amperes N.O.: 10 A
Pilot Duty: 125 VA @ 120 VAC
Sensor Type
Control Ambient
Temperature
Ambient Humidity
Control Enclosure Material
Agency Listings
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, contact Application Engineering at 1-800-275-5676. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
Controls Group
507 E. Michigan Street P.O. Box 423 Published in U.S.A. Milwaukee, WI 53201 www.johnsoncontrols.com
PTC Sensor with 6.6 ft (2.0 m) leads
Operating: -30 to 140°F (-34 to 60°C)
Shipping: -40 to 185°F (-40 to 85°C)
0 to 95% RH Noncondensing; Maximum Dew Point: 85°F (29°C)
Case and Cover: NEMA 1 - High-Impact Thermoplastic
UL: File E27734; CCN’s XAPX (US), XAPX7 (Canada) FCC: CFR 47, Part 15, Class A. DOC, Class A
8 A419ABG-3 Electronic Temperature Control Installation Instructions
Loading...