FANs 930, 930.5, 125, 121
Product/Technical Bulletin A350R
Issue Date April 8, 2014
System 350
A350R Electronic Temperature Reset Control (with Relay)
The A350R Electronic Temperature Reset Control is
designed to raise or lower the setpoint of supply water
temperature based upon a proportionate drop or rise
in temperature at the master (outdoor) sensor. The
control output is a Single-Pole, Single-Throw (SPST)
relay with Light-Emitting Diode (LED) relay status
indication.
The A350R’s differential may be adjusted for a given
application. An adjustable reset ratio adapts to a
variety of weather zones and to the specific heat loss
characteristics of most buildings.
TM
As are all System 350
housed in a NEMA 1, high-impact plastic enclosure.
The modular design provides easy, plug-together
connections for quick installation and future
expandability.
products, the A350R is
Figure 1: A350R Electronic Temperature
Reset Control
Features and Benefits
Modular Design Enables stage, display, and transformer
modules to be purchased and installed as
necessary
Adjustable Master Reset
Setpoint (M.R.S.)
Adjustable Minimum and
Maximum Supply
Temperature
Selectable Warm Weather
Shutdown Temperature
Adjustable Setback
Temperature
Enables the user to select a master (outdoor)
sensor temperature starting point for the
supply reset ramp
Permits compliance with equipment
manufacturer’s specifications
Saves energy by disabling equipment when
master sensor temperature rises to a point
where heating is no longer required
Saves energy by lowering the supply
temperature setpoint at night or during
unoccupied periods
The A350R Electronic Temperature Reset Control can
be used as a standalone device or in conjunction with
plug-together accessory modules. The addition of an
S350A or S350C for on/off output, or an S350P for a
proportional or proportional plus integral control,
allows this system to control a variety of single or
multiple stage Heating, Ventilation, and Air
Conditioning (HVAC) applications. Typical applications
include reset of single or multistage boilers.
peration
O
IMPORTANT: Use this A350R Electronic
Temperature Reset Control (with
Relay) only as an operating control.
Where failure or malfunction of the
reset module could lead to personal
injury or property damage to the
controlled equipment or other
property, additional precautions must
be designed into the control system.
Incorporate and maintain other
devices, such as supervisory or alarm
systems or safety or limit controls,
intended to warn of or protect against
failure or malfunction of the reset
module.
IMPORTANT: Utiliser ce A350R Electronic
Temperature Reset Control (with
Relay) uniquement en tant que
dispositif de contrôle de
fonctionnement. Lorsqu'une
défaillance ou un dysfonctionnement
du reset module risque de provoquer
des blessures ou d'endommager
l'équipement contrôlé ou un autre
équipement, la conception du système
de contrôle doit intégrer des dispositifs
de protection supplémentaires. Veiller
dans ce cas à intégrer de façon
permanente d'autres dispositifs, tels
que des systèmes de supervision ou
d'alarme, ou des dispositifs de
sécurité ou de limitation, ayant une
fonction d'avertissement ou de
protection en cas de défaillance ou de
dysfonctionnement du reset module.
The A350R operates on 24 VAC/VDC and provides a
Single-Pole, Single-Throw relay output. A front panel
LED lights to indicate the relay is energized. Features
include:
adjustable reset ratio
adjustable master reset setpoint
adjustable minimum and maximum supply
temperature
adjustable differential
selectable relay for Minimum ON Time
selectable warm weather shutdown temperature
adjustable setback temperature
Celsius Scale Conversion
As shipped from the factory, each A350R is installed
with the Fahrenheit temperature scale decal. A Celsius
temperature scale decal is provided under the cover of
the A350R. If the Celsius scale is desired, see the
Installation and Wiring section.
Reset Ratio Adjustment
Reset ratio is defined as the ratio of the change in
master sensor temperature to the change in supply
temperature setpoint. Example: For an application with
a reset ratio of 1:2, a one degree drop in master
sensor (for example, outdoor air) temperature causes
a two degree rise in the supply temperature setpoint.
Refer to Figure 2 for an example.
Reset ratio adjustment is made using the
potentiometer marked RESET RATIO. Refer to
Figure 4 for location.
Minimum Supply Temperature and Master
Reset Setpoint Adjustments
The minimum supply temperature and the master
reset setpoint adjustments determine the starting point
for the reset ramp. As the master (outdoor) sensor
temperature falls below the master reset setpoint, the
supply setpoint rises according to the reset ratio. As
the master sensor temperature rises above the master
reset setpoint, the supply setpoint will be maintained at
the minimum supply temperature. Refer to Figure 2 for
an example.
Minimum supply temperature adjustment is made
using the potentiometer marked MIN SUPPLY, and
master reset setpoint adjustment is made using the
potentiometer marked M.R.S. Refer to Figure 4 for
locations.
2 System 350 A350R Electronic Temperature Reset Control (with Relay) Product/Technical Bulletin
Maximum Supply Temperature
Adjustment
The maximum supply adjustment determines an end
point for the reset ramp. Refer to Figure 2 for an
example.
As the master sensor temperature drops below the
master reset setpoint, the supply setpoint temperature
rises according to the reset ratio. Upon further
reduction in master sensor temperature, the supply
setpoint temperature continues to rise until it reaches
the maximum supply temperature setpoint. The supply
temperature is maintained at the maximum supply
temperature setpoint even on a further decrease in
master sensor temperature. Use the formula found in
Adjustments section to determine the reset ratio.
Maximum supply temperature adjustment is made
using the potentiometer marked MAX SUPPLY.
Refer to Figure 4 for location.
Supply T emperature
Setpoint (°F)
200
T =20
D
Maximum Supply
Tempe r at ur e = 200
OFF
160
155
150
(Relay de-energized)
ON
(Rela y en er gized)
Supply Set point = 160° F
Dif ferential =
7 Degree s
Figure 3: Example of Differential
Minimum Relay ON Time Selection
In addition to the differential, the relay operation is also
affected by the selectable Minimum ON Time delay.
Once the relay is energized, it remains energized until
both the Minimum ON time has expired, and the
supply temperature is equal to or greater than the
calculated setpoint. The time delay applies only to the
relay internal to the A350R. A jumper block, located on
the cover mounted circuit board (refer to Figure 4), is
used to select one of four minimum ON time delay
settings: OFF, 1 min., 2 min., or 3 min.
180
Reset Ratio
160
140
120
100
Minimum Supply
Temper ature = 100
204060
Master S ensor Tempe r ature (°F)
(T = Design Temperature of the Building)
D
= (70-20):(200-100)
= 50:100
= 1:2
Master Reset
Setpoint = 70
70
Figure 2: Example of Reset Schedule for a
Hot Water Boiler Application
Differential Adjustment
Differential is the change in supply temperature
required to energize and to de-energize the relay.
Figure 3 is an example.
Warm Weather Shutdown Temperature
Selection
The A350R has a feature that automatically shuts
down the heating equipment when the master sensor
temperature rises to a value where heating is no
longer desired. When the master sensor drops 3°F
(1.7°C) below the warm weather setpoint temperature,
the A350R returns to standard operation.
A jumper block located on the base-mounted circuit
board is used to select one of five shutdown settings.
(Refer to Figure 4.) Available settings are OFF, 60°,
64°, 68°, and 72°F (OFF, 16°, 18°, 20°, and 22°C).
Placing the jumper block horizontally across the center
set of pins (OFF position) disables warm weather
shutdown. As shipped from the factory, the warm
weather shutdown feature is set to the OFF position.
IMPORTANT: Do not place the jumper across the
top or bottom two pins. This disables
the warm weather shutdown, and
causes a small shift in the maximum
supply setpoint and the master reset
setpoint.
The differential can be adjusted between 1 and 30F°
(0.5 to 17C°). Adjustment is made using the
potentiometer marked DIFF, as shown in Figure 4.
System 350 A350R Electronic Temperature Reset Control (with Relay) Product/Technical Bulletin 3
Setback Adjustment
The A350R has an integral setback feature which,
when enabled, lowers the calculated supply setpoint
by the setback value. This calculated supply setpoint
will not go below the Minimum Supply Temperature
setting.
Setback is enabled by an external time clock switch
that shorts terminals IN and COM together. The
CLK350 Time Control, which is compatible with the
A350R, requires a 24 VAC source. Other external time
controls may be used with the A350R, but they must
have a minimum switch rating of 5 mA at 5 VDC.
When enabled, the Setback LED on the face of the
A350R illuminates to indicate the control is operating
in the setback mode. Setback is adjustable from
0 to 30F° (0 to 17C°) via the setback potentiometer
located at the top of the cover-mounted circuit board.
See Figure 4 for its location.
dd-on Modules
A
The S350 Stage Modules, D350 Digital Temperature
Display Module, and Y350R Power Module connect
together and plug into the A350R via female
connectors located on the left side and male
connectors located on the right side of each module.
The maximum number of add-on modules is listed in
Table 1.
Table 1: Maximum Number of S350 Stage
Modules per A350R
Power
Source
Y350R
External
Class 2
Transformer
Number
of S350A
or S350C
Modules
Allowed
9 6 4
9 8 7
Number
of S350A
or S350C
Modules
(with
1 S350P)
Allowed
Number
of S350A
or S350C
Modules
(with
2 S350Ps)
Allowed
S350A On-Off Stage Modules
S350A On-Off Stage Modules receive power, setpoint,
and sensor input from the A350R Reset Control. The
S350A Stage Modules perform switching functions
based on the A350R’s calculated supply setpoint and
supply sensor temperature, but the offset and
differential are selected within the S350A.
Note: Plug the S350A only into the right side of the
A350R. The S350A will not function properly if
plugged into the left side of the A350R.
For more information on these modules, refer to
System 350
S352 Pressure On/Off Stage Modules
Product/Technical Bulletin (LIT-930080).
TM
S350 Temperature, S351 Humidity, and
S350C Slave Stage Modules
S350C Slave Stage Modules receive power, and
sensor input from the A350R Reset Control. S350C
Slave Stage Modules perform switching functions
based on the setpoint and differential selected at the
S350C.
Note: Unlike the S350A, the S350C can plug into
either side of the A350R. When the S350C is
plugged into the left side of the A350R, it
controls to the S350C setpoint based on the
master sensor temperature input. When the
S350C is plugged into the right side of the
A350R, it controls to the S350C setpoint
based on the supply sensor temperature.
For more information on these modules, refer to
System 350
Module Product/Technical Bulletin (LIT-930084).
TM
S350C Temperature Slave Stage
S350P Proportional Stage Modules
S350P Proportional Stage Modules receive power,
setpoint, and sensor input from the A350R Reset
Control. The S350P Proportional Stage Module
responds with an analog 0 to 10 VDC and 0 to 20 mA
output signal based on the A350R’s calculated supply
setpoint and sensor temperature, as well as the offset
and throttling range selected at the S350P.
Note: For each S350P added, the number of S350A
or S350C Stage Modules that can be used
with a Y350R decreases by two. If an external
transformer is used, the number of S350A and
S350C Stage Modules used decreases by one
for each additional S350P.
4 System 350 A350R Electronic Temperature Reset Control (with Relay) Product/Technical Bulletin
Note: Plug the S350P only into the right side of the
A350R. The S350P will not function properly if
plugged into the left side of the control.
For more information on these modules, refer to
System 350
Temperature Stage Module Product/Technical Bulletin
(LIT-930086).
TM
S350P Proportional Plus Integral
Loading...
+ 9 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.