Johnson Controls A28PA-2C, A28PJ-1C Data Sheet

Johnson Controls A28PA-2C, A28PJ-1C Data Sheet

Multi-Stage Electromechanical Temperature Controls

Code No. LIT-1927130

 

 

A28 Two-Stage Agricultural Thermostat with NEMA 4X Enclosure

Description

The A28PJ and A28PA are two-stage temperature controls with raintight and dusttight enclosures.

Refer to the A28 Series Two-Stage Temperature Controls with NEMA1 Enclosure Product Bulletin (LIT-125130) for important product application information.

Features

rugged thermoplastic gasketed enclosures that meet NEMA 4X specifications

O-ring sealed setpoint adjustment knobs

range scale with oversized white markings for easy readability in low light

exposed portion of liquid-filled sensing elements are plated and plastic coated to resist damage in corrosive atmospheres

Applications

Designed for use in agricultural and industrial applications that require compliance with Article 547 of the National Electrical Code.

Repair Information

If the A28 Two-Stage Agricultural Thermostat with NEMA 4X Enclosure fails to operate within its specifications, replace the unit. For a replacement thermostat, contact the nearest Johnson Controls® representative.

A28PJ, A28PA Thermostat

Selection Chart

Product Code Number

Switch Action

Range °F (°C)

Differential F° (C°)

Bulb and Capillary

Range Adjuster

A28PJ-1C

Two-SPDT

30 to 110

2 (1.1) each stage

1-3/8 in. x 2-1/4 in.

Knob

 

 

(-1 to 43)

2 to 7 (1.1 to 3.9) adjustable between stages

coiled

 

 

 

 

 

 

 

A28PA-2C

Two-SPDT

30 to 110

2 (1.1) each stage

1-3/8 in. x 2-1/4 in.

Knob

 

 

(-1 to 43)

2 to 7 (1.1 to 3.9) adjustable between stages

coiled

 

Technical Specifications

Electrical Ratings

 

 

 

 

 

Motor Ratings VAC

120

208

 

240

277

 

 

A28PJ

 

 

 

AC Full Load A

6.0

3.4

 

3.0

AC Locked Rotor A

36.0

20.4

 

18.0

Non-Inductive or Resistance Load A

10.0

9.2

 

8.0

7.2

(Not Lamp Loads)

 

 

 

 

 

Pilot Duty

 

 

125

VA, 24 to 277 VAC1

 

 

 

A28PA

 

 

 

AC Full Load A

16.0

9.2

 

8.0

AC Locked Rotor A

96.0

55.2

 

48.0

Non-Inductive or Resistance Load A

16.0

9.2

 

8.0

7.2

(Not Lamp Loads)

 

 

 

 

 

Pilot Duty

 

 

125

VA, 24 to 277 VAC1

 

1. When used as a two-circuit control, the total connected load must not exceed 2,000 VA.

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult th Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.

R-64