Johnson Controls A25CN Series Manual Reset

PSC9629
Serie A25CN
Limit Control Manual Reset
I
These warm air limit controls "lock out" on a temperature increase to the control setpoint. Manual reset is required to re-close the electrical contacts. A typical application is to stop air-conditioning or ventilating fans in the event of excessive return air temperature, as
from a fire.
D
escription
A rod and tube type sensing element actuates the switch contacts. Main contacts (1 - 2) are normally closed, and open when the temperature at the element rises to the dial setpoint. Contacts are re-closed only by operation of the reset lever. The reset lever is "trip-free" and cannot be used to block contacts in a closed position.
European Refrigeration Controls Catalogue
ote
N
Catalog Section 1 Product Bulletin A25
Issue 25/04/2003
A25CN
L
ocation
Select a location in the duct or plenum where the temperature element senses the average temperature to be controlled and is in free air circulation.
M
ounting
The instrument is mounted by means of the flange which is supplied with the control. The element is to be inserted in the duct and must be in the airstream as much as possible. It should not be in contact with any object inside the duct.
These controls are designed for use only as operating controls. Where an operating control failure would result in personal injury or loss of property it is the responsibility of the installer to add devices or systems that protect against, or warn of, control failure.
A
djustment
These thermostats are standard available with a knob adjustment. This knob can be removed in the field to provide screwdriver adjustment.

Feature and Benefits

Rod and tube type of element Gives maximum response
Allows high maximum element temperature
Adjustable duct mounting flange Allows various lengths insertion of the element
into the airstream
Trip-free manual reset Override is not possible in the control function
Dust-tight Penn switch
Prevent pollution of the contacts by
electromagnetic influences
© 2003 Johnson Controls Inc. Catalogue Section 1
Order No. PD-A25-E
2
C
ontact function
R
epair and replacement
Issue 25/04/2003
A25
2
Fig. 1
1 - 2 opens on temperature increase.
3
? >
1
imensions (mm)
D
Repair is not possible. In case of an improperly functioning control, please check with your nearest supplier. When contacting the supplier for a replacement you should state the type/model number of the control. This number can be found on the data plate or cover label.
1 Dial knob 2 Reset lever 3 Flange 4 Set screw 1/4 "- 20 UNC 5 Ø 22.3 cable inlet hole for PG 16.
Catalogue Section 1 © 2003 Johnson Controls Inc.
Order No. PD-A25-E