Johnson Controls A19ZBC-2C Data Sheet

A19ZBC-2 Defrost Duration and
Fan Delay Control
Single-Stage Electromechanical Temperature Controls
A19 Defrost Duration and Fan Delay Control
The A19 Defrost Duration and Fan Delay Control is a remote bulb control with adjustable defrost termination temperature and preset fan delay temperature.
Refer to the A19ZBC Type Temperature Control Product Bulletin (LIT-121071) for important product application information.
Features
• sensing element unaffected by barometer pressure and cross ambient temperature problems
• limited adjustment range
Applications
Use for defrost termination control for refrigerated display cases.
Selection Chart
Product Code Number
A19ZBC-2C Single-Pole,
Switch Action
Double-Throw (SPDT)
Code No. LIT-1927095
Repair Information
If the A19 Defrost Duration and Fan Delay Control fails to operate within its specifica tions, replace the unit. For a replacement cont rol, contact the nearest Johnson representative.
Controls®
Technical Specifications
• maximum bulb temperature: 140°F (60°C)
• fan delay temperature: factory set at 25°F (-4°C)
Electrical Ratings
Motor Ratings VAC 120 208 240
AC Full Load A 16.0 9.2 8.0 AC Locked Rotor A 96.0 55.2 48.0
Non-Inductive or Resistance Load A (Not Lamp Loads)
Pilot Duty 125 VA, 24 to 277 VAC
Defrost Termination °F (°C)
45 to 85 (7 to 29) 19/64 in. x 3-1/8 in.; 6 ft. capillary Knob
16.0 9.2 8.0
Bulb and Capillary
Range Adjuster
The performance specifications are nomina l and con form to accep table ind ustry stand ards. For applicati ons at con ditions be yond these specification s, consult th Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.