A19ZBA Water Chiller Control
Single-Stage Electromechanical Temperature Controls
A19 Water Chiller Control with Locked Cut-Out/Adjustable Cut-In
Description
The A19 Water Chiller Control is a remote bulb
temperature control with limited setpoint
range, adjustable differential, and adjustable
cut-out.
Refer to the A19ZBA Type Temperature
Control Product Bulletin (LIT-121065) for
important product application information.
Features
• adjustable cut-out (38 to 47°F)
• wide differential adjustment range
Accessories
• includes Code No. FTG13A-600R Packing
Nut as standard
• replacement cover: CVR61A-600R
Selection Chart
Product Code
Number
A19ZBA-1C Single-Pole, Single-Throw
Switch
Action
(SPST)
Close high, open low
Range
°F (°C)
38 to 80 (3 to 27) 8 to 40 (4 to 22)
Applications
Use for water chillers.
Repair Information
If the A19 Water Chiller Control with Locked
Cut-Out/Adjustable Cut-In fails to operate
within its specifications, replace the unit. For a
replacement control, contact the nearest
Johnson
Controls®
representative.
Technical Specifications
Maximum bulb temperature is 140°F (60°C).
Electrical Ratings
Motor Ratings VAC 120 208 240
AC Full Load A 16.0 9.2 8.0
AC Locked Rotor A 96.0 55.2 48.0
Non-Inductive or
Resistance Load A
(Not Lamp Loads)
Pilot Duty 125 VA, 24 to 277 VAC
Differential
F° (C°)
Adjustable
16.0 9.2 8.0
Bulb and
Capillary
3/8 in. x 3-7/16 in.
6 ft. capillary
Code No. LIT-1927090
Bulb Well No.
(Order Separately)
WEL14A-602R Knob
Range
Adjuster
The performance specifications are nomina l and con form to accep table ind ustry stand ards. For applicati ons at con ditions be yond these specification s, consult th
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.
R-37