Jenn-Air JXW8236WS, JXW8030WS, JXW6030WR User Manual

JENN-AIR® 30" AND 36" (76.2 CM AND 91.4 CM)
WALL-MOUNT CANOPY RANGE HOOD
HOTTE DE CUISINIÈRE JENN-AIR® POUR MONTAGE
MURAL 30" ET 36" (76,2 CM ET 91,4 CM)
Installation Instructions and Use & Care Guide
1-800-JennAir (1-800-536-6247) or visit our website at www.jennair.com.
In Canada, call: 1-800-807-6777, or visit our website at www.jennair.ca.
Instructions d’installation et Guide d’utilisation et d’entretien
Au Canada, pour assistance, installation ou service, composez le 1-800-807-6777 ou visitez notre site web à www.jennair.ca.
Table of Contents/Table des matières...................2
IMPORTANT: READ AND SAVE THESE INSTRUCTIONS. FOR RESIDENTIAL USE ONLY. IMPORTANT : LIRE ET CONSERVER CES INSTRUCTIONS. POUR UTILISATION RÉSIDENTIELLE UNIQUEMENT.
LI3U1B/W10274303G
TABLE OF CONTENTS
TABLE DES MATIÈRES
RANGE HOOD SAFETY .................................................................3
INSTALLATION REQUIREMENTS................................................5
Tools and Parts ............................................................................5
Location Requirements................................................................5
Venting Requirements..................................................................6
Electrical Requirements ...............................................................7
INSTALLATION INSTRUCTIONS.................................................. 7
Prepare Location..........................................................................7
Install Range Hood.......................................................................8
Connect Vent System ..................................................................9
Make Electrical Connection .......................................................10
Install Vent Covers .....................................................................10
Install Filters................................................................................11
Complete Installation .................................................................11
RANGE HOOD USE......................................................................11
Display........................................................................................11
Light............................................................................................12
Timer...........................................................................................12
Fan Speed Buttons ....................................................................12
RANGE HOOD CARE...................................................................12
Cleaning......................................................................................12
WIRING DIAGRAM ......................................................................14
ASSISTANCE OR SERVICE.........................................................15
WARRANTY ..................................................................................16
SÉCURITÉ DE LA HOTTE DE CUISINIÈRE ...............................18
EXIGENCES D'INSTALLATION...................................................20
Outillage et pièces......................................................................20
Exigences d'emplacement.........................................................20
Exigences concernant l’évacuation ...........................................21
Spécifications électriques ..........................................................22
INSTRUCTIONS D’INSTALLATION.............................................23
Préparation de l'emplacement...................................................23
Installation de la hotte ................................................................24
Raccordement du circuit d'évacuation......................................24
Raccordement électrique...........................................................25
Installation du cache-conduit.....................................................26
Installation des filtres..................................................................26
Achever l’installation ..................................................................26
UTILISATION DE LA HOTTE .......................................................26
Afficheur .....................................................................................27
Éclairage.....................................................................................27
Minuterie.....................................................................................27
Boutons de vitesse du ventilateur..............................................27
ENTRETIEN DE LA HOTTE DE CUISINIÈRE .............................28
Nettoyage ...................................................................................28
SCHÉMA DE CÂBLAGE ..............................................................29
ASSISTANCE OU SERVICE.........................................................30
GARANTIE.....................................................................................31
2
RANGE HOOD SAFETY
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others. All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING.”
These words mean:
You can be killed or seriously injured if you don't immediately
DANGER
WARNING
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can happen if the instructions are not followed.
follow instructions.
can be killed or seriously injured if you don't
You instructions.
follow
3
IMPORTANT SAFETY INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC
SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
Use this unit only in the manner intended by the
manufacturer. If you have questions, contact the manufacturer.
Before servicing or cleaning the unit, switch power off at
service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
Installation work and electrical wiring must be done by
qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction.
Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the heating equipment manufacturer's guideline and safety standards such as those published by the National Fire Protection Association (NFPA), the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
When cutting or drilling into wall or ceiling; do not damage
electrical wiring and other utilities.
Ducted fans must always be vented outdoors. CAUTION: For general ventilating use only. Do not use
to exhaust hazardous or explosive materials and vapors.
CAUTION: To reduce risk of fire and to properly exhaust
air, be sure to duct air outside - do not vent exhaust air into spaces within walls or ceilings, attics or into crawl spaces, or garages.
WARNING: TO REDUCE THE RISK OF FIRE, USE ONLY
METAL DUCTWORK.
WARNING: TO REDUCE THE RISK OF A RANGE TOP
GREASE FIRE:
Never leave surface units unattended at high settings.
Boilovers cause smoking and greasy spillovers that may ignite. Heat oils slowly on low or medium settings.
Always turn hood ON when cooking at high heat or when
flambeing food (i.e. Crepes Suzette, Cherries Jubilee, Peppercorn Beef Flambé).
Clean ventilating fans frequently. Grease should not be
allowed to accumulate on fan or filter.
Use proper pan size. Always use cookware appropriate for
the size of the surface element.
WARNING: TO REDUCE THE RISK OF INJURY TO
PERSONS IN THE EVENT OF A RANGE TOP GREASE FIRE, OBSERVE THE FOLLOWING:
SMOTHER FLAMES with a close fitting lid, cookie sheet, or
metal tray, then turn off the burner. BE CAREFUL TO PREVENT BURNS. If the flames do not go out immediately, EVACUATE AND CALL THE FIRE DEPARTMENT.
NEVER PICK UP A FLAMING PAN - you may be burned.
DO NOT USE WATER, including wet dishcloths or towels -
a violent steam explosion will result.
Use an extinguisher ONLY if:
– You know you have a class ABC extinguisher, and you
already know how to operate it.
– The fire is small and contained in the area where it
started. – The fire department is being called. – You can fight the fire with your back to an exit.
a
Based on "Kitchen Fire Safety Tips" published by NFPA.
WARNING: To reduce the risk of fire or electrical shock,
do not use this fan with any solid-state speed control device.
a
READ AND SAVE THESE INSTRUCTIONS
4
INSTALLATION REQUIREMENTS
Tools and Parts
Gather the required tools and parts before starting installation. Read and follow the instructions provided with any tools listed here.
Tool s neede d
Level
Drill with 1¼" (3.0 cm), ³⁄₈" (9.5 mm), ⁷⁄₆₄" (2.75 mm) and
¹⁄₈" (3.0 mm) drill bits
Pencil
Wire stripper or utility knife
Tape measure or ruler
Pliers
Caulking gun and weatherproof caulking compound
Vent clamps
Jigsaw or keyhole saw
Flat-blade screwdriver
Metal snips
Phillips screwdriver
Parts needed
Home power supply cable
½" (12.7 mm) UL listed or CSA approved strain relief
3 UL listed wire connectors
For vented installations, you will also need:
1 wall or roof cap
Metal vent system
For non-vented (recirculating) installations, you will also need:
Recirculation Kit Part Number W10272064 for non-vented
(recirculating) installations only. See “Assistance or Service” section to order.
Location Requirements
IMPORTANT: Observe all governing codes and ordinances. Have a qualified technician install the range hood. It is the
installer's responsibility to comply with installation clearances specified on the model/serial rating plate. The model/serial rating plate is located behind the left filter on the rear wall of the vent hood.
Canopy hood location should be away from strong draft areas, such as windows, doors and strong heating vents.
Cabinet opening dimensions that are shown must be used. Given dimensions provide minimum clearance.
Grounded electrical outlet is required. See “Electrical Requirements” section.
The canopy hood is factory set for venting through the roof or wall. For non-vented (recirculating) Installation see “For Non­vented (recirculating) Installations” in “Connect Vent System” section. Recirculation Kit Part Number W10272064 is available from your dealer or an authorized parts distributor.
All openings in ceiling and wall where canopy hood will be installed must be sealed.
For Mobile Home Installations
The installation of this range hood must conform to the Manufactured Home Construction Safety Standards, Title 24 CFR, Part 328 (formerly the Federal Standard for Mobile Home Construction and Safety, Title 24, HUD, Part 280) or when such standard is not applicable, the standard for Manufactured Home Installation 1982 (Manufactured Home Sites, Communities and Setups) ANSI A225.1/NFPA 501A, or latest edition, or with local codes.
Product Dimensions
14 ⁷⁄₈"
(37.8 cm)
12 ³⁄₄"
(32.3 cm)
Parts supplied
Remove parts from packages. Check that all parts are included.
Hood canopy assembly with ventilator and light bulbs
installed
2 glass mounting brackets
Vent transition with back draft dampers installed
Blower support bracket
Glass mantle
Vent cover support bracket (3 pieces)
Mounting template
2-piece vent cover
2 - 2.9 x 6.5 mm screws
8 - 4 x 8 mm screws
6 - 5 x 45 mm mounting screws
2 - 8 x 40 mm wall anchors
4 - 10 x 50 mm wall anchors
35" (88.9 cm) min. *60 ³⁄₄" (154.3 cm) max. 56 ⁵⁄₁₆" (143.0 cm) max.
19 ³⁄₄"
(50 cm)
28"
(71.7 cm)
*For non-vented (recirculating) installations
30" - 36"
(76.2 cm - 91.4 cm)
5
Installation Dimensions
13 ⁷⁄₈"
11 ⁷⁄₈"
(30 cm)
"X" bottom of canopy to cooking surface
14 ¹⁄₄"
(36 cm)
(35 cm)
*8" (20.3 cm) min.
2" (5.1 cm) min.
26 ⁷⁄₈"
(68 cm)
30" - 36"
(76.2 cm - 91.4 cm)
cooking surface
*For non-vented (recirculating) installations
IMPORTANT:
Minimum distance “X”: 24" (61.0 cm) from electric cooking surface. Minimum distance “X”: 27" (68.6 cm) from gas cooking surfaces. Suggested maximum distance “X”: 36" (91.4 cm)
For vented installations, the chimneys can be adjusted for ceilings between 8’ (2.44 m) and 10’ 2" (3.1 m).
For non-vented (recirculating) installations, the chimneys can be adjusted for ceilings between 8’ (2.44 m) and 10’ 6" (3.2 m).
*NOTE: The range hood chimneys are adjustable and designed to
meet varying ceiling or soffit heights depending on the distance “X” between the bottom of the range hood and the cooking surface. For higher ceilings, a Stainless Steel Chimney Extension Kit Part Number W10272071 is available from your dealer or an authorized parts distributor. The chimney extension replaces the upper chimney shipped with the range hood.
Venting Requirements
(vented models only)
Vent system must terminate to the outdoors, except for non-
vented (recirculating) installations.
Do not terminate the vent system in an attic or other enclosed
area.
Do not use 4" (10.2 cm) laundry-type wall cap.
Use metal vent only. Rigid metal vent is recommended.
Plastic or metal foil vent is not recommended.
The length of vent system and number of elbows should be
kept to a minimum to provide efficient performance.
For the most efficient and quiet operation:
Use no more than three 90° elbows.
Make sure there is a minimum of 24" (61 cm) of straight vent
between the elbows if more than 1 elbow is used.
Do not install 2 elbows together.
Use clamps to seal all joints in the vent system.
The vent system must have a damper. If the roof or wall cap
has a damper, do not use the damper supplied with the range hood.
Use caulking to seal exterior wall or roof opening around the
cap.
The size of the vent should be uniform.
Cold Weather Installations
An additional back draft damper should be installed to minimize backward cold air flow and a thermal break should be installed to minimize conduction of outside temperatures as part of the vent system. The damper should be on the cold air side of the thermal break.
The break should be as close as possible to where the vent system enters the heated portion of the house.
Makeup Air
Local building codes may require the use of makeup air systems when using ventilation systems greater than specified CFM of air movement. The specified CFM varies from locale to locale. Consult your HVAC professional for specific requirements in your area.
Venting Methods
This canopy hood is factory set for venting through the roof or wall.
A 8" (20.0 cm) round vent system is needed for installation (not included). The hood exhaust opening is 8" (20.0 cm) round.
NOTE: Flexible vent is not recommended. Flexible vent creates back pressure and air turbulence that greatly reduce performance.
Vent system can terminate either through the roof or wall. To vent through a wall, a 90° elbow is needed.
Rear discharge
A 90° elbow may be installed immediately above the hood.
For Non-Vented (recirculating) Installations
If it is not possible to vent cooking fumes and vapors to the outside, the hood can be used in the non-vented (recirculating) version, fitting a charcoal filter and the deflector. Fumes and vapors are recycled through the top grille.
Roof Venting Wall Venting Non-vented
(recirculating)
A. Roof cap B. 8" (20.0 cm)
round vent
NOTE: Wall venting may not be possible for all installations.
A. Wall cap B. 8" (20.0 cm)
round vent
A. Deflector B. 8" (20.0 cm)
round vent
6
Calculating Vent System Length
To calculate the length of the system you need, add the equivalent feet (meters) for each vent piece used in the system.
Vent Piece 8" (20.0 cm) Round
45° elbow 2.5 ft
90° elbow 5.0 ft
Maximum equivalent vent length is 35 ft (10.7 m).
(0.8 m)
(1.5 m)
Example vent system
90 elbow
2 ft
(0.6 m)
The following example falls within the maximum recommended vent length of 35 ft (10.7 m).
1 - 90° elbow = 5.0 ft (1.5 m) 1 - wall cap = 0.0 ft (0.0 m) 8 ft (2.4 m) straight = 8.0 ft (2.4 m)
Length of system = 13.0 ft (3.9 m)
6 ft (1.8 m)
Wall cap
If the house has aluminum wiring, follow the procedure
below:
1. Connect a section of solid copper wire to the pigtail
leads.
2. Connect the aluminum wiring to the added section of
copper wire using special connectors and/or tools designed and UL listed for joining copper to aluminum.
Follow the electrical connector manufacturer's recommended procedure. Aluminum/copper connection must conform with local codes and industry accepted wiring practices.
Wire sizes and connections must conform with the rating of
the appliance as specified on the model/serial rating plate. The model/serial plate is located behind the filter on the rear wall of the range hood.
Wire sizes must conform to the requirements of the National
Electrical Code, ANSI/NFPA 70 (latest edition), or CSA Standards C22. 1-94, Canadian Electrical Code, Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes and ordinances.
INSTALLATION INSTRUCTIONS
Prepare Location
It is recommended that the vent system be installed before
hood is installed.
Before making cutouts, make sure there is proper clearance
within the ceiling or wall for exhaust vent.
Check your ceiling height and the hood height maximum
before you select your hood.
1. Disconnect power.
2. Determine which venting method to use: roof, wall, or non-
vented.
3. Select a flat surface for assembling the range hood. Place
covering over that surface.
Electrical Requirements
Observe all governing codes and ordinances. Ensure that the electrical installation is adequate and in
conformance with National Electrical Code, ANSI/NFPA 70 (latest edition), or CSA Standards C22.1-94, Canadian Electrical Code, Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes and ordinances.
If codes permit and a separate ground wire is used, it is recommended that a qualified electrician determine that the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park
Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
A 120 Volt, 60 Hz., AC only, 15-amp, fused electrical circuit is
required.
WARNING
Excessive Weight Hazard
Use two or more people to move and install range hood.
Failure to do so can result in back or other injury.
4. Using 2 or more people, lift range hood onto covered surface.
Range Hood Mounting Screws Installation
5. Determine and mark the centerline on the wall where the
canopy hood will be installed.
6. Select a mounting height between a minimum of
24" (61.0 cm) for an electric cooking surface, a minimum of 27" (68.6 cm) for a gas cooking surface, and a suggested maximum of 36" (91.4 cm) above the range to the bottom of the hood and mark a reference line on the wall.
7. Tape template in place, aligning the template centerline and
bottom of template with hood bottom line and with the centerline marked on the wall.
7
F
B
2. Install vent cover bracket to wall about ¹⁄₈" (3.0 mm) away
from the ceiling. Use 2 - 5 x 45 mm screws with 8 x 40 mm drywall anchors supplied.
A
E
B
C
D
A. Centerline B. Lower support bracket C. 5 x 45 mm screws D. Mounting height reference E. Fastener locations
F. W al l
8. Place the support bracket on the template aligning it with the
traced rectangle. Mark centers of 4 fastener locations through the template to the wall, 2 for support bracket, 2 for bottom rear of blower housing.
IMPORTANT: All screws must be installed into wood. Remove the template.
9. Drill ⁷⁄₆₄" (2.75 mm) pilot holes at all locations where screws
are being installed into wood. NOTE: When mounting into a concrete wall, drill ⁵⁄₁₆" (8 mm)
pilot holes and use anchors supplied.
10. Attach the support bracket to the wall using 2 - 5 x 45 mm
screws at the top 2 drilled hole locations.
A. Vent cover bracket B. Centerline on wall
Complete Preparation
1. Determine and make all necessary cuts in the wall for the vent
system. Install the vent system before installing the hood. See “Venting Requirements” section.
2. Determine the required height for the home power supply
cable and drill a 1¼" (3.2 cm) hole at this location.
3. Run wire through the home power supply cable according to
the National Electrical Code or CSA Standards and local codes and ordinances. There must be enough ½" conduit and wires from the fused disconnect (or circuit breaker) box to make the connection in the hood’s electrical terminal box.
NOTE: Do not reconnect power until installation is complete.
4. Use caulk to seal all openings.
Install Range Hood
1. Using 2 or more people, hang blower housing on lower
support bracket using the 2 mounting hooks on the rear of the blower housing.
A. Support bracket B. 5 x 45 mm screws C. Centerline on wall
Vent Cover Bracket Assembly and Installation
1. Assemble the 3 pieces of the vent cover bracket using 4 -
4 x 8 mm screws provided. The assembled bracket should be sized to dimension "X" to fit inside the upper vent cover.
C
A. Vent cover bracket assembly B. Upper vent cover
C. 4 x 8 mm screws
8
A. Lower support bracket B. Mounting hooks C.Adjust in and out
(for leveling front to back).
D. Adjust up and down
(for leveling left to right).
E. Blower housing
2. Level the blower housing with leveling screws in mounting
hooks, using a level across bottom of blower housing.
3. Remove the metal grease filter and secure the blower
housing with two screws in the bottom holes located in the rear of the blower.
A. Rear of blower housing B. Bottom 5 x 45 mm screw holes
Glass Mantle Installation
1. Place the glass mantle onto the hood.
2. Connect glass mantle to range hood with the 2 glass
mounting brackets and four 4 x 8 mm screws.
C
Connect Vent System
Vented Installation Only
1. Fit vent system over transition piece.
2. Seal connection with clamps.
3. Check that backdraft dampers work properly.
For Non-vented (Recirculating) Installation:
1. Assemble the 3 parts of the deflector with 2 - 3.5 x 9.5 mm
screws provided. The assembled deflector should be sized to fit the width of the vent cover bracket installed earlier.
C
A
B
A. Vent cover bracket width B. Deflector C. 3.5 x 9.5 mm screws
2. Connect the deflector to the vent cover bracket using 4 - 3.5
x 9.5 mm screws provided.
A
B
B
A
B
B
A. Vent cover bracket
A. Glass mantle B. Glass mounting bracket C. 4 x 8 mm screws
3. Measure the length of 8" (20.3 cm) round vent (not provided)
B. 3.5 x 9.5 mm screws
needed to connect the transition to the deflector. NOTE: Vent should fit inside deflector a minimum of
1" (2.5 cm)
4. Install vent between the transition and the deflector.
5. Seal connection with clamps.
6. Check that backdraft dampers work properly.
9
Make Electrical Connection
C
B
WARNING
Electrical Shock Hazard Disconnect power before servicing. Replace all parts and panels before operating. Failure to do so can result in death or electrical shock.
1. Disconnect power.
2. Remove terminal box cover.
3. Remove the knockout in the terminal box cover and install a
UL listed or CSA approved ¹⁄₂" strain relief.
4. Run 3 wires, black, white and green (14AWG), in ¹⁄₂" conduit
from service panel to terminal box. Use caulking to seal opening.
B
A
WARNING
Electrical Shock Hazard Electrically ground blower. Connect ground wire to green and yellow ground wire
in terminal box. Failure to do so can result in death or electrical shock.
7. Connect green (or bare) ground wire from home power supply
to yellow-green ground wire (E) in terminal box using UL listed wire connectors.
8. Tighten strain relief screw.
9. Install terminal box cover.
10. Check that all light bulbs are secure in their sockets.
11. Reconnect power.
Install Vent Covers
Push lower cover down onto hood and lift upper cover to ceiling and install with two 2.9 x 6.5 mm screws.
NOTE: For vented installations the upper vent cover may be reversed to hide slots.
C
D
F
E
A. UL listed or CSA approved strain relief B. Home power supply cable C. Terminal box D. Black wires E. Green (or bare) wire connected to yellow-green wire
F. White w i r e s
5. Use UL listed wire connectors and connect black wires (D)
together.
6. Use UL listed wire connectors and connect white wires (F)
together.
A
D
D
A. Vent cover bracket B. Upper vent cover C. Lower vent cover D. 2.9 x 6.5 mm screws
10
Loading...
+ 22 hidden pages