■ A UL listed or CSA approved strain relief for M\," (2.2 cm)
■ (4) UL listed wire connectors for 8-gauge wires
For vented installations:
■ 3Z\v" x 10" (8.3 cm x 25.4 cm) metal ducting
■ Jenn-Air
For non-vented installations:
■ Recirculation Kit part number W10807915 (See the
†
®TORX and T20 are registered trademarks of Acument Intellectual Properties, LLC.
TORX®† drivers
strain reliefs)
to cabinet)
cabinet floor)
blower motor assembly bottom)
mounting brackets)
to cooktop)
knockout
®
wall cap:
Jenn-Air® 3¼" x 10" (8.3 cm x 25.4 cm) Surface Wall Cap
Damper part number A403.
See the “Assistance or Service” section in your Use and
Care manual to order.
“Assistance or Service” section in your Use and Care
manual to order.)
a. Recirculation duct housing
b. (4) Mounting screws
c. (2) Charcoal filters
d. Recirculation housing cover
e. (2) Mounting screws – cover
f. Duct extension
g. (4) Mounting screws – duct extension
For non-vented installations side recirculation only:
■ 3Z\v" x 10" (8.3 cm x 25.4 cm) metal duct – length required
is determined by the distance from the exhaust outlet to the
back flat surface of the Recirculation Kit housing.
Check local codes. Check existing electrical supply. See the
“Electrical Requirements” section.
It is recommended that all electrical connections be made by
a licensed, qualified electrical installer.
Location Requirements
IMPORTANT: Observe all governing codes and ordinances.
When installing the cooktop, use the minimum dimensions given.
■ To eliminate the risk of burns or fire by reaching over the
heated surface units, cabinet storage space located above
the surface units should be avoided. If cabinet storage is to
be provided, the risk can be reduced by installing a range
hood that projects horizontally a minimum of 5" (12.7 cm)
beyond the bottom of the cabinets.
■ Use the countertop opening dimensions that are given
with these Installation Instructions. Given dimensions are
minimum clearances and provide 0" (0 cm) clearance.
■ The model/serial/rating label is located on the front face of
the electrical junction box cover.
A
A. Model/serial/rating label location
■ Grounded electrical supply is required. See the “Electrical
Requirements” section.
■ If cabinet has drawers, drawers will need to be removed
and drawer fronts installed on front of cabinet.
NOTE: The exhaust system is for outside venting. For
non-vented (recirculating) installation, see “For non-vented
(recirculating) installations only” in the “Connect Vent System”
section. Recirculating Kit part number W10807915 is available
from your dealer or an authorized parts distributor.
IMPORTANT: An undercounter built-in oven cannot be installed
under this product.
3
Product Dimensions
Right Side
Cooktop
C
B
HI
A. 29/32" (6.5 cm)
B. 13/32" (2.8 cm)
C. 73/8" (18.7 cm)
D. 95/8" (24.5 cm)
E. 1525/32" (40.1 cm)
Top View
A. 36" (91.4 cm)
B. 2111/32" (54.2 cm)
C. 5/64" (2.0 mm) radius (4-corner radius)
Front View
G
E
F
F. 349/16" (87.8 cm)
G. 11/32" (8.45 mm) typical sides
H. 1/8" (3.25 mm)
I. 5/64" (2.0 mm)
Side View – Left
M
K
C
A
A. 111/8" (28.2 cm)
B. 111/32" (28.0 cm)
C. 111/8" (28.3 cm)
D. 151/4" (38.7 cm)
E. 15/16" (2.4 cm) typical right,
A B
C
D
F. 7/16" (1.1 cm) typical right,
G. 31/8" (7.9 cm) typical right,
J
left, or front position
left, or front position
left, or front position
L
H
B
H. 97/8" (25.0 cm) typical right,
left, or front position
J. 415/16" (12.5 cm)
K. 55/8" (14.4 cm)
L. 23/4" (7.0 cm)
M. 11/8" (2.9 cm)
N. 5/64" (0.2 cm)
O. 9" (22.9 cm) min.
P. 151/4" (38.7 cm) max.
P
O
Recirculation Assembly (accessory)
N
GF
D
C
C
B
A. 209/32" (51.5 cm)
B. 181/2" (47.0 cm)
C. 9/32" (7.2 mm) typical front and back
A
Blower Housing Assembly
NOTE: Vent exhaust – shown for right exhaust. It can also be
positioned for left or front exhaust.
Front Side
D
G
F
N
AE
E
B
A. 183/8" (46.6 cm)
B. 33/4" (9.5 cm)
C. 53/4" (14.7 cm)
D. 63/4" (17.1 cm)
E. 9/16" (14 mm)
F. 9/16” (14 mm)
G. 97/8" (25.0 cm)
A
H
A
J
M
H. 175/8" (44.8 cm)
J. 33/32" (7.8 cm)
K. 2" (5.0 cm)
L. 3/16" (4.8 mm) diameter (4)
M. 5/16" (7.9 mm)
N. 17" (43.2 cm)
K
L
4
Recirculation Cover (part of Recirculation Kit)
A
B
A. 181/2" (47.0 cm)
B. 331/32" (10.1 cm)
C. 11/16" (1.7 cm)
C
Cabinet Dimensions
IMPORTANT: If installing a range hood or microwave hood
combination above the range, follow the range hood or
microwave hood combination installation instructions for
dimensional clearances above the cooktop surface.
NOTES:
■ Cabinet opening dimensions shown are for 25" (64 cm)
countertop depth, 24" (61 cm) base cabinet depth, and 36"
(91 cm) countertop height. Dimensions must be met in order
to ensure a flush fit to the back wall.
■ For clarification, all cabinet illustrations are shown with the
door and front panel removed.
Countertop Cutout and Clearances
A
D
Cutout Dimensions
NOTE: All dimensions for cabinet cutouts are to be located
from the centerline/center point of the countertop cutout.
Style 1 – Cabinet Cutouts for Vented Installations
Cabinet cutout areas are for venting out of the right-hand side of
the blower motor assembly to the back or through the floor. All
cutouts are to be located from the centerline/center point of the
countertop cutout.
Centerline/center point
of countertop cutout
17"
(439 mm)
11"
(280 mm)
A
B
4" min.
(101 mm)
C
B
L
F
E
G
H
I
K
A. 36" (91.4 cm)
B. Combustible area above countertop (shown by dashed box above)
C. 30" (76.2 cm) minimum clearance between top of cooktop platform
and bottom of uncovered wood or metal cabinet (24" [61 cm]
minimum clearance if bottom of wood or metal cabinet is covered by
not less than 1/4" [0.6 cm] flame-retardant millboard covered with not
less than No. 28 MSG sheet steel, 0.015" [0.04 cm] stainless steel, or
0.024" [0.06 cm] aluminum or 0.020" [0.05 cm] copper)
D. 13" (33 cm) recommended upper-cabinet depth
E. 211/16" (6.8 cm)
F. 207/8" (53.0 cm)
G. 18" (45.7 cm) minimum clearance from upper cabinet to countertop
within minimum horizontal clearances to cooktop
H. Junction box or outlet; 12" (30.5 cm) minimum from bottom
of countertop
I. Junction box or outlet; maximum 24" (61 cm) from centerline
of cabinet
J. 357/16" (90.0 cm)
K. 21/2" (6.4 cm) minimum distance to nearest left- and right-side
combustible surface above cooktop
L. 115/32" (3.7 cm) minimum clearance between back wall and countertop
J
K
NOTE: After making the countertop cutout, some installations
may require notching down the base cabinet sidewalls to clear
the cooktop base. To avoid this modification, use a base cabinet
with sidewalls wider than the cutout.
5
/16" min.
3
/8"
(10 mm)
Centerline/center point
of countertop cutout
A. The vent supply area in back of the cabinet is for venting out of the
back of the cabinet, using a 31/4" x 10" (8.3 cm x 25.4 cm) vent duct
and a flat 90° elbow.
B. The vent supply area in the cabinet floor is for venting through the
bottom of the cabinet using 31/4" x 10" (8.3 cm x 25.4 cm) vent duct
and a 90° elbow.
(8 mm)
NOTE: Gray areas are references for ducting locations.
5
Style 2 – Cabinet Cutouts for Recirculation Front
Kick Plate Installations
Cabinet cutout areas for recirculation venting out of the front of
the blower motor assembly to the front kick plate of the cabinet.
Centerline/center point
Center line/center point
of countertop cutout
of countertop cutout
Inside
Inside
cabinet
C
B
cabinet
back
back
Style 3 – Cabinet Cutouts for Side Recirculation
Installations
Cabinet cutout areas for recirculation venting out of the right-side
of the blower motor assembly to the right side of the cabinet.
Center line/center point
Centerline/center point
of countertop cutout
of countertop cutout
Inside
Inside
cabinet
cabinet
back
back
D
A
H
A
H
E
F
G
Centerline/center point
Center line/center point
of countertop cutout
of countertop cutout
A. Cutout in cabinet floor for blower motor housing –
recirculation position
B. 21/2" (6.4 cm)
C. 143/4" (37.5 cm)
D. 33/4" (9.5 cm)
E. Cutout in cabinet kick plate for recirculation duct assembly
F. 13/16" (2.0 cm)
G. 173/64" (43.3 cm)
H. 331/32" (10.1 cm)
Cabinet floor
Cabinet oor
Cabinet kick plate
Cabinet kick-plate
D
C
B
Center line/center point
of countertop cutout
A. Cutout in cabinet floor for blower motor
housing – recirculation position
B. 21/2" (6.4 cm)
C. 143/4" (37.5 cm)
D. 33/4" (9.5 cm)
E. Cutout in cabinet right-end panel
for recirculation duct assembly
F. 63/16" (16.0 cm)
G. 173/64" (43.3 cm)
H. 331/32" (10.1 cm)
E
G
Use the same cabinet cutout dimensions E, F, G, and H for
recirculation out the left side of the cabinet.
NOTE: Left-side recirculation recommendation: There must be a
minimum of 7B\," (19.4 cm) between the face panel of the blower
motor housing assembly and the left outside of the cabinet.
6
Venting Requirements
IMPORTANT: This appliance must be exhausted outdoors
unless you are using the Recirculation Accessory Kit. See the
“Venting Methods” section and the “Accessories” section in
your Use and Care manual to order.
■ Do not terminate the vent system in an attic or other
enclosed area.
■ Vent system must terminate to the outside.
■ Use only a 3Z\v" x 10" (8.3 cm x 25.4 cm) rectangular metal
vent or 6" (15.2 cm) round metal vent. Rigid metal vent is
recommended. Do not use plastic or metal foil vent.
■ Before making cutouts, make sure there is proper clearance
within the wall or floor for the exhaust vent.
■ Do not cut a joist or stud unless absolutely necessary.
If a joist or stud must be cut, then a supporting frame must
be constructed.
■ The size of the vent should be uniform.
■ The vent system must have a damper.
■ Use vent clamps and metal duct tape to seal all joints in the
vent system.
■ Use caulking to seal exterior wall or roof opening around
the cap.
■ Determine which venting method is best for your application.
For Best Performance:
■ Use 26-gauge minimum galvanized or 25-gauge minimum
aluminum metal vent. Poor quality pipe fittings can reduce
airflow. For external venting, flexible metal vent is not
recommended.
NOTE: Local codes may require a heavier gauge material.
■ Metal duct may be reduced to 30-gauge galvanized steel
or 26-gauge aluminized steel if allowed by local codes.
This reduction is based on information in the International
Residential Codes Section M1601.1 (2006 edition).
■ Avoid installing 2 elbows together.
■ Use no more than three 90° elbows.
■ If an elbow is used, install it as far away as possible from
the hood’s vent motor exhaust opening.
■ Make sure there is a minimum of 18" (45.7 cm) of straight
vent between the elbows if more than one elbow is used.
Elbows too close together can cause excess turbulence
that reduces airflow.
■ Do not use a 5" (12.7 cm) elbow in a 6" (15.2 cm) or
3¼" x 10" (8.3 cm x 25.4 cm) system.
■ Do not reduce to a 5" (12.7 cm) system after using a
6" (15.2 cm) or 3¼" x 10" (8.3 cm x 25.4 cm) fittings.
■ Avoid forming handmade crimps. Handmade crimps may
restrict airflow.
■ Use a Jenn-Air
®
vent cap for proper performance. If an
alternate wall or roof cap is used, be certain the cap size
is not reduced and that it has a backdraft damper.
■ Use vent clamps and metal duct tape to seal all joints
in the vent system.
■ Use caulking to seal exterior wall or roof opening around
the cap.
The length of vent system and number of elbows should be
kept to a minimum to provide efficient performance.
The maximum equivalent length of the vent system is 35 ft
(10.7 m). For altitudes above 4,500 ft (1272 m), reduce
recommended vent run by 20% for best performance.
Cold Weather Installations
An additional backdraft damper should be installed to minimize
backward cold air flow and a thermal break installed to minimize
conduction of outside temperatures as part of the vent system.
The damper should be on the cold air side of the thermal break.
Makeup Air
Local building codes may require the use of makeup air systems
when using ventilation systems greater than specified CFM of air
movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements
in your area.
Venting Methods
Common venting methods are shown for a counter-mounted
downdraft cooktop. The cooktop may be vented through the
wall or floor.
Option 1 – Roof VentingOption 2 – Wall Venting
B
B
A
A
A. 31/4" x 10" (8.3 cm x 25.4 cm)
rectangular floor venting
B. Roof cap
Option 3 – Venting Between Floor Joist
Front view of cabinet with doors removed
BA
A. 31/4" x 10" (8.3 cm x 25.4 cm)
rectangular wall venting
B. Wall cap
A. 31/4" x 10" (8.3 cm x 25.4 cm)
rectangular wall venting
B. Wall cap
7
Concrete Slab Installations – Exhaust Through Wall
K
(0.6 m)
wall cap
BA
E
F
D
O
C
Vent Piece6" (15.2 cm) Round
6" (15.2 cm)
5.0 ft (1.5 m)
to 3Z\v" x 10"
(8.3 cm x 25.4 cm)
90° elbow transition
3Z\v" x 10"
5.0 ft (1.5 m)
(8.3 cm x 25.4 cm)
90° elbow
G
N
M
A. Wall cap
B. 6" (15.2 cm) round metal vent
C. 16" (40.6 cm) maximum
D. 6" (15.2 cm) round PVC sewer pipe
E. 31/4" x 10" (8.3 cm x 25.4 cm) rectangular 90° metal vent elbow
F. 31/4" x 10" (8.3 cm x 25.4 cm) rectangular to 6" (15.2 cm)
round metal vent transition
G. 6" (15.2 cm) round PVC coupling
H. Concrete slab
I. 6" (15.2 cm) round PVC sewer pipe
J. 6" (15.2 cm) round 90° PVC sewer pipe elbow
K. Tightly pack gravel or sand completely around pipe.
L. 30 ft (9.1 m) maximum
M. 6" (15.2 cm) round 90° PVC sewer pipe elbow
N. 6" (15.2 cm) round PVC coupling
O. 12" (30.5 cm) minimum
L
H
I
J
Calculating Vent System Length
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
Vent Piece6" (15.2 cm) Round
45° elbow2.5 ft (0.8 m)
3Z\v" x 10"
5.0 ft (1.5 m)
(8.3 cm x 25.4 cm)
flat elbow
3Z\v" x 10"
0.0 ft (0.0 m)
(8.3 cm x 25.4 cm)
wall cap
Example vent system
90˚ elbow
6 ft (1.8 m)
2 ft
1 - 90° elbow= 5 ft (1.5 m)
8 ft (2.4 m) straight= 8 ft (2.4 m)
1 - wall cap= 0 ft (0 m)
System length= 13 ft (3.9 m)
90° elbow5.0 ft (1.5 m)
6" (15.2 cm) wall cap0.0 ft (0.0 m)
3Z\v" x 10"
4.5 ft (1.4 m)
(8.3 cm x 25.4 cm)
to 6" (15.2 cm)
transition
6" (15.2 cm)
1 ft (0.3 m)
to 3Z\v" x 10"
(8.3 cm x 25.4 cm)
transition
3Z\v" x 10"
5.0 ft (1.5 m)
(8.3 cm x 25.4 cm)
to 6" (15.2 cm)
90° elbow transition
NOTE: A flexible vent is not recommended. Flexible vents
create back pressure and air turbulence that greatly reduce
performance.
Recirculation: Non-Vented (Recirculating)
Installations Only
You will need to order:
■ Recirculation Kit part number W10807915 (See the
“Assistance or Service” section in your Use and Care
manual to order.)
■ You may also need a section of 3Z\v" x 10" (8.3 cm x 25.4 cm)
metal duct – length required is determined by the distance
from the exhaust outlet to the back flat surface of the
Recirculation Kit housing.
8
Electrical Requirements
WARNING
Electrical Shock Hazard
Disconnect power before servicing.
Use 8 gauge copper wire.
Electrically ground cooktop.
Failure to follow these instructions can result in death,
fire, or electrical shock.
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrical installer determine
that the ground path and wire gauge are in accordance with
local codes.
Check with a qualified electrical installer if you are not sure the
cooktop is properly grounded.
Make sure that the electrical connection and wire size are
adequate and in conformance with the National Electrical Code,
ANSI/NFPA 70 - latest edition or CSA Standards C22.1-94,
Canadian Electrical Code, Part 1 and C22.2 No. O-M91 - latest
edition, and all local codes and ordinances.
A copy of the above code standards can be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
Before You Make the Electrical Connection:
To properly install your cooktop, you must determine the type of
electrical connection you will be using and follow the instructions
provided for it here.
■ A 3-wire or 4-wire, single phase, 120-/240-volt, 60 Hz,
AC-only electrical supply on a separate, 40-amp circuit
breaker is required. If a fused system is used, fuse both
sides of the line.
■ The cooktop should be connected directly to the junction
box through the flexible metal conduit. The flexible, armored
cable extending from the fuse box or circuit breaker box
should be connected directly to the junction box.
■ Locate the junction box to allow as much slack as possible
between the junction box and the cooktop so that the
cooktop can be moved if servicing becomes necessary
in the future.
■ A UL listed or CSA approved conduit connector must
be provided at each end of the power supply cable
(at the cooktop and at the junction box).
■ If the house has aluminum wiring, follow the procedure
below:
1. Connect a section of solid copper wire to the
pigtail leads.
2. Connect the aluminum wiring to the added section
of copper wire using special connectors and/or tools
designed and UL listed for joining copper to aluminum.
Follow the electrical connector manufacturer’s recommended
procedure. Aluminum/copper connection must conform with
local codes and industry accepted wiring practices.
INSTALLATION INSTRUCTIONS
Prepare Cooktop
WARNING
Excessive Weight Hazard
Use two or more people to move and install cooktop.
Failure to do so can result in back or other injury.
1. Open product as instructed on product packaging.
2. Remove shipping materials and tape from cooktop.
3. Using 2 or more people, remove the cooktop from
the carton.
NOTE: Always handle the cooktop from the underside of
the cooktop chassis, not from the stainless steel frame or
the metal covers on the bottom of the cooktop.
4. Using 2 or more people, place the cooktop upside
down on a protected surface.
9
Install Foam Strips
1. Remove foam strip from literature and hardware package.
2. Measure and cut 4 pieces: 2 pieces 211/4" (54.0 cm) long
and 2 pieces 35" (88.9 cm) long.
3. Remove backing from the 211/4" (54.0 cm) foam strips and
apply the foam strips, adhesive-side down, to each end of
the outer flange on the underside of the cooktop trim.
4. Remove backing from the 35" (88.9 cm) foam strips and
apply the foam strips, adhesive-side down, to the front and
rear outer flanges on the underside of the cooktop trim.
Do not overlap the foam strips.
B
A
Cooktop Mounting Brackets Installation
NOTE: For ease of installation, install cooktop mounting
brackets to cabinet before installing cooktop into cabinet.
Installing Mounting Brackets to Cabinet Sides
NOTE: Cabinets wider than 36" (91.4 cm) may require additional
sides (Z\x" [1.3 cm] thick wood, minimum) to be constructed
inside of the cabinet at a width of 34>\zn" (87.8 cm). The inside
of each sidewall should be located 17>\cx" (43.9 cm) from the
center line of the cooktop cutout and parallel to the sides of the
cooktop cutout.
1. Draw a horizontal line on the inside of both cabinet sides or
added sidewall 1C\zn" (30 mm) down from the top surface of
the countertop.
2. Align the 4 brackets 1M\," (47 mm) from the front and back
cutout surface of the countertop on the marked horizontal
A
lines and orient as shown with 1 front bracket and 1 rear
bracket on each side.
17/8"
(47 mm)
3
1
17/8"
(47 mm)
/16"
(30 mm)
B
A
B
D
A
C
A. Foam strip - 211/4" (54.0 cm) long (2 pieces)
B. Foam strip - 35" (88.9 cm) long (2 pieces)
C. Cooktop trim - edge flange (right and left sides)
D. Cooktop trim - edge flange (front and rear)
NOTE: The foam strip (optional) keeps the underside of the
cooktop frame from debris and helps the cooktop sit flat on
uneven counters.
A
A
B
C
A. Marked location lines on inside of
cabinet sidewalls (typical both ends)
B. Cooktop mounting brackets (4)
C. M4 x 12 mm screws (8)
3. Mark and pre-drill the mounting holes using a Z\," (3 mm)
drill bit. (Do not drill through the cabinet sidewalls.)
4. Using 2 M4 x 12 mm mounting screws (supplied) for each
mounting bracket, attach the 4 mounting brackets to the
cabinet sides. A shorter screw length (not supplied) may
be required if the cabinet sidewall thickness is less than
Z\x" (12.7 mm).
10
Install Cooktop and Blower Motor Assembly
1. Using 2 or more people, place cooktop into the cutout.
2. Align cooktop to sit flat onto the countertop.
3. Install 4 M5 x 50 mm cap screws, lock washers, and flat
washers (1 each corner) to secure the cooktop to the
mounting brackets. Tighten screws to pull cooktop tight
to the countertop.
A
A
B
C
D
C
D
B
C
E
F
E
G
F
Install Mounting Feet/Spacers to Blower
Motor Assembly
1. Install the mounting feet (2) to the bottom of the blower
motor assembly, using 2 M5 x 10 mm flat-head screws
per foot, and tighten.
A
B
C
A. Blower motor assembly front side
B. Mounting feet (2)
C. M5 x 10 mm screws - flat head (4)
Prepare Blower Motor Assembly
A. Cooktop
B. Cooktop vent slots
C. Countertop
D. Mounting brackets (4)
E. M5 x 50 mm cap screws, lock
washers, and flat washers (4 each)
F. Cabinet (shown with front removed)
G. Cutout location in cabinet floor
(for recirculation installations only)
NOTES:
■ Make sure that the front edge of the cooktop is parallel to
the front edge of the countertop. If repositioning is needed,
lift entire cooktop up from the cutout to avoid scratching
the countertop.
■ Do not block vent slots on the front of the cooktop.
Style 1 – Vented or Recirculation to the Right
1. Assemble the 2-piece telescoping rectangular vertical duct
to the blower motor assembly top duct extension. Secure
with screw and metal duct tape.
A
B
C
A. Telescoping rectangular duct (2 pieces)
B. M4 x 9.5 mm screw
C. Blower motor assembly top duct extension
11
Style 2 – Recirculation to the Front
1. Using a T20® TORX® driver, remove the 2 screws and cover
from the electrical junction box on the front panel of the
blower motor assembly housing and set aside.
2. Using a T20® TORX® driver, remove the 4 screws and the
electrical junction box from the mounting bracket and
set aside.
NOTE: Do not remove any electrical connections.
8. Reassemble the panel and motor assembly into the front of
the blower motor assembly housing. Install the 11 screws
and tighten.
A
B
D
C
D
C
B
A
E
A. Cover – electrical junction box
B. Electrical junction box
C. Mounting bracket – electrical junction box
D. Blower motor assembly housing
E. Screws (6)
3. Using a T20® TORX® driver, remove the 11 screws and cover
panel from the front blower motor assembly housing.
A
D
B
C
C
A. Blower motor assembly housing
B. Cover panel
C. Screws (11 for each plate)
D. Panel and motor assembly
4. Using a T20® TORX® driver, remove the 3 screws and the
electrical junction box mounting bracket from panel and
set aside.
5. Disconnect the 9-pin blower motor electrical connector.
6. Using a T20® TORX® driver, remove the 11 screws that attach
the panel and motor assembly to the right side of the blower
motor assembly housing. Remove the panel and motor
assembly from the blower motor assembly housing.
7. Assemble the electrical box bracket to the front panel using
the 3 screws and tighten.
C
A. Blower motor assembly housing
B. Panel and blower motor assembly
C. Screws (22)
D. Front panel
9. Reconnect the 9-pin blower motor electrical connector.
10. Reassemble the panel to the right side of the blower motor
assembly housing. Install the 11 screws and tighten.
11. Reassemble the electrical box to the bracket using the
4 screws and tighten.
12. Assemble the 2-piece telescoping rectangular vertical duct
to the blower motor assembly top duct extension. Secure
with screw and metal duct tape.
A
B
C
A. Telescoping rectangular duct (2 pieces)
B. M4 x 9.5 mm screw
C. Blower motor assembly top duct extension
Style 3 - Vented or Recirculation to the Left
1. Using a T20® TORX® driver, remove the 11 screws and panel
from the left side of the blower motor assembly housing and
set aside.
2. Disconnect the 9-pin blower motor electrical connector.
12
D
C
B
A
E
A. Blower motor assembly housing
B. Mounting bracket – electrical junction box
C. Electrical junction box
D. Cover – electrical junction box
E. Screws (6)
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.