Jenn-Air JDR8880RDS10 Installation Instruction

INSTALLER: LEAVE THESE INSTRUCTIONS WITH THE APPLIANCE
INSTALLATION MANUAL
Dual Fuel 30-inch Wide Free-Standing Range
PLEASE KEEP THIS MANUAL FOR FUTURE REFERENCE
THE MANUAL IS INTENDED TO ASSIST IN THE INITIAL INSTALLATION AND ADJUSTMENTS OF THE RANGE.
CLEARANCE DIMENSIONS
SPECIAL WARNING
Only qualified personnel should install or service this range.
Read “Safety Instructions” in the Use & Care book before using range.
Range may be installed with zero inches clearance adjacent to (against) combustible construction at the rear and on the sides below the cooktop. For complete information in regard to the installation of wall cabinets above the range and clearances to combustible wall above the cooking top see the installation drawings. For SAFETY CONSIDERATIONS do not install a range in any combustible cabinetry which is not in accord with the installation drawings.
Improper installation, adjustment, alteration, service, maintenance or use of range can result in serious injury or property damage.
ALL RANGES CAN TIP AND CAUSE INJURIES TO PERSONS.
INSTALL ANTI-TIP DEVICES PACKED WITH RANGE.
FOLLOW ALL INSTALLATION INSTRUCTIONS.
Your range may not be equipped with some of the features referred to in this manual.
* NOTE: The 30 inch (76.2 cm) dimension may be
reduced to not less than 24 inches (61 cm) when the wall cabinets in a domestic home are protected with fireproof materials in accordance with American National Standards -- National Fuel Gas Code or in mobile homes when they are protected with fireproof materials in accordance with the Federal Standard for Mobile Home Construction and Safety.
To eliminate the risk of burns or fire by reaching over heated surface units, cabinet storage space located above the surface units should be avoided. If cabinet storage is to be provided, the risk can be reduced by installing a range hood that projects horizontally a minimum of 5 inches (13 cm) beyond the bottom of the cabinets.
CAUTION: This range has been designed in
accordance with the requirements of various safety agencies and complies with the maximum allowable wood cabinet temperatures of 194°F. If this range is installed with cabinets that have a lower working temperature than 194°F, discoloration, delamination or melting may occur. Contact Customer Service for associated cabinet dimensions and installation accessories.
8101P729-60
(03-06-00)
ANTI-TIP DEVICE INSTALLATION INSTRUCTIONS
NOTE: A risk of range tip over exists if the appliance is
not installed in accordance with the installation instructions provided. The proper use of this device minimizes the risk of TIP-OVER. In using this device the consumer must still observe the safety precautions as stated in the USE and CARE MANUAL and avoid using the oven door and/or lower drawer as a step stool.
Installation instructions are provided for wood and cement in either floor or wall. Any other type of construction may require special installation techniques as deemed necessary to provide adequate fastening of the ANTI-TIP bracket to the floor or wall.
STEP 1 -- Locating The Bracket (see figure 1)
A. Determine where either the right or left rear “edge” of
the range will be located and mark the floor or wall.
B. Place the BRACKET 9/16(14.5 mm) from the
marked “EDGE” toward center of opening and against the back wall as shown in figure 1, with orientation hole against wall.
C. Use the bracket as a template and mark the required
holes, as shown in figure 1 for the type of construction you will be using.
STEP 2 -- Anti-Tip Bracket Installation
A. Wood Construction:
1. Floor: Locate the center of the two holes identified in figure 1 as “HOLES FOR FLOOR”. Drill a 1/8 (3 mm) pilot hole in the center of each hole (a nail or awl may be used if a drill is not available). Secure the ANTI-TIP bracket to the floor with the two screws provided. Proceed to STEP 3.
2. Wall: Locate the center of the two holes identified in figure 1 as “HOLES FOR WALL. Drill an angled 1/8(3 mm) pilot hole in the center of each hole as shown in figure 2. (A nail or awl may be used if a drill is not available). Secure the ANTI-TIP bracket to the wall with the two screws provided as shown in figure 2. Proceed to STEP 3.
B. Cement or Concrete Construction:
1. Suitable screws for concrete construction can be obtained at a hardware store. Drill the required size hole for the screws obtained into the concrete at the center of the holes identified in figure 1 as “HOLES FOR FLOOR”. Secure the ANTI-TIP bracket to the floor. Proceed to STEP 3.
STEP 3 -- Range Installation
A. For safety considerations as well as optimum
performance, adjust the range so it is level and to desired height prior to installing in cabinet opening.
NOTE: Cooktop MUST
be flush or above
countertop.
Levelness may be checked by placing a spirit level or a large pan of water on the cooktop or oven rack. Adjust the range by tipping it forward or back and rotate the leveling feet as required.
NOTE: A minimum clearance of 1/4(6 mm) is required between the range and the leveling foot that will engage the anti-tip bracket, (see figure 2).
CAUTION: Damage to the range may occur if range is moved or lifted by grasping the main top, backguard or door handles.
B. Align the range to its designated location and prepare
to slide it back into position. Connect gas line and plug in power cord to outlet following guidelines outlined in connecting the range and remainder of installation instructions.
C. Slide range in place visually inspecting to verify that
power cord and gas line are freely routed and contained within recessed area of back panel.
D. To check the range for proper installation of the
anti-tip bracket, use a flashlight and look underneath the bottom of the range to see that one of the rear leveling feet is engaged in the bracket slot.
9/16”
(14.5 mm)
FROM EDGE
OF RANGE
MARKED EDGE
OF RANGE
NOTE: USE A MINIMUM OF (2) SCREWS
TO INSTALL ANTI-TIP BRACKET TO THE WALL OR FLOOR.
ORIENTATION HOLE
HOLES FOR WALL
HOLES FOR FLOOR (EACH SIDE)
ATTACH ANTI-TIP BRACKET WITH A MINIMUM OF TWO (2) LONG SCREWS TO THE WALL OR FLOOR.
ANTI-TIP BRACKET
LEVELING FOOT
SCREWS MUST ENTER WOOD OR METAL.
WALL PLATE
ANTI-TIP BRACKET
SCREW BRACKET TO WALL
SLIDE IN TO SECURE
FIGURE 1 FIGURE 2
-- 4 --
RANGE BOTTOM
1/4” (6mm) MIN.
CONNECTING THE RANGE
ELECTRIC SUPPLY
The range must be installed in accordance with Local and National Electric Code (NEC) ANSI/NFPA No. 70-latest edition. See rating plate for total connected KW rating.
ELECTRIC SUPPLY (Canada)
The range must be installed in accordance with Local and Canadian Electric Code CSA STD.C22.1 latest edition. See rating plate for total connected KW rating.
OUTSIDE WIRING
Your local utility company will tell you whether the present electric service to your home is adequate. It may be necessary to increase the size of the wiring to the house and service switch to take care of the electrical load demanded by the range. The kilowatt rating for the range is specified on the rating plate located on front of range.
HOUSE WIRING
Most local Building Regulations and Codes require that all electrical wiring be done by licensed electricians. All wiring should conform to Local and National Electrical Codes. This range requires a single phase three wire 120/240 or a 120/208 volt, 60 Hz, AC circuit. Wiring codes require a separate circuit be run from the main entrance panel to the range and that it be equipped with separate disconnect switch and fuses, either in the main entrance panel or in a separate switch and fuse box. In some communities, a solid or flexible continuous armored conduit must be used from main entrance panel to the terminal box on the rear of the range. Others will permit the termination of the range circuit at a polarized three or four wire plug-in outlet placed at a convenient point near the back of the range. The range is then connected to this outlet through an approved range connector (pigtail) fastened securely to the terminal block with proper strain relief at the range and a three or four pronged plug at the opposite end.
by local code. USE COPPER OR ALUMINUM CONDUCTORS. Main terminal block is recognized for Copper or Aluminum conductors. If a flexible power cord is required, it is recommended a cord no longer than 4 ft. be used. Make connections as explained below and with reference to the appropriate illustration (see figures 6 and
7). After installation, insure tightness of all electrical connections and replace all covers.
Remove terminal block access cover from range back. (See figure 5).
RANGE CONNECTIONS (Canada)
This model was shipped direct from the factory with service cord (pigtail) attached. There are no range connections necessary. Just plug into the range outlet.
NOTE: Cord replacement -- ONLY a power supply cord rated at 240 volts minimum, 40 amperes or 50 amperes power supply cord that is marked for use with nominal 13/8″ (34.93 mm) diameter connection opening, with closed loop terminals and marked for use with ranges shall be used.
RANGE CONNECTIONS
Some models are shipped direct from the factory with service cords (pigtails) attached. There are no range connections necessary on these models. Just plug into the range outlet. On models not provided with a service cord, connection to the power supply is necessary. REMEMBER -- only a 4--conductor cord is to be used on new branch--circuit installations (1996 NEC), mobile homes, recreational vehicles, or in an area where local codes prohibit grounding through the neutral conductor. Hence, 4--wire service MUST be provided for such installations. 3--wire service may be used when permitted
FIGURE 3
-- 5 --
CONNECTING THE RANGE
Gas Supply
Installation of this range must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1-latest edition.
In The Commonwealth Of Massachusetts
This product must be installed by a licensed plumber or gas fitter when installed within the Commonwealth of Massachusetts.
A “T” handle type manual gas valve must be installed in the gas supply line to this appliance.
A flexible gas connector, when used, must not exceed a length of three (3) feet / 36 inches.
In Canada the range must be installed in accordance with the current CGA Standard CAN/CGA--B149 -- Installation Codes for Gas Burning Appliances and Equipment and/or local codes.
Gas leaks may occur in your system and result in a dangerous situation. Gas leaks may not be detected by smell alone. Gas suppliers recommend you purchase and install an UL approved gas detector. Install and use in accordance with the manufacturer’s instructions.
excess of 1/2 lbs./sq. in. (3.5 kPa) (13.8 in. water column).
2. The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 lbs./sq. in. (3.5 kPa) (13.8 in. water column).
Gas Supply Connection (See figure 3)
A QUALIFIED SERVICEMAN OR GAS APPLIANCE INSTALLER MUST MAKE THE GAS SUPPLY CONNECTION. Leak testing of the appliance shall be conducted by the installer according to the instructions given in section h.
NATURAL GAS SUPPLY LINE MUST HAVE A NATURAL GAS SERVICE REGULATOR. INLET PRESSURE TO THIS APPLIANCE SHOULD BE REDUCED TO A MAXIMUM OF 14 INCHES WATER COLUMN (0.5 POUNDS PER SQUARE INCH (P.S.I.). LIQUEFIED
PETROLEUM (L.P.) MUST HAVE A L.P. GAS PRESSURE REGULATOR. INLET PRESSURE TO THIS APPLIANCE SHOULD BE REDUCED TO A MAXIMUM OF 14 INCHES WATER COLUMN (0.5 P.S.I.). INLET PRESSURES IN EXCESS OF 0.5 P.S.I. CAN DAMAGE THE APPLIANCE PRESSURE REGULATOR AND OTHER GAS COMPONENTS IN THIS APPLIANCE AND CAN RESULT IN A GAS LEAK.
NOTE: This range is shipped from the factory set for Natural Gas at 4water column pressure.
/PROPANE GAS SUPPLY LINE
Checking Pressure Of House Piping System
1. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in
Gas supply pressure for testing regulator must be at least 1water column pressure above manifold pressure shown on serial plate.
If conversion to LP Gas is required, convert appliance before installation.
-- 8 --
Loading...
+ 21 hidden pages