JCC JCEM001 User Manual

25mm
8mm
Earth (Green/Yellow)
Switched Live (Brown)
Neutral (Blue/grey)
Un/Switched Live (Black)
Wire preparation
company
JCC Emergency Remote Pack Self-Test
LV connection from Invertor to Luminaire
Mains supply from Invertor to LED Driver
LV connection from LED Driver to Invertor
OutIn
3A Fused Switched Live
Technical Support: +44(0)1243 838986 Customer Services: +44(0)1243 838999
BS EN ISO9001 - 2015 - Registered Firm Certificate No. GB 1552
Important warranty information
This product is supported by a 2-year standard warranty which will extend to 3 years if registered within the first year of purc (2 year on batteries). Please register at jcc.co.uk/warranty - Terms and conditions apply.
The installer will be asked to provide the following information, which is detailed on a label attached to the product’s chassi Product Code/Date Code.
3 hour maintained LED emergency lighting pack
WARNINGS AND CAUTIONS
To be installed in accordance with the local current wiring regulations and standards
To avoid electric shock, serious injury or property damage, isolate power before installing, removing or servicing the product
It is recommended that this product is installed by an electrician or a competent person with sufcient experience to install this product
Any broken or damaged parts should be replaced as soon as possible. JCC will not accept responsibility for claims arising from sub-standard installations; which will void the warranty
Emergency product routine inspection and tests must be undertaken at times of least risk and in accordance with EN 50172:2004. A copy of this report must accompany any tting returned to the JCC for any reason
INSTALLATION INSTRUCTIONS ENGLISH
Read instructions and check that you have all of the tools and accessories required to complete the installation correctly. Isolate power supply before starting the installation.
a
1. Wire the emergency remote pack to the mains supply as indicated
in gure 1. If a dimmable variant,
connect the dimming control wires (DALI/1-10V/DSI) as shown in the product instruction sheet
RoHS
Compliant
EL
IP20
2. Connect the two core cable from the
remote pack into the mains input terminals of the driver (not supplied) as shown in
gure 2.
jcc.co.uk
3. Connect the driver low voltage
output from the driver to the
remote pack as shown in gure 3.
4
2
1
4. Connect the low voltage output
from the invertor to the luminaire
(not supplied) as shown in gure 4.
6. Ensure the green LED charge indicator is located alongside the luminaire and is
visible once the tting is installed and operational. Reconnect mains power
supply and test for operation. (Allow 24hrs for batteries to charge before testing).
5. Connect batteries to the remote pack prior to completing the installation.
3
Electrical Input connection
5
100-240V~ 50/60Hz +1Hz (6-60VDC 50W max output) Class II with earth provision
NE
Usw/L Sw/L
NE
Usw/L Sw/L
Loop in/Loop out connections
4
JCC Lighting Products Ltd. Lux Park, Chichester Business Park, City Fields Way, Tangmere, Chichester, West Sussex, PO20 2FT
s:
hase.
3
2
Emergency range routine inspection and test
53
35
All tests must be undertaken at times of least risk and in accordance with EN 50172:2004 as indicated below:
Prole & Dimensions
All dimensions in millimetres
258
.4
Daily: Indicators of the emergency remote pack should be visually inspected for correct operation.
Monthly: (in addition to the daily check) If automatic testing devices are used, the results of the
short duration tests shall be recorded. Test shall be carried out as follows:
Switch the luminaire over to emergency mode to operate from the batteries by simulating a
failure of supply to the normal lighting, for a period sufcient to ensure correct luminaire operation.
NOTE: The period of simulation failure should be sufcient for the purpose of this clause
whilst minimising damage to the system components e.g lamps. During this period, all luminaires and signs shall be checked to ensure that they are present, clean and functioning correctly. At the end of this test period, the supply to the normal lighting should be restored and any indicator lamp or device should be checked to ensure that
is showing that the normal supply has been restored.
Annually: If automatic testing devices are used, the results of the short duration tests shall be
recorded. For all other systems the monthly inspection shall be carried out and the following additional tests made:
a) Each luminaire and internally illuminated sign shall be tested monthly as above but for
its full duration in accordance with the manufacturer’s information.
b) The normal supply for the luminaire should be restored and any charge indicator lamp or
device should be checked to ensure that it shows the normal supply has been restored. The charging arrangements should be checked for proper functioning.
c) The date of the test and its results shall be recorded in the system logbook.
A copy of this report must accompany any tting returned to the manufacturer for any reason.
General Information
Our products are designed to comply with the requirements of UK law and the relevant
industry national and international standards and should not be modied in any way. All
emergency lighting systems should comply with the recommendations of BS5266-1: Code of Practice for the Emergency Lighting of Premises and be installed by competent engineers in accordance with the relevant wiring regulations. Before installing any type of Emergency Lighting
always seek the advice and approval of the local Fire Prevention Ofcer (or equivalent authority).
Maintenance
Failed or faulty light sources connected to this equipment should be replaced immediately. These units are designed especially for a long and trouble free life. Under normal conditions, will require no routine maintenance or service beyond the inspection and test regime of BS5266-1.
Both mains supply and battery protection fusing is incorporated internally. Should access to these
or any other part of the circuitry be required this must be undertaken only by suitably qualied
person. Special care must be taken when removing the cover to circuitry and battery. Only replacement components authorised by the company must be used. Disposal of replaced components should be in accordance with the component manufacturers instructions.
Battery pack
Inverter
267
Operation/Testing LED Indicator Status
Normal operation Green solid Mains on/No fault
Normal operation Green solid Auto function test - 1 minute
Normal operation Green solid Auto 3 hour duration test
Fault indication
Fault indication
Fault indication Red ash Duration test fault
Red Flash/0.5s On 3.0s Off
Red Flash/2x 0.5s On 2.5s Off LED fault
Battery fault
Emergency test record sheet
Month Test Type First Year Second Year Third Year Fourth Year Fifth Year
Sign Date Sign Date Sign Date Sign Date Sign Date
January Functional
February Functional
March Functional
April Functional
May Functional
June Functional
July Functional
August Functional
September Functional
October Functional
November Functional
December 3 hour