IRIS S552, S550, S556 Applications Manual

IRIS MODEL S550 APPLICATION MANUAL
FLAME MONITORING SYSTEM
MODEL S550, S552, S556 VIEWING HEAD
APPLI CATION MANUAL
PAGE 1
IRIS MODEL S550 APPLICATION MANUAL
TABLE OF CONTENTS
COM PARI SON WITH OTHER MODEL 500 VH’s ...2
TECH NOL OGY USED IN THE S550......................3
CA BLE PREPA RA TION DWG ................................4
FI NAL AS SEM BLY (CA BLE) DWG .........................4
WIR ING OF VIEW ING HEAD .................................5
IR DE TEC TOR ........................................................6
UV DE TEC TOR .......................................................7
ORI FIC ING ..............................................................7
DE FAULT SET TINGS FOR THE S550 ...................8
BEF ORE MAK ING AD JUST MENTS.......................10
NEW P520/P522 FRONT PANEL...........................10
CALI BRAT ING THE S550.......................................10
EX AM IN ING RE SULTS GAIN SET TINGS CALIB ...10
CHECKING OR CHANG ING UV GAIN...................11
CHECKING OR CHANG ING IR FIL TER.................11
CHECKING OR CHANG ING IR GAIN ....................11
MAN UAL SETUP OF THE S550 .............................12
RE TURN TO DE FAULT SET TINGS ........................12
AN GLE OF VIEW ....................................................13
GEN ERAL COM MENTS .........................................13
TECH NI CAL HELP..................................................13
FIGURE 1 FRONT PANEL DRAW ING ....................14
WHERE S550 SET TINGS ARE STORED ..............8
US ING TWO VIEW ING HEADS PER AM PLI FIER .9
FIGURE 2 VH OUT LINE DRAW ING .......................14
FIG 3 FLOW CHART OF S550 PROGRAMMING ...15 FIG 4 FLOWCHART OF S552 PROGRAMMING ...16 FIG 5 FLOW CHART OF S556 PROGRAMMING ...17
PAGE 2
IRIS MODEL S550 APPLICATION MANUAL
S550 GENERAL DESCRIPTION
The IRIS Model S550 is a state- of- the-art flame monitor viewing head utilizing two types of detectors, an IR (infrared) solid state and UV (ultra violet) tube.
The S550’s work with the latest version of the P520/P522 signal processors. Like other viewing heads in the S500 family, the S550’s produce output pulse rates propor tional to the flame signal strength; the pulse rates are displayed at the front panel of the signal processors. But, unlike the other members of the S500 family, certain parameters in the S550 viewing head can be selected or adjusted remotely from the front panel of the P520/P522 signal processors. The parameters are:
a) UV gain 0-99 b) Fil ter Se lec tion 1-8 c) IR gain 0-699
Once adjusted, the new parameters are stored in EEPROM in the signal processor. If power is removed from the signal processor which powers the viewing head and then reapplied, the signal processor then automati cally re-sends the stored parameters out to the S550 viewing head. In addition, at the front panel of the signal processors the operator may also select “CAL”, a semiau to ­matic mode which will help to speed up the S550 setup. This is explained in detail in the section called CALIBRATING THE S550 on page 10. Also notice the FLOWCHART OF S550 PROGRAMMING , Fig ure 3 on page 15. Thus the S550 is a dual­ sensor viewing head where the gain and filter selec tions are adjusted remotely and stored in the P520/P522 signal processors.
S552 GENERAL DESCRIPTION
The S552 is for IR sensing only. It is basically an S550 without a UV capability. The P520 or P522 will be aware of which viewing head of the S550 family is connected to it so that only those adjust ­ments which are appro priate to the S552 will be made available to the operator. These adjust ments apply to the S552:
When it comes to features like CAL, which will be described later, the operator is only given those choices which are appro priate. For example, he does not have to choose between calibrating with the UV sensor or the IR sensor; in CAL he is only offered the choice of calibrating with the IR sensor or not. This is shown in the FLOWCHART OF S552
PROGRAMMING
, Fig ure 4 on page 16.
To keep the manual straightforward only the operation of an S550 is described. If one has an S552 one should simply disregard references to those features of the S550 which are UV-related.
S556 GENERAL DESCRIPTION
The S556 is for UV sensing only. It is basically an S550 without an IR capability. The P520 or P522 will be aware of which viewing head of the S550 family is connected to it so that only the adjustment which is appro priate to the S556 will be made available to the operator:
a) UV gain 0-99
When it comes to features like CAL, which will be described later, the operator is only given those choices which are appro priate. For example, he does not have to choose between calibrating with the UV sensor or the IR sensor; in CAL he is only offered the choice of calibrating with the UV sensor or not. This is shown in the FLOWCHART
OF S556 PROGRAMMING
, Fig ure 5 on page 17.
To keep the manual straightforward only the operation of an S550 is described. If one has an S556 one should simply disregard references to those features of the S550 which are IR-related.
COM PARI SON WITH OTHER MODEL 500 SE RIES VIEW ING HEADS
The S550 uses a Germanium sensor for IR detection like an S511 and uses a high- voltage vacuum tube sensor for UV detection like the S506’s, but both sensors are in the same housing in the S550. The pulses from the UV and IR sensors are summed inter nally into a single pulse stream out to the signal processor.
a) Filter Selection 1-8 b) IR gain 0-699
PAGE 3
A dual-LED indicator is used to indicate the pulse rate out of the S550. It is visible at the rear of the
IRIS MODEL S550 APPLICATION MANUAL
viewing head housing. (See Fig. 2). For every 128 pulses from the UV sensor it emits one green pulse; for every 128 pulses from the IR sensor it emits one red pulse. With a count rate of 1200 displayed at the signal processor the LED will flash 9 or 10 times per second. This is very useful for aiming and sighting the viewing head. One can readily distin guish differ ences in pulse rates at the LED and use this indicator to adjust the sighting to obtain a maximum pulse rate at the LED and therefore a maximum reading at the signal processor.
The S550 differs from older models in that the gain for each sensor and the selection of the filter for IR may be set remotely through the front panel of the P520/P522 signal processors.
Also the earlier IR sensitive family members had only 4 high pass filters to choose from; the S550 has 8:
S511 & S512 S550
LL 36 Hz 1 16 Hz
L 71 Hz 2 24 Hz
M 105 Hz 3 33 Hz
H 186 Hz 4 52 Hz
5 75 Hz
6 100 Hz
7 155 Hz
8 215 Hz
TECH NOL OGY USED IN THE S550
The UV and IR sensors in the S550 share a common optical axis efficiently by using a unique dichroic beamsplitting mirror. Over 80% of the ultra violet light is reflected off the surface of the 45 de gree mirror and yet over 80% of the infrared radiation is trans mitted through the beamsplitting mirror.
The electronics in the S550 is designed using highly reliable surface mount technology.
The high pass frequency responses of eight different filters in the S550 and S552 are imple ­mented compu ta tionally in a high- performance, CMOS micro con troller inside the viewing heads. This approach reduces the parts count and
PAGE 4
IRIS MODEL S550 APPLICATION MANUAL
PAGE 5
IRIS MODEL S550 APPLICATION MANUAL
increases the reliability of the S550 compared to earlier approaches that used discrete analog compo nents to implement four active filters. The micro con troller also handles commu ni ca tions with the P520/P522 signal processors.
WIRING OF VIEWING HEAD
Wiring of the viewing head is made to the terminals on the rear backplane PC board (or output module) on the P520 signal processor and is made to the terminals on the lower right side of the P522. These terminals are listed functionally as follows:
TERM DE SCRIP TION
GND
+V
SC
SIG
Power Ground +24 VDC power to view ing head Shut ter Drive Sig nal to V.H. Flame Sig nal from V.H.
1. Strip 2 inches of the cable outer cover from the cable removing any cello phane wrap or filler material and strip the insulation from the shielded wire (if insulated over shield) a full 2 inches to expose shield.
2. Slide the shield back until a bulge develops close to where the wire exits the cable outer covering.
3. Carefully spread a few strands of the shield at the bulge (making sure not to break any strands) to cre ate an opening and slip wire out of shield through opening.
4. Carefully return shield to original shape and length by pulling gently, then cover with plastic shrink tubing to prevent shorts.
5. Slide nut (with threads toward the cable end), the washer and the grommet onto cable approxi mately 6 inches.
SIG GND
Sig nal Ground
The figures on the previous pages show a four conductor cable to the viewing head. Note that the flame signal wire going to terminal SIG is shielded and the shield is termi nated at both ends of the cable(SIG GND).
The standard IRIS Model 500 cable is desig nated as part number C328. It is specified as a four conductor cable with one wire shielded. The shield is used as the signal ground wire which goes to terminal SIG GND on the P520/P522 and to pin 3 on the viewing head plug. The shield is a braided type for this appli cation (a foil type shield should not be used) so that a solid signal ground is maintained. This signal ground shield is also the self- checking or shutter drive circuit return path. It is recom mended that the IRIS cable be used for all appli ca tions. Ref er to the diagrams on pages 3 and 4 for wiring details.
Connec tions of the IRIS cable to the viewing head plug should be done as follows:
Remove the plug from its packaging and layout the components.
6. Slip the cable through the bottom opening of the connector making sure that the cable outer jacket is secure under the cable clamp and tighten the two screws on the cable clamp.
7. Reassemble the grommet, flat washer, and cable entry nut and tighten.
8. Bef ore wiring to connector, strip each wire 3/8" as shown in assembly drawing on pre ­vious page.
9. Proceed to wire the connector as follows: (Ref ­er to drawings on page 3 for terminal locations.)
Connect viewing head signal wire (the shielded wire) WHT to terminal No. 1 by inserting into opening and then tight ening the retaining screw. Connect the self- checking signal wire BLK to terminal No. 2. Connect the signal ground shield from WHT wire with shrink tubing to terminal No. 3. Connect + 24 VDC power wire RED to terminal No. 4. Connect the power ground wire GRN to terminal No. 5. Assemble the back of the plug and insert jackscrew through plug assembly.
PAGE 6
IRIS MODEL S550 APPLICATION MANUAL
The cable wiring on the other end going to the signal processor is easier to do. The cable should be prepared in a similar way to the plug end particu larly the shield from the WHT wire. Make sure the shield doesn't touch the other terminals.
SIGHT ING OF VIEW ING HEAD
The sighting of the viewing head should be parallel to the cen terline of the burner in the direction of the flame. The sight pipe should be mounted as close to the cen terline as possible; the idea is to sight along the flame rather than across the flame. This will help prevent drop outs of the flame under changing load condi tions.
Utilizing a sighting or the sight pipe aimed at the root of the flame (where the turbulent combustion air mixes with the flame) is a good starting point for optimizing the sighting. Using a swivel mount to “zero-in” on the highest signal will assure maximum performance. Make sure the diameter of this sight pipe is large enough to allow a reasonable field of view. The S550’s has two angles of view, one for the IR detector, which is
1.0° and one for the UV detector which is about
3.0°; this trans lates into a circle of view that varies with the viewing distance as shown in the following table.
Dis tance Dis tance
ft inches inches inches
2 24 .64 1.3
3 36 .73 1.9
6 72 1.45 3.8
12 144 2.90 7.6
18 216 4.35 11.4
Di ame ter of
IR view
Di ame ter of
UV view
Detecting flame in a sulfur recovery unit can present problems for flicker type flame monitors such as the IR detector in the S550 viewing head. The IR detector will detect natural gas used for the warm-up of the reactor. Usually the combustion air is turbulent enough to cause a good flicker
signal. When the sour gas is intro duced and the natural gas shut down the flame signal may drop off or drop out entirely. The reason for this is that there is a complete change in the flicker content for the existing viewing head sighting. If this is the case, then one should try and optimize the flame signal for the sour gas by “zeroing-in” on this flame, not the warm-up burner.
After optimizing the sighting for the sour gas one may find that the signal level is too low on the natural gas. One should then try the UV detector for this appli cation. It may be necessary to use two sets of set points for flame ON and flame OFF, one set for proving and detecting the natural gas flame and the other for proving and detecting the sour gas flame. The switch-over from Channel A to Channel B should be done when removing the natural gas burner. This can be imple mented from the burner control system. This switch-over and the use of Channels A and B with their independent settings is explained in the section
ASSIGNING DIFFERENT S550 SETTINGS TO CHANNEL A and B on page 9.
IR DETECTOR
The IR detector responds to the flicker content in the flame. Flame flicker is caused by the combustion, or forced air injected into the flame. This combustion air can be mixed with the fuel (pulverized coal) or can be intro duced separately. In either case, forced air at high velocity is intro ­duced in such a way as to aid the combustion process. This air is usually made turbulent by causing it to swirl with spin vanes located in the burner barrel.
Flame flicker is created when this turbulent air mixes with the flame. It is composed of random frequencies from zero Hz to over 2,000 Hz. The amount of high frequency flicker (above 200 Hz) is dependent on the fuel and burner. The amplitude of the flicker frequencies always follows an exponential curve with zero frequency having the highest amplitude and the higher frequencies the lowest. The amplitude level of the higher frequencies is usually 40dB down (factor of 100) from zero Hz or DC.
PAGE 7
IRIS MODEL S550 APPLICATION MANUAL
The S550 and S552 respond to flicker frequencies 16 Hz and above. They ignore the lower frequencies so it is important to sight the viewing head on the highly turbulent portion of the flame that contains these higher frequencies. One can predict where these higher frequencies will be by examining the burner with regard to where the flame envelope begins and where the turbulent air enters this flame. This spot can be chosen by examining the drawings of the burner but it is better to do this empiri cally by using a swivel mount on the viewing head.
UV DETECTOR
The S550 viewing head with its dichroic mirror and UV tube have a combined spectral response of 190-215 nm. The UV tube is inher ently a pulsing device, that is, the power supply has been designed so that the tube emits pulses when UV radiation is present. Its output is pulse stream of randomly spaced pulses whose average rate is propor tional to the UV radiation present.
The very narrow spectral response of the S550 viewhead makes it ideal for discrimi nating between flame and glowing refractory and other burners. How ever, because the tube responds to only the very short wavelengths, problems can occur because this radiation is easily absorbed and masked, for example with pulverized coal, by unburned fuel or other impurities in the fuel. Sour gas (H2S) will readily absorb these short 200nm wavelengths as well as other waste fuels resulting in a dropout of the flame signal. Even standard glass will absorb this wavelength, hence, the necessity of using a quartz lens with this viewing head.
In general, the UV viewing head will work well on natural gas flames. It will respond to oil flames but with a lower signal level. The sighting for both oil and gas flames should be parallel to the axis of the burner and aimed at the root of the flame, as with the IR detector. (See pre vious section IR
DETECTOR.
) Photo graphs of gas and oil flames using visual and UV-sensitive film show clearly that the UV zone is much smaller than the visible zone, and the highest UV intensity occurs near the flame root. In addition, the zone of higher UV intensity does not overlap the same zones of
adjacent or opposing burners so that, with proper sighting, discrimi nation is predictable.
As a general rule, the sighting of the S550 when using the UV detector, will be more likely a “line­ of- sight” than the IR flicker detector which will read flame signals bouncing off the side of the sight pipe and other “reflectors”. Sometimes the reading with the IR detectors can be greater with a reflected signal than the direct line of sight. The UV detector on the other hand, will have to be aimed at the part of flame that has the highest concen tration of UV, which usually is at the root of the flame (at the throat of the burner) and in a very narrow region. The angle of view of the S550 UV is somewhat wider than the S550 IR but this does not offset the fact that the UV radiation present is from a very small region.
This small region emitting UV is not the case how ever, for low NOX gas burners. The UV radiation is usually much less in intensity and spread out with this type of burner, such that one gets relatively high readings from all over the furnace when many burners are on. This is particu larly true when flue gas recir cu lation is used. There will be, how ever, a relatively stronger signal near the “root” of the flame and this more intense spot should be located during the aiming or sighting process. This “root” or intense spot may be further out than with the standard gas burner so it is imperative that one use a swivel mount when making these sighting adjust ments.
Also, another factor one must con sid er when aiming the viewing head is the load condition of the boiler. The flames from a burner can be radically different at different loads. This is one of the reasons for trying to pick a sighting initially that will minimize this changing flame at different loads. If the flame moves further out at higher loads then the parallel to the burner axis sighting will be the best. Using a large diameter sight pipe with a swivel mount is recom mended for all instal la tions on large multi burner boilers.
ORIFICING
There are many appli ca tions where the burner flames can be so bright they will saturate the S550 sensors. With these condi tions orificing the
PAGE 8
IRIS MODEL S550 APPLICATION MANUAL
viewing head sight path will greatly improve the performance, particu larly with regard to discrimi ­nation between flames. Although saturation is less likely with the Ge (germanium) IR photo de tector used for the S550 as compared to prior model viewing heads using the PbS (lead sulfide) type photo de tector, the possi bility should not be ignored. Saturation is more prob able with large power utility boilers where the burners are very large and relatively close to one another. If one cannot look at the flame with the naked eye without it hurting, then orificing should be used. This eye test works for incan descent type flames such as oil and coal but will not be valid for natural gas flames.
Orificing may help improve the discrimi nation charac ter istics for the UV detector as well as the IR. The UV tube in the S550 is not likely to saturate; how ever, orificing will usually improve the discrimi nation ratio for large size burners.
An orificing disc is simply a metal disc with a circular hole in the cen ter which is placed directly in front of the lens. Four orificing discs are available with cen ter hole diameters of 3/8, 1/4, 3/16 and 1/8 inch. These discs are installed with retaining rings in the flange at the edge of the 1/2 inch NPT female pipe thread for the purge air. An internal type retaining ring is first installed by positioning a ring in the machined groove inside flange opening from the housing side. The orificing disc is then inserted. Use a second retaining ring to hold it in place so that it is sandwiched tightly between the two retaining rings.
Usually an orificing disc with a larger diameter hole is tried first. There will be a reduction in the signal level so if the associated S550 and signal processor has been previ ously calibrated it will be necessary to calibrate the processor again so that the gain settings will be correct. If the discrimi ­nation is still not satis factory then try an orificing disc with a smaller diameter hole.
Generally speaking, orificing should always be considered when the burner(s) are large (50K lbs of steam and up), particu larly when the IR
detector is used which would be the case for oil or pulverized coal.
The following table shows the signal reducing charac ter istics of the different orificing discs:
Ap er ture
Hole
1" 2 1
3/8" 5.3 1/8
1/4" 8 1/16
3/16" 10.7 1/32
1/8" 16 1/64
Fn
(f Stop)
Rela tive light
pass ing power
DEFAULT SETTINGS FOR THE S550
A new P520 / P522 will send the S550’s default “Gains” as follow:
UV Gain = 32 (out of 0-99 range) Fil ter = Fil ter 3 (high pass above 33Hz) IR Gain = 451 (out of 0- 699 range)
These are nominal settings that should allow for initial sightings and adjust ments. Both UV and IR sensors are active in the default mode. They are the same settings that will be active in an S550 when used with an older version of the P520/P522 or with an M502 signal processor. If the settings for the S550 have been changed from the default settings the operator may reset the “Gain” to the factory default from the P520 / P522 control panel. (See Return to Default Settings on Page 12.)
WHERE S550 SETTINGS ARE STORED
Settings for the S550s are stored in EEPROM in the particular P520/P522 which made the adjust -
ments. On subse quent power-up cycles the P520/P522 will send out the settings again to the S550 viewing head. In fact, if one S550 is exchanged with another one, the P520/P522 cannot tell one S550 from another and will send out the same settings. This simplifies field replace ments; all S550’s are made to very close
PAGE 9
IRIS MODEL S550 APPLICATION MANUAL
tolerences, so any other S550 will work virtually the same as the one it replaces.
NOTE: the S550 is designed to work only with newer P520/P522 signal processors. How ever, besides working with newer signal processors, S552’s and S556’s are designed to work also with older P520/P522 and M502 signal processors; with these they will operate at their default gain settings.
AS SIGN ING DIF FER ENT S550 SET TINGS TO CHAN NEL A AND B
With the P520/P522 an operator may assign one group of S550 settings to Channel A and another group of S550 settings to Channel B, just as he would assign different Flame ON and Flame OFF set points to Channels A and B. How one may store settings for each channel in the P520/P522 will be briefly reviewed.
If the CHAN SEL input to the P520/P522 is open or de-energized, then the Channel A lighted push­ button on the front panel will be continu ously ON. If a voltage of 7.5V to 30V is applied across the two CHAN SEL inputs, then Channel B will be selected and the Channel B lighted push button will be continu ously ON. When Channel A is selected, any P520/P522 parameters changed (this includes Flame ON and Flame OFF set points and the analog gain of the P520/P522 as well as the gain and filter selection for the S550) will be stored for use when Channel A is selected. Similarly, when Channel B is selected any P520/P522 changes are stored for use when Channel B is selected. When the CHAN SEL input is changed, the P520/P522 changes the set points in use accord ingly and sends the appro ­priate gain and filter selec tions to the S550 viewing head.
In the P520/P522 there is a way to observe and change settings for the channel which is not selected: simply press the other channel push button - it will blink indicating that the selection is temporary - and then proceed as if the CHAN SEL input had changed. This method is available for examining or changing Flame ON and Flame OFF set points and other settings in the P520/P522. The same pro ce dure applies to manually changing
S550 settings when the desired channel is not selected: press the push- button for the desired channel and then proceed. During the process of examining or changing the S550 settings, with the Channel A and B (NO and YES) push buttons, the red LED for the channel which the changes apply, will be blinking.
One should visually check which channel push button is lighted when the S550 settings are being reviewed or changed. It is easy to get into the S550 CAL modes with the wrong channel selected. For example, if the Channel A LED is on or blinking and one intends to press both buttons at the same time to enter the CAL mode for Channel A, but, instead, one presses the Channel B push button well bef ore the Channel A push button, the P520/P522 will think that the operator has selected Channel B then subse quently pressed both push buttons. Then, in the CAL modes, the red LED for Channel B will be blinking, which is not what was intended. If this happens, one should get out of the CAL mode, select the desired channel, and press both push buttons again to reenter the CAL mode, but this time pressing both push buttons at approxi mately the same time.
USING TWO VIEWING HEADS PER AMPLIFIER
Two viewing heads can easily be hooked up to the same amplifier using the V.H. A and V.H. B inputs. To permit this to work properly the P520 or P522 should be wired so that a 24VDC channel select signal will be applied simul ta ne ously to the coil of the VH select relay and to the channel select input. Then, when the channel selection is changed, the alternate set of data inputs from viewing head B will be switched into the signal processor by the VH select relay and the processor will apply a different group of set points and gains in response to the A/B Channel switch.
There is no restriction on how viewing heads may be mixed between the two channels. One can have an S550 on one channel and an S511 on another, or an S552 on one channel and an S556 on another, or any combination. Of course, the earlier 500 series viewing heads - Models S506, S511 and S512 - are not adjustable remotely as the S550 family of viewing heads are. The P520 or
PAGE 10
IRIS MODEL S550 APPLICATION MANUAL
P522 signal processors will continue to work as they have in the past with an earlier 500 series viewing head when the channel with that viewing head is selected.
BEFORE MAKING ADJUSTMENTS
Bef ore making any adjust ments to the S550 one should optimize the flame signal strength by aiming the viewing head at the most intense part of the flame as explained in the two pre vious sections IR DETECTOR and UV DETECTOR. This operation should be done with the default settings.
NEW P520/P522 FRONT PANEL
Please ref er to Fig. 1 at the end of this manual which shows the current front panel for the P520/P522. The words NO , CAL and YES are shown here in black but are actually red. This latest version of the P520/P522 signal processors may be used to commu nicate with the S550 viewing heads as described below.
CALIBRATING THE S550
The S550 calibrate feature is designed to aid with the setup of the S550. It is basically an auto mat ic gain adjustment for the selected sensor; the gain for the sensor not selected is set to zero. CAL tries to bring the displayed count to about 1200. It also automati cally sets the Flame ON set point at 800 and Flame OFF set point at 600, which control the Flame Relay. The filter selection remains unchanged.
3) Bring the firing rate of the burner to a low fire condition.
4) If the flame relay has not pulled in, adjust the flame on & off set points so it does pull in.
5) Decide whether to calibrate using the UV or IR sensor. See earlier sections on IR
DETECTOR and UV DETECTOR.
At the front panel of the P520/P522 press both A and B push buttons simul ta ne ously. The display will respond with “CAL?”. Press YES. The display will then show “CALu”. Press YES to calibrate the UV response or press NO. If NO is pressed the display will show
“CALr”. Press YES to calibrate the IR
response. (Pressing NO will return the P520/P522 to normal operation, exiting the S550 CAL mode.) The P520/P522 will automati cally adjust the gain for the selected sensor; this takes a few seconds. If this adjustment is successful the display will show
“----”, and the P520/P522 will return to
normal operation, displaying a reading of 1100 to 1300. But if the signal input is too low the P520/P522 will display “2-Lo”. Press the RESET button to return to the pre vious settings. If the signal level is too high, the display will show “OriF”. (See section on
ORIFICING.) Press RESET to return to the pre -
vious settings.
Calibration Pro ce dure:
1) Make a quick initial adjustment of the sighting of the viewing head, trying to obtain a high pulse rate. Red pulses from the LED indicate that the IR sensor is producing output pulses; green pulses indicate that the UV sensor is producing output pulses.
2) Be sure that the external input for CHAN SEL is properly set for the channel about to be calibrated and that the channel LED is on continu ously. When Using the calibrate feature one does not have the option of working with the channel that is not selected by the external input.
PAGE 11
6) If step 5 was successful, re-aim the S550 for a final adjustment using the LED to adjust the viewing angle for a maximum pulse rate. Then redo the CAL sequence as in step 5). The Flame Relay will remain pulled-in. The display should show a reading between 1100 and 1300.
7) Review the settings for F.F.R.T. And TIME DELAY ON and adjust if necessary.
EXAMINING THE RE SULTS OF GAIN SET TINGS FROM CALIBRATION
The gain settings deter mined automati cally by the forgoing calibration pro ce dure may be viewed by following the steps below for checking or changing the UV and IR gain. Changes to these
IRIS MODEL S550 APPLICATION MANUAL
settings, of course, may be made. The auto mat ic calibration process is not sacred; it only finds gain values. The user may change these, if he wishes, to suit his needs. For example, one may wish to increase the gain so the nominal displayed value is 1500 instead of 1200.
Note that the calibration pro ce dure sets the gain of the sensor not being used to zero, but one can adjust the gain of the unused sensor so the S550 responds to both sensors. The S550 sums the sensor outputs.
CHECKING OR CHANGING UV GAIN
At the front panel of the P520/P522 press both A and B push buttons simul ta ne ously. The current numerical data on the 4 digit display will be replaced with “CAL?” meaning, “Do you wish to Calibrate?” If you press YES you will enter the Calibration mode described in the pre vious section. Press NO to enter the Adjust mode. The display will show “AdJ?” meaning, “Do you wish to make manual adjust ments?” If you do, press the button near YES, which is the B push button. The display will show “AuNN” where NN is the current UV gain with the range 00 - 99. A gain of 00 turns off the sensor. To change the UV gain use the up or down push buttons. If you then press YES the new value will be stored; if you press NO (Channel A push- button) the new value will be ignored.
CHECKING OR CHANGING IR FILTER
You next have an oppor tunity to change the IR filter. The display will show “ArFN” where N is the current filter selected ranging from 1 to 8. Use the up and down push- buttons to change the filter if you wish. See COMPARISON WITH OTHER
MODEL 500 SERIES VIEWING HEADS for a listing
of the high-pass frequencies for these filters. Press YES to accept a new filter value or NO to ignore any changes you may have made.
For further infor mation please call the factory or contact IRIS Systems Inc. See page 13 for contact infor mation.
CHECKING OR CHANGING IR GAIN
You now have an oppor tunity to make a final adjustment of the IR gain. After the filter selection, the display will show “ANNN” where NNN, the IR gain, ranges from 000 to 699. The up and down push- buttons can be used to change the IR gain. Changed values can be accepted by pressing YES or ignored by pressing NO. If the S550 settings are changed, the display will show “----” indicating that the values are stored in EEPROM bef ore continuing with the normal numerical display.
If you do change the IR gain you may be surprised to see the displayed gain values “jump” as you scroll through them. As you increase the gain from zero you will see this sequence:
000 - 099 150 - 199 250 - 299 350 - 399 450 - 499 550 - 599 650 - 699
The two least significant digits are linear gain multi pliers; e.g., from 150 to 199 is a 99/50 increase in gain. But the most significant digit is nonlinear; with each step change in the most significant digit, the gain doubles. For example, a setting of 250 has twice the gain as a setting of
150. Now it is possible to see why, as the gain is
increased from 150 to 199 the next step is to 250; an increase from 150 to 199 is an increase of 99/50, which is a gain increase of almost 2, but the next step to 250 is to a gain increase, theore ti cally, to exactly 2. This relationship is true of all the gains to 699.
It is recom mended that the #3 default filter (33Hz cutoff) be used for all of the initial setup proce ­dures described in this manual. Further infor ­mation on how these filters can affect the discrimi ­nation ratio is found in the P520 APPLI CATION
MANUAL and in the P522 APPLI CATION MANUAL
in the section MULTI BURNER REQUIRE MENTS.
The two least significant digits can be used below 050 down to 000; 000, of course, selects a gain of zero (which turns OFF the sensor). When the display is ramped down from 699 the following sequence will be seen:
PAGE 12
IRIS MODEL S550 APPLICATION MANUAL
673 - 637 573 - 537 473 - 437 373 - 337 273 - 237 173 - 137 073 - 000
This approach makes a wide range available for gain multi plier changes using the two least significant digits. For example, over a range of 137 to 199 the gain is changed by a ratio of 99/37. It is advan ta geous for moderate changes in gain to change only the gain multi plier digits because the response to these changes is very linear. When changes are made in the most significant gain digit, the gain change is not always exactly an ideal 2:1 step change.
MAN UAL SETUP OF THE S550
The steps below for manual setup should result in the P520 or P522 displaying a reading close to 1200 with flame on. This pro ce dure should pro ­vide similar gain settings for each selected sensor as in the CALIBRATION pro ce dure described earlier.
1) Bring the firing rate of the burner to a low fire condition.
stays the same or actually increases, the S550 is saturated. Continue reducing the gain in steps of 100 until the displayed reading is reduced. Then set the gain so the reading is in the 1000 to 1400 range. If the IR sensor was not saturated one can skip para graph 5) below.
5) If the S550 was saturating one should check the aiming of the S550 again using the LED on the back of the housing to adjust the viewing angle of the head for a maximum pulse rate. If the LED pulse rate is then too high (the LED is ON almost continu ously) change the gain once more by using the Adjust Mode pro ce dure to get a reading in the 1000 to 1400 range. Then maximize the pulse rate by re-aiming the S550 viewing head. This pro ce ­dure of optimizing the sighting and adjusting the gain may have to be done more than one time to be assured that the S550 is properly setup.
6) If the UV sensor has been chosen adjust the gain (00-99) using the Adjust Mode so the displayed reading is close to 1200. The UV sensor is not likely to saturate but if the flame signal readings are very high on low gain settings then one should orifice the sighting. See section ORIFICING.
2) Be sure that the external input for CHAN SEL is properly set for the channel calibration (A or B) that is currently being set and the channel LED is ON continu ously.
3) Decide whether to setup the S550 using the UV or IR sensor bef ore aiming the viewing head. In some flames the best UV reading of the flame envelope may be found at a different location from the best IR reading. See earlier sections IR DETECTOR and UV DETECTOR . Use the Adjust Mode (“AdJ?”) pro ce dure for the S550 described above and set the gain for the sensor not being used to zero.
4) If the IR sensor is being used, bef ore final aiming but with a typical reading on the display, verify that the S550 is not saturated by reducing the IR gain by 100. The displayed reading should be reduced by roughly 1/2. If it
PAGE 13
7) Set or at least check the Flame ON and Flame OFF set points. If they are still at the factory default values (Flame ON at 800 and Flame OFF at 600) they may be satis factory as they are. If the Flame ON reading is less than 1200 the Flame OFF setting should be propor tion ­ately less.
8) Review the settings for F.F.R.T. and TIME DELAY ON and adjust if necessary.
RE TURN TO DE FAULT SET TINGS
There are three major branches on the decision tree after one gets into the S550 setup by pressing the A and B push buttons. Ref er to Fig. 3 at the end of this manual. That is, if one says NO to “CAL?”, one is asked if one wishes to do adjust. If one says NO to “AdJ?”, one is asked if one wishes to go back to the default settings. If one says NO to “dEF?”, then the P520/P522 and S550 continue
with normal operation. If one says YES to defaults, then the original default settings are stored for the selected channel overwriting the pre vious S550 settings for that channel.
ANGLE OF VIEW
The angle of view for S550 viewing head utilizing the IR detector will be the same as the S511 because the Ge photo de tector element is 1mm in
diameter which results in an angle of 1.0°. When using the UV detector the angle of view will be the
same as the S506 which is about 3.0 °. See section
SIGHTING OF VIEWING HEAD for details.
GENERAL COMMENTS
It will be obvious to the user of this new innovative product that this is the ultimate state­ of- the-art flame monitor. The way it works has been described only in a general sense and obviously the algorithms imple mented by the embedded controller software are proprietary and will not be made pub li c. Any existing P520 or P522 signal processor can be upgraded to an S550 compatible processor by changing the controller chip and the front panel.
IRIS MODEL S550 APPLICATION MANUAL
TECH NI CAL HELP
For technical help in applying this product please contact: Factory and Repairs:
IRIS Systems Inc. (JB Systems, Inc.)
4944 - 113th Avenue North
Largo, FL 33760
Tel: 727 545-3900 Fax: 727 547-9589
Sales and Appli ca tions Support:
IRIS Systems Inc.
7583 Vantage Placey Delta, BC V4G 1A5
Tel: 604 584-4747
604 538-5972
Fax: 604 581-9790
1-800-667-IRIS
PAGE 14
IRIS MODEL S550 APPLICATION MANUAL
Figure 1
PAGE 15
Figure 2
IRIS MODEL S550 APPLICATION MANUAL
PAGE 16
Fig ure 3
IRIS MODEL S550 APPLICATION MANUAL
PAGE 17
Fig ure 4
IRIS MODEL S550 APPLICATION MANUAL
Fig ure 5
PAGE 18
IRIS MODEL S550 APPLICATION MANUAL
PAGE 19
5 June 1997