International comfort products PGX3 Series, PGX336060, PGX336080, PGX336100, PGX342080 Installation Instructions Manual

...
Printed in U.S.A.
509 01 2601 02 81309
PACKAGED GAS / ELECTRIC UNITS
Installation Instructions
PGX3 Series
3 Phase
Code: PGX3
TABLE OF CONTENTS
UNIT DIMENSIONS 2 - 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAFE INSTALLATION REQUIREMENTS 4. . . . . . . . . . . . . . . . . . . . . . . . .
LOCATING THE UNIT 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEARANCES 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GROUND LEVEL INSTALLATION 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ROOFTOP INSTALLATION 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HOISTING 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DOWNFLOW CONVERSION 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HEATING VENT ASSEMBLY 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONDENSATE DRAIN 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PRE-EXISTING COMMON VENT CHECK 7. . . . . . . . . . . . . . . . . . . . . . . . .
GAS SUPPLY AND PIPING 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ORIFICES 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTRICAL WIRING 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DUCTWORK 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FILTERS 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AIRFLOW ADJUSTMENT 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
START-UP PROCEDURES 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GAS PRESSURES 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HEATING START-UP PROCEDURES 14. . . . . . . . . . . . . . . . . . . . . .
OPERATION 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MAINTENANCE 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSPECTION AND CLEANING 17. . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPONENT LOCATION 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RIGGING 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WIRING DIAGRAMS 20 - 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
A32−1/2 826 B47−3/8 1203 C47−3/8 1203 D3−1/8 79 E11−1/8 283 F 12 306 G14−1/4 363 H14−1/4 363 I 12 306 J 4 102 K 3/4 & 1 19 & 25 L4−1/4 108 M4−3/8 111 N14−1/2 368 P12−1/4 311 Q12−1/8 308 R14−1/4 363 S12−1/4 318
COMBINATION GAS/
ELECTRIC UNITS
‘‘B’’ Chassis
(47
3
/8 x 473/8)
ROOF CURB
for units in
‘‘B’’ Chassis
(47
3
/8 x 473/8)
Units in ‘‘B’’ Chassis Configuration PGX336
Units in ‘‘B’’ Chassis Configuration PGX336
ELECTRICAL
POWER
LOW VOLTAGE 1/2” (12.7) CONDUIT
GAS CONNECTION
1/2” (12.7) PIPE
CONDUIT (”K” DIM.)
21/2”
(63.5)
3” (76.2)
11/2” (38.1)
211/4”
(539.75)
11−1/8”
(282.575)
4”
(101.6)
”G”
”F”
”H”
”K”
’D”
”E”
”C”
”B”
”A”
”C”
”B”
”A”
”D”
”G”
”E”
”I”
”H”
”F”
”L”
”J”
”N”
”R”
”M”
”S”
”Q”
”P’’
A42−3/4 1086 B39−3/4 1010 C 18 457 D 18 457 E3−3/4 95 F42−3/4 1086 G39−3/4 1010 H 18 457 K* 14 356
‘‘B’’ CHASSIS UNIT DIMENSIONS
1. Unit Dimensions
Unit Base shown separately to illustrate bottom of duct openings.
* Roof curbs are also available in 8” (203) and 24” (610) heights (K Dimensions).
COMBINATION GAS/
ELECTRIC UNITS
‘‘C’’ Chassis
(47
3
/8 x 73)
ROOF CURB
for
‘‘C’’ Chassis
(47
3
/8 x 73)
Units in ‘‘C’’ Chassis Configuration PGX34260
”C”
”B”
”A”
”I”
”E”
”G”
”D”
”F”
”J”
”H”
”L”
”N”
”R”
”S”
”Q”
”P”
”M”
SUPPLY
RETURN
”G”
”F”
”H”
”K”
’D”
”E”
”C”
”B”
”A”
”J”
”I”
”T”
A 36 914 B47−3/8 1203 C 73 1354 D4−5/8 117 E 15 361 F 12 307 G18−3/4 476 H18−3/4 476 I 12 306 J 4 102 K 1 & 11/4 25 & 31 L4−1/4 108 M5−1/4 133 N12−1/4 311 P 19 483 Q 15 381 R 19 483 S12−1/4 318 T16−7/8 429
A67−3/4 1721 B64−3/4 1645 C 23 584 D 23 584 E2−1/2 64 F42−3/4 1086 G39−3/4 1010 H 23 584 I 12 305 J 12 305 K* 14 356
‘‘C’’ CHASSIS UNIT DIMENSIONS
Unit Base shown separately to illustrate bottom of duct openings.
* Roof curbs are also available in 8” (203) and 24” (610) heights (K Dimensions).
3
4
2. SAFE INSTALLATION REQUIREMENTS
Installation and servicing of airconditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified personnel should install, repair, or service airconditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters. All other operations should be performed by trained service personnel. When working on air−conditioning equipment, observe precautions in the literature, tags, and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISON HAZARD
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, fire, or an explosion which could result in personal injury or unit damage. Consult a qualified installer, service agency, or gas supplier for information or assistance. The qualified installer or agency must use only factory−authorized kits or accessories when modifying this product.
!
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISON HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Before performing service or maintenance operations on unit, turn off gas supply to unit. Then turn off unit main power switch and install lockout tag.
!
Recognize safety information. This is the safety−alert symbol . When you see this symbol in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safetyalert symbol. DANGER identifies the most serious hazards which will result in serious injury or death. WARNING signifies a hazard which could result in serious injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices.
We require these instructions as a minimum for a safe installation.
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISON HAZARD
!
Failure to carefully read and follow all instructions in this manual could result in furnace malfunction, property damage, personal injury and/or death. Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local building codes or, in the absence of local codes, with the National Fuel Gas Code NFPA 542005/ANSI Z223.12005 and the National Electrical Code NFPA70−2005 or in Canada the National Standard CAN/CGA B1491 and CSA C.22.1 Canadian Electrical Code Part 1.
The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
SAFETY CONSIDERATIONS
Use only with type of gas approved for this unit. Refer to unit rating plate.
Install this unit only in a location and position as specified in section 3 of this manual.
Never test for gas leaks with an open flame. Use a com­mercially available soap solution made specifically for the detection of leaks to check all connections, as specified in section 5.
Always install unit to operate within the unit’s intended temperaturerise range with a duct system, which has an external static pressure within the allowable range, as specified in section 9. Refer to unit rating plate for the al­lowable external static pressures.
All connecting ductwork to the unit (supply and return) must be sealed to the unit casing as specified in section 7.
Do NOT use this furnace as a construction heater.
Check to see that filters are installed correctly and are the
proper type an size.
NOTE: It is the personal responsibility and obligation of the customer to contact a qualified installer to ensure that the installation is adequate and conforms to governing codes and ordinances.
UNIT SAFETY
CAUTION
!
Failure to follow this caution may reduce unit reliability. It is recommended that a qualified service technician
check the heat exchanger integrity every two (2) years, after the first four (4) years of operation.
INTRODUCTION
The PGX3 unit is a fully selfcontained, combination Category I gas heating/electric cooling unit designed for outdoor installation (See pages 2 and 3 for unit dimensions). All unit sizes have return and discharge openings for both horizontal and downflow configurations, and are factory−shipped with all downflow duct openings covered.
Units may be installed either on a rooftop, cement slab, or directly on the ground if local codes permit.
!
5
Models with a ”1” in the twelfth position of the model number are dedicated Low NOx units designed for California installations. The emissions of these models do not exceed 40 nanograms of nitrogen oxide emissions per joule of heat output as shipped from the factory, and must be installed in California Air Quality Management Districts or any other regions in North America where a Low NOx rule exists.
3. LOCATING THE UNIT
ACCESS PANELS
See Figure 1 for a general view of unit and location of access panels.
CARBON MONOXIDE POISONING HAZARD.
!
Failure to follow this warning could result in personal injury and/or death.
Keep blower door closed.
CLEARANCES
The location MUST allow for minimum clearances and should not be adjacent to a patio or other area where the unit’s operating sound level might be objectionable. The combustion air inlet openings MUST not be obstructed (see
Figure 1). In addition, local codes MUST be observed.
NOTE: Units with available filter racks
( 3 to 5 ton), need a
26 minimum clearance at side of unit for removal of filters. See chart below if unit is going to be placed near combustible construction or materials.
While minimum clearances are acceptable for safety reasons, they may not allow adequate air circulation around the unit for proper operation in the cooling mode. Whenever possible, it is desirable to allow additional clearance, especially around the condenser inlet and discharge openings.
Do NOT install the unit in a location that will permit discharged air from the condenser to recirculate to the condenser inlet.
Do NOT operate unit in a corrosive atmosphere containing chlorine, fluorine, or any other corrosive chemicals.
CAUTION
!
UNIT DAMAGE HAZARD Failure to follow this caution may result in shorten life
of unit components.
Minimum Clearances to Combustible Construction
Furnace Plenum 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Duct Side 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Condenser Inlet 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Service (Side) 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Service Side
(Front Combustion Air Inlet) 30. . . . . . . . . . . . .
Clearance between 3 Ft. Overhang
and Top of Unit 30. . . . . . . . . . . . . . . . . . . . . . . .
Combustible Base
(Wood or Class A, B or C
roof covering material) 0. . . . . . . . . . . . . . . . . . . .
FIGURE 1
Minimum Clearances and Access Panels
(B Chassis Shown)
Burner Compartment
Panel
Blower Compartment Panel
800001
Internal Filter Access from Burner Compartment Side 26’’ (C Chassis Units)
30’’
30’’
C Chassis 6’’
30’’
30’’
36’’
2’’
B Chassis 2’’
INSTALLATION
NOTICE
Unit will NOT operate properly unless it is installed level front to rear and side to side. The slope MUST NOT be greater than
1
/8″ per foot (10mm per meter). For side
to side leveling, the drain side MUST always be lower.
Ground Level Installation
Ground level platform requirements:
The unit MUST be situated to provide safe access for servicing.
Platform may be made of either concrete or pressure treated wood and MUST be level and strong enough to support unit weight.
Position platform separate from building foundation.
Install in well−drained area, with top surface of platform
above grade level.
Platform must be high enough to allow for proper condensate trap installation and drainage. See FIGURE 4 and associated text for more information about condensate drainage.
Rooftop Installation
Rooftop platform requirements:
The unit MUST be situated to provide safe access for servicing.
The existing roof structure MUST be adequate to support the weight of the unit or the roof MUST be reinforced. Check the weight of the unit in relation to the roof structure and local building codes or ordinances and reinforce roof structure if necessary. See the last page of this manual for unit weights.
Support for the unit MUST be level and strong enough to carry unit weight. The support may consist of a platform or a combination of platform and roof beams or curb.
See Hoisting section for hoisting instructions.
HOISTING
NOTE: All access panels MUST be secured in place before
6
hoisting.
The unit should be hoisted with two lifting slings. Attach the slings to rigging shackles that have been hooked through holes in the base rail.
Two spreader bars MUST be placed on top of the unit to protect the unit from damage from the pressure exerted by the slings. Make sure that all equipment is adequate to handle the weight of the unit and that the slings will not allow the unit to shift.
Refer to FIGURE 18 on the back cover of this manual for illustrated rigging instructions and weight chart.
DOWNFLOW CONVERSION
NOTE: In downflow applications with roof curbs or jack
stands, the center rail under the unit must be removed. The center rail is attached to the base rail with screws.
These units are adaptable to downflow use. To convert to downflow use, follow these steps:
1. Remove the blockoff plates found in the return air compartment and the supply air compartment.
NOTE: Blockoff plate in the supply air compartment only contains one screw. If reinstalling plate, back part of plate MUST fit into mating dimples on flange. To reinstall, slant plate into dimples, then put plate into position and fasten with screw.
FIGURE 2
Heating Vent Assembly
Screws for
‘‘B’’ Chassis
(47
3
/8 x 473/8)
Screw for
‘‘C’’ Chassis
(47
3
/8 x 73)
2. Install the removed plates on the horizontal return and supply air openings.
3. Install roof curb on the building. Be sure to follow all directions included with curb and all applicable building codes in your installation. See page 2 or 3 for appropriate roof curb to use.
Heating Vent Assembly
The flue cover is packed with installation screws in the return air compartment. Refer to FIGURE 3 and assemble as shown.
FIGURE 3
Heating Vent Assembly
Flue Support
(Shipped mounted to unit)
Flue Cover
UNIT DAMAGE
CAUTION
!
Do not operate the unit without the vent assembly installed.
Failure to follow this caution may result in unit damage.
Condensate Drain
The condensate drain outlet is a
3
/4″ (19.1mm) female PVC connection located at the bottom of the unit to the right of the filter access panel (see FIGURE 4).
The circulating blower creates a negative pressure on the condensate drain line that can prevent the condensate from draining properly. To combat this negative pressure, a field supplied condensate trap that will allow a standing column of water of at least 2″ (50.8mm) MUST be installed . Top of outlet from trap MUST be at least 1 (25.4mm) below top of outlet from unit. Install the trap as near to the unit as
possible for proper drainage.
A
3
/4″ (19.1mm) drain line MUST be installed if required by local codes or if location of unit requires it. Run the drain line to an open drain or other suitable disposal point.
FIGURE 4
Condensate Drain Information*
* Condensate trap MUST be installed.
3
/4″ (19.1mm)
Drain Line
803027
1 (25.4mm)
2 (50.8mm)
3
/4″ (19.1mm) Threaded Female PVC Fitting
4-1/2
25-1/2 (‘‘B’’ Chassis) 32-1/4 (‘‘C’’ Chassis)
*
7
4. PRE−EXISTING COMMON VENT CHECK
If the installation of this new combination gas heat/electric cool unit involves removing an existing gas−fired furnace from a common vent system with other gas−fired appliances (gasfired hot water heater, etc.), the existing vent system must be checked and inspected by a qualified technician. The qualified technician can determine if the existing vent system will properly vent the flue products of the remaining gas−fired appliances. In many cases, the existing vent system may be oversized for the remaining appliances.
5. GAS SUPPLY AND PIPING
NOTE: Because there are many types of liquified petroleum
(LP) gases, the term LP as used in this manual refers to propane gas. If you intend to use any type of LP gas, proper precautions MUST be used in the handling, piping, and use of such gas. NOTE: In Canada, installations MUST be performed by licensed LP installers.
The UL rating plate located on the side panel on the unit contains the model number, type of gas, gas input rating, and other important information.
FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death and/or property damage.
Make certain the unit is equipped to operate on the type of gas available. Models designated as natural gas are to be used with natural gas only. Models designated for use with liquefied petroleum (LP) gas are shipped with orifices sized for commercially pure propane gas. They MUST not be used with butane or a mixture of butane and propane unless properly sized orifices are installed by a licensed LP installer.
!
GAS PIPING
The gas supply line MUST be of adequate size to handle the Btu/hr requirements and length of the run for the unit being installed. Determine the minimum pipe size for natural gas from the table in FIGURE 5 or FIGURE 6. Base the length of the run from the gas meter or source to the unit.
Gas Pipe Size
Btu ratings of all other gas appliances MUST be considered for sizing of main gas line. Check gas line to installation for compliance with local codes or, in the absence of local codes, with the National Fuel Gas Code NFPA 542005/ANSI Z223.12005 or in Canada the National Standard CAN/CGA B149−1 or current editions.
Gas Pipe Size, Length and Btu/hr Capacity for Schedule 40 Iron Pipe (English)
20 190 350 730 1,100 2,100
40 130 245 500 760 1,450
60 105 195 400 610 1,150
FIGURE 5
Btu/hr (in thousands)
LP GAS
NATURAL GAS
Pipe Length
(Includes
Fittings)
3
/4″ 1″ 11/4″ 11/2″ 2″
20 189 393 732 1,496 2,299
40 129 267 504 1,039 1,559
60 103 217 409 834 1,275
Btu/hr (in thousands)
Pipe Length
(Includes
Fittings)
1
/2″
3
/4″ 1″ 11/4″ 11/2″
Pipe Length
(Includes
Fittings)
6.1m 56 103 214 322 615
12.2m 38 72 147 223 425
18.3m 31 57 117 179 337
FIGURE 6
kW**
LP GAS
NATURAL GAS
Pipe Length
(Includes
Fittings)
3
/4″ 1″ 11/4″ 11/2″ 2″
6.1m 55 115 215 438 674
12.2m 38 78 148 305 457
18.3m 30 64 120 244 374
kW**
1
/2″
3
/4″ 1″ 11/4″ 11/2″
**kW (Kilowatts) is the metric equivalent of Btu/hr.
Gas Pipe Size, Length and Btu/hr Capacity for Schedule 40 Iron Pipe (English)
PIPING AT UNIT
Connections
In the state of Massachusetts:
This product must be installed by a licensed Plumber or Gas Fitter.
When flexible connections are used, the maximum length shall not exceed 36 inches.
When lever type gas shutoffs are used they shall be Thandle type.
The use of copper tubing for gas piping is not approved by the state of Massachusetts.
NOTE: The rules listed apply to natural and LP gas pipe installations.
1. If installation is for LP gas, have LP gas installer use TWOSTAGE REGULATION and make all connections from storage tank to unit.
2. Use black iron or steel pipe and fittings or other pipe approved by local code.
3. If copper tubing is used, it MUST comply with limitation set in Fuel Gas Code.
NOTE: If a flexible gas connector is used, it MUST be acceptable to local authority. Connector MUST NOT be used inside the furnace or be secured or supported by the furnace or ductwork. Do not use a connector which has
Loading...
+ 16 hidden pages