International Comfort Products FMU4X, FMU4P Installation Manual

INSTALLATION INSTRUCTIONS
UNCASED HORIZONT AL F AN COIL UNIT
FMU4X, FMU4P
NOTE: Read the entire instruction manual before starting
installation.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 1.........................
INTRODUCTION 1....................................
INSTALLATION 2.....................................
Step 1 — Check Equipment 2.........................
Step 2 — Mount Fan Coil 2...........................
Step 3 — Supply--Air Connections 3....................
Step 4 — Condensate Drain 3.........................
Step 5 — Electrical Connections 3.....................
Step 6 — Select Proper Blower Speed 4................
Step7—TXV 4.....................................
START-- UP 4.........................................
SEQUENCE OF OPERATION 4.........................
CARE AND MAINTENANCE 5..........................
AIRFLOW PERFORMANCE TABLES 5..................
WIRING DIAGRAM 6..................................
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to individual instructions packaged with kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have a fire extinguisher available. Read these instructions thoroughly and follow all warning or cautions included in literature and attached to the unit. Consult local building codes and the current editions of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety alert symbol
. When you see this symbol on the unit and in instructions
or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
INTRODUCTION
FMU4P and FMU4X Fan Coils are designed for horizontal orientation and are suitable for ceiling installations in conditioned space. These units are available with field--installed electric heat, and are used indoors as the fan
coil for split--system heat pumps or air conditioners. The
FMU4P models use a refrigerant piston metering device and
are available in 18,000 through 36,000 Btuh nominal cooling capacities. The FMU4X models have a factory--installed TXV and are available in 18,000 through 30,000 Btuh nominal cooling capacities. All units utilize a 3--speed PSC motor.
Field--installed heaters are available in 5, 7.5, and 10 kW sizes. The coil is equipped with sweat -- type connections and is vapor-- charged with dry nitrogen.
Units are designed for horizontal applications only. Local codes may limit this free--air--return type unit to installation in single--level applications.
NOTE: Nuisance sweating may occur if the unit is installed in a humid location with low airflow.
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing unit, always turn off all power to unit. There may be more than 1 disconnect switch. Turn off accessory heater power if applicable. Lock out and tag switch with a suitable warning label.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
WARNING
!
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.
CAUTION
Specifications subject to change without notice.
496 01 8101 02 4/7/16
INSTALLA TION INSTRUCTIONS Fan Coil: FMU4X, FMU4P
A
B
C
D
26-3 /8 [67670 mm ]
10-1/4”
[
260 mm ]
7-7
/8
[
200
m
m ]
5
[
127
m
m
]
16-1 /4 [
412 m
m
]
1[ 25 mm ]
Low voltagage
connection
V
aporliline comection
copper (sweat)
Liquid
line comection
copper (sweat)
High voltage connnnection
3/8” [35 mm] dia knock outs
Auxiliary drain c
onnection 3/4” ”
[20 mm]
male pipe thrhread(n(npt)
Primary
drain cononncetion 3/4” ”
[20mm]
male pipe thrhread(n(npt)
Figure 1 -- Dimensional Drawing
li
26-
onn
dr
20
7-
12
[20 mm]
[20mm]
26
10-1/4”
apo
41
16-
Lo
1-1-3/8” [35 mm]
Model Size
Table1–DimensionalData
Dimensions- inches [mm]
A B C D
Unit Operating Weight
lbs (kg)
A13183
18 37-1/4 [946] 34-11/16 [881] 30 [762] 6-1/2 [165] 75 (34) 24 37-1/4 [946] 34-11/16 [881] 30 [762] 6-1/2 [165] 75 (34) 30 49-1/4 [1251] 46-11/16 [1186] 42 [1067] 6-1/2 [165] 93 (42) 36 49-1/4 [1251] 46-11/16 [1186] 42 [1067] 6-1/2 [165] 93 (42)
INSTALLATION
Step 1 — Check Equipment
Unpack unit and move to final location. Remove from carton, avoid lifting from blower wheels, taking care not to damage unit. Inspect equipment for damage prior to installation. File claim with shipping company if shipment is damaged or incomplete. Locate rating plate on unit. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications. NOTE: Installation clearance from combustible materials is 0” (0 mm) from unit and supply--air duct.
Step 2 — Mount Fan Coil
Fan Coil Mounting
Mounting slots on the top of the unit are provided for attachment of the fan coil to supporting structure. The supporting structure must be designed to safely support the full weight of the fan coil. Field supplied washers and bolts capable of supporting the fan coil load should be used to secure the fan coil to the supporting structure at the mounting slots.
2 496 01 8101 02
The fan coil must be mounted level to ensure proper drainage of condensate. If the supporting structure is not level at the points of fan coil attachment, then spacers must be used to level the fan coil. After mounting unit, install refrigerant tubing as follows:
1. Route tubing to connection points.
2. Remove plugs from liquid and vapor lines.
3. Wrap the TXV or piston body with a wet rag to prevent overheating.
4. Braze connections using either silver bearing or non--silver bearing brazing material. Do not use soft solder (materials which melt below 800_F / 427_C). Consult local code requirements. Always flow nitrogen through the system refrigerant lines while brazing.
5. Pressurize system and leak--test. Repeat procedure until leak--free.
NOTE: FMU4P fan coils are shipped with a piston metering device designed for the most common outdoor unit matches. The piston included with the fan coil is unique to this product and cannot be replaced with the piston shipped with the outdoor unit. Refer to AHRI ratings to check if your combination can use the piston shipped with the unit or requires an accessory TXV.
Specifications subject to change without notice.