International Comfort Products FAS072, FHS072, FAS091, FHS091, FAS120 Installation Manual

...
INSTALLATION INSTRUCTIONS
FAS/FHS Series, Package Air Handling Units
6 to 25 Ton Air Conditioners
6to20TonHeatPump
NOTE: Read the entire instruction manual before starting the installation
SAFETY CONSIDERATIONS 1...................
PRE--INSTALLATION 2.........................
Moving and Storage 2..........................
Rigging 2....................................
INSTALLATION 2–29..........................
General 2....................................
Uncrating 2..................................
Accessories 2.................................
Rated Indoor Airflow (cfm) 14...................
Unit Positioning 15............................
Unit Isolation 16..............................
Refrigerant Piping Access 16....................
Refrigerant Piping 16..........................
Condensate Drain 23...........................
Fan Motors and Drives 23.......................
Power Supply and Wiring 24....................
Connecting Ductwork 29.......................
Return--Air Filters 29..........................
START--UP 30.................................
SERVICE 30–45...............................
Panels 30....................................
Fan Motor Lubrication 30.......................
Fan Shaft Bearings 31..........................
Centering Fan Wheel 31........................
Fan Shaft Position Adjustment 31................
Individual Fan Wheel Adjustment 32..............
Fan Belts 32.................................
Fan Rotation 32...............................
Fan Pulley Alignment 32.......................
Pulley and Drive Adjustment 32..................
Condensate Drains 32..........................
Return--Air Filters 32..........................
Coil Removal 32..............................
Cleaning Cooling Coil 33.......................
Cleaning Insulation 33.........................
Replacing Filters 33...........................
START--UP CHECKLIST 47--48..................
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions package
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the safety--alert symbol
unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
. When you see this symbol on the
Specifications are subject to change without notice.
508 01 1603 00 01/2016
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, turn off main power switch to unit and install lock(s) and lockout tag(s). Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate. Unit may have more than one power switch.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause in personal injury,death and/or equipment damage.
R--410A refrigerant systems operate at higher pressures than standard R--22 systems. Do not use R--22 service equipment or components on Puron refrigerant equipment.
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
PRE--INSTALLATION
1. The power supply (v, ph, and Hz) must correspond to that specified on unit rating plate.
2. The electrical supply provided by the utility must be sufficient to handle load imposed by this unit.
3. Refer to Installation, General section (page 2) and
Fig. 1 and Fig. 2 for locations of electrical inlets, condensate drain, duct connections, and required clearances before setting unit in place.
4. This installation must conform with local building codes and with the NEC (National Electrical Code) or ANSI (American National Standards Institute)/NFPA (National Fire Protection Association) latest revision. Refer to provincial and local plumbing or wastewater codes and other applicable local codes.
Moving and Storage -- To transfer unit from truck to storage site, use a fork truck. Do not stack units more than 2 high during storage. If unit is to be stored for more than 2 weeks before installation, choose a level, dry storage site free from vibration. Do not remove plastic wrap or skid from unit until final installation.
Rigging -- All FAS/FHS Series units can be rigged by using the shipping skid. Units are shipped fully assembled. Do not remove shipping skids or protective covering until unit is ready for final placement; damage to bottom panels can result. Use slings and spreader bars as applicable to lift unit.
INSTALLATION
General -- Allow the following clearances for service
access and airflow:
1
S Rear: 3 ft (914 mm) [2
accessory]
1
S Front: 2 S Right Side: 3 S Left Side: 2
/2ft (762 mm)
1
/2ft (1067 mm)
1
/2ft (762 mm)
/2ft (762 mm) with electric heat
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing FAS/FHS units.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment damage.
Ensure voltage listed on unit data plate agrees with electrical supply provided for the unit.
2 508 01 1603 00
Specifications are subject to change without notice.
For units equipped with an economizer, refer to the accessory installation instructions for additional clearance requirements. Be sure floor, wall, or ceiling can support unit weight (Tables 1A – 1D). See Fig. 1, Fig. 2 and Fig. 3 for dimensions.
Uncrating -- Move unit as near as possible to final location before removing shipping skid.
Remove metal banding, top skid, and plastic wrap. Examine unit for shipping damage. If shipping damage is evident, file claim with transportation agency. Remove base skid just prior to actual installation.
Check nameplate information against available power supply and model number description in Fig. 4.
NOTE: Be sure to remove the styrofoam shipping pad from the thermostatic expansion valve (TXV). Verify that it has been removed. See Fig. 5.
Accessories -- Refer to instructions shipped with each accessory for specific information.
Table1A—PhysicalData,English—6to15TonCoolingUnits
UNIT FAS 072 091 120 150 180
NOMINAL CAPACITY (T ons)
6 7
1/
2
10 12
OPERATING WEIGHT (lb)
Base Unit with TXV 399 404 425 695 713
Plenum 175 175 175 225 225
FANS
Qty...Diam. (in.) 1...15 1...15 1...15 2...15 2...15
Nominal Airflow (cfm) 2400 3000 4000 5000 6000
Airflow Range (cfm) 1800---3000 2250---3750 3000---5000 3750--- 6250 4500 --- 7500
Nominal Motor Hp (Standard Motor)
208/230---1 --- 60 1.3 2.4
208/230---3 --- 60 and 460 --- 3 --- 60 2.4 2.4 2.4 2.9 3.7
5 7 5 --- 3 --- 6 0 1.0 2.0 2.0 3.0 3.0
Motor Speed (rpm)
208/230---1 --- 60 1725 1725
208/230---3 --- 60 and 460 --- 3 --- 60 1725 1725 1725 1725 1725
5 7 5 --- 3 --- 6 0 1725 1725 1725 1725 1725
REFRIGERANT
Operating charge (lb) (approx per circuit)
DIRECT--- EXPANSION COIL
{
R---410A R---410A R---410A R--- 410A R --- 410A
3.0 3.0 1.5/1.5 2.0/2.0 2.5/2.5
Enhanced Copper Tubes, Aluminum Sine---Wave Fins
Max Working Pressure (psig) 650 650 650 650 650
Face Area (sq ft) 6.67 8.33 10.0 13.25 17.67
No. of Splits 1 1 2 2 2
No. of Circuits per Split 12 15 9 12 16
Split Type...Percentage Face...50/50 Face...50/50 Face...50/50
Rows...Fins/in. 4...15 4...15 4...15 4...15 4...15
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...1
DX Coil — Liquid Refrigerant (ODF) 1...
Steam Coil, In (MPT) 1...2
Steam Coil, Out (MPT) 1...1
Hot Water Coil, In (MPT) 1...1
Hot Water Coil, Out (MPT) 1...1
1/
8
5/
8
1/
2
1/
2
1/
2
1/
2
1...1
1...
1...2
1...1
1...1
1...1
1/
8
5/
8
1/
2
1/
2
1/
2
1/
2
2...1
2...
1...2
1…1
1...1
1...1
1/
8
5/
8
1/
2
1/
2
1/
2
1/
2
Condensate (PVC) 1...15/8ODM / 11/4IDF
FILTERS
Throwaway — Factory Supplied
Quantity...Size (in.) 4...16 x 24 x 2 4...16 x 24 x 2 4...16 x 24 x 2
Access Location Either Side Either Side Either Side Either Side Either Side
STEAM COIL
}
Max Working Pressure (psig at 260° F) 20 20 20 20 20 Tota l Fa ce A r ea ( s q f t ) 6.67 6.67 6.67 13.33 13.33
Rows...Fins/in. 1...9 1...9 1...9 1...10 1...10
HOT WATER COIL
}
Max Working Pressure (psig) 150 150 150 150 150
Tota l Fa ce A r ea ( s q f t ) 6.67 6.67 6.67 13.33 13.33
Rows...Fins/in. 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5
Water Volume
(gal) 8.3 8.3 8.3 13.9 13.9
(ft3) 1.1 1.1 1.1 1.85 1.85
LEGEND
DX — Direct Expansion TXV — Thermostatic Expansion Valve
{
Units are shipped without refrigerant charge.
}
Field installed accessory only.
1/
2
1/
2...1
8
5/
2...
8
1/
1...2
2
1/
1…1
2
1...2 1...2
1...2 1...2
4...16 x 20 x 2
4...16 x 24 x 2
15
2...1
2...
1...2
1…1
4...16 x 20 x 2
4...16 x 24 x 2
1/
8
5/
8
1/
2
1/
2
508 01 1603 00 3
Specifications are subject to change without notice.
Table 1A (Cont.) — Physical Data, English — 20 and 25 Ton Cooling Units
UNIT FAS 240 300
NOMINAL CAPACITY (Tons) 20 25
OPERATING WEIGHT (lb)
Base Unit with TXV 730 1050
Plenum 225 325
FANS
Qty...Diam. (in.) 2...15 2...18
Nominal Airflow (cfm) 8000 10000
Airflow Range (cfm) 6000 – 10000 7500 – 12500
Nominal Motor Hp (Standard Motor)
208/230---3 --- 60 and 460 --- 3 --- 60 5.0 7.5
5 7 5 --- 3 --- 6 0 5.0 7.5
Motor Speed (rpm)
208/230---3 --- 60 and 460 --- 3 --- 60 1760 1760
5 7 5 --- 3 --- 6 0 1745 1755
REFRIGERANT R --- 410A R---410A
Operating charge (lb) (approx per circuit)
DIRECT--- EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine--- Wave Fins
Max Working Pressure (psig) 650 650
Face Area (sq ft) 19.88 24.86
No. of Splits 2 2
No. of Circuits per Split 18 20
Split Type...Percentage Face...50/50 Face...50/50
Rows…Fins/in. 4…15 4…15
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 2...11/
DX Coil — Liquid Refrigerant (ODF) 2...5/
Steam Coil, In (MPT) 1...21/
Steam Coil, Out (MPT) 1...1/
Hot Water Coil, In (MPT) 1...2 1...2
Hot Water Coil, Out (MPT) 1...2 1...2
Condensate (PVC) 1...11/4ODM/1 IDF 1...11/4ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size (in.)
Access Location Either Side Either Side
STEAM COIL
}
Max Working Pressure (psig at 260° F) 20 20
Tota l Fa ce A r ea ( s q f t ) 13.33 15.0
Rows...Fins/in. 1...10 1...10
HOT WATER COIL
}
Max Working Pressure (psig) 150 150
Tota l Fa ce A r ea ( s q f t ) 13.33 15.0
Rows...Fins/in. 2...8.5 2...12.5
Water Volume
(gal) 13.9 14.3
(ft3) 1.85 1.90
LEGEND
DX — Direct Expansion TXV — Thermostatic Expansion Valve
{
Units are shipped without refrigerant charge.
}
Field installed accessory only.
{
3.5 4.5
8
8
2
2
4...16 x 20 x 2
4...16 x 24 x 2
2...13/
8
2...5/
8
1...21/
2
1...1/
2
4...20 x 24 x 2
4...20 x 25 x 2
4 508 01 1603 00
Specifications are subject to change without notice.
Table 1B — Physical Data, SI — 21 to 52 kW Cooling Units
UNIT FAS 072 091 120 150 180
NOMINAL CAPACITY (kW)
OPERATING WEIGHT (kg)
Base Unit with TXV 173 175 184 304 311
Plenum 80 80 80 102 102
FANS
Qty...Diam. (mm) 1...381 1...381 1...381 2...381 2...381
Nominal Airflow (L/s) 1133 1604 1888 2360 2831
Airflow Range (L/s) 850 --- 1416 1203--- 2006 1416 --- 2360 1770---2949 2124---3539
Nominal Motor kW (Standard Motor)
208/230---1 --- 60 0.97 1.79
208/230---3 --- 60 and 460 --- 3 --- 60 1.79 1.79 1.79 2.16 2.16
5 7 5 --- 3 --- 6 0 0.75 1.49 1.49 2.24 2.24
Motor Speed (r/s)
208/230---1 --- 60 28.8 28.8
208/230---3 --- 60 and 460 --- 3 --- 60 28.8 28.8 28.8 28.8 28.8
5 7 5 --- 3 --- 6 0 28.8 28.8 28.8 28.8 28.8
REFRIGERANT
Operating charge (kg) (approx per circuit)
{
DIRECT--- EXPANSION COIL
Max Working Pressure (kPag) 4481 4481 4481 4481 4481
Face Area (sq m) 0.62 0.77 0.93 0.93 1.64
No. of Splits 1 1 2 2 2
No. of Circuits per Split 12 15 9 12 16
Split Type...Percentage Face...50/50 Face...50/50 Face...50/50
Rows...Fins/m 4...591 4...591 4...591 4...591 4...591
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...1
DX Coil — Liquid Refrigerant (ODF) 1...
Steam Coil, In (MPT) 1...2
Steam Coil, Out (MPT) 1...1
Hot Water Coil, In (MPT) 1...1
Hot Water Coil, Out (MPT) 1...1
Condensate (PVC) 1...15/8ODM / 11/4IDF
FILTERS
Quantity...Size (mm) 4...406 x 610 x 51
Access Location Either Side Either Side
STEAM COIL
}
Max Working Pressure (kPag at 126° C) 138 138 138 138 138
Tota l Fa ce A r ea ( s q m ) 0.62 0.62 0.62 1.24 1.24
Rows...Fins/m 1...355 1...355 1...355 1...394 1...394
HOT WATER COIL
}
Max Working Pressure (kPag) 1034 1034 1034 1034 1034
Tota l Fa ce A r ea ( s q m ) 0.62 0.62 0.62 1.24 1.24
Rows...Fins/m 2...335 2...335 2...335 2...335 2...335
Water Volume
(L) 31.4 31.4 31.4 52.6 52.6
(m3) 0.031 0.031 0.031 0.052 0.052
LEGEND
DX — Direct Expansion TXV — Thermostatic Expansion Valve
{
Units are shipped without refrigerant charge.
}
Field installed accessory only.
21 26 35 43 52
R---410A R---410A R---410A R--- 410A R --- 410A
1.36 1.36 0.68/0.68 0.90/0.90 1.13/1.13
Enhanced Copper Tubes, Aluminum Sine---Wave Fins
1/
8
5/
8
1/
2
1/
2
1/
2
1/
2
1...1
1...
1...2
1...1
1...1
1...1
1/
8
5/
8
1/
2
1/
2
1/
2
1/
2
2...1
2...
1...2
1..1
1...1
1...1
1/
8
5/
8
1/
2
1/
2
1/
2
1/
2
1/
2...1
2...
1...2
1..1
8
5/
8
1/
2
1/
2
2...1
2...
1...2
1..1
1...2 1...2
1...2 1...2
Throwaway — Factory Supplied
4...406 x 508 x 51
4...406 x 610 x 51
1/
8
5/
8
1/
2
1/
2
508 01 1603 00 5
Specifications are subject to change without notice.
Table 1B (Cont.) — Physical Data, SI — 70 and 87 kW Cooling Units
UNIT FAS 25A 28A
NOMINAL CAPACITY (kW) 70 87
OPERATING WEIGHT (kg)
Base Unit with TXV 331 477
Plenum 102 148
FANS
Qty...Diam. (mm) 2...381 2...457
Nominal Airflow (L/s) 3775 4119
Airflow Range (L/s) 2831 – 4719 3539 – 5899
Nominal Motor kW (Standard Motor)
208/230---3 --- 60 and 460 --- 3 --- 60 3.73 5.60
5 7 5 --- 3 --- 6 0 3.73 5.60
Motor Speed (r/s)
208/230---3 --- 60 and 460 --- 3 --- 60 29.1 29.1
5 7 5 --- 3 --- 6 0 29.1 29.3
REFRIGERANT R --- 410A R---410A
Operating charge (kg) (approx per circuit)
DIRECT--- EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine--- Wave Fins
Max Working Pressure (kPag) 4481 4481
Face Area (sq m) 1.85 2.30
No. of Splits 2 2
No. of Circuits per Split 18 20
Split Type...Percentage Face...50/50 Face...50/50
Rows…Fins/m 4…591 4…591
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 2...11/
DX Coil — Liquid Refrigerant (ODF) 2...5/
Steam Coil, In (MPT) 1...21/
Steam Coil, Out (MPT) 1...1/
Hot Water Coil, In (MPT) 1...2 1...2
Hot Water Coil, Out (MPT) 1...2 1...2
Condensate (PVC) 1...11/4ODM/1 IDF 1...11/4ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size (mm.)
Access Location Either Side Either Side
STEAM COIL
}
Max Working Pressure (kPag at 126° C) 138 138
Tota l Fa ce A r ea ( s q m ) 1.24 1.39
Rows...Fins/m 1...394 1...394
HOT WATER COIL
}
Max Working Pressure (kPag) 1034 1034
Tota l Fa ce A r ea ( s q m ) 1.24 1.39
Rows...Fins/m 2...335 2...335
Water Volume
(L) 52.6 54.1
(m3) 0.052 0.054
LEGEND
DX — Direct Expansion TXV — Thermostatic Expansion Valve
{
Units are shipped without refrigerant charge.
}
Field installed accessory only.
{
1.59 2.04
8
8
2
2
4...406 x 508 x 51
4...406 x 610 x 51
2...13/
8
2...5/
8
1...21/
2
1...1/
2
4...508 x 610 x 51
4...508 x 635 x 51
6 508 01 1603 00
Specifications are subject to change without notice.
Table 1C — Physical Data, English — 6 to 15 Ton Heat Pump Units
UNIT FHS 072 072**AA2 091 120 180
NOMINAL CAPACITY (Tons)
6 6 7
1/
2
OPERATING WEIGHT (lb)
Base Unit with TXV 381 381 385 427 713
Plenum 175 175 175 175 225
FANS
Qty...Diam. (in.) 1...15 1...15 1...15 1...15 2...15
Nominal Airflow (cfm) 2400 2400 3000 4000 6000
Airflow Range (cfm) 1800--- 3000 1800---3000 2250---3750 3000 --- 5000 4500---7500
Nominal Motor Hp (Standard Motor)
208/230---1 --- 60 1.3 1.3 2.4
208/230---3 --- 60 and 460 --- 3 --- 60 2.4 2.4 2.4 2.4 3.7
5 7 5 --- 3 --- 6 0 1.0 1.0 2.0 2.0 3.0
Motor Speed (rpm)
208/230---1 --- 60 1725 1725 1725
208/230---3 --- 60 and 460 --- 3 --- 60 1725 1725 1725 1725 1725
5 7 5 --- 3 --- 6 0 1725 1725 1725 1725 1725
REFRIGERANT
Operating charge (lb) (approx per circuit)
{
DIRECT--- EXPANSION COIL
R---410A R ---410A R --- 410A R---410A R ---410A
3.0 3.0 3.0 2.0/2.0 3.0/3.0
Enhanced Copper Tubes, Aluminum Sine---Wave Fins
Max Working Pressure (psig) 650 650 650 650 650
Face Area (sq ft) 8.33 8.33 8.33 10.0 16.56
No. of Splits 1 1 1 2 2
No. of Circuits per Split 15 12 12 9 10
Split Type...Percentage Face...50/50 Face...50/50
Rows...Fins/in. 3...15 4...15 4...15 4...15 4...15
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...1
DX Coil — Liquid Refrigerant (ODF) 1...
Steam Coil, In (MPT) 1...2
Steam Coil, Out (MPT) 1...1
Hot Water Coil, In (MPT) 1...1
Hot Water Coil, Out (MPT) 1...1
1/
8
5/
8
1/
2
1/
2
1/
2
1/
2
1...1
1...
1...2
1...1
1...1
1...1
1/
8
5/
8
1/
2
1/
2
1/
2
1/
2
1...1
1...
1...2
1...1
1...1
1...1
1/
8
5/
8
1/
2
1/
2
1/
2
1/
2
Condensate (PVC) 1...15/8ODM / 11/4IDF
FILTERS
Throwaway — Factory Supplied
Quantity...Size (in.) 4...16 x 24 x 2 4...16 x 24 x 2 4...16 x 24 x 2 4...16 x 24 x 2
Access Location Either Side Either Side Either Side Either Side Either Side
STEAM COIL
}
Max Working Pressure (psig at 260° F) 20 20 20 20 20
Tota l Fa ce A r ea ( s q f t ) 6.67 6.67 6.67 6.67 13.33
Rows...Fins/in. 1...9 1...9 1...9 1...9 1...10
HOT WATER COIL
}
Max Working Pressure (psig) 150 150 150 150 150
Tota l Fa ce A r ea ( s q f t ) 6.67 6.67 6.67 6.67 13.33
Rows...Fins/in. 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5
Water Volume
(gal) 8.3 8.3 8.3 8.3 13.9
(ft3) 1.1 1.1 1.1 1.1 1.85
LEGEND
DX — Direct Expansion TXV — Thermostatic Expansion Valve
{
Units are shipped without refrigerant charge.
}
Field installed accessory only.
2...1
2...
1...2
1...1
1...1
1...1
10
15
1/
8
5/
8
1/
2
1/
2
1/
2
1/
2
2...1
2...
1...2
1...1
1...2
1...2
4...16 x 20 x 2
4...16 x 24 x 2
1/
8
5/
8
1/
2
1/
2
508 01 1603 00 7
Specifications are subject to change without notice.
Table 1C (Cont.) — Physical Data, English — 20 Ton Heat Pump Units
UNIT FHS 240
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (lb)
Base Unit with TXV 720
Plenum 225
FANS
Qty...Diam. (in.) 2...15
Nominal Airflow (cfm) 8000
Airflow Range (cfm) 6000---1000
Nominal Motor Hp (Standard Motor)
208/230---3 --- 60 and 460 --- 3 --- 60 5.0
5 7 5 --- 3 --- 6 0 5.0
Motor Speed (rpm)
208/230---3 --- 60 and 460 --- 3 --- 60 1745
5 7 5 --- 3 --- 6 0 1745
REFRIGERANT
Operating charge (lb) (approx per circuit)
DIRECT--- EXPANSION COIL
{
Enhanced Copper Tubes, Aluminum Sine---Wave Fins
Max Working Pressure (psig) 650
Face Area (sq ft) 19.88
No. of Splits 2
No. of Circuits per Split 18
Split Type...Percentage Face...50/50
Rows...Fins/in. 4...15
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 2...1
DX Coil — Liquid Refrigerant (ODF) 2...
Steam Coil, In (MPT) 1...2
Steam Coil, Out (MPT) 1...1
Hot Water Coil, In (MPT) 1...2
Hot Water Coil, Out (MPT) 1...2
Condensate (PVC) 1...15/8ODM / 11/4IDF
FILTERS
Throwaway — Factory Supplied
Quantity...Size (in.)
Access Location Either Side
STEAM COIL
}
Max Working Pressure (psig at 260° F) 20
Tota l Fa ce A r ea ( s q f t ) 13.33
Rows...Fins/in. 1...10
HOT WATER COIL
}
Max Working Pressure (psig) 150
Tota l Fa ce A r ea ( s q f t ) 13.33
Rows...Fins/in. 2...8.5
Water Volume
(gal) 13.9
(ft3) 1.85
LEGEND
DX — Direct Expansion TXV — Thermostatic Expansion Valve
{
Units are shipped without refrigerant charge.
}
Field installed accessory only.
20
R---410A
3.5
4...16 x 20 x 2
4...16 x 24 x 2
1/
8
5/
8
1/
2
1/
2
8 508 01 1603 00
Specifications are subject to change without notice.
Table 1D — Physical Data, SI — 21 to 52 kW Heat Pump Units
UNIT FHS 072 072**AA2 091 120
NOMINAL CAPACITY (kW)
21 21 26 35
180
52
OPERATING WEIGHT (kg)
Base Unit with TXV 173 173 175 194 323
Plenum 80 80 80 80 102
FANS
Qty...Diam. (mm) 1...381 1...381 1...381 1...381 2...381
Nominal Airflow (L/s) 1133 1133 1604 1888 2831
Airflow Range (L/s) 850--- 1416 850---1416 1203---2006 1416---2360 2124---3539
Nominal Motor kW (Standard Motor)
208/230---1 --- 60 0.97 0.97 1.79
208/230---3 --- 60 and 460 --- 3 --- 60 1.79 1.79 1.79 1.79 2.76
5 7 5 --- 3 --- 6 0 0.75 0.75 1.49 1.49 2.24
Motor Speed (r/s)
208/230---1 --- 60 28.8 28.8 28.8
208/230---3 --- 60 and 460 --- 3 --- 60 28.8 28.8 28.8 28.8 28.8
5 7 5 --- 3 --- 6 0 28.8 28.8 28.8 28.8 28.8
REFRIGERANT
Operating charge (kg) (approx per
{
circuit)
DIRECT--- EXPANSION COIL
R---410A R---410A R--- 410A R --- 410A R---410A
1.36 1.36 1.36 0.91/0.91 1.36/1.36
Enhanced Copper Tubes, Aluminum Sine---Wave Fins
Max Working Pressure (kPag) 4482 4482 4482 4482 4482
Face Area (sq m) 0.77 0.77 0.77 0.93 1.54
No. of Splits 1 1 1 2 2
No. of Circuits per Split 15 12 12 9 10
Split Type...Percentage Face...50/50 Face...50/50
Rows...Fins/m 3...591 4...591 4...591 3...591 4...591
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...1
DX Coil — Liquid Refrigerant (ODF) 1...
Steam Coil, In (MPT) 1...2
Steam Coil, Out (MPT) 1...1
Hot Water Coil, In (MPT) 1...1
Hot Water Coil, Out (MPT) 1...1
1/
8
5/
8
1/
2
1/
2
1/
2
1/
2
1...1
1...
1...2
1...1
1...1
1...1
1/
8
5/
8
1/
2
1/
2
1/
2
1/
2
1...1
1...
1...2
1...1
1...1
1...1
1/
8
5/
8
1/
2
1/
2
1/
2
1/
2
2...1
2...
1...2
1...1
1...1
1...1
1/
8
5/
8
1/
2
1/
2
1/
2
1/
2
2...1
2...
1...2
1...1
1...2
1...2
Condensate (PVC) 1...15/8ODM / 11/4IDF
FILTERS
Quantity...Size (mm) 4...406 x 610 x 51 4...406 x 610 x 51 4...406 x 610 x 51 4...406 x 610 x 51
Throwaway — Factory Supplied
4...406 x 508 x 51
4...406 x 610 x 51
Access Location Either Side Either Side Either Side Either Side Either Side
STEAM COIL
}
Max Working Pressure (kPag at 126° C) 138 138 138 138 138
Tota l Fa ce A r ea ( s q m ) 0.62 0.62 0.62 0.62 1.24
Rows...Fins/m 1...355 1...355 1...355 1...355 1...394
HOT WATER COIL
}
Max Working Pressure (kPag) 1034 1034 1034 1034 1034
Tota l Fa ce A r ea ( s q m ) 0.62 0.62 0.62 0.62 1.24
Rows...Fins/m 2...335 2...335 2...335 2...335 2...335
Water Volume
(L) 31.4 31.4 31.4 31.4 52.6
(m3) 0.031 0.031 0.031 0.031 0.052
LEGEND
DX — Direct Expansion TXV — Thermostatic Expansion Valve
{
Units are shipped without refrigerant charge.
}
Field installed accessory only.
1/
8
5/
8
1/
2
1/
2
508 01 1603 00 9
Specifications are subject to change without notice.
Table 1D — Physical Data, SI — 70 kW Heat Pump Units
UNIT FHS
240
NOMINAL CAPACITY (kW) 70
OPERATING WEIGHT (kg)
Base Unit with TXV 327
Plenum 102
FANS
Qty...Diam. (mm) 2...381
Nominal Airflow (L/s) 3775
Airflow Range (L/s) 2831---4719
Nominal Motor kW (Standard Motor)
208/230---3 --- 60 and 460 --- 3 --- 60 3.73
5 7 5 --- 3 --- 6 0 3.73
Motor Speed (r/s)
208/230---3 --- 60 and 460 --- 3 --- 60 29.1
5 7 5 --- 3 --- 6 0 29.1
REFRIGERANT
Operating charge (kg) (approx per circuit)
DIRECT--- EXPANSION COIL
{
Enhanced Copper Tubes, Aluminum Sine---Wave Fins
R---410A
1.59
Max Working Pressure (kPag) 4481
Face Area (sq m) 1.85
No. of Splits 2
No. of Circuits per Split 18
Split Type...Percentage Face...50/50
Rows...Fins/m 4...591
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 2...1
DX Coil — Liquid Refrigerant (ODF) 2...
Steam Coil, In (MPT) 1...2
Steam Coil, Out (MPT) 1...1
Hot Water Coil, In (MPT) 1...2
Hot Water Coil, Out (MPT) 1...2
Condensate (PVC) 1...15/8ODM / 11/4IDF
FILTERS
Quantity...Size (mm)
Throwaway — Factory Supplied
4...406 x 508 x 51
4...406 x 610 x 51
Access Location Either Side
STEAM COIL
}
Max Working Pressure (kPag at 126° C) 138
Tota l Fa ce A r ea ( s q m ) 1.24
Rows...Fins/m 1...394
HOT WATER COIL
}
Max Working Pressure (kPag) 1034
Tota l Fa ce A r ea ( s q m ) 1.24
Rows...Fins/m 2...335
Water Volume
(L) 52.6
(m3) 0.052
LEGEND
DX — Direct Expansion TXV — Thermostatic Expansion Valve
{
Units are shipped without refrigerant charge.
}
Field installed accessory only.
1/
8
5/
8
1/
2
1/
2
10 508 01 1603 00
Specifications are subject to change without notice.
Fig. 1 -- Dimensions – 6 -- 10 Ton Units
C160032
508 01 1603 00 11
Specifications are subject to change without notice.
Fig. 2 -- Dimensions – 12.5 -- 20 Ton Units
C160033
12 508 01 1603 00
Specifications are subject to change without notice.
Fig. 3 -- Dimensions – 25 Ton Units
C160034
508 01 1603 00 13
Specifications are subject to change without notice.
Rated Indoor Airflow (cfm)
The following tables list the rated indoor airflow used for the AHRI efficiency rating for the units covered in this document.
CAS (Single Circuit) with FAS
Model Number Full Load Airflow (cfm)
CAS072*A/B --- FAS072 2400 CAS072*G/H --- FAS072 2625 CAS090*G/H --- FAS091 3000
CAS091 --- FAS091 3000 CAS121 --- FAS120 4000 CAS151 --- FAS150 4375 CAS181 --- FAS180 6000 CAS241 --- FAS240 8300
CAS (Dual Circuit) with FAS
Model Number Full Load Airflow (cfm)
CAS120 --- FAS120 4000 CAS150 --- FAS150 4400 CAS180 --- FAS180 6000 CAS240 --- FAS240 8300
CHSwithFHS
Model Number Full Load Airflow (cfm)
CHS072*A/B --- FHS072 2400
CHS072*G/H --- FHS072 2400
CHS091*A/B --- FHS091 3000
CHS091*G/H --- FHS091 2625
CHS121*A/B --- FHS120 3000
CHS121*G/H --- FHS120 3000
CHS180 --- FHS180 6000 CHS240 --- FHS240 7400
MODEL SERIES FAS091MAAA0A0A
Position Number
F = R-410A Fan Coil Unit
A = Air Conditioning (Cooling Only) H = Heat Pump
12345678910111213
Type
14
S = Standard Efficiency
072 = 6 Tons (1 circuit) 091 = 7.5 Tons (1 circuit) 120 = 10 Tons (2 circuit) 150 = 12.5 Tons (2 circuit) (FAS units only) 180 = 15 Tons (2 circuit) 240 = 20 Tons (2 circuit) 300 = 25 Tons (2 circuit) (FAS units only)
K = 208/230−1−60 H = 208/230−3−60 M = 460/208/230−3−60 L = 460−3−60 S = 575−3−60
A = Standard Static Standard Efficiency Motor / Standard Drive
• 6 to 15 ton 208/230v, 460v, 575v-3-60, 6 & 7.5 ton 208/230-1-60, 1-speed
• all 2-speed B = High Static Standard Efficiency Motor / High Drive
• 6 to 15 ton 208/230V, 460v, 6 to 10 ton 575v-3-60, 1-speed
• all 2-speed D = Standard Static High Efficiency Motor / Standard Drive
• 20 & 25 ton all 3 phase E = High Static High Efficiency Motor / High Drive
• 15 to 25 ton all 3 phase
A = Cu/Al
A = Future Use
Efficiency
Nominal Tonnage
Voltage
Fan Motor Options
Indoor Coil
Future Use
0 = Single Speed Indoor Fan Motor 2 = Two Speed Indoor Fan Motor (VFD)
A = Standard - Unpainted B = Painted cabinet (Gray)
A = Standard
Notes:
• All FAS072-150 units and FHS 072-120 units with a “M” voltage designation are triple voltage; i.e., 208/230/460-3-60. FAS 180 units are also triple voltage in the “M” configuration unless the High Staic motor option is used that is discrete 460-3-60. Units that require 2-speed indoor fan motor must use dedicated voltage models listed. The VFD used is not multi-voltage.
• Size 300 units and single-phase 072 and 091 units designate standard motor and high static drive.
Fan Speed Controller
Painted Cabinet Options
Future Use0 = Future Use
C160035
Fig. 4 -- Model Number Nomenclature
14 508 01 1603 00
Specifications are subject to change without notice.
TXV COIL
REMOVE FOAM BLOCK
LEGEND
TXV — Thermostatic Expansion Valve
Fig. 5 -- Foam Block Location
C10683
Unit Positioning -- The unit can be mounted on the floor for vertical application with return air entering the face of the unit and supply air discharging vertically through the top of the unit. The unit can also be applied in a horizontal arrangement with return air entering horizontally and the supply air discharging horizontally. When applying the unit in a horizontal arrangement, ensure the condensate drain pan is located at the bottom center of the unit for adequate condensate disposal. See Fig. 6 for condensate connections for each unit position.
IMPORTANT: Do NOT attempt to install unit with return air entering top panel of unit. Condensate will not drain from unit.
Typical positioning and alternate return air locations are shown in Fig. 6. Alternate return air locations can be used by moving the unit panel from the alternate return air location to the standard return air location. Refer to overhead suspension accessory drawing (Fig. 7) for preferred suspension technique. The unit needs support underneath to prevent sagging.
PLUG
CONDENSATE DRAIN
LEGEND
Accessory Line Alternate Air Intake and Discharge
Air Intake and Discharge
Note: Maintain recommended clearances
per Unit Dimension figures
Fig. 6 -- Typical Unit Positioning
PLUG
C160036
508 01 1603 00 15
Specifications are subject to change without notice.