The signal words DANGER, WARNING, CAUTION,
and NOTE are used to identify levels of hazard
seriousness. The signal word DANGER is only used
on product labels to signify an immediate hazard. The
signal words WARNING,CAUTION, and NOTE will
be used on product labels and throughout this manual
and other manuals that may apply to the product.
DANGER− Immediate hazards which will result in
severe personal injury or death.
WARNING − Hazards or unsafe practices which
could result in severe personal injury or death.
CAUTION − Hazards or unsafe practices which may
result in minor personal injury or product or property
damage.
NOTE − Used to highlight suggestions which will
result in enhanced installation, reliability, or operation.
Signal Words in Manuals
The signal word WARNING is used throughout this
manual in the following manner:
!
The signal word CAUTION is used throughout this
manual in the following manner:
!
Signal Words on Product Labeling
Signal words are used in combination with colors
and/or pictures on product labels.
WARNING
WARNING
CAUTION
TABLE OF CONTENTS
!
Model Number Identification2 − 3..................
Wiring Diagram4 − 5.............................
Performance Data6 − 8...........................
Parts Drawing FEM4X1800−48009 − 12............
Parts List FEM4X1800−480013 − 16................
Parts Drawing FEM4X350017 − 19.................
Parts List FEM4X350020.........................
Parts Drawing FEM4X600021 − 25.................
Parts List FEM4X600026.........................
Parts Drawing WAHM, WAHT27 − 30...............
Parts List WAHM, WAHT31 − 36...................
ELECTRICAL SHOCK HAZARD
Failure to turn off electric power could result in
personal injury or death.
Before installing or servicing system, turn off
main power to the system. There may be more than
one disconnect switch, including accessory
heater(s).
TECHNICAL SUPPORT MANUALFan Coils: FEM4X, WAHM**4, WAHT**4
ACCESSORIES PART NUMBER IDENTIFICATION GUIDE
EBAC01NCBA
EB = Evaporator Blower
AC = Accessory
01 = Product Identifier Number
NCB = Non−Combustible Base Kit
DFK = Down Flow Kit
PLG = Power Plug (no heat kit)
SPK = Single Point Wiring Kit
FKS = Filter Kit Small
FKM = Filter Kit Medium
FKL = Filter Kit Large
FKX = Filter Kit Extra Large
CTK = Condensate Trap Kit (PVC pipe)
Sales Code
ELECTRIC HEATER MODEL NUMBER IDENTIFICATION GUIDE
EHK05AKN1
EHK = Electric Heater Kit
05 = 5 kW
07 = 7 kW
09 = 9 kW
10 = 10 kW
15 = 15 kW
18 = 18 kW
20 = 20 kW
25 = 25 kW
30 = 30 kWNOMINAL HEAT VALUE
Sales Code
K = 208 / 230 single−phase
H = 208 / 230, 3−phase
KC = 208 / 230, supplied as single phase, field convertible to 3−phase
HC = 208 / 230 supplied as 3−phase, field convertible to single phaseVOLTAGE (60 Hz)
Product Identifier
Engineering Code
496 04 5301 023
TECHNICAL SUPPORT MANUALFan Coils: FEM4X, WAHM**4, WAHT**4
TECHNICAL SUPPORT MANUALFan Coils: FEM4X, WAHM**4, WAHT**4
AIRFLOW PERFORMANCE − CFM at a given Speed and Static reading
Model
FEM4X1800
FEM4X2400
FEM4X3000
FEM4X3500
FEM4X3600
FEM4X4200
FEM4X4800
Blower Speed
Medium701659619578538499
Medium823786747707665622
Medium10331000965928888846
Medium128212381192114210901036
Medium132712821236118711351081
Medium147914371392134412931240
Medium165216171581154315041463
AIRFLOW PERFORMANCE − CFM at a given Speed and Static reading
ModelBlower Speed
FEM4X6000B
High766739706666619566
Low614572530486441396
High941905868830792753
Low633583533482431378
High1130109710631028992955
Low840802760713663609
High143713981354130812571204
Low1168111 810671014959903
High147914371392134412931240
Low1192115111001039970890
High161615781533148014201353
Low130312581211116111081054
High180517721739170416691632
Low145814181377133512921248
Tap 5189718671836180817741736
Tap 4181717851757172416931655
Tap 3181717851757172416931655
Tap 2165716211589155715181474
Tap 1144314121377133212861243
Measured Static Pressure, inlet to outlet (inches water column)
0.100.200.300.400.500.60
Measured Static Pressure, inlet to outlet (inches water column)
0.100.200.300.400.500.60
NOTES:
1. Airflow based upon dry coil at 230v with factory approved filter and electric heater (2 element heater sizes 1800 through 3600, 3 element heater sizes 4200
through 6000).
2. Airflow at 208 volts is approximately the same as 230 volts because the ECM motor is a constant torque motor. The torque doesn’t drop off at the
speeds the motor operates.
3. To avoid potential for condensate blowing out of drain pan prior to making drain trap: Return static pressure must be less than 0.40 in. wc. Horizontal
applications of 4200 − 6000 sizes must have supply static greater than 0.20 in. wc.
4. Airflow above 400 cfm/ton on 4800 − 6000 size could result in condensate blowing off coil or splashing out of drain pan.
5. Not recommended for use above 0.60 inches water column external static pressure.
6. Shading − Airflow outside 450 cfm/ton.
6496 04 5301 02
TECHNICAL SUPPORT MANUALFan Coils: FEM4X, WAHM**4, WAHT**4
AIRFLOW PERFORMANCE − CFM at a given Speed and Static reading
ModelBlower Speed
WAHM184A*
WAHT184A*
WAHM244A*
WAHT244A*
WAHM304A*
WAHT304A*
WAHM364A*
WAHT364A*
WAHM424A*
WAHT424A*
WAHM484A*
WAHT484A*
WAHM604A*
WAHT604A*
High766739706666619566
Medium701659619578538499
Low614572530486441396
High941905868830792753
Medium823786747707665622
Low633583533482431378
High1130109710631028992955
Medium10331000965928888846
Low840802760713663609
High143713981354130812571204
Medium128212381192114210901036
Low1168111 810671014959903
High161615781533148014201353
Medium147914371392134412931240
Low130312581211116111081054
High180517721739170416691632
Medium165216171581154315041463
Low145814181377133512921248
High205720241989195419161878
Medium179917661731169516581618
Low166716331596155815171475
Measured Static Pressure, inlet to outlet (inches water column)
0.100.200.300.400.500.60
STATIC PRESSURE CORRECTION FROM DRY TO WET COIL (inches of water column)
Airflow performance chart above was developed using fan coils with DRY coils.
When taking a static reading across a WET coil, adjust the static pressure numbers by adding the values in this table (for a given CFM, wet coil will
have greater static pressure drop than dry coil).
TECHNICAL SUPPORT MANUALFan Coils: FEM4X, WAHM**4, WAHT**4
STATIC PRESSURE CORRECTION FROM DRY TO WET COIL (inches of water column)
Airflow performance chart above was developed using fan coils with DRY coils.
When taking a static reading across a WET coil, adjust the static pressure numbers by adding the values in this table (for a given CFM, wet coil will
have greater static pressure drop than dry coil).
STATIC PRESSURE DROP ACROSS FILTER (inches of water column)
Model
WAHM184A*
WAHT184A*
WAHM244A*
WAHT244A*
WAHM304A*
WAHT304A*
WAHM364A*
WAHT364A*
WAHM424A*
WAHT424A*
WAHM484A*
WAHT484A*
WAHM604A*
WAHT604A*
400600800100012001400160018002000
.020.044.075−−−−−−
−.044.075.110−−−−−
−−.048.072.100−−−−
−−−.072.100.130−−−
−−−−.070.092.120−−
−−−−−.092.120.152−
−−−−−−.120.152.187
CFM
8496 04 5301 02
TECHNICAL SUPPORT MANUALFan Coils: FEM4X, WAHM**4, WAHT**4
A
B
C
D
FEM4X
1800
2400
3000
3600
4200
4800
Z
AH
JJ
AJ
Y
W
AK
22
E
P
HH
R
ZZ
1
NOTE: This illustration is for
reference only. Your unit may
differ in appearance or may not
include all components shown.
Please refer to Parts List for
exact parts listing.
F
496 04 5301 029
H
G
20
TECHNICAL SUPPORT MANUALFan Coils: FEM4X, WAHM**4, WAHT**4
FEM4X
1800
A
2400
3000
3600
Z1
4200
4800
C
B
AF
AG
22
E
AK
HH
ZZ
R
D
Z2
UU
JJ
W
AJ
AH
P
1
NOTE: This illustration is for
reference only. Your unit may
differ in appearance or may not
include all components shown.
Please refer to Parts List for
exact parts listing.
10496 04 5301 02
F
H
20
G
TECHNICAL SUPPORT MANUALFan Coils: FEM4X, WAHM**4, WAHT**4
FEM4X
1800
2400
3000
3600
NN
AE
4200
4800
SS
RR
PP
AD
7
AM
AN
AR
19
8
21
PL
AC
MM
AB
TT
6
LL
KK
13
J
K
L
7
8
21
WW
M
X
AP
N
13
6
XX
NOTE: This illustration is for
reference only. Your unit may
differ in appearance or may not
include all components shown.
Please refer to Parts List for
exact parts listing.
496 04 5301 0211