International Comfort Products FCM4X2400AT1, FCM4X3600AT1, FCM4X4800AT1, FCM4X6000AT1 User Manual

TECHNICAL SUPPORT MANUAL
Fan Coils
FCM4X
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manuals that may apply to the product.
DANGER -- Immediate hazards which will result in severe personal injury or death.
WARNING -- Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION -- Hazards or unsafe practices which may
result in minor personal injury or product or property damage.
NOTE -- Used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Signal Words in Manuals
The signal word WARNING is used throughout this manual in the following manner:
!
The signal word CAUTION is used throughout this manual in the following manner:
!
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures on product labels.
WARNING
WARNING
CAUTION
TABLE OF CONTENTS
Model Number Identification 2.....................
Wiring Diagram 3................................
Performance Data 4 -- 5...........................
Parts Drawing FCM4X2400--6000 6 -- 9.............
Parts List FCM4X2400--6000 10 -- 12...............
MODELS
FCM4X2400AT1 FCM4X3600AT1 FCM4X4800AT1 FCM4X6000AT1
!
ELECTRICAL SHOCK HAZARD
Failure to turn off electric power could result in personal injury or death.
Before installing or servicing system, turn off main power to the system. There may be more than one disconnect switch, including accessory heater(s).
WARNING
496 04 4201 01 October 2011
TECHNICAL SUPPORT MANUAL Fan Coils: FCM4X
FAN COIL MODEL NUMBER IDENTIFICATION GUIDE
DIGIT POSITION
1 2 3 4 5 6,7,8,9 10 11
F C M 4 X 2400 A T
F=FanCoil UNIT
C = Communicating MOTOR TYPE M = Multiposition
4 = Environmentally Sound R--410A REFRIGERANT
X=TXV METERING DEVICE 2400 = 24,000 BTUH = 2 tons 3600 = 36,000 BTUH = 3 tons 4800 = 48,000 BTUH = 4 tons 6000 = 60,000 BTUH = 5 tons NOMINAL CAPACITY A = Standard AT = Tin Coated Copper Tube SALESCODE/FEATURES
ACCESSORIES PART NUMBER IDENTIFICATION GUIDE
EB AC 01 NCB A
EB = Evaporator Blower AC = Accessory 01 = Product Identifier Number DFS = Down Flow Slope Kit DFA = Down Flow “ A “ Kit DPK = Horizontal Drain Pan kit DSC = Disconnect Kit GSK = Gasket Kit TXVX = R410A TXV Kit Sales Code
ELECTRIC HEATER MODEL NUMBER IDENTIFICATION GUIDE
EHK 05 A K N 1
EHK = Electric Heater Kit EHC = Communicating Electric Heater Kit 05 = 5 kW
07 = 8 kW 09 = 9 kW 10 = 10 kW 15 = 15 kW 18 = 18 kW 20 = 20 kW 25 = 24 kW 30 = 30 kW NOMINAL HEAT VALUE Sales Code K = 208 / 230 single--phase H = 208 / 230, 3--phase KC = 208 / 230, supplied as single phase, field convertible to 3--phase HC = 208 / 230 supplied as 3--phase, field convertible to single phase VOLTAG E (60 Hz) N = No Protection F = Fused B = Breaker ELECTRICAL PROTECTION Engineering Code
2 496 04 4201 01
TECHNICAL SUPPORT MANUAL Fan Coils: FCM4X
Models:
FCM4X2400AT1 FCM4X3600AT1 FCM4X4800AT1 FCM4X6000AT1
496 04 4201 01 3
TECHNICAL SUPPORT MANUAL Fan Coils: FCM4X
PHYSICAL DATA
MODEL FCM4X SIZE 24 36 48 60
COIL
Refrigerant Metering Device R--410A REFRIGERANT TXV TXV Size 2Ton 3Ton 4Ton 5Ton Configuration A Slope A A Rows—Fins/In. 3 / 14.5
Face Area (Sq Ft) 3.46 3.46 5.93 7.42
MATCHES OUTDOOR UNIT SIZES
Nominal Cooling Tons 1.5, 2, 2.5, 3 2, 2.5, 3, 3.5 2.5, 3, 3.5, 4 3, 3.5, 4, 5
FAN
Air Discharge Upflow, Downflow, Horizontal CFM/Ton (Nominal) 350+ Motor HP (ECM) 1/2 1/2 1/2 3/4 Filter
21--1/2--in (546 mm) x
CABINET CONFIGURATION OPTIONS
16--3/8--in
(417 mm)
1--piece 1--piece 1--piece Modular
19--7/8--in
(505 mm)
19--7/8--in
(505 mm)
23--5/16--in
(592 mm)
PERFORMANCE DATA
AIRFLOW DELIVERY — COOLING, HEATING, ELECTRIC HEATING MODES
The FCM4X fan coils will provide airflow at a rate that is requested by the wall control during air conditioning or heat pump heating (without electric heat) modes. The nominal airflow for both heating and cooling modes is 350 cfm/ton nominal size of the outdoor unit installed. The airflow actually requested by the wall control is modified by its internal algorithms for zoning, comfort or efficiency concerns. Refer
to the documentation for the wall control for more information on how the wall control controls the fan coil. Safe operation of electric heaters requires airflow delivery at or above the minimum CFM for electric heater application listed in the chart below. The fan coil will adjust its airflow delivery to maintain safe airflow as operating mode and staging conditions require.
FCM4X FAN COIL AIRFLOW DELIVERY CHART (CFM) — ELECTRIC HEATING MODELS
ELECTRIC HEATER kW RANGE
MODEL FCM4X OUTDOOR UNIT CAPACITY BTUH
EMERGENCY
18,000
24
36
48
60
Note 1: Emergency -- Air conditioner with electric heater application, or emergency heat. Note 2: These airflows are minimum airflows as UL listed. Note 3: Dashed entry indicates that the heater/fan coil/outdoor unit combination is not approved. Do not apply.
24,000 30,000 36,000
EMERGENCY
24,000 30,000 36,000 42,000
EMERGENCY
30,000 36,000 42,000 48,000
EMERGENCY
36,000 42,000 48,000 60,000
5 7--9 10 15 20 24--25 30
625 625 650 800 975
675 675 800 975
1125
675 800
975 1125 1305
1050 1050 1125 1300 1625
625 625 725 875 975
700 875 875 975
1125
700 875
975 1125 1305
1050 1050 1125 1300 1625
675 675 775 875 975
775 875
875 1025 1125
775
875 1025 1125 1305
1050 1100 1150 1300 1625
775
— 900 925
1025
850
1100 1100 1150 1150
850
1100 1150 1150 1305
1050 1350 1350 1350 1625
950
— 1125 1125
1050
1150 1150
1250 1350
1050
1150
1250 1250 1350
1125
1350 1350 1500 1750
— — — — —
— — — — —
1400
— — —
1500 1750
— 1750 1750
— — — — —
— — — — —
1425
— — —
1600 1750
— 1750 1750