International Comfort Products FCM4X24 Installation Manual

INSTALLATION INSTRUCTIONS
Fan Coils
FCM4X24--60
These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manuals that may apply to the product.
DANGER -- Immediate hazards which will result in severe personal injury or death.
WARNING -- Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION -- Hazards or unsafe practices which may result in minor personal injury or product or
property damage.
NOTE -- Used to highlight suggestions which will result in enhanced installation, reliability , or operation.
Signal Words in Manuals
The signal word WARNING is used throughout this manual in the following manner:
WARNING
!
The signal word CAUTION is used throughout this manual in the following manner:
!
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures on product labels.
WARNING
CAUTION
TABLE OF CONTENTS
Introduction 2.......................................
INSTALLATION 2...................................
Check Equipment 2..............................
Mount Fan Coil 2................................
Air Ducts 6.....................................
Electrical Connections 7..........................
Refrigerant Tubing Connection & Evacuation 9......
Condensate Drain 9.............................
Unit Start--Up 10................................
Accessory Installation 10.........................
Start--Up and Troubleshooting 1 1..................
FCM4X Fan Coil Sequence of Operation 15.........
CARE AND MAINTENANCE 15.......................
R--410A Quick Reference Guide 17....................
!
PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD
Failure to carefully read and followthis warning could result in equipment malfunction, property damage, personal injury and/or death.
Installation or repairs made by unqualified persons could result in equipment malfunction, property d am­age, personal injury and/or death.
The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
Installation must conform with local building codes and with the National Electrical Code NFPA70 current edition.
WARNING
496 01 4201 03 Mar/2016
INSTALLA TION INSTRUCTIONS Fan Coils: FCM4X
INTRODUCTION
Model FCM4X fan coils are designed to be installed with the Observert Communicating Wall Control. The FCM4X fan coils will provide airflow at a rate commanded by the Wall Control. The nominal airflow/ton rate is 350 CFM/ton. The Wall Control will modify the commanded airflow under certain operating modes. Refer to the Wall Control literature for further system control details. This fan coil will not respond to commands from a common thermostat except under certain emergency situations explained in this document. The instructions contained herein provide guidance to successfully install this fan coil.
Model FCM4X fan coil units are designed for flexibility and can be used for upflow, horizontal, or downflow applications. These units are designed specifically for R--410A refrigerant and must be used only with R--410A refrigerant air conditioners and heat pumps as shipped.
INSTALLATION
Procedure 1. — Check Equipment
Unpack unit and move to final location. Remove carton taking care not to damage unit.
Inspect equipment for damage prior to installation. File claim with shipping company if shipment is damaged or incomplete. Locate unit rating plate which contains proper installation information. Check rating plate to be sure unit matches job specifications.
Procedure 2. — Mount Fan Coil
FCM4X unit can stand or lie on floor, or hang from ceiling or wall. Allow space for wiring, piping, proper trapping and servicing unit.
IMPORTANT: When unit is installed over a finished ceiling and/or living area, building codes may require and it is recommended by the factory, a field--supplied secondary condensate pan to be installed under the entire unit. Some localities may allow the alterative of running a separate, secondary condensate line. Consult local codes for additional restrictions or precautions.
FCM4X fan coils can be installed for upflow and horizontal--left applications as factory shipped. (See Figures 1, 2 and 3.) FCM4X units can be installed for horizontal--right applications with field modifications. FCM4X units may be converted for downflow applications using factory--authorized accessory kits.
NOTE: To ensure proper drainage for horizontal installations, unit must be installed so it is within 1/8” / 3.18 mm level of the length and width of unit.
A. Modular Units
The FCM4X60 Fan Coil are 2--piece modular units. Modular construction allows installer to disassemble unit into 2 components, coil box and blower box, for ease of installation.
These units are designed to meet low air leak requirements currently in effect. Because of this, units need special attention in the condensate pan and drain connection area and when brazing tubing.
These units are available for application in systems of 24,000 through 60,000 Btuh nominal cooling capacities. Factory--authorized, field--installed electric heater packages are available in 5 through 30 kW. See Specifications for available accessory kits.
If the unit is located in an area of high humidity, nuisance sweating of the casing may occur. On these installations a wrap of 2(51 mm) fiberglass insulation with a vapor barrier is recommended.
To disassemble unit, remove rear corner brackets by removing 2 screws which secure brackets. Remove either 2 screws in each front corner of coil box, or 2 screws in blower box. (See Fig. 4.) Do not remove all 4 screws in each corner. Sections may now be separated by lifting top section from lower section.
To reassemble, reverse above procedure. Be certain to reinstall all fasteners when reassembling.
B. Upflow Installation
If return air is to be ducted through a floor, set unit on floor over opening and use 1/8” / 3.18 mm to 1/4” / 6.35 mm thick fireproof resilient gasket between duct, unit, and floor.
Side return is a field option on slope coil models. Cut opening per dimensions. (See Fig. 1.) A field--supplied bottom closure is required.
All return--air must pass through the coil.
C. Horizontal Installations
Units must not be installed with access panels facing up or down.
Be sure installation complies with all applicable building codes that may require installation of a secondary condensate pan.
1. Arrange support for unit by setting it in or above secondary condensate pan.
2. When suspending unit from ceiling dimples in casing indicate proper location of screws for mounting metal support straps. (See Fig. 2.)
2 496 01 4201 03
INSTALLA TION INSTRUCTIONS Fan Coils: FCM4X
Figure 1 Slope Coil Unit in Upflow Application
POWER ENTRY OPTIONS
24 -- 17.5” (444.5 mm) 36, 48 -- 21” (533.4 mm) 60 -- 24” (609.6 mm) FRONT SERVICE CLEARANCE
ACOIL
UNITS
UPFLOW/DOWNFLOW
SECONDARY DRAIN
FIELD SUPPLIED SUPPLY DUCT
LOW VOLT ENTRY OPTIONS
38.1 mm)
1--1/2”
UPFLOW/DOWNFLOW
PRIMARY DRAIN
19”
(482.6 mm)
FIELD MODIFIED SIDE RETURN
19”
2--1/2”
(63.5 mm)
(482.6 mm)
LOCATION FOR 36 UNITS ONLY
UPFLOW/DOWNFLOW
SECONDARY DRAIN
UPFLOW/DOWNFLOW
PRIMARY DRAIN
FIELD SUPPLIED RETURN PLENUM
Figure 2 Slope Coil in Horizontal--Left Application (Factory Ready unit only)
A-- COIL
HORIZONTAL LEFT
FIELD SUPPLIED HANGING STRAPS
UNIT
SECONDARY DRAIN
24 36, 48 21” (533.4 mm)
60 24” (609.6 mm) FRONT SERVICE CLEARANCE (FULL FACE OF UNIT)
DRAIN
YPRIMAR
A07139
LOW VOLT ENTRY OPTIONS
/4” (44.45 mm)
3
1
FILTER ACCESS
CLEARANCE
PRIMARY DRAIN
A07140
POWER ENTRY OPTIONS
SECONDARY DRAIN
496 01 4201 03 3
INSTALLA TION INSTRUCTIONS Fan Coils: FCM4X
Figure 3 A Coil in Horizontal--Left Application
A
FACTORY SHIPPED
HORIZONTAL LEFT
APPLICATION
B C
HORIZONTAL
DRAIN PAN
Figure 4 Modular Unit Assembly
BLOWER BOX
2 SCREWS
2 SCREWS
REAR CORNER BRACKET
2 SCREWS
COIL BOX
COIL
BRACKET
COIL
SUPPORT
RAIL
DRAIN PAN
SUPPORT BRACKET
COIL
BRACKET
PRIMARY DRAIN
AIR SEAL ASSEMBL
Y
REFRIGERANT
CONNECTIONS
D. Horizontal--Right Conversion of Units with Slope
HORIZONTAL LEFT
SECONDARY DRAIN
HORIZONTAL LEFT
A00072
Coils
NOTE
: Gasket kit number EBAC01GSK is required for
horizontal slope coil conversion to maintain low air leak/low sweat performance.
1. Remove blower and coil access panels and fitting panel. (See Fig. 5.)
2. Remove screw securing coil assembly to right side casing flange.
3. Remove coil assembly.
4. Lay fan coil on its right side and reinstall coil assembly with condensate pan down.
5. Attach coil to casing flange using previously removed coil mounting screw.
6. Make sure pan cap in fitting door is properly seated on fitting door to retain low air leak rating of the unit.
7. Add gaskets included in kit per kit instructions.
8. Reinstall access panels and fitting panel, aligning holes with tubing connections and condensate pan connections.
Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating. Install grommets after brazing.
E. Horizontal Right Conversion of Units With A--Coil
To convert units for horizontal right installations:
1. Remove blower and coil access panels. (See Fig. 6.)
2. Remove metal clip securing fitting panel to condensate pan. Remove fitting panel.
3. Remove 2 snap--in clips securing A--coil in unit.
4. Slide coil and pan assembly out of unit.
5. Remove horizontal drain pan support bracket from coil support rail on left side of unit and reinstall on coil support rail on right side of unit.
4 496 01 4201 03
INSTALLA TION INSTRUCTIONS Fan Coils: FCM4X
6. Convert air seal assembly for horizontal right. a. Remove air seal assembly from coil by removing 4
screws.
b. Remove air splitter (B) from coil seal assembly by
removing 3 screws. (See Fig. 6 inset)
c. Remove filler plate (A) and install air splitter (B) in
place of filler plate.
d. Install filler plate (A) as shown in horizontal right
application.
e. Remove condensate troughs (C) and install on
opposite tube sheets.
f. Install hose onto plastic spout.
7. Install hose onto plastic spout.
8. Slide coil assembly into casing. Be sure coil bracket on
each corner of vertical pan engages coil support rails.
9. Reinstall 2 snap--in clips to correctly position and
secure coil assembly in unit. Be sure clip with large offset is used on right side of unit to secure horizontal pan.
Figure 5
Slope Coil in Horizontal Right Application
COIL MOUNTING
SCREW
10. Remove two oval fitting caps from left side of the coil, access panel, and fitting panel.
1 1. Remove insulation knockouts on right side of coil
access panel.
12. Remove 2 oval coil access panel plugs and reinstall into holes on left side of coil access panel and fitting panel.
13. Install condensate pan fitting caps (from Step 10) in right side of coil door making sure that cap snaps and seats cleanly on back side of the coil door. Make sure no insulation interferes with seating of cap.
14. Reinstall access and fitting panels, aligning holes with tubing connections and condensate pan connections. Be sure to reinstall metal clip between fitting panel and vertical condensate pan.
Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating.
BLOWER ASSEMBLY
COIL
SUPPORT
RAIL
SLOPE COIL
SKI
DRAINPAN
REFRIGERANT CONNECTIONS
PRIMARY DRAIN
SECONDARY DRAIN
A03001
496 01 4201 03 5
Loading...
+ 11 hidden pages