Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical
components. Only trained and qualified service personnel
should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance
functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service
personnel. When working on air-conditioning equipment,
observe precautions in the literature, tags and labels
attached to the unit, and other safety precautions that may
apply.
Follow all safety codes, including ANSI (American National
Standards Institute) Z223.1. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguisher available for all brazing operations.
It is important to recognize safety information. This is the
safety-alert symbol . When you see this symbol on the
unit and in instructions or manuals, be alert to the potential
for personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety-alert symbol. DANGER identifies the most serious
hazards which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal
injury or death. CAUTION is used to identify unsafe
practices, which may result in minor personal injury or
product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation,
reliability, or operation.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury
or death.
Before performing service or maintenance operations on
unit, turn off main power switch to unit and install lock(s)
and lockout tag(s). Ensure electrical service to rooftop
unit agrees with voltage and amperage listed on the unit
rating plate. Unit may have more than one power switch.
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal inju-
ry, death and/or equipment damage.
R-410A refrigerant systems operate at higher pres-
sures than standard R-22 systems. Do not use R-22
service equipment or components on R-410A refrigerant equipment.
WARNING
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause personal injury
or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from
refrigerants and oils.
508 01 1603 017-19
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropriate protective clothing, safety
glasses and gloves when handling parts and servicing
air conditioning equipment.
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment
damage.
Ensure voltage listed on unit data plate agrees with elec-
trical supply provided for the unit.
PRE-INSTALLATION
1. The power supply (v, Ph, and Hz) must correspond to
that specified on unit rating plate.
2. The electrical supply provided by the utility must be
sufficient to handle load imposed by this unit.
3. Refer to the General Installation section and Fig. 1-3
for locations of electrical inlets, condensate drain,
duct connections, and required clearances before
setting unit in place.
4. This installation must conform with local building
codes and with the NEC (National Electrical Code) or
ANSI (American National Standards Institute)/NFPA
(National Fire Protection Association) latest revision.
Refer to provincial and local plumbing or wastewater
codes and other applicable local codes.
Moving and Storage
To transfer unit from truck to storage site, use a fork truck.
Do not stack units more than 2 high during storage. If unit is
to be stored for more than 2 weeks before installation,
choose a level, dry storage site free from vibration. Do not
remove plastic wrap or skid from unit until final installation.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
All panels must be in place when rigging. Unit is not de-
signed for handling by fork truck when packaging is removed.
If using top crate as spreader bar, once unit is set, carefully lower wooden crate off building roof top to ground.
Ensure that no people or obstructions are below prior to
lowering the crate.
Rigging
All FAS/FHS units can be rigged by using the shipping skid.
Units are shipped fully assembled. Do not remove shipping
skids or protective covering until unit is ready for final placement; damage to bottom panels can result. Use slings and
spreader bars as applicable to lift unit.
INSTALLATION
General
Allow the following clearances for service access and
airflow:
•Rear: 3 ft (914 mm) [2
heat accessory]
•Front: 2
•Right side: 2
•Left side: 2
1
/2 ft (762 mm)
1
/2 ft (762 mm)
1
/2 ft (762 mm)
1
/2 ft (762 mm) with electric
For units equipped with an economizer, refer to the accessory installation instructions for additional clearance requirements. Be sure floor, wall, or ceiling can support unit weight
(Tables 4 – 11). See Fig. 1-3 for dimensions.
Uncrating
Move unit as near as possible to final location before removing shipping skid.
Remove metal banding, top skid, and plastic wrap. Examine
unit for shipping damage. If shipping damage is evident, file
claim with transportation agency. Remove base skid just prior to actual installation.
Check nameplate information against available power supply and model number description in Fig. 4.
NOTE: Be sure to remove the styrofoam shipping pad from
the thermostatic expansion valve (TXV). Verify that it has
been removed. See Fig. 5.
Accessories
Refer to instructions shipped with each accessory for specific information.
Rated Indoor Airflow (cfm)
Tables 1-3 list the rated indoor airflow used for the AHRI
efficiency rating for the units covered in this document.
There is no matched pair available for size 300 and 336
models.
Base Unit with TXV399404425695713
Plenum175175175225225
FANS
Qty...Diam. (in.)1...151...151...152...152...15
Nominal Airflow (cfm)24003000400050006000
Airflow Range (cfm)1800-30002250-37503000-50003750-62504500-7500
Nominal Motor Hp (Standard
Motor)
208/230-1-601.32.4———
208/230-3-60 and 460-3-602.42.42.42.93.7
575-3-601.02.02.03.03.0
Motor Speed (rpm)
208/230-1-6017251725———
208/230-3-60 and 460-3-6017251725172517251725
575-3-6017251725172517251725
REFRIGERANTR-410A
Operating charge (lb) (approx
per circuit)*
DIRECT-EXPANSION COILEnhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig)650
Face Area (sq ft)6.678.3310.013.2517.67
No. of Splits11222
No. of Circuits per Split121591216
Split Type...Percentage—Face...50/50
Rows...Fins/in.4...15
PIPING CONNECTIONS
Quantity...Size (in.)
DX Coil — Suction (ODF)1...1
DX Coil — Liquid
Refrigerant (ODF)
Steam Coil, In (MPT)1...21/
Steam Coil, Out (MPT)1...11/
Hot Water Coil, In (MPT)1...11/
Hot Water Coil, Out (MPT)1...1
Condensate (PVC)1...1
FILTERSThrowaway — Factory Supplied
Quantity...Size (in.)4...16 x 24 x 24...16 x 24 x 24...16 x 24 x 2
Access LocationEither Side
STEAM COIL†
Max Working Pressure (psig
at 260°F)
Total Face Area (sq ft)6.676.676.6713.3313.33
Rows...Fins/in.1...91...91...91...101...10
HOT WATER COIL†
Max Working Pressure (psig)150150150150150
Total Face Area (sq ft)6.676.676.6713.3313.33
Rows...Fins/in.2...8.52...8.52...8.52...8.52...8.5
Water Volume
(gal)8.38.38.313.913.9
3
(ft
)1.11.11.11.851.85
LEGEND
DX— Direct Expansion
TXV — Thermostatic Expansion Valve
* Units are shipped without refrigerant charge.
† Field-installed accessory only.
3.03.01.5/1.52.0/2.02.5/2.5
1
1...
/
8
5
/
8
2
2
2
1
/
2
1...11/
1...5/
1...21/
1...11/
1...11/
1...11/
8
8
2
2
2
2
2...11/
8
2...5/
8
1...21/
2
1...11/
2
1...11/
2
1...11/
5
2
/8 ODM / 11/4 IDF
2...11/
8
2...5/
8
1...21/
2
1...11/
2
1...21...2
1...21...2
4...16 x 20 x 2
4...16 x 24 x 2
2...11/
2...5/
1...21/
1...11/
4...16 x 20 x 2
4...16 x 24 x 2
2020202020
8
8
2
2
508 01 1603 01Specifications subject to change without notice.3
Table 5 — Physical Data (English) — 20 to 30 Ton Cooling Units (FAS)
Qty...Diam. (in.)2...152...182...18
Nominal Airflow (cfm)80001000012000
Airflow Range (cfm)6000 – 100007500 – 125009000 – 15000
Nominal Motor Hp (Standard Motor)
208/230-3-60 and 460-3-605.07.510.0
575-3-605.07.510.0
Motor Speed (rpm)
208/230-3-60 and 460-3-60174517451745
575-3-60174517551755
REFRIGERANTR-410A
Operating charge (lb) (approx per circuit)*3.54.55.0
DIRECT-EXPANSION COILEnhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig)650
Face Area (sq ft)19.8824.8629.83
No. of Splits222
No. of Circuits per Split182024
Split Type...PercentageFace...50/50
Rows...Fins/in.4...154...154...15
PIPING CONNECTIONS
Quantity...Size (in.)
DX Coil — Suction (ODF)2...1
DX Coil — Liquid Refrigerant (ODF)2...5/
Steam Coil, In (MPT)1...21/
Steam Coil, Out (MPT)1...1/
Hot Water Coil, In (MPT)1...2
Hot Water Coil, Out (MPT)1...2
Condensate (PVC)1...1
FILTERSThrowaway — Factory Supplied
Quantity...Size (in.)
Access LocationEither Side
STEAM COIL†
Max Working Pressure (psig at 260°F)20
Total Face Area (sq ft)13.3315.015.0
Rows...Fins/in.1...101...101...10
HOT WATER COIL†
Max Working Pressure (psig)150
Total Face Area (sq ft)13.3315.015.0
Rows...Fins/in.2...8.52...12.52...12.5
Water Volume
(gal)13.914.3
3
(ft
)1.861.90
LEGEND
DX— Direct Expansion
TXV — Thermostatic Expansion Valve
* Units are shipped without refrigerant charge.
† Field-installed accessory only.
1
/
8
4...16 x 20 x 2
4...16 x 24 x 2
2...13/
8
8
2
2
1
/4 ODM/1 IDF
4...20 x 24 x 2
4...20 x 25 x 2
2...13/
8
4Specifications subject to change without notice.508 01 1603 01
Table 6 — Physical Data (SI) — 21 to 52 kW Cooling Units (FAS)
Base Unit with TXV173175184304311
Plenum808080102102
FANS
Qty...Diam. (mm)1...3811...3811...3812...3812...381
Nominal Airflow (L/s)11331604188823602831
Airflow Range (L/s)850-14161203-20061416-23601770-29492124-3539
Nominal Motor kW (Standard
Motor)
208/230-1-600.971.79———
208/230-3-60 and 460-3-601.791.791.792.162.16
575-3-600.751.491.492.242.24
Motor Speed (r/s)
208/230-1-6028.828.8———
208/230-3-60 and 460-3-6028.828.828.828.828.8
575-3-6028.828.828.828.828.8
REFRIGERANTR-410A
Operating charge (kg) (approx
per circuit)*
DIRECT-EXPANSION COILEnhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (kPag)44814481448144814481
Face Area (sq m)0.620.770.930.931.64
No. of Splits11222
No. of Circuits per Split121591216
Split Type...Percentage——Face...50/50
Rows...Fins/m4...5914...5914...5914...5914...591
PIPING CONNECTIONS
Quantity...Size (in.)
DX Coil — Suction (ODF)1...1
DX Coil — Liquid
Refrigerant (ODF)
Steam Coil, In (MPT)1...21/
Steam Coil, Out (MPT)1...11/
Hot Water Coil, In (MPT)1...11/
Hot Water Coil, Out (MPT)1...1
Condensate (PVC)1...1
FILTERSThrowaway — Factory Supplied
Quantity...Size (mm)4...406 x 610 x 51
Access LocationEither Side
STEAM COIL†
Max Working Pressure (kPag
at 126°C)
Total Face Area (sq m)0.620.620.621.241.24
Rows...Fins/m1...3551...3551...3551...3941...394
HOT WATER COIL†
Max Working Pressure (kPag)1034
Total Face Area (sq m)0.620.620.621.241.24
Rows...Fins/m2...3352...3352...3352...3352...335
Water Volume
(L)31.431.431.452.652.6
3
(m
)0.0310.0310.0310.0520.052
LEGEND
DX— Direct Expansion
TXV — Thermostatic Expansion Valve
* Units are shipped without refrigerant charge.
† Field-installed accessory only.
1.361.360.68/0.680.90/0.901.13/1.13
1
1...
/
8
5
/
8
2
2
2
1
/
2
1...11/
1...5/
1...21/
1...11/
1...11/
1...11/
8
8
2
2
2
2
2...11/
8
2...5/
8
1...21/
2
1...11/
2
1...11/
2
1...11/
5
2
/8 ODM / 11/4 IDF
2...11/
2...5/
1...21/
1...11/
8
8
2
2
2...11/
2...5/
1...21/
1...11/
1...21...2
1...21...2
4...406 x 508 x 51
4...406 x 610 x 51
138
8
8
2
2
508 01 1603 01Specifications subject to change without notice.5
Table 7 — Physical Data (SI) — 70 to 105 kW Cooling Units (FAS)
Qty...Diam. (mm)2...3812...4572...457
Nominal Airflow (L/s)377541195663
Airflow Range (L/s)2831 – 47193539 – 58994247 – 7079
Nominal Motor kW (Standard Motor)
208/230-3-60 and 460-3-603.735.607.46
575-3-603.735.607.46
Motor Speed (r/s)
208/230-3-60 and 460-3-6029.129.129.1
575-3-6029.129.329.3
REFRIGERANTR-410A
Operating charge (kg) (approx per circuit)*1.592.042.27
DIRECT-EXPANSION COILEnhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (kPag)4481
Face Area (sq m)1.852.302.77
No. of Splits222
No. of Circuits per Split182024
Split Type...PercentageFace...50/50
Rows...Fins/m4...5914...5914...591
PIPING CONNECTIONS
Quantity...Size (in.)
DX Coil — Suction (ODF)2...1
DX Coil — Liquid Refrigerant (ODF)2...5/
Steam Coil, In (MPT)1...21/
Steam Coil, Out (MPT)1...1/
Hot Water Coil, In (MPT)1...2
Hot Water Coil, Out (MPT)1...2
Condensate (PVC)1...1
FILTERSThrowaway — Factory Supplied
Quantity...Size (mm)
4...406 x 508 x 51
4...406 x 610 x 51
Access LocationEither Side
STEAM COIL†
Max Working Pressure (kPag at 126°C)138
Total Face Area (sq m)1.241.391.39
Rows...Fins/m1...3941...3941...394
HOT WATER COIL†
Max Working Pressure (kPag)1034
Total Face Area (sq m)1.241.391.39
Rows...Fins/m2...3352...4932...493
Water Volume
(L)52.654.1
3
(m
)0.0520.054
LEGEND
DX— Direct Expansion
TXV — Thermostatic Expansion Valve
* Units are shipped without refrigerant charge.
† Field-installed accessory only.
1
/
8
2...13/
8
8
2
2
1
/4 ODM/1 IDF
2...13/
8
4...508 x 610 x 51
4...508 x 635 x 51
6Specifications subject to change without notice.508 01 1603 01
Table 8 — Physical Data (English) — 6 to 15 Ton Heat Pump Units (FHS)
Base Unit with TXV381381385427713
Plenum175175175175225
FANS
Qty...Diam. (in.)1...151...151...151...152...15
Nominal Airflow (cfm)24002400300040006000
Airflow Range (cfm)1800-30001800-30002250-37503000-50004500-7500
Nominal Motor Hp (Standard
Motor)
208/230-1-601.31.32.4——
208/230-3-60 and 460-3-602.42.42.42.43.7
575-3-601.01.02.02.03.0
Motor Speed (rpm)
208/230-1-60172517251725——
208/230-3-60 and 460-3-6017251725172517251725
575-3-6017251725172517251725
REFRIGERANTR-410A
Operating charge (lb) (approx
per circuit)*
DIRECT-EXPANSION COILEnhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig)650
Face Area (sq ft)8.338.338.3310.016.56
No. of Splits11122
No. of Circuits per Split151212910
Split Type...Percentage———Face....50/50
Rows...Fins/in.3...154...154...154...154...15
PIPING CONNECTIONS
Quantity...Size (in.)
DX Coil — Suction (ODF)1...1
DX Coil — Liquid
Refrigerant (ODF)
Steam Coil, In (MPT)1...21/
Steam Coil, Out (MPT)1...11/
Hot Water Coil, In (MPT)1...11/
Hot Water Coil, Out (MPT)1...1
Condensate (PVC)1...1
FILTERSThrowaway — Factory Supplied
Quantity...Size (in.)4...16 x 24 x 24...16 x 24 x 24...16 x 24 x 24...16 x 24 x 2
Access LocationEither Side
STEAM COIL†
Max Working Pressure (psig at
260°F)
Total Face Area (sq ft)6.676.676.676.6713.33
Rows...Fins/in.1...91...91...91...91...10
HOT WATER COIL†
Max Working Pressure (psig)150
Total Face Area (sq ft)6.676.676.676.6713.33
Rows...Fins/in.2...8.52...8.52...8.52...8.52...8.5
Water Volume
(gal)8.38.38.38.313.9
3
(ft
)1.11.11.11.11.85
LEGEND
DX— Direct Expansion
TXV — Thermostatic Expansion Valve
* Units are shipped without refrigerant charge.
† Field-installed accessory only.
3.03.03.02.0/2.03.0/3.0
1
1...
/
8
5
/
8
2
2
2
1
/
2
1...11/
1...5/
1...21/
1...11/
1...11/
1...11/
8
8
2
2
2
2
1...11/
8
1...5/
8
1...21/
2
1...11/
2
1...11/
2
1...11/
5
2
/8 ODM / 11/4 IDF
2...11/
2...5/
1...21/
1...11/
1...11/
1...11/
8
8
2
2
2
2
2...11/
2...5/
1...21/
1...11/
1...2
1...2
4...16 x 20 x 2
4...16 x 24 x 2
20
8
8
2
2
508 01 1603 01Specifications subject to change without notice.7
Table 9 — Physical Data (English) — 20 Ton Heat Pump Units (FHS)
FHS UNIT240
NOMINAL CAPACITY (Tons)20
OPERATING WEIGHT (lb)
Base Unit with TXV720
Plenum140
FANS
Qty...Diam. (in.)2...15
Nominal Airflow (cfm)8000
Airflow Range (cfm)6000-10000
Nominal Motor Hp (Standard Motor)
208/230-3-60 and 460-3-605.0
575-3-605.0
Motor Speed (rpm)
208/230-3-60 and 460-3-601745
575-3-601745
REFRIGERANTR-410A
Operating charge (lb) (approx per circuit)*3.5/3.5
DIRECT-EXPANSION COILEnhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig)650
Face Area (sq ft)19.9
No. of Splitsno2
No. of Circuits per Split2
Split Type...PercentageFace....50/50
Rows...Fins/in.4...15
PIPING CONNECTIONS
Quantity...Size (in.)
DX Coil — Suction (ODF)2...1
DX Coil — Liquid Refrigerant (ODF)2...5/
Steam Coil, In (MPT)1...21/
Steam Coil, Out (MPT)1...11/
Hot Water Coil, In (MPT)1...2
Hot Water Coil, Out (MPT)1...2
Condensate (PVC)1...1
FILTERSThrowaway — Factory Supplied
Quantity...Size (in.)
Access LocationRight or Left Side
STEAM COIL†
Max Working Pressure (psig at 260°F)20
Total Face Area (sq ft)13.33
Rows...Fins/in.1...10
HOT WATER COIL†
Max Working Pressure (psig)150
Total Face Area (sq ft)13.33
Rows...Fins/in.2...8.5
Water Volume
(gal)13.9
3
(ft
)1.85
LEGEND
DX— Direct Expansion
TXV — Thermostatic Expansion Valve
* Units are shipped without refrigerant charge.
† Field-installed accessory only.
1
/
8
8
2
2
1
/4 ODM/1 IDF
4...16 x 20 x 2
4...16 x 24 x 2
8Specifications subject to change without notice.508 01 1603 01
Table 10 — Physical Data (SI) — 21 to 52 kW Heat Pump Units (FHS)
Base Unit with TXV173173175194323
Plenum80808080102
FANS
Qty...Diam. (mm)1...3811...3811...3811...3812...381
Nominal Airflow (L/s)11331133160418882831
Airflow Range (L/s)850-1416850-14161203-20061416-23602124-3539
Nominal Motor kW (Standard
Motor)
208/230-1-600.970.971.79——
208/230-3-60 and 460-3-601.791.791.791.792.76
575-3-600.750.751.491.492.24
Motor Speed (r/s)
208/230-1-6028.828.828.8——
208/230-3-60 and 460-3-6028.828.828.828.828.8
575-3-6028.828.828.828.828.8
REFRIGERANTR-410A
Operating charge (kg) (approx
per circuit)*
DIRECT-EXPANSION COILEnhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (kPag)4482
Face Area (sq m)0.770.770.770.931.54
No. of Splits11122
No. of Circuits per Split151212910
Split Type...Percentage———Face...50/50
Rows...Fins/m3...5914...5914...5913...5914...591
PIPING CONNECTIONS
Quantity...Size (in.)
DX Coil — Suction (ODF)1...1
DX Coil — Liquid
Refrigerant (ODF)
Steam Coil, In (MPT)1...21/
Steam Coil, Out (MPT)1...11/
Hot Water Coil, In (MPT)1...11/
Hot Water Coil, Out (MPT)1...1
Condensate (PVC)1...1
FILTERSThrowaway — Factory Supplied
Quantity...Size (mm)4...406 x 610 x 514...406 x 610 x 514...406 x 610 x 514...406 x 610 x 51
Access LocationEither Side
STEAM COIL†
Max Working Pressure (kPg at
126°C)
Total Face Area (sq m)0.620.620.620.621.24
Rows...Fins/in.1...3551...3551...3551...3551...394
HOT WATER COIL†
Max Working Pressure (kPag)1034
Total Face Area (sq m)0.620.620.620.621.24
Rows...Fins/m2...3352...3352...3352...3352...335
Water Volume
(L)31.431.431.431.452.6
3
(m
)0.0310.0310.0310.0310.052
LEGEND
DX— Direct Expansion
TXV — Thermostatic Expansion Valve
* Units are shipped without refrigerant charge.
† Field-installed accessory only.
1.361.361.360.91/0.911.36/1.36
1
1...
/
8
5
/
8
2
2
2
1
/
2
1...11/
1...5/
1...21/
1...11/
1...11/
1...11/
8
8
2
2
2
2
1...11/
8
1...5/
8
1...21/
2
1...11/
2
1...11/
2
1...11/
5
2
/8 ODM / 11/4 IDF
2...11/
2...5/
1...21/
1...11/
1...11/
1...11/
8
8
2
2
2
2
2...11/
2...5/
1...21/
1...11/
1...2
1...2
4...406 x 508 x 51
4...406 x 610 x 51
138
8
8
2
2
508 01 1603 01Specifications subject to change without notice.9
Table 11 — Physical Data (SI) — 70 kW Heat Pump Units (FHS)
FHS UNIT240
NOMINAL CAPACITY (kW)70
OPERATING WEIGHT (kg)
Base Unit with TXV326
Plenum44
FANS
Qty...Diam. (mm)2...381
Nominal Airflow (L/s)3775
Airflow Range (L/s)2831-4719
Nominal Motor kW (Standard Motor)
208/230-3-60 and 460-3-603.73
575-3-603.73
Motor Speed (r/s)
208/230-3-60 and 460-3-6029.1
575-3-6029.1
REFRIGERANTR-410A
Operating charge (kg) (approx per circuit)*1.59/1.59
DIRECT-EXPANSION COILEnhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (kPag)4482
Face Area (sq m)1.85
No. of Splits2
No. of Circuits per Split2
Split Type...PercentageFace...50/50
Rows...Fins/m591
PIPING CONNECTIONS
Quantity...Size (in.)
DX Coil — Suction (ODF)2...1
DX Coil — Liquid Refrigerant (ODF)2...5/
Steam Coil, In (MPT)1...21/
Steam Coil, Out (MPT)1...11/
Hot Water Coil, In (MPT)1...2
Hot Water Coil, Out (MPT)1...2
Condensate (PVC)1...1
FILTERSThrowaway — Factory Supplied
Quantity...Size (mm)
4...406 x 610 x 51
4...406 x 508 x 51
Access LocationRight or Left Side
STEAM COIL†
Max Working Pressure (kPag at 126°C)138
Total Face Area (sq m)1.24
Rows...Fins/m1...394
HOT WATER COIL†
Max Working Pressure (kPag)1034
Total Face Area (sq m)1.24
Rows...Fins/m2...335
Water Volume
(L)52.6
3
(m
)0.052
LEGEND
DX— Direct Expansion
TXV — Thermostatic Expansion Valve
* Units are shipped without refrigerant charge.
† Field-installed accessory only.
1
/
8
8
2
2
1
/4 ODM/1 IDF
10Specifications subject to change without notice.508 01 1603 01
Fig. 1 — Unit Dimensions (6-10 Ton Units)
508 01 1603 01Specifications subject to change without notice.11
Fig. 2 — Unit Dimensions (12.5 to 20 tons)
12Specifications subject to change without notice.508 01 1603 01
Fig. 3 — Unit Dimensions (25 and 30 tons)
508 01 1603 01Specifications subject to change without notice.13
MODEL SERIES
Position Number
Type
Voltage
Fan Motor Options
Indoor Coil
0 = Single Speed Indoor Fan Motor
2 = Two Speed Indoor Fan Motor Controller (VFD)
A = Standard - Unpainted
B = Painted cabinet (Gray)
A = Standard
Notes:
• All FAS072-150 units and FHS 072-120 units with a “M” voltage designation are triple voltage; i.e., 208/230/460-3-60.
FAS 180 units are also triple voltage in the “M” configuration unless the High Static motor option is used.
“M” voltage is not available on 2-speed indoor fan motor option.
• Single-phase 072 and 091 units designate standard motor and high static drive.
A = Standard Static Standard Efficiency Motor / Standard Drive
• 6 to 15 ton 208/230v, 460v, 575v-3-60, 6 and 7.5 ton 208/230-1-60, 1-speed
• all 2-speed
B = High St
atic Standard Efficiency Motor / High Drive
• 6 to 15 ton 208/230V, 460v, 6 to 10 ton 575v-3-60, 1-speed
• all 2-speed
D = Standard Static High Efficiency Motor / Standard Drive
• 20, 25, 30 ton all 3 phase
E = High Static High Efficiency Motor / High Drive
• 15 to 30 ton all 3 phase
F = R-410A Fan Coil Unit
A = Air Conditioning (Cooling Only)
H = Heat Pump
S = Standard Efficiency
Nominal Tonnage
Future Use
Fan Spee
d Controller
FAS09 1MAAA0 A0A
1
23
4
5
6
7
89
1011
12
13
14
Unit Positioning
The unit can be mounted on the floor for vertical application with return air entering the face of the unit and supply
air discharging vertically through the top of the unit. The
unit can also be applied in a horizontal arrangement with
return air entering horizontally and the supply air discharging horizontally. When applying the unit in a horizontal arrangement, ensure the condensate drain pan is located at
the bottom center of the unit for adequate condensate disposal. See Fig. 6 for condensate connections for each unit
position.
Fig. 4 — Model Number Nomenclature
Typical positioning and alternate return air locations are
shown in Fig. 6. Alternate return air locations can be used
by moving the unit panel from the alternate return air location to the standard return air location. Refer to overhead
suspension accessory drawing (Fig. 7) for preferred suspension technique. The unit needs support underneath to
prevent sagging.
IMPORTANT: Do NOT attempt to install unit with
return air entering top panel of unit. Condensate will
not drain from unit.
14Specifications subject to change without notice.508 01 1603 01
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.