Intermatic T1871BR Owner's Manual

MODEL: T1871BR
24 HOUR DIAL TIME SWITCH MECHANISM WITH ‘’SKIPPER ’’
®
LR3730
2 NORMALLY OPEN - 2 NORMALLY CLOSED SET OF CONTACTS
(MAY BE WIRED AS DOUBLE POLE DOUBLE THROW)
40 AMP. RESISTIVE,EACH POLE 120-480V. AC; 40 AMP. INDUCTIVE TUNGSTEN OR 1000 V.A. PILOT DUTY EACH POLE 120-277 V. AC; 2 H.P. (24 FLA) - 120 V. AC; 5 H.P. (28 FLA) - 240 V. AC
WIRING INSTRUCTIONS: To wire
switch follow diagram above. If DOUBLE POLE switch action is required,
install jumpers (extend supply wires) between terminals 1-6 and 3-8. Use solid or stranded COPPER only wire insulation to suit installation. See gauge selection table for normal service application.s To make power connections see illustration below. Replace front insulator before turning on electricity. Motor voltage and cycle (Hz.) must be as specified.
PROGRAMMING INSTRUCTIONS
OPERATING INSTRUCTIONS
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
TIME POINTER
TIME DIAL
OFF TRIPPER
MANUAL LEVER
MIN.
MAX.
MINIMUM
COPPER
WIRE SIZE
(AWG)
14 12 10
8
TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly. See caution below. For additional tripper pairs on CLOCK-
DIAL order 156T1948A. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and
align the exact time-of-day on the CLOCK-DIAL (the time now, when switch is being put into operation) TO TIME POINTER. DO NOT MOVE THE POINTER. TO SKIP OPERATION(S) ON SELECTED DAY(S): Insert SKIPPING SCREW(S) in SKIPPER WHEEL for day(s) automatic operation(s) is/are NOT required. Tighten screws firmly. Move MANUAL LEVER to “OFF” and rotate SKIPPER
WHEEL to locate correct day-of-week opposite DAY ARROW--”YESTERDAY” if ON/CUTOUT TRIPPER has not yet advanced wheel “TODAY” if it has.
TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER bellow CLOCK­DIAL left or right as indicated by arrows. This will not effect next operation. CAUTION: TO AVOID SLOW TRIPPER ACTION FAILURE, DO NOT OPERATE SWITCH MANUALLY NOR PLACE A TRIPPER 4 HOURS PRIOR TO ON/OFF CUTOUT TRIPPER SWITCHING. IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day.
See programming instructions.
158TS12928
LOAD
(AMP)
15 20 30 40
INSUL-
ATION
TEMP(°C)
60 60 60 75
ON/CUTOUT
TRIPPER
DAY ARROW
SKIPPER WHEEL
SKIPPING SCREW
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
120 V. 240 V. 208 V.
2
2 1/2
3 4
3
5
5
7/12
1/2
1 2
-
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
3 PHASE
240 V.
71/2
10
3 5
120V 60 Hz
SUPPLY
GROUND SCREW
CLOCK MOTOR
WIRING DIAGRAM
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE INSULATION CLEARS PRESSURE PLATE
TO LOAD(S)