Intermatic T174CR Supplementary Manual

Page 1
MODEL: T174CR
24 HR DIAL TIME SWITCH WITH “SKIPPER®” AND SPRING-WOUND CARRY-OVER MOTOR
DOUBLE POLE SINGLE THROW (DPST)
IN TYPE 3R RAINPROOF ENCLOSURE,
40 AMP. RESISTIVE, EACH POLE 120-480 VOLT A.C. 40 AMP INDUCTIVE, OR TUNGSTEN OR 1000 VA. PILOT DUTY EACH POLE - 120V -277V AC; 2 HP (24 FLA) - 120V AC; 5 HP (28 FLA) - 240V AC.
WIRING INSTRUCTIONS: To wire switch follow diagram above. Use solid
or stranded COPPER only wire with insulation to suit installation. See gauge selection table for normal service applications. To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum). REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF
operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1978A.
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK-DIAL (the time now, when switch is being put into operation) to the pointer.
DO NOT MOVE POINTER.
3. TO SKIP OPERATION(S) ON SELECTED DAY(S): Insert SKIPPING SCREW(S) in SKIPPER WHEEL for day(s) automatic operation(s) is/are NOT required. Tighten screws firmly. Move MANUAL LEVER to “OFF” and rotate SKIPPER WHEEL to locate correct day-of-week
opposite DAY ARROW--”YESTERDAY” if ON/CUTOUT TRIPPER has not yet advanced wheel “TODAY” if it has.
OPERATING INSTRUCTIONS
TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below CLOCK-DIAL left or right as indicated by arrows. This will not effect
next operation.
CAUTION: TO AVOID SLOW SWITCH ACTION FAILURE, DO NOT OPERATE SWITCH MANUALLY NOR PLACE A TRIPPER 4 HOURS PRIOR TO ON/CUTOUT TRIPPER SWITCHING.
IN CASE OF POWER F
AILURE,
reset CLOCK-DIAL to
proper time-of-day. See programming instructions.
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
158TS10930
PRESSURE PLATE TERMINAL SCREW MAKE SURE WIRE
INSULATION CLEARS PRESSURE PLATE
MINIMUM
COPPER
WIRE SIZE
(AWG)
MAX. LOAD
(AMP)
MIN.
INSUL-
ATION
TEMP(°C)
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
3 PHASE
120 V. 240 V. 208 V.
240 V.
14 12 10
8
15 20 30 40
60 60 60 75
1/2
1 2
-
2
2 1/2
3 5
N/A
N/A
TIME POINTER
TIME DIAL
OFF TRIPPER
MANUAL LEVER
ON/CUTOUT
TRIPPER
DAY ARROW
SKIPPER WHEEL
SKIPPING SCREW
CLOCK MOTOR: 208-277 VOLTS - 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE ART NO. (WG--) ON MOTOR COVER.
CLOCK
MOTOR
GROUND
A
1
2
277 480 VOLT CONNECT MOTOR LEADS TO TERMINALS “A” AND 2 AND SUPPLY NEUTRAL TO TERMINAL “A”.
TO LOAD
GRD
LINE 1
WIRING DIAGRAM
3
4
LINE 2
240V
SUPL
Y
LR3730
Project1 7/27/04 4:30 PM Page 1