Intermatic T173CR Owner's Manual

MODEL: T173CR
24 HR DIAL TIME SWITCH WITH “SKIPPER®” AND SPRING-WOUND CARRY-OVER MOTOR
DOUBLE POLE SINGLE THROW DPST)
IN TYPE 3R RAINPROOF ENCLOSURE,
LR3730
40 AMP. RESISTIVE, INDUCTIVE, TUNGSTEN OR 1000 VA. PILOT DUTY PER POLE - 120/208/277 VOLT AC; 2 HP (24 FLA) - 120V AC; 5 HP (28 FLA) - 240V AC.
CLOCK MOTOR: 110-125 VOLTS - 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE ART NO. (WG--) ON MOTOR COVER.
TIME POINTER
TIME DIAL
OFF TRIPPER
MANUAL LEVER
or stranded COPPER only wire with insulation to suit installation. See gauge selection table for normal service applications. To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum). REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
MINIMUM
COPPER
WIRE SIZE
(AWG)
14 12 10
8
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1948A.
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK-DIAL (the time now, when switch is being put into operation) to the pointer.
DO NOT MOVE POINTER.
3. TO SKIP OPERATION(S) ON SELECTED DAY(S): Insert SKIPPING SCREW(S) in SKIPPER WHEEL for day(s) automatic operation(s)
has not yet advanced wheel “TODAY” if it has. OPERATING INSTRUCTIONS
• TOOPERATESWITCHMANUALLY:Move MANUAL LEVER below CLOCK-DIAL left or right as indicated by arrows. This will not effect next operation.
CAUTION: TO AVOID SLOW SWITCH ACTION FAILURE, DO NOT OPERATE SWITCH MANUALLY NOR PLACE A TRIPPER 4 HOURS PRIOR TO ON/CUTOUT TRIPPER SWITCHING.
• IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day. See programming instructions.
158TS12931
MAX. LOAD
(AMP)
15 20 30 40
MIN.
INSUL-
ATION
TEMP(°C)
60 60 60 75
ON/CUTOUT
TRIPPER
DAY ARROW
SKIPPING SCREW
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
120 V. 240 V. 208 V.
2
1/2
2 1/2
1
3
2
5
-
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
SKIPPER WHEEL
3 PHASE
N/A
WIRING DIAGRAM
GRD
A 1 2
NEUT. LINE 1 LINE 2
120/240 VOLT 3 WIRE SUPPLY
240 V.
N/A
CLOCK
MOTOR
3
4
TO LOAD
GROUND
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE INSULATION CLEARS PRESSURE PLATE
Loading...