Intermatic T173 Owner's Manual

MODEL: T173
LR3730
24 HR DIAL TIME SWITCH WITH “SKIPPER®
DOUBLE POLE SINGLE THROW (DPST)
40 AMP. RESISTIVE, INDUCTIVE, TUNGSTEN OR 1000 VA. PILOT DUTY PER POLE - 120/208/277 VOLT AC; 2 HP (24 FLA) - 120V AC; 5 HP (28 FLA ) - 240V AC.
CLOCK MOTOR: 110-125 VOLTS - 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
TIME POINTER
TIME DIAL
OFF TRIPPER
MANUAL LEVER
WIRING INSTRUCTIONS: To wire switch follow diagram above. Use solid
or stranded COPPER only wire with insulation to suit installation. See gauge selection table for normal service applications. To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum). REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
MINIMUM
COPPER
WIRE SIZE
(AWG)
14 12 10
8
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1948A.
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK-DIAL (the time now, when switch is being put into operation) to the pointer.
DO NOT MOVE POINTER.
3. TO SKIP OPERATION(S) ON SELECTED DAY(S): Insert SKIPPING SCREW(S) in SKIPPER WHEEL for day(s) automatic operation(s)
is/are NOT required. Tighten screws firmly. Move MANUAL LEVER to “OFF” and rotate SKIPPER WHEEL to locate correct day-of-week opposite DAY ARROW--”YESTERDAY” if ON/CUTOUT TRIPPER
has not yet advanced wheel “TODAY” if it has. OPERATING INSTRUCTIONS
• TOOPERATESWITCHMANUALLY:Move MANUAL LEVER below CLOCK-DIAL left or right as indicated by arrows. This will not effect next operation.
CAUTION: TO AVOID SLOW SWITCH ACTION FAILURE, DO NOT OPERATE SWITCH MANUALLY NOR PLACE A TRIPPER 4 HOURS PRIOR TO ON/CUTOUT TRIPPER SWITCHING.
• INCASEOFPOWERFAILURE, reset CLOCK-DIAL to proper time- of-day. See programming instructions.
158TS10958
MAX. LOAD
(AMP)
15 20 30 40
MIN. INSUL­ATION
TEMP(°C)
60
60
60
75
ON/CUTOUT
TRIPPER
DAY ARROW
SKIPPER WHEEL
SKIPPING SCREW
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
120 V. 240 V. 208 V.
2
1/2
2 1/2
1
3
2
5
-
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
N/A
WIRING
DIAGRAM
NEUT.
LINE 1 LINE 2
120/240 VOLT 3 WIRE SUPPLY
3 PHASE
240 V.
N/A
CLOCK MOTOR
A
1
2
3
4
TO LOAD(S)
GROUND
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE INSULATION CLEARS PRESSURE PLATE