NN07325
158—02143REF Rev 7/14/20
Page 2 of 2
Required Additional Materials: To maintain outdoor and liquid-tight
ratings, the Myers hub (conduit fitting) installed on the SPD should be
utilized in conjunction with the sealing washer and chase nipple provided.
The sealing washer is placed between the Myers hub and wall of the
panelboard or enclosure to which the SPD is to be installed. Further, it is
recommended that thread seal tape (aka “Teflon tape”) be used to wrap the
threads of the chase nipple before installation in addition to using the
sealing washer. If other conduit connections are used in place of the
provided hardware, follow the manufacturer’s instructions on maintaining a
liquid tight seal on the connections.
1. Inspect the unit to determine if the unit:
• has the correct nominal system and Maximum Continuous
Operating Voltage (MCOV) ratings and is the correct configuration for
the installation site. (See Table 1 for specifications), it is required that
the power system voltages be verified with the appropriate meter prior
to installation and those values confirmed to be lower than the MCOV.
Use Table 2 to record your readings and verify the recorded values are
lower than those listed in Table 1 for the unit.
• is NOT damaged, do not attempt to install if it is damaged. Obtain a
proper replacement before proceeding with the installation.
2. De-energize the electrical panel or equipment and follow the established
lockout / tagout procedures. Confirm the location is de-energized using the
appropriate test equipment before proceeding with the SPD installation.
3. Select a location on the panel or equipment that allows the SPD leads to
reach their intended connection points using the shortest possible lead
lengths. A dedicated multipole breaker is recommended.
4. Remove a knockout sized for, or make an appropriate sized hole for the
conduit hub where the SPD is to be mounted. For an outdoor or liquid-tight
installation, follow the instructions provided in the CAUTION statement
above.
5. Remove the chase nipple from the Myers hub attached to the SPD.
Mount the SPD to the panelboard or enclosure by routing the wires from
SPD though the sealing washer (if outdoor or liquid-tight installation is
needed) and then open knockout or hole into the panel. On the inside of the
panel or enclosure, route the wires though the threaded end of the chase
nipple. Thread the chase nipple into the Myers hub and tighten so that the
SPD is mechanically attached to the panel or enclosure. Be careful not to
damage the insulation of the wires during the mounting process. If the
sealing washer is used, be sure it is not damaged or displaced by the Myers
hub and it maintains a liquid-tight seal. The mounting feet provided with the
SPD can also be used to aid in mechanically mounting the SPD as
necessary.
6. Cut the leads to the shortest possible length to reach the connection
point (i.e. breaker or grounding bar). Trim the insulation of the leads so that
they can be connected appropriately (review manufacturer’s instructions for
terminating to the breaker or grounding bar as needed). The shorter the
SPD leads, the better the SPD will protection against surges.
7. Twist the phase conductors and avoid sharp bends (NEC Art 285.12).
Make electrical connections appropriate for the application (see Power
System Diagrams). If your electrical system is not represented in the circuit
diagrams, contact manufacturer. Tighten the electrical terminals to the
terminal manufacturer’s specifications.
8. Energize panel or equipment and verify the LED status indicator is ON
(Blue).
9. Option Package – P/N suffix DG2 - Connecting Dry (voltage free) Relay
Contacts
• NOTE: SPD is equipped with sets of colored 18 to 22 AWG wires.
Blue = Common, Orange = N/C, Yellow = N/O when power is applied.
(SPDT; Form C)
• Contacts are rated at ≤60 W/125 VA (from 30 VDC @ 2 A to 150
VDC @ 0.4 A), max. switched current = 2 A.
• Follow rules for NEC class 2 wiring when routing alarm leads. To
maintain NEMA-4X (IP65) rating use appropriate cable and liquid
tight strain relief if needed (user supplied)
• Connect alarm circuit(s) to Normally Open (N/O) or Normally
Closed (N/C) circuits as required.
• If not using these contacts, please cap off the wires with a UL
Listed wire nut.
Power System Diagrams Showing SPD Wire Colors