TRANSIENT SURGE SUPPRESSORS FOR
AC POWER PANEL APPLICATIONS
USER MANUAL
1449 2nd Edition
SG Modular Series
GGEENNEERRAALL
This document provides detailed information on how to install and operate the SG Modular Series of Surge Protective Devices (SPD).
Units should be mounted as close as possible
to the AC panel to be protected. It is recom-
mended that conduit, preferably metallic, be utilized to accomplish this connection. The SG Modular Series Protectors are installed and connected in parallel ("shunt") across the
AC supply to be protected. Connecting wires do not carry the supply current, only the short duration currents associated with the suppression of a transient event.
Identified or indicated terminals must be connected exactly
with respect to the AC Power feeding the SPD. Failure to do so may result in damage to the device or pose a danger to personnel.
Incorrect installation may significantly impair the performance of the Surge Protective Device. It is particularly important that all installation procedures and guidelines be followed exactly.
INSTALLATION OF THIS DEVICE SHOULD ONLY BE PERFORMED BY A QUALIFIED LICENSED ELECTRICIAN.
Before starting any installation procedures, verify service voltages with an AC Voltmeter to ensure that the correct SPD Model has been selected.
D
O NOT CONNECT WITHOUT SECURING POWER FROM THE DISTRIBUTION PANEL.
C
HECK TO ENSURE THAT ALL CONNECTIONS ARE CORRECT AND SECURE BEFORE ENERGIZING. DO
NOT ENERGIZE WITH DOOR OPEN.
K
EEP THIS MANUAL IN A SAFE DRY PLACE FOR FUTURE REFERENCE.
A.)
B.)
C.)
D.)
E.)
F.)
G.)
H.) I.)
J.)
After determining a position to mount the device that will minimize the length of the connecting wires, drill a hole in the cabinet for the conduit to run the wires from the distribution panel to the connecting lugs inside the SPD. Installation is simplified if the wires enter the enclosure at the top (see figure #2) of the enclosure. Securely mount the TVSS unit using 1/4-20 bolts in the four (4) mounting holes provided in the enclosure's mounting flanges.
CONSTRUCTION
14 Gauge steel with continuous hinge. UL 50 Type 12 and Type 13. NEMA/EEMAC Type 12 and Type 13. JIC standard #GP-1-1967. CSA Type 12. IEC 529, IP65.
[Figure #2: Cabinet Top View]
[Figure #1: Cabinet Front View]
10.00"
(254mm)
14.75"
(375mm)
15.50"
(394mm)
12.94"
(329mm)
3.00"
(76mm)
6"
(152mm)
MMOOUUNNTTIINNGG IINNFFOORRMMAATTIIOONN
((AALLLL MMOODDUULLAARR SSGG MMOODDEELLSS))
Page: 2
FINISH
ANSI 61 Gray polyester. Powder coating inside and out over phosphatized sufaces.
1.030"
(26.162mm) Dia.
APPLICATION or TECHNICAL ASSISTANCE
Contact Intermatic at 1-800-391-4555 or on the web at www.intermatic.com
Page: 3
Before starting the installation, measure the Line voltage with an AC voltmeter to ensure the correct device has been selected for the current application. The MCOV (maximum continuous operating voltage) Cannot
exceed the maximum limits for the following service voltages:
INSTALLATION INSTRUCTIONS
120/208Vac, Three Phase Wye, 4 Wire + Ground
277/480Vac, Three Phase Wye, 4 Wire + Ground
120/240Vac, Three Phase Delta, 4 Wire + Ground
240 or 480Vac, Three Phase Delta, 3 Wire + Ground
120 or 240Vac, Single Phase, 2 Wire + Ground
Requires a 1 Pole Breaker
Requires a 2 Pole Breaker
Requires a 3 Pole Breaker
120/240V
ac, Split Phase, 3 Wire + Ground
PHASE A NEUTRAL
GND
120 VAC
120 VAC
PHASE B
120 or 240 VAC
PHASE
NEUTRAL
GND
PHASE A
NEUTRAL
GND
PHASE B
PHASE C
120 or 277
VAC
208 or 480
VAC
PHASE A
PHASE B
PHASE C NEUTRAL
208
VAC
240
VAC
240
VAC
(High Leg) “Orange”
240 or 480
VAC
PHASE B
PHASE A
PHASE C
GND
GND
OR
240 or 480
VAC
240 or 480
VAC
208 or 480
VAC
120 or 277
VAC
120 or 277
VAC
208 or 480 VAC
Requires a 3 Pole Breaker
Requires a 3 Pole Breaker
[Figure #6]
[Figure #7]
[Figure #5]
[Figure #4]
[Figure #3]
STANDARD ELECTRICAL CONFIGURATIONS
120VAC=150MCOV 220VAC=320MCOV 230VAC=320MCOV
240VAC=320MCOV 277VAC=320MCOV 480VAC=550MCOV
NOTE
Wye Configuration is applicable for: 220/380VAC 230/400VAC 240/415VAC
120 VAC 120 VAC