Intermatic LH User Manual

Installation Instructions
CAUTION:
before installing any Surge Protection Device. All wiring should be done by a qualified electrician and comply with the National Electric Code and local electric codes.
Turn off power to the electric service or panel and to equipment to be protected
INSTALLA TION
2. Turn Power OFF.
3. Remove the knock out from the load center or equipment panel that will position the SPD for the shortest wire lead distance. Note that the shorter the lead length between the SPD and the load center, the better the protection.
4. Mount the SPD to the panel or an adjacent wall. If the mounting position prevents the direct connection of the offset nipple to the load center or equipment panel, a short piece of conduit must be used to comply with the national Electric Code.
5. For Flush Mount Panels, use the Intermatic Flush Mount Plate Model number IG1FMP-H. a) Use the template enclosed with the Flush Mount Plate to mark the wall. b) Cut and remove the marked wall section. c) Remove the four corner bolts from the cover of the SPD, do not remove the cover. d) Position the Flush Mount Plate over the cover of the SPD and replace the four bolts. e) Mount the SPD to the wall after completing step 6 below.
6. Twist or ty-wrap lead wires to eliminate any space or gaps between them. Pass the wires through the selected knockout and secure the SPD.
7. Cut each wire lead to the proper length. DO NOT coil extra wire length.
8. Connect the GREEN wire lead to the system ground.
9. Connect the WHITE wire lead to the system neutral bus. When a panel is the main panel, the neutral bus may be the same as the ground bus.
10. Connect each phase wire to a circuit breaker. Make sure that the phase wires have the correct voltage level between them. Note that for the 240 volt High Leg Delta, the wire for the High Leg is colored RED, and must be connected to the leg that measures approximately 208 volts to neutral and to ground. Failure to comply with this instruction will result in failure of the SPD and void the warranty.
11. Check all connections for proper tightness or torque. Suggested torque values are published by the circuit breaker manufacturer.
12. Turn Power on.
13. Make sure that each indicator on the SPD is ON. If not, turn power off and recheck each installation step listed above.
14. For troubleshooting assistance, call Intermatic at 815-675-7000 and ask for Technical Support.
INSTALLATION NOTE:
The cover of the SPD may be rotated 180 Carefully remove the four corner bolt s , r otate the cover and reinstall the bolts. Care must be exercised t o prevent damage to the wire leads to the LED indicators.
degrees if the device must be installed in an inverted posit ion.
Commercial / Industri al Hardwire d
Surge Protection Devices
WIRING CONFIGURATIONS
Transformer
NOTE: All ‘LH’ units must be installed downstream from breaker or fuse of 400 amps or less capacity. A 30-amp breaker is recommended as a convenient connection point when installing on a breaker panel.
120 volt Single Phase
Transformer
Secondary
Load
Center
L1
N
G
Use 30 amp Breakers
Black/Negro Noir
White/Blanco Blanc
Green/Verde Vert
Model IG1201LH
120/240 volt Single (Split) Phase
Load
Transformer
Secondary
Center
L1
L2
N G
Use 30 amp Breakers
Black/Negro
Noir
Black/Negro
Noir
White/Blanco
Blanc
Green/Verde
Vert
Model IG2401LH
120/208 volt Three Phase WYE
Secondary
Load
Center
L1 L2
L3
N G
Use 30 amp Breakers
Black/Negro
Noir
Black/Negro
Noir
Black/Negro
Noir
White/Blanco
Blanc
Green/Verde
Vert
Model IG2083LYH
CONFIGURATION VOLTAGE
Line to Neutral 120 Line to Ground 120
CONFIGURATION VOLTAGE
Line to Line 240 Line to Neutral 120 Line to Ground 120
CONFIGURATION VOLTAGE
Line to Line 208 Line to Neutral 120 Line to Ground 120
L3
Secondary
120/240 volt Three Phase Delta High Leg Delta
Transformer Secondary
Load
Center
L1
L2
L3
N
G
Use 30 amp Breakers
Black/Negro
Noir
Red/Rojo
Rouge
Black/Negro
Noir
White/Blanco
Blanc
Green/Verde
Vert
Model IG2403LDH
277/480 volt Three Phase WYE
Transformer
Load
Center
L1 L2
N G
Use 30 amp Breakers
Black/Negro
Noir
Black/Negro
Noir
Black/Negro
Noir
White/Blanco
Blanc
Green/Verde
Vert
Model IG4803LYH
480 volt Three Phase DELTA
Transformer Secondary
Load
Center
L1
L2
L3
G
Use 30 amp Breakers
Black/Negro
Noir
Black/Negro
Noir
Black/Negro
Noir
Green/Verde
Vert
Model IG4803LDH
CONFIGURATION VOLTAGE
Line to Line 240 Line to Neutral 120 High Leg to Neutral 208 Line to Ground 120 High Leg to Ground 208
CONFIGURATION VOLTAGE
Line to Line 480 Line to Neutral 277 Line to Ground 277
CONFIGURATION VOLTAGE
Line to Line 480 Line to Ground 480
Contact your Intermatic Representative or Distributor for information on other hardwired panel Surge Protection Devices. Discover the convenience of integral fusing and the versatility of replaceable protection modules in Intermatic’s full line of Surge Protection Devices.
TEN YEAR LIMITED PRODUCT WARRANTY
For
®
INTERMATIC
HARDWIRED SURGE PROTECTION DEVICES
(1) What Is Covered By This Limited Warranty
Repair or Replacement of Product
Intermatic Incorporated ("Intermatic") warrants to the original purchaser only, Intermatic models IG1201LH, IG2401LH, IG2083LYH, IG2403LDH, IG4803LYH, IG4803LDH or IG1201EH, IG2401EH, IG2083YEH, IG2403DEH, IG4803YEH, IG4803DEH Surge Protection Devices (each a “Product”) shall be free from defects in material or workmanship for a period of ten
years (120 months) from date of purchase or 126 months from date of manufacture. If the purchaser discovers a defect in material or workmanship, the purchaser must promptly submit a warranty claim. Upon a determination by Intermatic that the Product is defective, Intermatic, at its sole option, shall correct any defect in material or workmanship by either repairing or replacing the Defective Product. Any repair, including both parts and labor, shall be at Intermatic’s expense. The foregoing remedies are the purchaser’s exclusive remedies for a breach of warranty.
For purposes of this Limited Warranty, a Power Transient shall mean over-voltage resulting from momentary voltage spikes or surges on an AC power line of magnitude that the Product, according to its specifications, is designed to stop b efore such spikes or surges affect downstream equipment.
The Product must be installed in the appropriate application in complete accordance with th e installation instructions. All buildi ng wiring and other connections to the Product must conform to all applicable national, state and local electrical codes; the Product must not be opened, modified, exposed to extreme heat or cold, submerged or subjected to abnormal use or service. All products must be used in accordance with the instructions provided with the Product and the purchaser shall be solely responsible for selecting a Product model with specifications appropriate for the equipment to be protected. Intermatic shall determine, in its sole discretion, whether any Product returned by a purchaser has been used in accordance with its instructions, is an appropriate model for the purchaser's use thereof, and whether the Product is defective.
(2) What Is Not Covered By This Warranty
Intermatic does not warrant (a) defects in the Product or damage to any equipment caused by the failure to properly install the Product, (b) damage caused by use of the Product for purposes other than those for which it was designed, (c) damage caused by disaster such as fire, flood and wind, (d) damage caused by unauthorized attachments or modification of the Product, (e) damage to the Product occurring during shipment, or (f) electrical disturbances exceeding published product specifications, (g) damage to the Product caused by any other abuse or misuse by the purchaser.
(3) Disclaimer of Warranty
THE FOREGOING WARRANTIES ARE IN LIEU OF ALL OTHER EXPRESSED WARRANTIES. TO THE EXTENT ALLOWED BY LAW, ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE LIMITED IN DURATION TO THE DURATION OF THIS LIMITED WARRANTY.
(4) Limitation of Remedies
IN NO CASE SHALL INTERMATIC BE LIABLE FOR ANY SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES BASED UPON BREACH OF WARRANTY, BREACH OF CONTRACT, NEGLIGENCE, STRICT TORT, OR ANY OTHER LEGAL THEORY. SUCH EXCLUDED DAMAGES INCLUDE, BUT ARE NOT LIMITED TO, DAMAGE TO SOFTWARE, LOSS OF DATA, LOSS OF PROFITS, LOSS OF SAVINGS OR REVENUE, LOSS OF USE OF THE PRODUCT OR ANY ASSOCIATED EQUIPMENT, COST OF CAPITAL, COST OF ANY SUBSTITUTE EQUIPMENT, FACILITIES OR SERVICES, DOWNTIME, THE CLAIMS OF THIRD PARTIES INCLUDING CUSTOME RS, DAMAGE TO PROPERTY AND PERSONAL INJURY. SOME STATES DO NOT ALLOW LIMITS ON WARRANTIES OR ON REMEDIES FOR BREACH IN CERTAIN TRANSACTIONS. IN SUCH STATES, THE LIMI TS IN THIS PARAGRAPH AND IN PARAGRAPH (3) MAY NOT APPLY.
(5) Time Limit for Bringing Suit
No action arising out of any claimed breach of warranty may be brought more than one year after the cause of action has occurred.
(6) No Other Warranties
Unless modified in writing signed by both parties, this agreement is understood to be the complete and exclusive agreement between the parties, superseding all prior agreements, oral or written, and all other communications between the parties relating to the subject matter of this agreement. No employee of Intermatic or any other party is authorized to make any warranty in addition to those made in this agreement.