Description
The SI-ID is a single input device that allows you to connect a
single non-addressable device to the PinPoint system. The
system provides flexible and reliable two-way communication
between the device and the controller.
Installation
1. Remove the lid to open the unit (Figure 1).
CAUTION You must be free of static electricity before
2. Set the PinPoint address DIP switches (Figure 2). Devices
are shipped with DIP switches set to 255. This is an invalid
address. The device will no communicate with the controller
until a valid address has been set. Refer to the controller’s
manual to determine the correct address setting for each
unit.
3. Remove the wiring knockouts (Figure 3) most convenient
for your installation.
4. Pull the PinPoint wiring through the wiring holes
5. Mount the unit by either using a standard double gang
receptacle box or using two #6 screws to mount the unit
through the wall mounting holes (Figure 3) directly to the
wall.
6. Strip 1/4 inch (6.4 mm) of insulation from the PinPoint
wires. Connect the wires to the appropriate screw terminals
(Figure 4) and tighten the screws.
7. Replace the lid and screw the unit together (Figure 1).
handling sensor circuit boards. Touch a
grounded, bare metal surface before
touching circuit boards or wear a grounding
strap.
Figure 1. Exploded view
Lid
Circuit board
Base
Figure 2. Circuit board
Figure 3. Wiring diagram
ON APEM
1 2 3 4 5 6 7 8
DIP switches
Terminal blocks
Figure 4. Wiring
47K EOL
47K EOL
T amper contact
Wiring knockouts
Wall mounting
hole
European double EOL configuration
COM IN + - + - COM IN + - + -
PinPoint bus PinPoint bus +
PinPoint bus PinPoint bus +
Out
In
47K EOL
Normally closed contact with EOL resistor
Wall mounting
hole
PinPoint bus PinPoint bus +
PinPoint bus PinPoint bus +
Out
In
SI-ID
2
Installation Instructions
Specifications
Housing material Flame retardant ABS
Operating voltage 8 to 27 VDC (as supplied by the panel)
Signaling voltage 4 to 9 V
Current draw 250mA
Signaling current 20mA
Operating temperature 32 to 131°F (0 to 55°C)
Relative humidity 10 to 90% non-condensing
Maximum line length 10,000 feet (3 km)
Dimensions:
Width 3.3 in. (8.4 cm)
Depth 1.3 in. (3.3 cm)
Height 2.8 in. (7.1 cm)
Color White
Listings UL 365, UL 609, UL 985, UL 1023, UL
1610, FCC, CE
Inputs:t
Input loop resistance Reported to panel
(47K EOL included)
> 1Meg Ohm Open
47K ± 5% Single EOL
94K ± 5% Double EOL
< 20 Ohm Short
FCC compliance
This device complies with Part 15 of the FCC rules. Operation is subject
to the following two conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including
interferences tha may cause undesired operation.
Product orderingt Description
Product Description
SI-ID Addressable single input interface that
allows you to connect a single nonaddressable device to the PinPoint bus.
12345 SW Leveton Drive
GE Security
Tualatin, OR 97062
503-692-4052
USA & Canada: 800-547-2556
Tech Support: 800-648-7424
www.ge-security.com
1036046C / September 2004