Interlogix 741UT Specsheet

Conventional Initiating Devices
Two- and Four-Wire Head & Terminal Base Smoke Detectors
700 Series

Overview

The FireworX 700 Series conventional photoelectric smoke detec­tor is an interchangeable head and base detector with a light­scattering optical sensor that provides outstanding stability and excellent response to a wide range of fires.
A pulsed infrared LED light source and a high-speed photodiode sensing element are housed in an omnidirectional sensing cham­ber protected by an insect screen. For easy cleaning, the detector features a field-replaceable optical chamber.
Model 721UT and 741UT photoelectric detectors include integral fixed temperature and rate-of-rise heat detectors. Also available is the 713-5U electronic heat detector head for areas too dusty for smoke detection.
FireworX 700 Series smoke detectors were the industry’s first conventional self-diagnostic detectors specifically designed for the demands of commercial and industrial environments. If the detector drifts out of its UL Listed sensitivity range or fails internal diagnostics, the alarm LED flashes once a second to indicate a trouble condition. This meets NFPA 72 field sensitivity testing requirements without the need for external meters.
Additional diagnostic information is activated by applying a magnet near the detector’s integral reed switch. This initiates a self-diag nostic routine and provides visual indication of sensitivity level, or if service is required. The magnet test causes the LED to blink. The number of blink counts corresponds to a smoke detector sensitivity range.
And, if they become dirty over time, the 700 Series detectors automatically adjust the alarm threshold through built-in drift com­pensation. If the detector ever does need to be cleaned, the pat­ented field replaceable optical chamber makes cleaning a snap.

Standard Features

• Self-diagnostic capabililty continually monitors operation
• Meets NFPA 72 sensitivity test requirements
• Head and terminal base design (base sold separately)
• Automatic drift compensation
• Field-replaceable optical chamber
• Low-profile design blends into the ceiling
• Advanced alarm verification nuisance alarm immunity
• Continuity switch in base to ease installation
• Extensive two-wire compatibility listings
Engineering Specifications
The FireworX 700 Series photoelectric smoke detector, is a low­profile, self-diagnostic, two-wire or four-wire detector that moni­tors its own sensitivity and operational status. The detector meets NFPA 72 field sensitivity testing requirements without the need for external meters. Built-in drift compensation automatically adjust the sensitivity if the detector gets dirty. The 700 Series features an alarm verification feature to further reduce the chance of a nuisance alarm. Normal sensing occurs every 9 seconds. This rate doubles when a signal exceeding the alarm threshold value is sensed. Two additional successive signals above the threshold level initiate an alarm. The patented optical sensing chamber is field replaceable, allowing quick and easy cleaning and maintenance.
A manually operated switch between terminals 1 and 2 establishes continuity across the alarm initiating circuit at initial installation of the base simplifying testing without the smoke head in place. The switch automatically opens when a detector head is plugged in.
Page 1 of 2 D A T A S H E E T FX85001-0598
No t to be used for i nst allat ion p urp oses. Issue 2.1
interlogix.com
North America
T 885-286-8889
Technical Specifications
Electrical
Voltage 8.5 — 33VDC, non polarity sensitive Maximum ripple (peak to peak) 10% (Vp - p) Typical standby current (24V) 70μA Typical alarm current (24V) up to 60 mA max, if not limited by control panel Relay contacts 2A @ 30VDC, 1A @ 120 VAC Photoelectric Sensitivity 2.85%, + 0.37, – 1.00% Operating temperature 32°F to 120°F (0°C to 49°C) Operating humidity range 0 to 95% Non-condensing RFI immunity 20 V/m min; 0-1000 MHz Remote LED output current 5 mA min, 8.5 mA max Drift compensation adjustment 1.0%/ft. max
Environmental
Heat Sensor Ratings (721UT, 741UT, 713-5U)
Maximum wind velocity 300 ft/min or Field wiring size 12-18 AWG Remote test input (721UT) 100 ohm max Reset voltage 2.5V max Reset time 1 second max UL two-wire compatibility
identifier
Physical
Color White head and base Detector head dimensions 4” D x 1.75” H (10 cm x 4.44 cm) Base dimensions 701U, 702U: 6” D x .06” H (15.24 cm x 1.3 cm) Total height, (head and base) 1.98” (5 cm) H
Regulations
Listing UL 268, FM, CSFM, MEA approved
Fixed 135°F/ Rate of rise 15°F/min., >105°F (8.3°C/min., >40.6°C)
S10A (711U, 721UT, 713-5U) S11A (731U)
Asia
T 852-2907-8108 F 852-2142-5063
Australia
T 61-3-9239-1200 F 61-3-9239-1299
Europe
T 32-2-725-11-20 F 32-2-721-40-47
Latin America
T 561-998-6100 F 561-994-6572
interlogix.com
Specifications subject to change without notice.
© 2012 Interlogix. All rights reserved.

Ordering Information

711U Smoke detector head only, photoelectric, two-wire 721UT Smoke detector head only, photoelectric, two-wire
w/integral heat, output for remote LED
731U Smoke detector head only, photoelectric, two-wire,
use 702RU base for aux. relay functionality 741U Smoke detector head only, photoelectric, four-wire 701U Smoke detector base, 3 terminals, 6” dia. 702U Smoke detector base, 6 terminals, 6” dia. 702RU Smoke detector base, 6 terminals, aux. relay, 6” dia.
Compatibility
Heads Bases
711U 701U, 702E, 702U
731U 702RU
741U 702U
713-5U 701U
Note: Bases sold separately
05-31-12
Page 2 of 2 D A T A S H E E T FX85001-0598