Interlogix 600-1070 User Manual

Concord LCD Keypad with 2-Way Voice
Current (mA)
Conditions
110
Maximum alarm current with the buzzer sounding and the keypad illuminated from a button press
60
Typical operation
23
Power saving mode (no panel AC power)
Wire gauge (unshielded or shielded)
Max. keypad wire length between keypad and panel
18
750 feet
22
300 feet
Wire gauge (unshielded or shielded)
Max. keypad zone wire length between keypad and sensor
22
100 feet
Hardwire zone End of Line (EOL) resistor should be 2K ohm.
Installation Sheet
Description
The Concord LCD Keypad with 2-Way Voice provides control of all programming and operation of compatible security systems.
A supervised hardwire zone provides an additional zone without added wiring to the panel. Opening the removable swing-down door reveals a label with basic system operating commands.
* Not UL approved as a primary annunciator. Not investigated for use as two-way verification.
Tools and Equipment needed
4-conductor, 18- or 22-gauge wire
#2 Phillips screwdriver
#6 screws and anchors (included)
Screws for gang box installation
The hardwire zone is intended for use with intrusion
sensors only. This zone input does not provide power for sensors such as PIRs, fire detectors, etc.
Up to 16 keypads can be installed on a Concord 4 system of which a maximum of two can be connected to two-way audio or a single keypad plus an audio verification module.
Table 1: Keypad Power Usage
Table 2: Maximum SuperBus and Audio Wire Lengths
Note: Interlogix recommends using shielded cable to prevent
crosstalk between the speaker and microphone.
Table 3: Maximum Hardwire Zone Wire Lengths
Saw or utility knife for cutting wallboard
Installation
Installation Guidelines
Mount the keypad in an environmentally controlled area (32°F to 120°F/0°C to 49°C).
When mounting the keypad, allow at least 6 inches below it for the swing-down cover.
When connecting two-way voice to the keypad, any additional speaker devices on the system should be connected in parallel with the keypad speaker connection. Note: Siren volume will be reduced if connected in series.
This information differs from the information listed in the Concord 4 Installation Manual.
Do not exceed the maximum available power given in the panel installation instructions.
P/N 466-4434 • REV H 13FEB15 1 / 9
Installing the Mounting Plate
1. Place the keypad on a flat surface so that the mounting plate is facing as shown in Figure 1 on page 2.
2. Remove the mounting plate from the keypad as described in Figure 1 on page 2.
Figure 1: Removing Mounting Plate From Keypad
3. Place the mounting plate on the wall and mark the primary and tamper mounting holes, making sure to leave a 6 inch clearance below the keypad for the door to open. See Figure 2 below.
Note: Gang box mounting screws are not provided with
this keypad.
4. Insert anchors into the wall at the marked locations where studs are not present.
5. Align the mounting plate over the selected mounting locations and secure the back plate using the screws provided.
Note: Do not over tighten screws or the mounting plate
may bind and prevent the keypad from mounting properly.
Figure 2: Marking the Mounting Holes
To enable the tamper function:
1. Remove the two small flathead screws that attach the terminal block plate to the mounting plate.
2. Mount according to the process above.
Note: Tamper screws must be installed into a stud.
Wiring the Keypad
CAUTION: Use static electricity precautions when
handling electronic components. Utiliser les précautions de l'électricite statique lors de la manipulation des composants électroniques.
1. Remove the panel AC and backup battery power.
2. Run wires (18- or 22-gauge) from the panel and sensor to the keypad location.
4-conductor (no 2-way voice) between panel and
keypad
8-conductor (with 2-way voice) between panel and
keypad
Note: Interlogix recommends using shielded cable to
prevent crosstalk between the speaker and microphone.
2-conductor (to sensor) between keypad and hardwire
sensor (if installed)
3. When routing the wires, route all wiring connections from the access area directly to the terminal, keeping wires short and flat. No loops of wire should run outside the access area.
Note: Do not run any excess wire outside the access area as it will make the assembly of the keypad onto the mounting plate difficult.
6. Cut a hole in the wall at the wire access area of the mounting plate to pull the wiring cable through.
Optional Tamper Mounting
Note: Tamper mounting hardware is not supplied with this
product.
Wiring the Keypad – SB2000
1. Pull the ground, +12 volt and bus wires through the access area.
2. Connect the Bus to the 9 position terminal block as shown in Figure 3 below.
Figure 3: Connecting the Keypad
Note: For bus wire length over 150 feet, a 120 ohm
termination resistor is needed across A to B at the panel.
2 / 9 Concord LCD Keypad with 2-Way Voice Installation Sheet
Wiring the Keypad – Speaker and Microphone
1. Pull the speaker and microphone wires through the access area.
2. Connect the speaker and microphone wires to the 9 position terminal block as shown in Figure 4 below, Figure 5 below and Figure 6 below.
3. If other audio devices will be installed on the system, wire accordingly as shown in the following diagrams.
Note (1): Interlogix recommends using shielded cable to prevent crosstalk between the speaker and microphone.
Note(2): The keypad is not UL approved as a primary
annunciator.
Note(3): Installations requiring an AVM in addition to the
Keypad Audio require the addition of a 10 K ohm resistor (included) on the MIC wire of the AVM to equalize the MIC performance of both devices.
Figure 4: Keypad to Audio Diagram (keypad only)
Figure 6: Keypad to Audio Diagram (with Audio Verification Module)
Wiring the Keypad – Hardwire Zone
1. Pull the hardwire zone wires through the access area.
2. Connect the hardwire zone wires to the 9 position terminal block as shown in Figure 7 below.
3. Insert the end-of-line (EOL) resistor at the last device in the loop. See Figure 7 below. Note: The EOL resistor must be located at the last device in the loop.
4. Use a maximum of five contacts.
Figure 5: Keypad to Audio Diagram (multiple speakers)
Note: The keypad does not supply power for sensors.
Sensor Zones must be of the normally open or closed contact type.
Figure 7: Hardwire Zone
Concord LCD Keypad with 2-Way Voice Installation Sheet 3 / 9
External Contact Wiring
Normally closed
Normally open
Short = Tamper
Open = Tamper
2K ohm = Normal
Short = Alarm
Open = Alarm
2K ohm = Normal
Key
Function
Scroll through available options at current menu tier
Enter pauses when programming telephone numbers (no end user function)
Delete certain program settings Also used as Quick Exit key for end-user
Table 4: External switches
Note: A bus failure will result in a zone trouble condition.
Attaching the Keypad to the Mounting Plate
1. Align the right side of the keypad over the hooks on the mounting plate. See Figure 8 below.
2. Swing the left side of the keypad over the latches on the mounting plate, until the latches snap into place. See Figure 8 below.
Figure 8: Attaching the Keypad to the Mounting Plate
Figure 9: Function Key Decals
Please refer to Table 5 below or to the specific panel installation/user manual for more information on when specific key presses are required.
Note: The Auxiliary Alarm Key is not evaluated for and not to be used for UL 1637 (medical) applications.
Note: To remove, depress both latches on the left side
and then swing the left side of keypad away from the wall, removing the keypad from the hooks.
Applying Decals
A set of decals is included with the keypad for labeling the function keys. For Concord 4, the function keys are programmed: Fire (F1), Auxiliary (F2) and Police (F3).
Carefully apply the function key decals (as needed) on the keypad as shown in Figure 9 below.
Table 5: Key Functions
Power up and Bus Communication
Follow the steps below for powering up the panel and for verifying that the keypad and the panel are properly communicating with each other.
Note: Upon power up, the panel scans the bus for connected devices, assigns a unit number to each bus device, and automatically learns the device ID number of each bus device.
1. Verify that all wiring between the panel and keypad is correct.
2. Connect the panel battery and restore AC power. Alphanumeric keypads briefly show SCANNING BUS DEVICES, then displays date and time.
4 / 9 Concord LCD Keypad with 2-Way Voice Installation Sheet
Optional (steps 1 through 7)
1. At the keypad, enter program mode by pressing 8 + installer/dealer code (default = 4321) + 0 + 0. The keypad should display SYSTEM PROGRAMMING.
2. Press . The display should show SECURITY.
3. Press or until the display shows ACCESSORY MODULES, then press . The display should show BUS DEVICES.
4. Press . The display shows the lowest device address and its ID. The following example shows what a device address display may look like:
UNIT - ID 002110185*
*The 8-digit SuperBus ID number is also located on a label on the back of the keypad.
5. Press or to cycle through all bus device addresses until the keypad appears.
6. After verifying the keypad device ID, press repeatedly until the display shows SYSTEM PROGRAMMING.
7. Press or until the display shows EXIT PROGRAMMING READY, then press . The keypad should show the date and time display.
Figure 10: Connecting a Programming KeypadConcord 4
2. Activate the keypad by pressing + installer/dealer CODE + + .
Programming
To program options for the newly installed keypad (such as key beeps) see the specific panel Installation Instructions.
Connecting the Keypad for System Programming Only
For installations that don’t include an alphanumeric keypad as
a permanent part of the system, connect one for system programming to the Programming Keypad Header on the panel.
To do this, first connect a Programming Keypad Cable (60-
791) to the keypad wires. See the Programming Keypad Cable Installation Instructions (P/N 466-1604), included with the cable). Then, use the appropriate procedure for connecting the keypad.
To connect a programming keypad to a Concord 4 panel:
1. With the panel powered up, connect the cable to the Programming Keypad Header Pins. See Figure 10 below.
3. Enter program mode by pressing + installer/dealer CODE + + and program the panel using the panel Installation Instructions.
4. When programming is completed, disconnect the programming keypad.
Testing
Note: Contact the central monitoring station before activating
alarms to avoid dispatching local police and fire departments. Test the keypad by arming/disarming the system, activating the
keypad panics, bypassing sensors, and by turning chime and lights on/off to verify correct operation. Refer to the panel User’s Manual for complete system operating instructions.
Adjusting Display Brightness
The keypad display can be adjusted for easier viewing to help compensate for lighting conditions in the keypad location.
The brightness adjustment lightens or darkens the background. To adjust display brightness:
1. Enter user programming mode by pressing 9 + user, partition, or system master CODE. The display shows SYSTEM MENU, then TIME AND DATE.
2. Press until the display shows OPTIONS, then press . The display should show DOWNLOADING ON/OFF (current setting).
3. Press twice. The display should show KEYPAD BRIGHTNESS 2 (default setting).
4. Enter a setting from 0 (darkest background) to 3 (brightest background), then press .
5. The display flashes the entered selection, then stops after pressing and displays the new setting and brightness level.
Concord LCD Keypad with 2-Way Voice Installation Sheet 5 / 9
6. Exit user programming mode.
LED
System status
Solid blue (while backlights are on)
System is disarmed, status is normal
Solid red (while backlights are on)
System armed
Flashing red
System is in alarm
Flashing blue
System is disarmed, trouble or alarm condition present (for example protest, low battery, supervisory, bus trouble, tamper, open zone, etc.)
Problem
Action/Solution
Keypad doesn’t power
up (no display and no beeps when keys are pressed).
Check for correct wiring connections at keypad and panel terminals.
Make sure panel battery is connected correctly and that the panel transformer is plugged in.
Make sure panel transformer is not plugged into an electrical outlet controlled by a switch. Relocate transformer to an unswitched outlet location, if necessary.
Keypad status blue LED is flashing and a trouble star is displayed on the LCD indicating a trouble condition and system
doesn’t respond to
commands from keypad.
Check for correct bus wiring connections (green and white wires) at keypad and panel terminals.
No sound coming from speakers
Check for correct wiring connections at keypad and panel terminals.
Compatibility
Concord 4
Power requirements
12 VDC nominal
Current - 110 mA
Maximum alarm current
Current - 60 mA
Typical operation
Current - 23 mA
Power saving mode (no panel AC power)
Operating temperature
32° to 120°F (0° to 49°C)
Storage temperature
-4° to 140°F (-20° to 60°C)
Humidity
95% relative, non-condensing
Dimensions
5.32” x 6.03 x .092” (L x W x D)
Manufacturer
UTC Fire & Security Americas Corporation, Inc. 1275 Red Fox Rd., Arden Hills, MN 55112-6943, USA
UL listings
UL 985 Household Fire Warning System Units UL 1023 Household Burglar-Alarm System Units UL1610 Central Station Burglar-Alarm Units
(Commercial Burglary) Note: See specific panel Installation Instructions
for complete UL installation requirements. Not investigated by UL for use as a medical alert.
Status LEDs
The keypad has LEDs that indicate the current system status at a glance. Table 6 below explains LED behavior.
Table 6: Status LEDs
Note: Solid status LEDs display only when a key is pressed or
backlighting is on. Flashing LEDs remain flashing until the fault or alarm condition is cleared.
Door and Hinge Removal
1. Remove the keypad from the mounting plate.
2. Using a screwdriver, back out the hinge retainer screws 1/8”. See Figure 11.
Troubleshooting
Specifications
3. Remove the door and hinges.
Note: Per SIA CP-01 2010 requirements, the door must remain attached and closed during normal operation.
Figure 11: Door and Hinge Removal
Regulatory Information
6 / 9 Concord LCD Keypad with 2-Way Voice Installation Sheet
FCC compliance
FCC Part 15 Information to the User
Changes or modifications not expressly approved
by Interlogix can void the user’s authority to
operate the equipment.
FCC Part 15 Class B
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against interference in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the
equipment and receiver.
Connect the affected equipment and the panel receiver to separate outlets, on different branch circuits.
Consult the dealer or an experienced radio/TV technician for help.
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
L’utilisation de ce dispositif est autorisée seulement aux conditions suivantes : (1) il ne doit pasproduire de brouillage et (2) l’utilisateur du dispositif doit être prêt à accepter tout brouillage radioélectrique reçu, même si ce brouillage est susceptible de compromettre le fonctionnement du dispositif.
Contact Information
For general information, see www.interlogix.com. For customer/technical support, see www.interlogix.com/customer-
support or call +1 855 286 8889.
© 2015 United Technologies Corporation. Interlogix is part of UTC Building and Industrial Systems, a unit of United Technologies Corporation. All rights reserved.
Limitation of Liability
To the maximum extent permitted by applicable law, in no event will Interlogix be liable for any lost profits or business opportunities, loss of use, business interruption, loss of data, or any other indirect, special, incidental, or consequential
Concord LCD Keypad with 2-Way Voice Installation Sheet 7 / 9
damages under any theory of liability, whether based in contract, tort, negligence, product liability, or otherwise. Because some jurisdictions do not allow the exclusion or limitation of liability for consequential or incidental damages the preceding limitation may not apply to you. In any event the total liability of Interlogix shall not exceed the purchase price of the product. The foregoing limitation will apply to the maximum extent permitted by applicable law, regardless of whether Interlogix has been advised of the possibility of such damages and regardless of whether any remedy fails of its essential purpose.
Installation in accordance with this manual, applicable codes, and the instructions of the authority having jurisdiction is mandatory.
While every precaution has been taken during the preparation of this manual to ensure the accuracy of its contents, Interlogix assumes no responsibility for errors or omissions.
Installer: Please provide this page to the end user.
8 / 9 Concord LCD Keypad with 2-Way Voice Installation Sheet
Concord LCD Keypad with 2-Way Voice Installation Sheet 9 / 9
Loading...