Integra EPRO-31 10K, EPRO-31 20K, EPRO-31 30K, EPRO-33 10K, EPRO-33 20K User Manual

...
USER MANUAL
EPRO-31 10K / 20K / 30K
ONLINE-DOUBLE CONVERSION UPS
ENGLISH
Technical information on this manual is property of INTEGRA
partially without written approval of INTEGRA.
INTEGRA can introduce modifications in their products or manuals without further notice. . INTEGRA is not responsible of mistakes or missing information in this manual. INTEGRA is not responsible for wrong use a third part can do of this information. Trademarks and logos in this manual are property of their owners.
.
This manual Information cannot be copied or distributed totally or
Xmart EPRO-31 10K / 20K
USER MANUAL - EPRO-31 10K / 20K / 30K
TABLE OF CONTENTS
1. SAFETY
2. AVAILABLE MODELS
3.- UPS INSTALLATION: SITE PLANING
SITE INSPECTION & INSTALLATION CONDITIONS TOWER UPS INSTALLATION EXTERNAL CIRCUIT BREAKERS & WIRING SELECTION
4.- UPS INSTALLATION: SINGLE UPS - TERMINAL BLOCK
UPS AC LINES CONFIGURATION AC TERMINAL BLOCKS EXTERNAL BATTERY CONNECTION
5.- UPS INSTALLATION: PARALLEL UPS - TERMINAL BLOCK
GENERAL COMMENTS UPS AC LINES CONNECTION PARALLEL CONTROL CABLES CONNECTION
6.- START-UP: SINGLE UPS
INSPECTION BEFORE START-UP SINGLE UPS - START UP PROCEDURE
7.- START-UP: PARALLEL UPS
REQUIREMENTS FOR PARALLEL UPS SYSTEMS INSPECTION BEFORE START-UP PARALLL UPS - START UP PROCEDURE
8.- OPERATION INTERFACE
FRONT PÀNEL: PUSH BUTTONS / LEDS / LCD
9.- OPERATION: SINGLE UPS
10.- OPERATION: PARALLEL UPS
REMOVING UPS FROM PARALLEL SYSTEM ADDING UPS TO PARALLEL SYSTEM
11.- UPS CONFIGUIRATION
12.- ERROR CODES, ALARMS & TROUBLESHOOTING
13.- TECHNICAL SPECIFICATIONS
14.- LIMITED WARRANTY
www.integra-ups.com 130805-EPRO-31 10K/20K/30K (ENGLISH) - 0
USER MANUAL - EPRO-31 10K / 20K / 30K
1. GENERAL SAFETY INSTRUCTIONS
WARNING: It is required to read and understand this manual. Follow all instructions given in this manual for starting up and
operating this product. Only qualified technician must start-up, operate and maintain this product. Keep manuals as a guide for
future consults. WARNING: This product operates with dangerous voltages. It must be installed, operated and maintained ONLY by qualified
technicians trained for this kind of products. Service personnel MUST know and understand very well all electric risks related to
this product. UPS manufacturer or distributor will never be responsible for any accident produced by lack of knowledge or
negligent practices at the moment of install, starting up or maintain this product.
UPS manufacturer or distributor is not liable for any damage that might rise from misusing this unit or defective installation.
WARNING: If you are not qualified technician do not try to install, operate or repair this product. WARNING: Do not try to install, operate or repair this product if you are not accompanied by another qualified person able to offer first aid support in case of emergency or accidents. WARNING: Internal area of this product is locked by screws. Do not try to access inside the UPS unless you are a qualified
technician. UPS must be checked, repaired and maintained by qualified personnel only.
CAUTION!!: ELECTRIC SHOCK RISK CAUTION: There are dangerous voltages in the UPS power outlets although the equipment is not plugged to power line. CAUTION: Inside this equipment, due to internal batteries, there are ALWAYS dangerous voltages, thought the UPS is OFF and
unplugged of power line. CAUTION: There are dangerous voltages in DC (Direct Current) Capacitors. Please Check Capacitor location in Figure 8.4.1. Wait
at least 10 minutes after turning off UPS before opening it to access inside.
DANGER: Power off UPS and unplugged it from AC Line before opening it to Access inside this unit. CAUTION: Before star ting the opening procedure, remove all jewelry and metallic objects such as: Rings, Watches, Bracelets,
etc., because they could contact conductive parts and components inside the UPS and this might cause discharges and/or short
circuits. Make sure using tools properly isolated to avoid electrical risks.
Transportation and Storage: Warnings and Recommendations
WARNING: This UPS must be transported only in its original package to be properly protected WARNING: This equipment must be storage in dry and ventilated site, in upright position. WARNING: Before storage this UPS, batteries must be recharged for 8 to 10 hours WARNING: During long term storage UPS must be recharged periodically according to this manual.
www.integra-ups.com 130805-EPRO-31 10K/20K/30K (ENGLISH) - 1
USER MANUAL - EPRO-31 10K / 20K / 30K
WARNING: EQUIPMENT DISPOSAL
Out of service units: It is strongly recommended to dispose this piece of equipment according to valid directives in your
country. At the moment of disposing all pieces need to be managed appropriately to avoid possible environmental damage or for some materials to be recycled.
Batteries : Do not throw it to fire (risk of explosion). Do not open the batteries, there are dangerous liquids inside
WARNING: BATTERIES MAINTENANCE
Batteries capacity, in general (of all kinds), decrease with time and use.
Our products contain high quality batteries only.
Batteries useful life in our UPS is between 4 and 5 years, considering environment temperature under 25 ºC and optimal
operational conditions. This time can be dramatically reduced by high temperature and other adverse operation condition.
Batteries life expectancy may be also affected by other operation conditions such as electrical service quality as well as number and kind of equipments connected to UPS
Batteries should be periodically tested to check capacity and assure and appropriate back up.
To enlarge batteries life expectancy it is recommendable to fully discharge UPS one every 2 to 3 months
During UPS storage recharge batteries according to the following table:
Storage Temperature Recharging Frequency Recharging Time
-25°C a +30°C Every 4 months During 6 hours
+30°C a +45°C Every 2 months During 6 hours
SAFETY STANDARDS
SAFETY: IEC/EN 62040-1
EMI (Radiated): IEC/EN 62040-2 (Cat 3)
EMI (Conducted): IEC/EN 62040-2 (Cat 3)
EMS Power-Frequency Magnetic Field: IEC/EN 61000-4-8 (Level 4)
EMS Low Freq. Signals: IEC/EN 61000-2-2
EMS (ESD): IEC/EN 61000-4-2 (Level 4)
EMS (RS): IEC/EN 61000-4-3 (Level 3)
EMS (EFT): IEC/EN 61000-4-4 (Level 4)
EMS (SURGE): IEC/EN 61000-4-5 (Level 4)
EMS (CS): IEC/EN 61000-4-6 (Level 3)
TRANSPORTATION: ISTA 1A
This product has been designed to operate in industrial and commercial applications. If it is used in different application some considerations for avoiding interferences could be necessary.
www.integra-ups.com 130805-EPRO-31 10K/20K/30K (ENGLISH) - 2
USER MANUAL - EPRO-31 10K / 20K / 30K
2.- AVAILABLE MODELS
EPRO-31 10K / 20K / 30K
UPS 3 phases IN (380V L-L & 220V L-N) & 1 phase OUT (220V L-N) for 380/220V systems. This kind of UPS includes electronic and internal batteries in same UPS cabinet. This UPS offers 2 kind of outputs:
Output 1: L1-N1:
battery mode this output is powered until UPS shutdowns because energy of the batteries has been drained.
Output 2: L2-N2:
configured to power off automatically in battery mode by reaching a programmable timer. In this way non critical equipments connected to output 2 can be disconnected when timer limit is reached leaving battery energy available for critical loads connected to output 1. Programmable function of output 2 is disable in factory settings. It must be enable if required. When programmable function is disable output 2 operates in same manner than output 1.
EPRO-31 10K-NB / 20K-NB / 30K-NB
UPS 3 phases IN (380V L-L & 220V L-N) & 1 phase OUT (220V L-N) for 380/220V systems. UPS cabinet only includes electronic parts. Batteries must be external.
Output 1: L1-N1:
battery mode this output is powered until UPS shutdowns because energy of the batteries has been drained.
Output 2: L2-N2:
configured to power off automatically in battery mode by reaching a programmable timer. In this way non critical equipments connected to output 2 can be disconnected when timer limit is reached leaving battery energy available for critical loads connected to output 1. Programmable function of output 2 is disable in factory settings. It must be enable if required. When programmable function is disable output 2 operates in same manner than output 1.
EXBATT BATTERY CABINETS
If external batteries are required for 230/120V models or for extending runtime, EXBATT external batteries can be connected directly to the UPS.
EXBATT-33-T10K:
EXBATT for EPRO-31 10K. Includes 20 batteries 12V/9AH with DC breaker 50Amps. DC voltage: 240Vdc (nominal).
EXBATT-33-T20K:
EXBATT for EPRO-31 20K. Includes 40 batteries 12V/9AH with DC breaker 100Amps. DC voltage: 240Vdc (nominal).
EXBATT-33-T30K:
EXBATT for EPRO-31 30K. Includes 60 batteries 12V/9AH with DC breaker 150Amps. DC voltage: 240Vdc (nominal).
WARNING
External battery packs for EPRO-31 models could be not compatible with some other EPRO UPS models. Make sure you will connect compatible external battery pack to your UPS to avoid permanent damages not covered by warranty.
This is the standard UPS output. It can provide 100% of the total capacity in watts of the UPS. In
This is a programmable output able to provide 100% of total UPS capacity. This output can be
This is the standard UPS output. It can provide 100% of the total capacity in watts of the UPS. In
This is a programmable output able to provide 100% of total UPS capacity. This output can be
www.integra-ups.com 130805-EPRO-31 10K/20K/30K (ENGLISH) - 3
USER MANUAL - EPRO-31 10K / 20K / 30K
REAR PANEL
1.- RS232 7.- FAN for power stage / Ventilación Forzada etapa de potencia
2.- USB 8.- EXBATT connector / Conector Baterías Externas
3.- EPO (Emergency Stop / Parada Emergencia) 9.- AC Input Breaker / Breaker de Entrada AC
4.- Share Current (for parallel UPS / para UPS paralelas) 10.- Terminal block cover / Tapa Regleta Conexiones
5.- Parallel Port (for parallel UPS / para UPS paralelas) 11.- MBS (Bypass Switch / Interruptor Bypass)
6.- Smart port / Puer to Inteligente 18.- Ground Terminal Block Cover / Cubierta terminal de Tierra
MODEL: (EPRO-31 10K) & (EPRO-31 10K-NB)
www.integra-ups.com 130805-EPRO-31 10K/20K/30K (ENGLISH) - 4
USER MANUAL - EPRO-31 10K / 20K / 30K
1.- RS232 7.- FAN for power stage / Ventilación Forzada etapa de potencia
2.- USB 8.- EXBATT connector / Conector Baterías Externas
3.- EPO (Emergency Stop / Parada Emergencia) 9.- AC Input Breaker / Breaker de Entrada AC
4.- Share Current (for parallel UPS / para UPS paralelas) 10.- Terminal block cover / Tapa Regleta Conexiones
5.- Parallel Port (for parallel UPS / para UPS paralelas) 11.- MBS (Bypass Switch / Interruptor Bypass)
6.- Smart port / Puer to Inteligente 18.- Ground Terminal Block Cover / Cubierta terminal de Tierra
MODEL: EPRO-31 20K
MODEL: EPRO-31 20K-NB
www.integra-ups.com 130805-EPRO-31 10K/20K/30K (ENGLISH) - 5
USER MANUAL - EPRO-31 10K / 20K / 30K
1.- RS232 7.- FAN for power stage / Ventilación Forzada etapa de potencia
2.- USB 8.- EXBATT connector / Conector Baterías Externas
3.- EPO (Emergency Stop / Parada Emergencia) 9.- AC Input Breaker / Breaker de Entrada AC
4.- Share Current (for parallel UPS / para UPS paralelas) 10.- Terminal block cover / Tapa Regleta Conexiones
5.- Parallel Port (for parallel UPS / para UPS paralelas) 11.- MBS (Bypass Switch / Interruptor Bypass)
6.- Smart port / Puer to Inteligente 18.- Ground Terminal Block Cover / Cubierta terminal de Tierra
MODEL: EPRO-31 30K MODEL: EPRO-31 30K-NB
www.integra-ups.com 130805-EPRO-31 10K/20K/30K (ENGLISH) - 6
USER MANUAL - EPRO-31 10K / 20K / 30K
3.- UPS INSTALLATION: SITE PLANNING
SAFETY INSTRUCTIONS
WARNING: Before revising this section you must read and understand very well section 1 of this manual: “GENERAL SAFETY INSTRUCTIONS”.
WARNINGS, RECOMMENDATIONS AND LIABILITY LIMITATION
REACH AND LIABILITY LIMITATION: The preparation of the site, wiring and all protection devices must be supplied by end user and it will not
be responsibility neither the UPS distributor nor the UPS technician in charge of the start-up. The place will be conditioned be end user or electrical contractor and must fulfill with local normative and directives and UPS technical requirements. This manual describes minimal conditions and technical requirements with which the site must accomplish. Directives and requirements described in this manual, do not pretend to substitute in any way local electrical directives or normative. In some cases, local directives or regulations might be more exigent than UPS technical requirements described by this manual. In that case end user electrical contractor must be sure to comply with all related local electrical regulations and directives.
WARNING: Power lines must be protected by protection devices against over current (breakers) or leak currents with capacity and technology
appropriate to effectively accomplish its function. Moreover, installation grounding must be correct.
WARNING: Install the UPS in well ventilated locations and leave room enough between UPS and close objects and structures
WARNING: Do not connect to UPS equipments or devices that exceed its capacity, this would overload the UPS.
WARNING: This product has been designed to be used indoors protected from water, direct sun light, dust and extreme temperature.
WARNING: Do not put any object on the UPS; do not apply any force over UPS. Do not cover UPS ventilation.
WARNING: This UPS must be connected to appropriate electrical service according to selected model. Technical specs sticker in the UPS
shows the UPS power ratings. DO NOT connect this UPS to any of its own power outlets, this could damage the unit permanently.
WARNING: Connect only computer related equipments to this UPS. DO NOT connect medical equipments or critical availability equipments to
this UPS. DO NOT connect AC motor based equipments. DO NOT connect home appliances (ovens, vacuum cleaners, refrigerators, etc.) to this
UPS.
www.integra-ups.com 130805-EPRO-31 10K/20K/30K (ENGLISH) - 7
USER MANUAL - EPRO-31 10K / 20K / 30K
SITE INSPECTION AND INSTALLATION CONDITIONS
REGULATIONS AND LEGAL DIRECTIVES
It is necessary to check that installation site, wiring and power protection in the installation supplied by end user, fulfill technical parameters required by UPS. A particular installation might accomplish with UPS requirements but not with local directives and regulations. The end user and/or electrical contractor will be responsible of watching for complying with electrical regulations and normative during electrical installation managed by end user. Inspection performed by installation technician is not intended to confirm regulations and directives accomplishing but only with technical needs for optimal UPS operation.
SITE INSPECTION
During transport of this UPS from a cold place to a warmer and more humid one, some condensation could be generated. Leave the
UPS for at least 2 hours to climate to new installation site.
Do not install the UPS outdoors or near water sources nor in wet environment
Do not install the UPS in sites exposed to sun light or heat sources. Temperature at operation site should never rise over 35 ºC.
Batteries’ life shortens over 25 ºC.
Installation site must be dry, fresh, free of dust, fibers and any other objects (conductors or not) suspended in the air that could get
into the UPS thru the ventilation system (Fan).
Do not block UPS ventilations
UPS INPUT AND OUTPUT POWER LINES PROTECTION
AC LINES PROTECTIONS DEVICES:
All UPS Inputs and outputs must be protected by circuit breakers and current leak protections. Protection capacity and type must fulfill local regulations as well as directives from this manual. Grounding must be according to local directives as well.
DC PROTECTIONS DEVICES:
For Ex models (with external batteries) there must be also DC Circuit Breakers between UPS and battery bank. Some Models include a DC breaker on the rear panel for external battery pack protection; otherwise an external DC Circuit breaker must be installed.
MATERIALS AND ELECTRICAL DEVICES
WARNING: Verify that all electrical lines involved in installation are open circuits and free of dangerous voltages before starting inspection
tasks. All switches related to these electrical lines must be in “OFF” position before starting UPS installation. After disconnecting power from electrical lines involved in installation, check again with a digital voltmeter that are free of dangerous voltages.
IMPORTANT: Warning label must be placed on primary involved circuit breakers to alert there are maintenance personnel working on these circuits to avoid accidental actuation on involved breakers.
www.integra-ups.com 130805-EPRO-31 10K/20K/30K (ENGLISH) - 8
USER MANUAL - EPRO-31 10K / 20K / 30K
TOWER UPS INSTALLATION
SITE CONSIDERATIONS
* This product has been designed to be used indoors, protected from water, direct sun light, dust and extreme temperature. * Install the UPS in well ventilated location or air conditioned room. Temperature must be always in acceptable range according to technical specifications table of this manual. It is strongly recommendable controlled room temperature between 21ºC to 24ºC for longer battery and UPS life. * There must be minimum 1 meter free room distance between UPS and any wall or object. It will allow better ventilation and it will allow service UPS when required. * Do not put any object on the UPS; do not apply any force over UPS. Do not cover UPS ventilation.
ELECTRICAL REQUIREMENTS (MANDATORY)
* All Power lines must be protected by magneto-thermal protection devices against over current (breakers) with capacity and technology appropriate to effectively accomplish its function as indicated in this manual. Moreover, installation grounding must be correct. * This UPS must be connected to appropriate electrical service according to selected model. Technical specs sticker in the UPS shows the UPS power ratings. DO NOT connect this UPS to any of its own power outlets, this could damage the unit permanently. * If external battery cabinets are connected to UPS, it is necessary to install one DC breaker between UPS and each external battery cabinet. Original External Battery cabinets normally include its own input breaker.
LEAK CURRENT PROTECTION
In many countries, now a day, it is legally required to install protections against current leakage to protect human beings in cases of leaks o discharges to ground. It is responsibility of the end user and/or electrical contractor selecting and including these protection devices in the electrical circuit of the UPS.
www.integra-ups.com 130805-EPRO-31 10K/20K/30K (ENGLISH) - 9
USER MANUAL - EPRO-31 10K / 20K / 30K
CIRCUIT BREAKERS AND WIRING SELECTION
Breakers and Gauge of the wires used in the installation must be rated to drive current values in Amps as indicated in below tables. NOTE every country has its local electrical requirements and regulations. If local electrical regulations require higher rates than suggested values in this section, please follow local regulations.
INPUT 3PH OUTPUT 1PH EXT. BATT
MODEL BREAKER & WIRING BREAKER & WIRING BREAKER & WIRING
10KVA
3PH / 1PH
20KVA
3PH / 1PH
Breaker: 63 Amps AC (Curve D)
Max. Nominal Current (Ph-N):
- 19A in normal mode (220V)
- 48A in bypass mode (208V)
Wiring (min. recommended size):
- Phase: 8 AWG (10 mm2)
- Neutral: 8 AWG (10 mm2)
- Ground: 8 AWG (10 mm2)
Breaker: 100 Amps AC (Curve D)
Max. Nominal Current (Ph-N):
- 38A in normal mode (220V)
- 95A in bypass mode (208V)
Wiring (min. recommended size):
- Phase: 4 AWG (25 mm2)
- Neutral: 4 AWG (25 mm2)
- Ground: 6 AWG (16 mm2)
Breaker: 200 Amps AC (Curve D)
Breaker: 63 Amps AC (Curve D)
Max. Nominal Current (Ph-N):
- 45A in normal mode (220V)
- 48A in bypass mode (208V)
Wiring (min. recommended size):
- Phase: 8 AWG (10 mm2)
- Neutral: 8 AWG (10 mm2)
- Ground: 8 AWG (10 mm2)
Breaker: 100 Amps AC (Curve D)
Max. Nominal Current (Ph-N):
- 90A in normal mode (220V)
- 95A in bypass mode (208V)
Wiring (min. recommended size):
- Phase: 6 AWG (16 mm2)
- Neutral: 6 AWG (16 mm2)
- Ground: 6 AWG (16 mm2)
Breaker: 200 Amps AC (Curve D)
Breaker: 50Amps DC (Curve C)
Wiring (min. recommended size):
* 8 AWG (10mm2)
Breaker: 100Amps DC (Curve C)
Wiring (min. recommended size):
* 6 AWG (16mm2)
Max. Nominal Current (Ph-N):
- 57A in normal mode (220V)
30KVA
3PH / 1PH
Recommended cable size according to 1999 NEC (301-17) based on 30ºC air ambient temperature for single cable.
IMPORTANT NOTE - BYPASS: Input breakers and cables are rated to drive current in bypass mode. Bypass mode is connected through 1st phase (R-N) only so that current in bypass mode is 3 times approx. higher than in normal mode. In normal mode input power is distributed in 3 input lines.
WARNING: Above wiring and breakers rates are only a suggestion. The wire size is strongly affected by diverse factors such as: Operation temperature, wire length, type of wire, quantity of conductors and kind of installation. Electrical contractor must assure an appropriate selection for wire and protection devices sizing for complying with local regulations for electrical installations. Wiring colors must be selected according to local directives and regulations
- 145A in bypass mode (208V)
Wiring (min. recommended size):
- Phase: 2 AWG (35 mm2)
- Neutral: 2 AWG (35 mm2)
- Ground: 4 AWG (25 mm2)
Max. Nominal Current (Ph-N):
- 136A in normal mode (220V)
- 145A in bypass mode (208V)
Wiring (min. recommended size):
- Phase: 2 AWG (35 mm2)
- Neutral: 2 AWG (35 mm2)
- Ground: 4 AWG (25 mm2)
Breaker: 150Amps DC (Curve C)
Wiring (min. recommended size):
* 3 AWG (35mm2)
www.integra-ups.com 130805-EPRO-31 10K/20K/30K (ENGLISH) - 10
USER MANUAL - EPRO-31 10K / 20K / 30K
4.- UPS INSTALLATION: SINGLE UPS - TERMINAL BLOCK
AC LINES CONNECTION PROCEDURE
• Make sure the UPS is Off before starting the installation.
UPS TERMINAL BLOCK PREPARATION
Remove cover of terminal block at the UPS rear panel. UPS Input wires must come from electric panel board and they must be protected by a circuit breaker protection device. Ground wires must be FIRST to be connected and LAST to be disconnected.
EPRO-31 10K & 10K-NB
• Remember to check all wires to be connected are not powered (including external batteries).
IMPORTANT NOTE: If terminal block information printed on rear panel of the UPS is different to information given in this manual, please follow terminal block information printed on UPS.
Output 1: L1-N1:
battery mode this output is powered until UPS shutdowns because energy of the batteries has been drained.
Output 2: L2-N2:
configured to power off automatically in battery mode by reaching a programmable timer. In this way non critical equipments connected to output 2 can be disconnected when timer limit is reached leaving battery energy available for critical loads connected to output 1. Programmable function of output 2 is disable in factory settings. It must be enable if required. When programmable function is disable output 2 operates in same manner than output 1.
www.integra-ups.com 130805-EPRO-31 10K/20K/30K (ENGLISH) - 11
This is the standard UPS output. It can provide 100% of the total capacity in watts of the UPS. In
This is a programmable output able to provide 100% of total UPS capacity. This output can be
USER MANUAL - EPRO-31 10K / 20K / 30K
EPRO-31 20K & 20K-NB
Output 1: L1-N1: This is the standard UPS output. It can provide 100% of the total capacity in watts of the UPS. In
battery mode this output is powered until UPS shutdowns because energy of the batteries has been drained.
Output 2: L2-N2:
configured to power off automatically in battery mode by reaching a programmable timer. In this way non critical equipments connected to output 2 can be disconnected when timer limit is reached leaving battery energy available for critical loads connected to output 1. Programmable function of output 2 is disable in factory settings. It must be enable if required. When programmable function is disable output 2 operates in same manner than output 1.
This is a programmable output able to provide 100% of total UPS capacity. This output can be
www.integra-ups.com 130805-EPRO-31 10K/20K/30K (ENGLISH) - 12
USER MANUAL - EPRO-31 10K / 20K / 30K
EPRO-31 30K & 30K-NB
www.integra-ups.com 130805-EPRO-31 10K/20K/30K (ENGLISH) - 13