InSinkErator AS-101K User Manual

®
AquaSaver
DISPOSER CONTROL CENTER
Installation Manual
Model AS-101K
The Danger signal indicates an immediately hazardous situation which, if not avoided, will result in death or serious injury.
The Warning signal alerts you to potential hazards or unsafe practices which, if not avoided, could result in severe personal injury or death.
The Caution signal alerts you to hazards of unsafe practices which, if not avoided, may result in minor personal injury or property damage.
Please be certain that the person who installs or uses this appliance carefully reads and understands the Safety Instructions contained in this manual.
Part No. 14177 Rev. Awww.insinkerator.com/foodservice
Table of Contents
Introduction/Features
Introduction ..................................................................................... 3
Features .......................................................................................... 3
Mounting The Control Center/Plumbing Connections
Mounting the Control Center........................................................... 4
Plumbing Connections .................................................................... 4
Electrical Connection Diagrams .................................................................. 5
Electrical Connections .................................................................................. 6
Operating Instructions/Aqua-Saver Adjustment
Operating Instructions ..................................................................... 7
Aqua-Saver Adjustment .................................................................. 7
Troubleshooting ............................................................................................. 8
Wiring Diagrams
Model No. AS-101K-1 (120V, 1 phase, 1/2 - 2 HP) ......................... 9
Model No. AS-101K-2 (208/230V, 1 phase, 1/2 - 2 HP) ................ 10
Model No. AS-101K-3 (208/230V, 3 phase, 1/2 - 10 HP) .............. 11
Model No. AS-101K-4 (380/460V, 3 phase, 1/2 - 10 HP) .............. 12
Warranty
FOODSERVICE DISPOSER CONTROL CENTER LIMITED WARRANTY
InSinkErator Foodservice Disposer Control Centers are warranted against defects in material and workmanship for one year from the date of installation. The warranty includes parts and labor, provided the service is performed by an InSinkErator Factory Authorized Service Center. This warranty does not apply if failure is due to: faulty or improper
electrical installation, faulty or improper plumbing installation, product abuse or misuse, or accidental damage.
Foodservice disposer accessories are included in this warranty only if they are included in the original disposer purchase package.
2
Introduction/Features
INTRODUCTION
The AS-101K Control Center is UL® and CUL® approved for use with InSinkErator Foodservice Disposers. See Table 1 for approved disposer and control center combinations. The control center operates the disposer and control center combinations. Its main functions are:
• To start and stop the disposer.
 Toreversethedirectionofthedisposermotor
automaticallyuponrestart.
• To start the water flow to the disposer.
• To regulate the amount of water needed for operation. Two solenoid valves are used to control high and low water flows.
• To allow water flow for several minutes to flush the drain line after the disposer is turned off.
Model Waste Disposer Model
AS-101K-1 AS-101K-2
AS-101K-3 AS-101K-4
Table 1. Approved Disposer and Control Center Combinations
Model Voltage Phase HP
AS-101K-1 120V 1 1/2-2
AS-101K-2 208/240V 1 1/2-2
AS-101K-3 208/240V 3 1/2-10
AS-101K-4 380/460V 3 1/2-10
Table 2. Electrical Specifications
SS50-26, SS75-27, SS100-28, SS125-25,
SS150-34, SS150-38, SS200-27, SS200-31
SS50-27, SS75-28, SS100-29, SS125-26,
SS150-36, SS150-39, SS200-29, SS200-32, SS300-25, SS300-27, SS500-28, SS500-30, SS750-13,
SS750-15, SS1000-10, SS1000-12
FEATURES
AUTOMATIC REVERSE
The disposer motor will reverse its direction of rotation automatically upon restart. To avoid motor damage, a five second delay feature prevents reversing while the motor is coasting.
WATER SHUTOFF DELAY (POST FLUSH)
After the motor is turned off, the water continues to flow for up to 10 minutes. The length of this post flush is controlled by the water shutoff delay timer. The post flush helps ensure that ground food waste is flushed out of the drain line. Adjust water shutoff delay as described in the operating instructions on page 8.
AUTOMATIC WATER REGULATION
This acts as an on-demand water saving system for InSinkErator Foodservice Disposers. It senses the load of the disposer, and regulates the amount of water necessary for grinding and non-grinding situations. This uses two solenoid valves.
NOTE: When the disposer is first turned on, both solenoids will operate. After the set time has expired, the flow to the disposer will slow to one gallon per minute if there is not food waste present in the grinding chamber.
AUTOMATIC TIMED DISPOSER SHUTOFF
This water saving feature allows the disposer to run for up to 10 minutes before it automatically shuts off and must be manually restarted.
NOTE: This feature is set in the manual position at the factory. To activate the automatic timed disposer shutoff, disconnect the electric power to the control center, then open the control center door. Locate the Dip Switch Module at the top of the printed circuit board (see Figure 8). Move the #5 dip switch from MANUAL to AUTOMATIC. The disposer now automatically shuts off 10 minutes after it starts.
EXTERNAL REMOTE CONTROL
One or more remote controls may be connected to the control center. These enable the operator to start or stop the disposer from any control station. A 24 V control circuit provides low voltage push button operation.
ELECTRIC DISCONNECT SWITCH
The lever switch on the front panel of the control center disconnects the line voltage. It interlocks with the front cover so that the cover cannot be opened unless the switch is in the off position.
NOTE: Use of the electrical disconnect switch results in a 30 second delay before system can be restarted. You must wait 30 seconds after reactivation of the line
disconnect switch before system will start.
LOW VOLTAGE CONTROL
Controls operate on a 24 V solid state control circuit.
ENCLOSURE
NEMA 4 construction.
PUSH BUTTON OPERATION
Push Black button to start disposer. Push Red button to stop disposer.
PROPERTY DAMAGE
Use of more than two solenoid valves will affect the overall function of the Aqua Saver systems. Extra solenoid valves will cause a reduction in voltage and solenoid actuation will not occur.
3
Mounting the Control Center/Plumbing Connections
MOUNTING THE CONTROL CENTER
Use the flanges at the back of the control center enclosure and only mount panel in the upright vertical position (door hinge is on the left). See Figure 1.
Locate control center within sight of disposer per local codes. Locate any remote control station within sight of disposer per local codes.
9-7/8"
(250.8 mm)
8-1/4"
(209.6 mm)
1"
(25.4 mm)
If box is mounted to the sink table, recess the box so that the buttons do not extend beyond the table’s edge.
PLUMBING CONNECTIONS
Two solenoid valves with flow control valves pre-installed (1 GPM and 7 GPM) are packed with the control center. The syphon breaker is supplied with all complete disposer packages (packed separately).
The solenoid valve is supplied with a 24 V coil. Make certain that the valves are plumbed according to the water flow direction arrows marked on the valve or the valves will not function properly.
The flow control valve regulates all water flowing into the disposer. This conserves water and prevents overloading. Check direction of water flow arrows.
Syphon breaker must be installed above the sink flood plane per local plumbing codes. Check direction of water flow arrows.
Sink Installation Trough Installation
15-3/4"
(400.1 mm)
15-1/8"
(384.2 mm)
14"
(355.6 mm)
5-5/16"
(134.9 mm) 6-3/4"
(171.5 mm)
Figure 1. Control Center Dimensions
NOTE: The AS-101K control center requires the use of two solenoid valves and two flow control valves. Figure 2 shows the proper installation for an AS-101K control center.
Figure 2. Typical Installation Diagram
4
24V Water Solenoid 1 GPM Flow Control
24V Water Solenoid 7 GPM Flow Control
L1 L2 L3
L1 L2 L3
On
Off
Hot
Pre-wired in
panel to
contactors
Power Supply Panel Ground Lug
2 3 4 6 7 7 13
14 NC M1 M2 M3
Disposer
M1 M2 M3
M1
M2 M3
1
4 10 5 6 12
MOTOR LEAD WIRE#
11
7 2 8 3 9
Electrical Connection Diagrams
2 3 4 6 7 7 13
24V Water Solenoid 1 GPM Flow Control
24V Water Solenoid
Hot
7 GPM Flow Control
L1 L2
Neutral
On
Off
L1 L2
Power Supply
Pre-wired in
panel to
contactors
14 M1/M3 M4/M6M2 M5 M7 NC NC
1 3 2
4 6 5 7
Disposer
Control Center Connection To Power Supply
Panel Ground Lug
Figure 3. Incoming 120 V Single Phase Line Power
Motor Leads
2 3 4 6 7 7 13
24V Water Solenoid 1 GPM Flow Control
24V Water Solenoid
Hot
7 GPM Flow Control
L1 L2
Neutral
On
Off
L1 L2
Power Supply
Pre-wired in
panel to
contactors
14 M1 M3/M4M2 M5 M6 M7 NC
4 5 6 7
1 2 3
Disposer
Control Center Connection To Power Supply
Panel Ground Lug
Motor Leads
Figure 4. Incoming 208-240 V Single Phase Line Power
Figure 5. Incoming 208-230 V Three Phase Line Power
2 3 4 6 7 7 13
24V Water Solenoid 1 GPM Flow Control
24V Water Solenoid 7 GPM Flow Control
Pre-wired in
panel to
contactors
L1 L2 L3
Hot
On
Off
L1 L2 L3
Power Supply Panel Ground Lug
14 NC M1 M2 M3
M1 M2 M3
Disposer
4 7 5 6 9
MOTOR LEAD WIRE#
1
2 3 10 11 12
M1 M2 M3
Figure 6. Incoming 380-460 V Three Phase Power
8
5
Electrical Connections
ELECTRIC SHOCK
• Turn off the electrical supply to the disposer before attempting any work on it. Use a voltmeter or circuit tester to ensure that power is off.
• All installation work must conform to local plumbing and electrical codes.
• All control centers and disposers must be carefully and permanently grounded.
• A properly fused disconnect must be installed at the electrical supply source for the control center.
The control center’s door disconnect must be in the
off position before the panel door can be opened. Power is still present at the disconnect until power is turned off at the electrical supply source.
LINE VOLTAGE
Connect the incoming line power to the electrical disconnect switch and connect the disposer motor to labeled terminal blocks in the control center. Use the appropriate voltage and phase electrical connection
diagram, Figure 3, 4, 5, or 6.
LOW VOLTAGE
The AS-101K control center uses low voltage (24 V) to operate contactor coils, solid state control circuit, push buttons, and solenoid valves. Red wires denote
a 24 V circuit.
REMOTE CONTROL STATION
Any number of remote control stations can be used. Mount remote controls within sight of the disposer per local codes. Refer to Figure 7. Remove jumper
wire between #2 and #3 when using remote control station.
Start
14
Dispos er
Multipl e Remote Start (N.O.)
Jumpe r Wire Remove d For Rem ote Opera tion
2 3 4 6 7 7 13
24V Water Sole noid 1 GPM Flow Cont rol
24V Water Sole noid 7 GPM Flow Cont rol
Stop
Multipl e Remote Stop (N.C.)
Figure 7. Remote Control Station Wiring
WATER SOLENOID VALVE
Two 24 V solenoid valves are supplied with all control centers. Connect one 24 V solenoid valve (in line with the 1 GPM flow control) to terminal 4 and 13, connect the other 24 V solenoid valve (in line with the 7 GPM flow control) to terminal 4 and 14. See Figure 7.
Wire per local electrical code using 7/8" diameter holes in bottom of control center cabinet and install NEMA 4 water-tight electrical connectors.
After completing the connections, replace all terminal block shields, close door, and fasten all locking clamps. Replace disposer motor cover. Turn on power.
Please read the disposer operating instructions and train your personnel before operating the disposer. The operating instructions include:
• Disposer operation
• How to restart the disposer after a jam condition
PROPERTY DAMAGE
• Ensure that control center voltage and phase match the disposer motor and electrical supply. Check name plates on disposer and control centers for voltage and phase specifications.
• Refer to the control center wiring diagrams in this manual for correct connection.
• Use NEMA 4 watertight electrical connectors (not supplied) when making electrical connections to the control center.
PERSONAL INJURY
• Allow only trained personnel to operate disposer.
• Use baffles and guarding to avoid splashing and ejection of materials.
• Do not put fingers or hands into the disposer.
• When attempting to remove objects from a disposer, use long-handled tongs or pliers.
• Turn power off before clearing a jam, removing an object from the disposer or pressing the red reset button. (See Troubleshooting).
• Disconnect electricity before adjusting set points.
6
Operating Instructions/Aqua-Saver Adjustment
OPERATING INSTRUCTIONS
TO START
1. Check to ensure disposer is free of foreign objects.
2. Ensure power is on.
3. Push start button. Disposer motor will run and water will flow into the disposer.
4. Water flow will decrease to 1 GPM approximately 30 seconds after intitial start-up if no load is present in disposer.
TO STOP
1. Push stop button. Disposer motor and water will stop.
2. Water may continue to flow into disposer for up to
10 minutes, per the time set on the water shutoff delay timer.
NOTE: This post-flush clears the drain lines of food waste.
PERSONAL INJURY
To adjust the water shutoff delay, disconnect the electrical power to the control panel and open the control center door.
WATER SHUTOFF DELAY ADJUSTMENT
Locate the water shutoff delay at the top of the printed circuit board in the AS-101K (See Figure 8). Set the dip switches for the desired water shut off delay. Use the guide printed on the circuit board to set minutes of delay. The dip switches should be moved to match the filled-in areas of the guide.
NOTE: This feature is set in the manual position at the factory. To activate the automatic timed disposer shut-off, disconnect the electric power to the control center, then open the control center door. Locate the Dip Switch Module at the top of the printed circuit board (see Figure 8). Move the #5 dip switch from MANUAL to AUTOMATIC. The disposer now automatically shuts off 10 minutes after it starts.
AQUA-SAVER ADJUSTMENT
ELECTRICAL SHOCK
• Turn off the electrical supply to the disposer before attempting any work on it. Use a voltmeter or circuit tester to ensure that power is off.
• Installation must conform to local plumbing and electrical codes.
• All control centers and disposers must be carefully and permanently grounded.
• A properly fused disconnect must be installed at the electrical supply source for the control center.
CURRENT SENSING CONTROL SET-UP
See Figure 9.
1. Adjust the trip delay to mid-setting. This adjusts the length of the time the water runs at full flow after grinding is completed. Mid-setting is approximately 15 seconds.
2. With the disposer running at high water flow:
a. Adjust the trip point control to maximum
position, the light is not illuminated.
b. Turn the trip point control counterclockwise
until the red fault light is illuminated, stop.
c. Turn the trip point control clockwise slowly,
stopping immediately when the red fault light is no longer illuminated. Turn slightly counterclockwise incrementally with the light remaining off to assure you are at the exact set point. To ensure sensitivity, the trip point must be set at the exact point the light becomes no longer illuminated.
NOTE: Water flow will decrease after trip delay time setting expires.
Figure 8.
Example 1: Dip switches 1, 2, 3, 4 pushed to the down
position will give a 0 minute delay.
Example 2: Dip switches 1, 3, 4 pushed to the up
position; and dip switch 2 pushed to the down position will give a 10 minute delay.
AUTOMATIC TIMED DISPOSER SHUTOFF
This water saving feature allows the disposer to run for up to 10 minutes before it automatically shuts off and must be manually restarted.
Figure 9.
7
Troubleshooting
PERSONAL INJURY
• Allow only trained personnel to operate disposer.
• Use baffles and guarding to avoid splashing and ejection of materials.
• Do not put fingers or hands into the disposer.
• When attempting to remove objects from a disposer, use long-handled tongs or pliers.
• Turn power off before clearing a jam, removing an object from the disposer or pressing the red reset button.
This control center was inspected and tested under operating conditions before shipment from the factory. In case of trouble, check the items listed below.
A. Disposer motor will not start and water
does not flow.
1. No incoming line power, turn line power on.
2. Electric disconnect switch is not ON. Turn electric disconnect to ON position.
3. Electrical disconnect switch has been reactivated and 30-second delay has not yet expired. Wait 30 seconds and try starting again.
4. Control circuit fuse FNA2 is blown. Replace fuse.
PROPERTY DAMAGE
Use only an FNA2 replacement fuse. Using another replacement fuse will result in product damage.
B. Disposer motor stops while grinding but water
continues to flow.
1. Control center wired for automatic shut-off. Press start button. If disposer runs for 10 minutes then shuts off, the automatic shutoff is active. If the manual setting is desired, change as indicated in the feature section.
2. Disposer is jammed. Press stop button and follow directions for unjamming that were supplied with the disposer.
3. Disposer motor overload protector has tripped.
Follow instruction in C1.
ELECTRICAL SHOCK/PROPERTY DAMAGE
• Troubleshooting other than what is recommended in this section should only be performed by qualified service personnel.
• Further troubleshooting performed by untrained personnel could result in electric shock or damage to the control center.
• All electrical checks must be performed by a qualified professional.
D. Water flows constantly before start button
is pushed.
1. Water solenoid valve is installed backward.
Water flow should be in the direction of the arrow on valve.
E. Water flow does not decease to 1 GPM.
1. Incorrect solenoid valve combination
connections. See Water Solenoid Valve, page 7.
2. Incorrect trip point adjustment. See Current
Sensing Control Setup, page 8.
3. Food load is present in disposer.
F. Water flow does not increase.
1. Insufficient food load is present.
2. Incorrect trip point. See Current Sensing Control
Setup, page 8.
3. Solenoid valve wiring incorrect in panel.
4. More than two water solenoids wired into
system. System should have one solenoid with a 1 GPM flow control and one solenoid with a 7 GPM flow control.
NOTE: Use shutoff valves to adjust water flow for multiple trough or sink nozzles.
G. Overload trips frequently.
1. Do not overload disposer with excess amounts of
garbage and water (see disposer instructions for recommended water flows).
C. Disposer will not start but water flows.
1. Overload protector on the disposer may have tripped. Press stop button. Locate red reset button on front of disposer electrical cover. Press to reset. If motor had been running, wait five minutes for the motor and overload to cool down before starting.
2. Disposer is jammed. Press stop button and follow directions for unjamming that were supplied with the disposer.
8
AS-101K-1 Wiring Diagram
ELECTRICAL SHOCK
• Turn off the electrical supply to the disposer before attempting any work on it. Use a voltmeter or circuit tester to ensure that power is off.
• Installation must conform to local electrical codes.
• All control centers and disposers must be carefully and permanently grounded.
• A properly fused disconnect must be installed at the electrical supply source for the control center.
M7
M7
M1
M1
4
4
4
4
6
6
120 V
1-phase
6
M4
M7
M7
M4
M6
M6
1/2 to 2 HP
M5
M5
L2
L2
M2
7
7
7
7
M2
L1
L1
9
9
PROPERTY DAMAGE
• Ensure that the control center voltage and phase match the disposer motor and electrical supply. Check nameplates on disposers and control centers for voltage and phase specification.
• The disposer motor wiring connection is shown in the disposer terminal box.
4
4
9
9
12
12
4
4
6
6
11
11
10
10
7
7
7
7
10
10
AC CURRENT
SENSOR
L2
L2
TRIP DELAY
TRIP POINT
1
2
3
4
5
L2
L2
4 7
14
7
STOP START
STOP START
3 7
3 7
Call Toll Free 1-800-845-8345 for the nearest InSinkErator Authorized Service Agency or to reach Technical Support.
WATER
WATER
SHUTOFF
SHUTOFF
DELAY
DELAY
PRINTED
PRINTED
CIRCUIT
CIRCUIT
BOARD
BOARD
7
7
12
12
11
11
666
666
4
4
13
13
2
2
M1
4
4
2
2
6
6
3
3
7
7
24V WATER
24V WATER
SOLENOID VALVE
SOLENOID VALVE
MOUNT IN LINE
MOUNT IN LINE
1 GPM
1 GPM
FLOW CONTROL
FLOW CONTROL
24V WATER
24V WATER
SOLENOID VALVE
SOLENOID VALVE
MOUNT IN LINE
MOUNT IN LINE
X GPM
7 GPM
FLOW CONTROL
FLOW CONTROL
7
7
M1
13
13
M2
14
M2
14
M3
M3
3
3
1
1
M4
M4 M6
M6
4 6 5 7
4 6 5 7
2
2
DISPOSER
MOTOR
4
4
M5 M7
M5 M7
X2
X2
4
4
H1
H1
H3
H3
GROUND
GROUND
NC NC
NC NC
H2 H4
H2 H4
XF
XF
FUSE
FUSE
2
2
(FNA2)
(FNA2)
L1
L1
L1 L2
L1 L2
INCOMING
INCOMING
POWER
POWER
OFF
L2
L2
ON
PANEL
PANEL GROUND
GROUND LUG
LUG
9
AS-101K-2 Wiring Diagram
ELECTRICAL SHOCK
• Turn off the electrical supply to the disposer before attempting any work on it. Use a voltmeter or circuit tester to ensure that power is off.
• Installation must conform to local electrical codes.
• All control centers and disposers must be carefully and permanently grounded.
• A properly fused disconnect must be installed at the electrical supply source for the control center.
4
4
9
9
12
12
4
4
M1
M1
4
4
4
4
6
6
6
6
M4
M4
M7
M7
L2
L2
L1
L1
M6
M6
11
11
M5
M5
10
M2
M2
10
9
9
PROPERTY DAMAGE
• Ensure that the control center voltage and phase match the disposer motor and electrical supply. Check nameplates on disposers and control centers for voltage and phase specification.
• The disposer motor wiring connection is shown in the disposer terminal box.
AC CURRENT
AC CURRENT
SENSOR
SENSOR
L2
L2
6
6
TRIP
TRIP
DELAY
DELAY
TRIP
TRIP
POINT
POINT
7
7
7
7
10
10
1
1
2
2
3
3
4
4
5
5
L2
L2
208/230 V
1-phase
4
4
7
7
14
14
7
7
1/2 to 2 HP
7
7
666
666
STOP START
STOP START
3 7
3 7
Call Toll Free 1-800-845-8345 for the nearest InSinkErator Authorized Service Agency or to reach Technical Support.
WATER
WATER
SHUTOFF
SHUTOFF
DELAY
DELAY
PRINTED
PRINTED
CIRCUIT
CIRCUIT
BOARD
BOARD
4
12
12
11
11
4
13
13
2
2
M3
1
1
2 3 4
2 3 4
DISPOSER
MOTOR
M3 M4
M4
4
4
2
2
6
6
3
3
7
7
24V WATER
24V WATER SOLENOID VALVE
SOLENOID VALVE MOUNT IN LINE
MOUNT IN LINE 1 GPM
1 GPM FLOW CONTROL
FLOW CONTROL
24V WATER SOLENOID VALVE MOUNT IN LINE X GPM FLOW CONTROL
13
13
7
M5 M6
5
5
X2
X2
4
4
M77
7
7
6
6
H1
H1
4
4
H3
H3
GROUND
GROUND
H2 H4
H2 H4
XF
XF
FUSE
FUSE
2
2
(FNA2)
(FNA2)
L1
L1
OFF
L1 L2
L1 L2
ON
INCOMING
INCOMING
POWER
POWER
L2
L2
PANEL GROUND LUG
10
AS-101K-3 Wiring Diagram
ELECTRICAL SHOCK
• Turn off the electrical supply to the disposer before attempting any work on it. Use a voltmeter or circuit tester to ensure that power is off.
• Installation must conform to local electrical codes.
• All control centers and disposers must be carefully and permanently grounded.
• A properly fused disconnect must be installed at the electrical supply source for the control center.
M2
M1
4
4
208/230 V
3-phase
1/2 to 10 HP
L1
L2
L3
PROPERTY DAMAGE
• Ensure that the control center voltage and phase match the disposer motor and electrical supply. Check nameplates on disposers and control centers for voltage and phase specification.
• The disposer motor wiring connection is shown in the disposer terminal box.
9
12
11
6
M3
6
4
4
10
9
7
7
6
10
7
7
AC CURRENT
SENSOR
L2
TRIP DELAY
TRIP POINT
L2
1
2
3
4
5
4 7
14
7
6
3
Call Toll Free 1-800-845-8345 for the nearest InSinkErator Authorized Service Agency or to reach Technical Support.
WATER SHUTOFF DELAY
H3
XF
FUSE
2
L2L1
ON
OFF
L2L1
INCOMING
POWER
H4H2
(FNA2)
L3
L3
PANEL GROUND LUG
H1
PRINTED CIRCUIT BOARD
7
12
11
6
6
STARTSTOP
7
2
4
13
2
4
6
3
24V WATER SOLENOID VALVE MOUNT IN LINE 1 GPM FLOW CONTROL
24V WATER SOLENOID VALVE MOUNT IN LINE 7 GPM FLOW CONTROL
13
7
7
M1
14
NC
M1
DISPOSER
MOTOR
X2
4
GROUND
4
M2
M3
M3
M2
11
AS-101K-4 Wiring Diagram
ELECTRICAL SHOCK
• Turn off the electrical supply to the disposer before attempting any work on it. Use a voltmeter or circuit tester to ensure that power is off.
• Installation must conform to local electrical codes.
• All control centers and disposers must be carefully and permanently grounded.
• A properly fused disconnect must be installed at the electrical supply source for the control center.
9
9
12
12
11
11
6
6
M3
M3
6
M2
M2
M1
M1
4
4
4
4
L1
L1
L2
L2
6
4
4
4
10
10
L3
L3
9
9
7
7
7
7
10
10
PROPERTY DAMAGE
• Ensure that the control center voltage and phase match the disposer motor and electrical supply. Check nameplates on disposers and control centers for voltage and phase specification.
• The disposer motor wiring connection is shown in the disposer terminal box.
6
6
AC CURRENT
AC CURRENT
SENSOR
SENSOR
L2
L2
L2
L2
380/460 V
TRIP
TRIP
DELAY
DELAY
TRIP
TRIP
POINT
POINT
7
7
7
7
1
1
2
2
3
3
4
4
5
5
4
4
7
7
14
14
7
7
1/2 to 10 HP
3-phase
7
7
11
11
6
6
6
6
6
6
STARTSTOP
STARTSTOP
7
3
3
7
Call Toll Free 1-800-845-8345 for the nearest InSinkErator Authorized Service Agency or to reach Technical Support.
PRINTED CIRCUIT BOARD
12
12
WATER SHUTOFF DELAY
H4H2
H3
H3
XF
XF
FUSE
FUSE
2
2
L2L1
L2L1
ON
OFF
L2L1
L2L1
INCOMING
INCOMING
POWER
POWER
H4H2
(FNA2)
(FNA2)
L3
L3
L3
L3
PANEL
PANEL
GROUND
GROUND
LUG
LUG
H1
H1
X2
X2
4
4
13
13
2
2
4
4
2
2
6
6
3
3
24V WATER
24V WATER
SOLENOID VALVE
SOLENOID VALVE
MOUNT IN LINE
MOUNT IN LINE
1 GPM
1 GPM
FLOW CONTROL
FLOW CONTROL
7
7
24V WATER
24V WATER
SOLENOID VALVE
SOLENOID VALVE
MOUNT IN LINE
MOUNT IN LINE 7 GPM
FLOW CONTROL
FLOW CONTROL
13
13
7
7
M1
M1
14
14
NC
NC
M1
M1
DISPOSER
M2
M2
M2
M2
MOTOR
4
4
GROUND
GROUND
4
4
M3
M3
M3
M3
12
Loading...