Ingersoll Rand TZE3500, TZE400 User Manual

Page 1
          ! 
This dryer configuration includes equipment options as selected (X) below:
EMS OPTION LDP OPTION 3V OPTION
More Than Air. Answers.
Online answers: http://www.air.irco.com Phone : 1-800-526-3615
Form: APDD 792
CCN: 38019683
Z103146 Rev. 10
Page 2
Page 3
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
FOREWORD
Reading this user manual will fully familiarize you with the Ingersoll-Rand adsorption dryer. You will be better able to run this equipment in accordance with its intended use.
This manual contains important information for safe, proper and economic dryer installation, start-up, operation and maintenance. Always keep it within reach where the adsorption dryer is being used.
It is necessary to follow all instructions as written. Careful reading will avert danger, avoid unnecessary downtime, and minimize work for yourself and wear on the equipment.
In addition to carefully reading this technical manual in its entirety, you must understand your National, State and local rules and regulations regarding safety in the workplace, their necessary precautions and procedures.
Each person responsible for the set-up, start-up, operation, maintenance or repair of this adsorption dryer must have first read and understood this user manual – including all the safety tips.
NOTE: Ingersoll-Rand recommends that installation, start-up and maintenance
be carried out by its factory-trained technicians in a regularly scheduled, site-dedicated program. This will ensure the safety of personnel, the integrity of equipment and the surety of warranty coverage.
i
Page 4
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
ii
Page 5
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
TABLE OF CONTENTS
1. INTRODUCTION ..................................................................................................................................................1
1.1 GENERAL.............................................................................................................................................................1
1.2 PRODUCT INFORMATION......................................................................................................................................1
1.2.1 Pressure Vessel Regulations ........................................................................................................................2
1.2.2 Leak Test......................................................................................................................................................2
1.3 SAFETY INSTRUCTIONS........................................................................................................................................2
1.3.1 Identification of Signs and Symbols in this Manual.....................................................................................2
1.3.2 General Safety Tips for Assembly, Inspection and Maintenance.................................................................3
1.4 TECHNICAL DATA SHEET ....................................................................................................................................4
1.4.1 Models TZE400 to TZE820 ..........................................................................................................................4
1.4.2 Models TZE1000 to TZE1800......................................................................................................................5
1.4.3 Models TZE2100 to TZE3500......................................................................................................................6
1.4.4 Dryer Flow Capacities ................................................................................................................................7
1.5 OVERLOADING ....................................................................................................................................................8
1.6 TRANSPORT .........................................................................................................................................................8
1.7 STORAGE .............................................................................................................................................................8
1.8 USE OF A PREFILTER AND AFTERFILTER..............................................................................................................8
2. INSTALLATION....................................................................................................................................................9
2.1 GENERAL.............................................................................................................................................................9
2.2 MECHANICAL ASSEMBLY....................................................................................................................................9
2.3 FILTER INSTALLATION.......................................................................................................................................10
2.3.1 Prefilter Installation (Shipped Loose) .......................................................................................................10
2.3.2 Afterfilter Installation (Shipped Loose) .....................................................................................................11
2.3.3 Filter Skid with 3 Valve Bypass (If Dryer Includes 3V Option).................................................................11
2.4 ELECTRICAL CONNECTION ................................................................................................................................11
2.5 EMS CONTROL CONNECTION ...........................................................................................................................12
3. EQUIPMENT OPERATION ..............................................................................................................................13
3.1 GENERAL OPERATING PRINCIPLES ....................................................................................................................13
3.1.1 Dryer Program Steps .................................................................................................................................14
3.2 OPERATOR CONTROLS / LOW-VOLTAGE CONTROL PANEL ...............................................................................16
3.2.1 Dryer Status ...............................................................................................................................................18
3.2.2 Alarm Information .....................................................................................................................................19
3.2.3 Dryer Operation Modes.............................................................................................................................20
3.2.4 Heater Sheath Information ........................................................................................................................20
3.2.5 Heater Outlet Information .........................................................................................................................21
3.2.6 Regeneration Outlet Information ...............................................................................................................21
3.2.7 Dryer Off, Dryer On, EMS On – 3-Position Switch..................................................................................21
3.2.8 Status Lamps..............................................................................................................................................22
3.2.9 Pressure Gages ..........................................................................................................................................22
3.3 INITIAL START-UP.............................................................................................................................................22
3.3.1 Pressurizing Dryer.....................................................................................................................................22
3.3.2 Energizing Dryer Controls ........................................................................................................................23
3.3.3 Pressure Switch Adjustment.......................................................................................................................24
3.3.4 EMS Start Up.............................................................................................................................................24
3.4 SHORT-TERM SHUTDOWN.................................................................................................................................26
3.5 SHUTDOWN IN CASE OF A FAULT OR FOR MAINTENANCE .................................................................................26
3.6 RESTARTING......................................................................................................................................................26
4. MAINTENANCE..................................................................................................................................................27
4.1 CHECKLIST ........................................................................................................................................................27
iii
Page 6
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
4.1.1 Daily Check ...............................................................................................................................................27
4.1.2 Weekly Check..............................................................................................................................................27
4.1.3 Quarterly Check (Every Three Months) ....................................................................................................27
4.1.4 Annual Check.............................................................................................................................................28
4.2 CHANGING THE FILTER ELEMENT......................................................................................................................28
4.3 REPLACEMENT OF THE DESICCANT ...................................................................................................................29
5. PARTS LISTINGS ...............................................................................................................................................31
5.1 PARTS LIST FOR TZE400 TO TZE650................................................................................................................31
5.2 PARTS LIST FOR TZE820 TO TZE1225..............................................................................................................32
5.3 PARTS LIST FOR TZE1500 TO TZE2100............................................................................................................33
5.4 PARTS LIST FOR TZE2500 TO TZE3500.............................................................................................................34
6. FAULTS AND TROUBLESHOOTING .............................................................................................................38
6.1 DEWPOINT HAS DETERIORATED .............................................................................................................38
6.2 HIGH HUMIDITY ALARM OR SENSOR FAILURE ...................................................................................39
6.3 PRESSURE DROP TOO HIGH .......................................................................................................................39
6.4 SWITCHING FAILURE ALARM ...................................................................................................................39
7. DRAWINGS..........................................................................................................................................................42
iv
Page 7
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
1. INTRODUCTION
1.1 GENERAL
This adsorption dryer includes the latest technology and safety features. Its use, however, can endanger life and limb and can lead to considerable damage to the equipment and other material assets if:
it is operated by personnel not instructed in its use,
it is improperly used,
it is improperly maintained or serviced.
Furthermore, ignorance of its use and proper service can result in the loss of any claim for damage.
This adsorption dryer is designed for neutral media (such as air or nitrogen) which is free of aggressive water, oil and solid elements. Ingersoll-Rand accepts no liability for corrosion damage or malfunctions caused by aggressive media.
Applications other than those mentioned in this manual must be agreed to by Ingersoll­Rand and confirmed in writing.
Ingersoll-Rand reserves the right to make changes at any time as may be necessary for increasing safety or efficiency, or In the interests of further product development.
1.2 PRODUCT INFORMATION
The adsorption dryer is used for the purpose of drying compressed air and other gases according to its contracted design. Depending on certain conditions at the inlet, it provides pure, dry and oil-free compressed air or gases. The standard model of adsorption dryer is equipped with two desiccant vessels and a prefilter and afterfilter.
This specific model of dryer includes an Energy Management System (EMS) that provides automatic monitoring and control of the work/regeneration cycle to optimize equipment efficiency. This manual includes references to optionally available Low Dew Point (LDP) and 3-valve bypass (3V) systems/assemblies which may or may not be provided. Selected options included with this dryer are indicated on the cover page by an “X” mark in the box.
1
Page 8
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
1.2.1 PRESSURE VESSEL REGULATIONS
The pressure vessels are designed and built to meet the American Society of Mechanical Engineers (ASME) standards. They fulfill the test of the certifying procedure and carry the ASME symbols U or UM.
RANGE OF APPLICATION
Design Pressure Max: 150 psig
Design Temperature
Max: 500 °F (260 °C)
Min: -20 °F (-29 °C)
1.2.2 LEAK TEST
Each Ingersoll-Rand adsorption dryer is subjected to, and passes, a leak test prior to shipment.
1.3 SAFETY INSTRUCTIONS
This manual contains basic tips which must be followed during set-up, operation and servicing. It is of utmost importance that it be read by the assembly technician before installation and start-up as well as by the specialist/operator in charge. It must always be within reach at the place where the adsorption dryer is being used.
1.3.1 IDENTIFICATION OF SIGNS AND SYMBOLS IN THIS MANUAL
The safety tips contained in this manual, whose disregard could endanger people and equipment, are indicated by a general danger sign and the additional markings Danger! or Attention! or Warning!
Danger! / Attention!
Safety sign in accordance with DIN 4844 - W9
Warning – high voltage!
Safety sign in accordance with DIN 4844 - W8
Safety tips printed directly on the adsorption dryer must be heeded at all times and must be kept completely legible.
2
Page 9
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
1.3.2 GENERAL SAFETY TIPS FOR ASSEMBLY, INSPECTION AND MAINTENANCE
The purchaser is to ensure that all assembly, maintenance and inspection work is carried out by personnel qualified to do it.
The personnel involved in assembly, operation, maintenance and inspection must have the corresponding qualifications to do this work. Areas of responsibility and supervision of the personnel must be clearly established by the purchaser. Should the personnel not possess the necessary knowledge, then they must be instructed. If need be, this training may be carried out by the manufacturer/supplier at the request of the purchaser. Further, the purchaser is to ensure that all personnel completely understand and follow the content of this manual.
Attention!
Never make structural changes to the adsorption dryer
Only use recommended spare parts as listed in section 5
Never weld on a pressure vessel or change it in any way
Carry out maintenance only when the adsorption dryer is OFF,
depressurized and disconnected from the electric power supply.
Danger!
Review the Material Safety Data Sheet (MSDS) provided with the desiccant
Wear protective clothing and goggles when working with the desiccant
If desiccant comes into contact with the eyes, rinse eyes immediately with a lot of clear water
If the desiccant is spilled, clean up without causing swirls of dust
In case of fire, there is no restriction on the use of fire extinguishing
material; the reaction with water and foam is defined as strong
A mask must be worn whenever handling desiccant.
3
Page 10
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
1.4 TECHNICAL DATA SHEET
1.4.1 MODELS TZE400 TO TZE820
Model TZE400 TZE500 TZE650 TZE820 Rated flow @ 100 psig & 100°F inlet conditions Chamber Outer Diameter 18 inches 18 inches 18 inches 20 inches
Desiccant Bed Composition & Pounds per Chamber
Inlet Connection 2-in NPT 2-in NPT 2-in NPT 3-in RF FLG Outlet Connection 2-in NPT 2-in NPT 2-in NPT 3-in RF FLG Recommended Prefilter Recommended Afterfilter Pilot Air Filter Standard Electric Rqmt 460 Vac/3-phase/60 Hz Heater 6 kW 6 kW 8 kW 12 kW
Cycle Time Outlet Pressure Dewpoint -40°F PDP (-100°F LDP)
EMS Control Setting -40°F PDP (-100°F LDP) High Humidity Alarm -35°F PDP (-95°F LDP) Pressure Switch Setpoints Purge Pressure Setting 70 psig 65 psig 55 psig 55 psig Low Purge Alarm Setpoint Heater Outlet Setpoint 425°F End Heating Temperature End Cooling Temperature 120°F Heater Sheath Alarm 1000°F Flow Directions Downward Drying – Upward Regeneration
400 scfm 500 scfm 650 scfm 820 scfm
Standard (no LDP option):
100% Activated Alumina
272 350 433 660
With LDP option – Layered:
33% Mol Sieve (bottom), 67% Activated Alumina (top).
1st MS: 90 1st MS: 115 1st MS: 143 1st MS: 218
2nd AA: 182 2nd AA: 235 2nd AA: 290 2nd AA: 442
HE563 DP563
AR-0003G/B
HE563 DP563
AR-0003G/B
HE 706 DP 706
AR-0003G/B
HE 1100 DP 1100
IR-DP19
8-Hour Cycle –
4 Hours Drying / 4 Hours Regeneration
PSL – 10 psig / PSH – 30 psig below line pressure
60 psig 55 psig 45 psig 45 psig
180°F
4
Page 11
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
1.4.2 MODELS TZE1000 TO TZE1800
Model TZE1000 TZE1225 TZE1500 TZE1800 Rated flow @ 100 psig & 100°F inlet conditions Chamber Outer Diameter 24 inches 24 inches 28 inches 28 inches
Desiccant Bed Composition & Pounds per Chamber
Inlet Connection 3 in RF FLG 3 in RF FLG 3 in RF FLG 4 in RF FLG Outlet Connection 3 in RF FLG 3 in RF FLG 3 in RF FLG 4 in RF FLG Recommended Prefilter Recommended Afterfilter Pilot Air Filter Standard Electric Rqmt 460 Vac/3-phase/60 Hz Heater 17 kW 21 kW 25 kW 28 kW
Cycle Time Outlet Pressure Dewpoint -40°F PDP (-100°F LDP)
EMS Control Setting -40°F PDP (-100°F LDP) High Humidity Alarm -35°F PDP (-95°F LDP) Pressure Switch Setpoints Purge Pressure Setting 70 psig 60 psig 65 psig 70 psig Low Purge Alarm Setpoint Heater Outlet Set Point 425°F End Heating Temperature 180°F End Cooling Temperature 120°F Heater Sheath Alarm 1000°F Flow Directions Downward Drying - Upward Regeneration
1000 scfm 1225 scfm 1500 scfm 1800 scfm
Standard (no LDP option):
100% Activated Alumina
825 990 1055 1320
With LDP option – Layered:
33% Mol Sieve (bottom), 67% Activated Alumina (top). 1st MS: 272 1st MS: 327 1st MS: 348 1st MS: 436 2nd AA: 553 2nd AA: 663 2nd AA: 707 2nd AA: 884
HE1100 DP1100
IR-DP19
HE 1380 DP 1380
IR-DP19
HE 2100 DP 2100
IR-DP19
HE 2100 DP 2100
IR-DP19
8 Hour Cycle –
4 Hours Drying / 4 Hours Regeneration
PSL – 10 PSIG / PSH – 30 PSIG below line pressure
60 psig 50 psig 55 psig 60 psig
5
Page 12
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
1.4.3 MODELS TZE2100 TO TZE3500
Model TZE2100 TZE2500 TZE3000 TZE3500 Rated flow @ 100 psig & 100°F inlet conditions Chamber Outer Diameter 30 inches 36 inches 40 inches 40 inches
Desiccant Bed Composition & Pounds per Chamber
Inlet Connection 4-in RF FLG 4-in RF FLG 6-in RF FLG 6-in RF FLG Outlet Connection 4-in RF FLG 4-in RF FLG 6-in RF FLG 6-in RF FLG Recommended Prefilter Recommended Afterfilter Pilot Air Filter Standard Voltage 460 Vac/3-phase/60 Hz Heater 30 kW 36 kW 43 kW 50 kW
Cycle Time Outlet Pressure
Dewpoint EMS Control Setting -40°F PDP (-100°F LDP) High Humidity Alarm -35°F PDP (-95°F LDP) Pressure Switch Set Points Purge Pressure Setting 60 psig 70 psig 65 psig 60 psig Low Purge Alarm Set Point Heater Outlet Set Point 425°F End Heating Temperature End Cooling Temperature Heater Sheath Alarm 1000°F Flow Directions Downward Drying - Upward Regeneration
2100 scfm 2500 scfm 3000 scfm 3500 scfm
Standard (no LDP option):
100% Activated Alumina
1485 1722 2310 2805
With LDP option – Layered:
33% Mol Sieve (bottom), 67% Activated Alumina (top). 1st MS: 490 1st MS: 568 1st MS: 762 1st MS: 926 2nd AA: 995 2nd AA: 1154 2nd AA: 1548
HE 2100 DP 2100
IR-DP19
HE 2750 DP 2750 IR-DP19
HE 4100 DP 4100
IR-DP19
2nd AA: 1879
HE 4100 DP 4100
IR-DP19
8-Hour Cycle –
4 Hours Drying / 4 Hours Regeneration
-40°F PDP (-100°F LDP)
PSL – 10 psig / PSH – 30 PSIG below line pressure
50 psig 60 psig 55 psig 50 psig
180°F
120°F
6
Page 13
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
1.4.4 DRYER FLOW CAPACITIES
The specific size/model of your dryer was selected to meet performance requirements based on an analysis of air supply and demand capacities. The model selection chart provided following should confirm that this dryer remains suitable for its intended use.
The table following is based on -40oF PDP, 8-hour cycle, activated alumina and average inlet air flow for non-LDP-equipped dryers with EMS. Consult our factory for rated air flows on LDP-equipped dryers.
Design Inlet
MODEL
TZE400 150 220 265 310 355 400 440 480 520 550 TZE500 150 305 355 400 460 500 550 590 645 680 TZE650 150 360 435 505 580 650 705 790 850 905 TZE820 150 460 550 640 735 820 905 990 1070 1150 TZE1000 150 615 715 805 920 1000 1140 1255 1325 1420 TZE1225 150 690 825 955 1100 1225 1360 1490 1610 1735 TZE1500 150 785 960 1150 1275 1500 1600 1730 1875 2010 TZE1800 150 1010 1210 1405 1610 1800 1995 2190 2375 2535 TZE2100 150 1095 1345 1600 1835 2100 2275 2500 2700 2890 TZE2500 150 1480 1735 1985 2270 2500 2820 3100 3355 3585 TZE3000 150 1685 2015 2340 2680 3000 3330 3645 3960 4235 TZE3500 150 1900 2300 2700 3095 3500 3845 4195 4570 4890
Air Pressure
(psig)
60 70 80 90 100 110 120 130 140
Rated inlet air flow (scfm) at given pressures (psig)
(Based upon 100oF inlet air temperature)
Higher pressures are optionally available. Consult factory.
To correct for an inlet temperature other than 100oF, multiply dryer capacity by the temperature correction factor listed below.
CORRECTION FACTOR FOR INLET TEMPERATURE
TEMPERATURE
DEGREES F
Correction Factor
Example: To size for an inlet flow of 950 SCFM @ 105 F and 110 psig.
1. Select model that produce at least 950 SCFM at 110 psig. This case would be the TZE1000 which can dry 1140 SCFM.
2. Multiply pressure corrected flow by the temperature correction factor to obtain the flow of the dryer corrected for pressure and temperature: 1140 X (0.85) = 969 SCFM
3. Confirm model selection. Model TZE1000 can flow 969 SCFM at the inlet conditions specified; requirements of 950 SCFM are less: TZE1000 is correct.
80 90 100 105 110 115 120
1.1 1.1 1.0 0.85 0.69 0.565 0.455
7
Page 14
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
NOTE: Settings for EMS: Standard Dryers: EMS Control -40°F (-40°C)
High Humidity -35°F (-35°C) LDP Dryers: EMS Control -100°F (-74°C) High Humidity -95°F (-69°C).
1.5 OVERLOADING
Attention! Protect the adsorption dryer from overloads!
The adsorption dryer can become overloaded if:
The flow volume of the medium to be dried increases
The temperature of the air at entry and, correspondingly, its
humidity increases
The minimum operating pressure decreases
The prefiltration and separation of impurities are not sufficient or the
filter drain fails
Introduction of oil into the air stream.
1.6 TRANSPORT
Immediately upon delivery of the adsorption dryer, it must be checked for any damage that may have occurred during transport. If necessary, the damage must be recorded on the shipping waybill/receipt. Liability for such damage usually rests with the shipper. Contact Ingersoll-Rand to arrange for any required service or replacement parts.
Attention!
For transport within your company site, only the skids of the adsorption dryer may be used. Lifting at any other points on the equipment will void the warranty and damage the equipment.
1.7 STORAGE
If the adsorption dryer is to be stored for a long period of time, its place of storage must be dry and free of dust. The ambient temperature cannot go below 33°F (+1°C).
1.8 USE OF A PREFILTER AND AFTERFILTER
In order to prevent droplets of condensate, oil and dirt from getting into the desiccant, a Ingersoll-Rand prefilter must be installed upstream of the adsorption dryer. An oil film on the desiccant reduces the drying capacity and the dewpoint. In order to prevent breakdown in downstream consumers caused by material that has been abraded from the desiccant bed, a Ingersoll-Rand afterfilter must be mounted behind the adsorption dryer. Since no condensate accumulates in the afterfilter, this filter is always equipped with a manual vent valve.
8
Page 15
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
Both filters are equipped with a differential pressure indicator to ensure a direct display of the degree of contamination of the filter elements.
2. INSTALLATION
2.1 GENERAL
Ensure that the installation site is free of dust, dirt and litter. The site floor must be level and strong enough to support the equipment. The site itself must be an heated environment (minimum 50°F) to ensure proper operation and warranty protection.
Ensure that the Ingersoll-Rand adsorption dryer is carried only by its skid base frame. The adsorption dryer must be positioned so that the side from which it is to be operated is easily accessible. The piping is to be connected at a slightly downward slope. Install isolation valves on the inlet and outlet sides of the adsorption dryer. Also, a bypass pipe with an additional isolation valve should be mounted onto the adsorption dryer to allow for an uninterrupted supply of compressed air in case the adsorption dryer requires maintenance or repair. The bypass assembly is optionally provided (see paragraph 1.2) or can be customer furnished. If vibrations occur at the installation site, the adsorption dryer skid frame is to be placed onto vibration dampers.
2.2 MECHANICAL ASSEMBLY
The equipment should be located in an area with adequate clearances for
service. An overhead clearance of not less than two feet above each desiccant tower is required for loading of the desiccant.
Remove all protective shipping crates, flange covers, etc.
Using the mounting holes provided on the skid, anchor the dryer to a solid, level
foundation designed to support the equipment.
Do not hydrostatically test the pressure vessels. All TZE dryer pressure vessels
and welded piping are hydrostatically tested at one and one-half times the design pressure after fabrication and before assembly.
Desiccant for models TZE820 and up is shipped loose and must be installed on
site. Refer now to paragraph 4.3 for instructions on installing the desiccant.
If the equipment is installed in a high traffic area, protective barriers may be
required to prevent possible damage of equipment and to prevent contact with hot surfaces.
Due to vibration during shipping some tube fittings may have loosened.
Therefore, inspect all connections and tighten if required.
9
Page 16
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
Ensure that the inlet and outlet connections to and from the dryer are made using
the correctly rated fittings and piping to meet the design conditions.
NOTE: System isolation and by-pass valves should be installed. If not supplied
by Ingersoll-Rand as part of the equipment package (i.e., 3V option – see paragraph 1.2), they should be supplied and installed by others. Ensure that this bypass facility is installed so that future servicing of the dryer system off-line may take place.
Full flow relief valves to protect the system from over-pressure must be
customer-provided in accordance with local regulations.
The purge exhaust on the TZE650 and smaller dryers is equipped with an
exhaust muffler. If required, the muffler can be removed and purge exhaust can be connected to a vent header. Follow recommendations for pipe sizing listed below.
The purge exhaust connection on the TZE820 and larger dryers must be
connected to a vent header. To ensure satisfactory regeneration of the desiccant chambers, the purge exhaust piping should be sized as follows to prevent back­pressure build up.
EXTENDED LENGTH PIPE SIZE REQUIRED TO 10 FEET SAME SIZE AS DRYER EXHAUST TO 25 FEET 1 SIZE LARGER THAN DRYER EXHAUST TO 50 FEET 2 SIZES LARGER THAN DRYER EXHAUST TO 100 FEET 3 SIZES LARGER THAN DRYER EXHAUST
Caution!
The noise at the outlet of the exhaust header may exceed 100 dBa, and the flow velocity will be high. Exhaust must be piped to an area where these flow velocities and noise levels can be safely tolerated.
2.3 FILTER INSTALLATION
2.3.1 PREFILTER INSTALLATION (SHIPPED LOOSE)
Mount prefilter in such a way as to allow clearance for the element installation
and removal.
Locate the prefilter as close to the dryer inlet connection as possible.
The filter must be piped so that the correct flow direction indicated on the filter is
followed.
10
Page 17
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
Ensure that all piping and valves are equivalent or larger in size to the dryer inlet
connection.
Connect drain port to a condensate collector. Use an easily visible collector to
aid in operational inspection.
2.3.2 AFTERFILTER INSTALLATION (SHIPPED LOOSE)
Mount afterfilter in such a way as to allow clearance for the element installation
and removal.
The filter must be piped so that the correct flow direction indicated on the filter is
followed.
Ensure that all piping and valves are equivalent or larger in size to the dryer inlet
connection.
2.3.3 FILTER SKID WITH 3 VALVE BYPASS (IF DRYER INCLUDES 3V OPTION)
Filters skid should be located as close to dryer as possible. Use the skid bolt
holes to secure the assembly.
Ensure that the skid is located such that the 3-valve bypass will bypass the dryer
and filters when in use.
Check the flow direction of each filter to ensure the prefilter is connected to the
inlet pipe of the dryer and afterfilter is connected to the outlet pipe of the dryer.
Connect the filter skid piping and dryer skid piping using materials and fabrication
procedures that are suitable for compressed air pressure piping. All flanges are ANSI B16.5 Class 150 raised face flanges.
2.4 ELECTRICAL CONNECTION
Warning – high voltage!
Be sure that power is removed from the line feed before making
Connect the dryer to a correctly sized power supply. Refer to the dryer
nameplate or the electrical drawing (see section 7) for the supply voltage and amperage requirement to properly size the electrical service. Only one electrical connection is required. All internal wiring was done at the factory.
connection between the site drop and the equipment.
11
Page 18
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
NOTE: A disconnect switch is not provided with the dryer and must be supplied
by the customer in accordance with the local electrical code.
Ground the frame of the dryer in accordance with the local electrical code.
It is recommended that the common alarm relay, located in the dryer control
panel, be connected to the control room or operator station so that an immediate response to the dryer alarm may be given when required.
Before energizing the electrical circuit, the electrical heater assembly should be
inspected to determine that no moisture has accumulated in the heater enclosure or terminations. A 1000V meg-ohmmeter should be used to determine the phase-to-ground insulation resistance for each phase. A minimum value of 500 kOhms should exist.
2.5 EMS CONTROL CONNECTION
A probe sample line must be run from downstream of the afterfilter.
A 10-ft length of 1/8-in stainless steel tubing and necessary compression fittings
are provided.
Tube fittings are to be installed downstream of the afterfilter at the differential
pressure indicator (DPI) port T-fitting on the afterfilter outlet nozzle
Remove the hexagonal plug from the DPI T-fitting.
Insert 1/8-in tubing into compression fitting and tighten.
Run the tubing back to the hygrometer housing. Cut to necessary length and
connect to the upper connection fitting. Tubing is semi-flexible so care must be taken when bending to ensure the tubing does not kink.
If the sample port is installed at a distance longer than the tubing supplied,
contact your Ingersoll-Rand distributor for assistance.
12
Page 19
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3. EQUIPMENT OPERATION
3.1 GENERAL OPERATING PRINCIPLES
This dryer model has two parallel adsorption chambers filled with desiccant. While the medium is being dried flowing top-down in one chamber, regeneration takes place from the bottom up in the other chamber. The changeover from one chamber to the other is controlled by the Energy Management System that monitors desiccant performance by measuring the outlet air dew point. It can operate continuously and is fully automatic.
The standard dryer with EMS has a cycle time of eight hours. Half the cycle time is dedicated to air drying work and the other half to desiccant regeneration, with one chamber working to dry the air while the other regenerates. The dryer is configured at the factory.
Wet air enters the working desiccant chamber (it can be either the left or right) at the inlet switching valves (top) and is dried as it flows downward through the desiccant bed. Dry air exits the dryer through the outlet check valve.
The regeneration of the off-line tower begins with a heating cycle. After having depressurized the off-line tower, the purge orifice allows a portion of the dry outlet air to flow across the regeneration heater. The heated regeneration air then passes upward through the desiccant bed where it picks up previously adsorbed moisture from the desiccant and is then evacuated to atmosphere through the purge exhaust valve.
At the completion of the regeneration heating cycle, the cooling cycle begins. The regeneration heater is de-energized. The purge orifice allows a portion of the dry outlet air to flow through the off-line tower. It is then evacuated to atmosphere through the purge exhaust valve. When the cooling cycle is completed, the purge exhaust valve is closed and the off-line tower is repressurized. Once at line pressure, the dryer is ready to switch drying from one tower to the other. Dryer models TZE3000 and 3500 have purge control valves which close once at line pressure and prior to switching from one tower to the other.
The purge air is controlled by a purge adjusting valve and purge orifice located in the purge line. Purge pressure is indicated on the purge pressure gauge.
Ingersoll-Rand high-efficiency prefilters and reverse-flow afterfilters are designed to remove solids, oil and water condensate from compressed air and other neutral, compressed gases. These filters provide high flows and low differential pressures.
13
Page 20
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
The prefilter is designed to flow from the inside to the outside. The afterfilter is designed to flow from the outside to the inside. Solids are filtered out by impact or by the effect of inertia, whereas oil particles and drops of moisture are filtered out by the effect of coalescence. The contaminants collect at the bottom of the filter vessel and are drained automatically or manually.
3.1.1 DRYER PROGRAM STEPS
This automatic dryer is equipped with a PLC which retains last-position data in the event of a power failure or fast shutdown. The dryer will restart at the last position or can be manually cycled on the operator interface to reset at step 1.
14
Page 21
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
STEP 1
OPEN LEFT CHAMBER
INLET VALVE
EV-1L & EV-11R (VALVE TO MOVE)
10-SEC TIMER/VALVE TO OPEN
10 SEC PASS, LEFT CHAMBER ABOVE 60 psig
STEP 8
OPEN RIGHT CHAMBER
INLET VALVE
EV-1R & EV-11L (VALVE TO MOVE)
10-SEC TIMER/VALVE TO OPEN
10 SEC PASS, RIGHT CHAMBER ABOVE 60 psig
STEP 2
5 SEC PASS
STEP 3
10 SEC PASS AFTER RIGHT CHAMBER BELOW 30 psig
STEP 4
HEATING TIMER FINISH OR PURGE OUTLET TEMP ABOVE 200-DEG F
STEP 5
IF COOLING TIMER DONE (100 MINUTES) OR PURGE OUTLET TEMP BELOW 120-DEG F & 60 MINUTES PASSED
CLOSE RIGHT
CHAMBER INLET VALVE
EV-1L & EV-11R WAIT 5 SEC
FOR VALVE TO CLOSE
DEPRESSURIZE
RIGHT CHAMBER
EV-2R & EV-3R (IF R/C <10 psig)
ENERGIZE EV-1L & EV-11R
RIGHT CHAMBER
HEATING PERIOD
START R/C HEATING MODE FOR 140 MINUTES MAXIMUM; ENERGIZE EV-1L AND EV11R
RIGHT CHAMBER
COOLING PERIOD
START R/C COOLING MODE FOR
100 MINUTES MAXIMUM /
60 MINUTES MINIMUM;
ENERGIZE EV-1L & EV-11R
CLOSE LEFT CHAMBER
STEP 9
5 SEC PASS
STEP 10
10 SEC PASS AFTER LEFT CHAMBER BELOW 30 psig
STEP 11
HEATING TIMER FINISH OR PURGE OUTLET TEMP ABOVE 200-DEG F
STEP 12
IF COOLING TIMER DONE (100 MINUTES) OR PURGE OUTLET TEMP BELOW 120-DEG F & 60 MINUTES PASSED
INLET VALVE
EV-1R & EV-11L WAIT 5 SEC FOR
VALVE TO CLOSE
DEPRESSURIZE LEFT CHAMBER
EV-2L & EV-3L (IF L/C <10 psig)
ENERGIZE EV-1R & EV-11L
LEFT CHAMBER
HEATING PERIOD
START L/C HEATING MODE
FOR 140 MINUTES MAXIMUM
ENERGIZE EV-1R & EV11L
LEFT CHAMBER
COOLING PERIOD
START L/C COOLING MODE FOR
100 MINUTES MAXIMUM /
60 MINUTES MINIMUM
ENERGIZE EV-1R & EV-11L
STEP 6
120 SEC PASS & BOTH CHAMBERS ARE ABOVE 60 psig
STEP 7
DRYER HALF-CYCLE COMPLETED (240 MINUTES) OR BAD DEWPOINT OR EMS OFF & BOTH CHAMBERS ARE ABOVE 60 psig
GO TO STEP 8
REPRESSURIZE
RIGHT CHAMBER
ENERGIZE EV-1L & EV-11R
RIGHT CHAMBER
STANDBY
ENERGIZE EV-1L & EV-11R
STEP 13
120 SEC PASS & BOTH CHAMBERS ARE ABOVE 60 psig
STEP 14
GO TO STEP 1
REPRESSURIZE
LEFT CHAMBER
ENERIZE EV-1R & EV-11L
LEFT CHAMBER
STANDBY
ENERGIZE EV-1R & EV11L
DRYER HALF-CYCLE COMPLETED (240 MINUTES) OR BAD DEWPOINT OR EMS OFF & BOTH CHAMBERS ARE ABOVE 60 psig
Su SD E
FIGURE 1 – DRYER PROGRAMMED STEPS
15
Page 22
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3.2 OPERATOR CONTROLS / LOW-VOLTAGE CONTROL PANEL
The operator status display and control interface (i.e., monitor) is detailed in Figure 2. It is provided to allow the operator to manually cycle through the programmed steps, and to indicate system status. The system operating setpoints cannot be changed at this panel.
16
Page 23
USER MANUAL
In order to choose one of the next four options, the SHIFT button
must be pressed first. An “s” in the lower right corner indicates the
shing
arrow on the right side of the screen indicates that more information is
available in the direction of the arrow and can be accessed by using
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
TEXT DISPLAY
F1 – DRYER STATUS F2 – MANUAL STEP AHEAD (MANUAL MODE ONLY) F3 – DRYER ALARM STATUS
– ALARM RESET
F4 SHIFT –
upper row is now active.
F5 – DRYER OPERATING MODE MENU F6 – HEATER SHEATH TEMPERATURE AND SETPOINT F7 – HEATER OUTLET TEMPERATURE AND SETPOINTS F8 – REGENERATION OUTLET TEMPERATURE AND SETPOINTS
Arrows allow user to scroll up or down within the display. A fla
the scroll arrows.
ESC – ACCESSES THE MENU MODE (ACCESS IS NOT REQUIRED). ENTER – NO FUNCTIONALITY FOR THIS BUTTON.
FIGURE 2 – OPERATOR MONITOR
17
Page 24
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3.2.1 DRYER STATUS
The F1 key is pressed to display the present status of the dryer. This allows you to see which step of the program cycle is currently engaged. A message can appear below the dryer status at any time when in manual mode. A blinking arrow on the right side of the display will indicate this. To access the messages, press the green arrow on the right side of the interface.
MESSAGE IDENTIFICATION MESSAGE DESCRIPTION
SELECT LEFT CHAMBER DRYING LEFT CHAMBER DRYING
R/C IN DEPRESS MODE LEFT CHAMBER DRYING R/C IN HEATING MODE LEFT CHAMBER DRYING R/C IN COOLING MODE LEFT CHAMBER DRYING R/C IN REPRESS MODE LEFT CHAMBER DRYING R/C IN STANDBY MODE
LEFT CHAMBER IN EMS MODE R/C IN STANDBY MODE
SELECT RIGHT CHAMBER DRYING RIGHT CHAMBER DRYING L/C IN DEPRESS MODE RIGHT CHAMBER DRYING L/C IN HEATING MODE RIGHT CHAMBER DRYING L/C IN COOLING MODE RIGHT CHAMBER DRYING L/C IN REPRESS MODE RIGHT CHAMBER DRYING L/C IN STANDBY MODE
RIGHT CHAMBER IN EMS MODE L/C IN STANDBY MODE
Opening the left chamber (L/C) inlet valve. Closing the right chamber (R/C) inlet valve.
Depressurizing the right chamber.
Heating the right chamber for regeneration.
Cooling the right chamber.
Pressurizing the right chamber. Right chamber in standby until the end of the
half cycle. The dryer is in EMS mode on the left chamber. This will extend the half cycle for a maximum of 12 hours or until the outlet dewpoint goes higher than -40°F. Opening the right chamber inlet valve. Closing the left chamber inlet valve.
Depressurizing the left chamber.
Heating the left chamber for regeneration.
Cooling the left chamber.
Pressurizing the left chamber. Left chamber in standby until the end of the
half cycle. The dryer is in EMS mode on the right chamber. This will extend the half cycle for a maximum of 12 hours or until the outlet dewpoint goes higher than -40°F.
18
Page 25
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3.2.2 ALARM INFORMATION
The F3 button is pressed to display the status of the dryer alarms. If there is no alarm, a NO ALARM message will appear. If more than one alarm is active, a flashing arrow will appear on the right side of the display. To access the messages, press the green arrow on the right side of the panel. In order to reset non-active alarms, press the F4 key. When all the alarm conditions have been cleared, the NO ALARM message will appear.
MESSAGE IDENTIFICATION MESSAGE DESCRIPTION
HEATER OUTLET OVER TEMPERATURE
THERMOCOUPLE MODULE IN ERROR
THERMOCOUPLE OUT OF RANGE
HEATER FAILURE ALARM FAIL REACH SETPOINT
OVERSHEATH ALARM SHEATH TEMPERATURE TOO HIGH
DEPRESS FAILURE ON LEFT CHAMBER
DEPRESS FAILURE ON RIGHT CHAMBER
REPRESS FAILURE ON LEFT CHAMBER
REPRESS FAILURE ON RIGHT CHAMBER
HIGH HUMIDITY ALARM NO ALARM Indicates no alarm is active.
Heater outlet temperature is above the setpoint. Indicates the thermocouple module has lost it’s 24Vdc supply. Indicates a thermocouple connected to the module is defective or open. The heater has failed to reach the setpoint temperature within 15 minutes. The heater sheath temperature is above the setting. The left chamber did not reach the low setting of the pressure switch within time limit. The right chamber did not reach the low setting of the pressure switch within time limit. The left chamber did not reach the high setting of the pressure switch within time limit. The right chamber did not reach the high setting of the pressure switch within time limit. Indicates the outlet dewpoint is above alarm setpoint.
19
Page 26
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3.2.3 DRYER OPERATION MODES
The F5 button is pressed to display the dryer mode of operation. The actual mode will be displayed whether it is in automatic or manual mode. To change the actual mode of the dryer, press F2 when in the dryer mode screen. The actual mode will change from one to the other each time the F2 button is pressed. If the dryer mode screen is left unattended for thirty seconds, it will automatically switch to the dryer status screen. In manual mode, the READY TO STEP AHEAD PRESS F2 TO CONTINUE message will be shown when the dryer is ready to perform the next step. In order to go to the next step in manual mode you must not be in the dryer operation mode screen. Failure to do so will simply change the operating mode of the dryer.
MESSAGE IDENTIFICATION MESSAGE DESCRIPTION
The dryer is in automatic mode. The dryer
DRYER IN AUTO MODE
DRYER IN MANUAL MODE
READY TO STEP AHEAD PRESS F2 TO CONTINUE
will perform its cycle without any external intervention except in case of alarm. The dryer is in manual mode. The dryer will need external intervention in order to do to the following step. If no external intervention is provided the dryer will stay in that step. The dryer is ready to go to the next step when in manual mode. The user must wait for this signal in order to press F2 for making the dryer step ahead in its cycle.
3.2.4 HEATER SHEATH INFORMATION
The F6 button accesses heater sheath information. On this screen the actual sheath temperature in degrees Fahrenheit is displayed and so is the temperature setpoint for the sheath over-temperature alarm. The setpoint cannot be changed from the panel.
MESSAGE IDENTIFICATION MESSAGE DESCRIPTION
Displays temperature of the heater sheath
HEATER SHEATH XXXX F ALARM SETPOINT YYYY F
20
(XXXX) and also at which temperature the dryer will turn in alarm (YYYY). Both temperatures are in degrees Fahrenheit.
Page 27
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3.2.5 HEATER OUTLET INFORMATION
The F7 button accesses the heater outlet information. On this screen the actual temperature in degrees Fahrenheit is displayed and so is the temperature setpoint for the heater outlet over-temperature and heating failure alarm. The setpoint cannot be changed at the panel.
MESSAGE IDENTIFICATION MESSAGE DESCRIPTION
Displays the heater outlet temperature HEATER OUTLET XXXX F HEAT CONTROL YYYY F
HEATER OUTLET XXXX F HEAT FAIL AT ZZZZ F
HEATER OUTLET XXXX F HEAT OVERTEMP VVVV F
(XXXX) and the regulation temperature
setting (YYYY) of the heater.
Both temperatures are in degrees F.
Displays the actual heater outlet temperature
(XXXX) and the heating failure alarm
temperature setting (ZZZZ).
Both temperatures are in degrees F.
Displays the actual heater outlet temperature
(XXXX) and the high outlet temperature
alarm setting (VVVV).
Both temperatures are in degrees F.
3.2.6 REGENERATION OUTLET INFORMATION
The F8 button accesses regeneration outlet information. On this screen the actual temperature in degrees Fahrenheit is displayed and so are the control setpoints for end of heating and end of cooling. The setpoints cannot be changed at the panel.
MESSAGE IDENTIFICATION MESSAGE DESCRIPTION
Displays the actual regeneration outlet REGEN OUTLET XXXX F HEAT SETPOINT YYYY F
temperature (XXXX) and the end of heating
mode temperature setting (YYYY).
Both temperatures are in degrees F.
Displays the actual regeneration outlet REGEN OUTLET XXXX F COOL SETPOINT ZZZZ F
temperature (XXXX) and the end of cooling
mode temperature setting (ZZZZ).
Both temperatures are in degrees F.
3.2.7 DRYER OFF, DRYER ON, EMS ON – 3-POSITION SWITCH
This 3-position switch provides for manual selection of dryer basic functions. Ensure that the switch is set at DRYER OFF before beginning the initial startup procedure.
21
Page 28
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3.2.8 STATUS LAMPS
A green light announces that there is POWER at the control panel when lit. A red light announces that there is an ALARM condition when lit. Refer to the operator monitor to determine the cause.
3.2.9 PRESSURE GAGES
Three gages are mounted in a row above the low-voltage control panel. The two outside read the pressure within each chamber (left side for left chamber, right for right) and the middle gage shows the purge pressure.
3.3 INITIAL START-UP
Attention!
All pipes and wire connections must be tightened!
Furthermore, before start-up:
The pipes must be checked for the presence of scale, abraded material from the threading, or other similar impurities.
All isolation valves on the prefilter, afterfilter and on the bypass line (if installed) should be closed.
The ambient temperature must not be less than 33°F.
NOTE: Breakdown resulting from faulty installation does not fall under the
Ingersoll-Rand warranty obligation.
3.3.1 PRESSURIZING DRYER
Prior to pressurizing the dryer system, verify the following:
DRYER OFF/DRYER ON/EMS ON switch is in the DRYER OFF position
System outlet block valve is closed
Prefilter, afterfilter and pilot air filter vent valves are closed
Desiccant chamber vent valve is closed
Pilot air isolation valve is open
Hygrometer adjustment/isolation valves are closed.
Slightly open the inlet isolation valve to slowly admit compressed air to the system. When full system operating pressure has been reached, all connections should be soap
22
Page 29
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
bubble tested for leaks. Any leaks should be repaired and retested prior to placing the equipment in service. If some gas other than the process air will be used for leak testing, consult Ingersoll-Rand for its compatibility with system components before proceeding.
Fully open the inlet isolation valve.
When the system is filled with process air and leak tight, slowly open the system outlet valve to pressurize the downstream piping. During this procedure, ensure that the dryer system pressure does not fall beyond 95% of its reading prior to opening the system outlet valve. This will protect the equipment internal components (i.e., filter elements, desiccant) from gas velocities above design conditions.
When pressurizing is complete, then fully open the system outlet valve to place the equipment in service.
Verify that the system inlet pressure and temperature are at the design operating levels (see paragraph 1.4)
Ensure that the pilot pressure regulator is set between 80 and 100 psig.
3.3.2 ENERGIZING DRYER CONTROLS
Turn 3-position switch to the DRYER ON position.
The operator monitor controls the dryer cycle. This should be used as a reference guide to ensure dryer is cycling. A manual mode is included in the dryer program to allow for fast cycling to verify to operation of the dryer.
Review the operational program of the dryer (paragraph 3.1.1) and the wiring schematic (see section 7) before operating the dryer.
NOTE: The hygrometer will signal an open circuit (the ALARM light will
illuminate) until probe cable is connected to hygrometer probe. This connection is described in paragraph 3.3.4 – leave it as is for now.
While dryer is in purge mode for either chamber, the regeneration pressure setting should be checked. Refer to paragraph 3.3.3 for the correct blower flow setting.
Warning!
Failure to correctly set the purge pressure can lead to improper regeneration of the desiccant bed, resulting in a dewpoint failure when the chamber is returned to service.
23
Page 30
USER MANUAL
ADJUSTMENT
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3.3.3 PRESSURE SWITCH ADJUSTMENT
On the TZE dryer there are four pressure switches: PSH-1, PSL-1, PSH-2 and PSL-2.
The PSH pressure switches are set at 30 psig below the operating pressure of the dryer, and use the normally open contact. When the adjustment is done, the contact between C and NC should close when increasing to the desired pressure.
The PSL switches are set at 10 psig regardless of the operating pressure and use the normally closed contact. When the adjustment is done, the contact between C and NC should close when decreasing to the desired pressure.
To increase the pressure, screw the knob toward the pressure switch diaphragm (see figure 3). To decrease the pressure, turn away from the pressure switch diaphragm.
KNOB
FIGURE 3 – PRESSURE SWITCH ADJUSTMENT
3.3.4 EMS START UP
Refer to the general assembly drawing provided in section 7, and to figure 4.
The EMS hygrometer probe has been shipped inside of its own sealed package to ensure that the probe does not become saturated with ambient air during storage and transport. Do not remove probe from the package until dryer system has been started and probe is to be inserted into the sample cell.
24
Page 31
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
Check that the sample line is connected from the dryer outlet to the inlet valve on the humidity probe sample cell.
Check that the humidity probe is installed into the sample cell.
Connect the cable to the humidity probe.
Fully open the inlet valve to the sample cell.
Partially open the discharge valve of the sample cell to vent off a small amount of
sample air. Do not fully open discharge valve.
Perform a soap bubble test to check for leaks on all parts of the sample line connections and the humidity sample cell.
The digital display will now read the dewpoint of the dryer system. It will take a short period of time for a humidity probe to be purged of humidity.
FIGURE 4 – HYGROMETER PROBE ASSEMBLY
NOTE: The dryer should be operated in the DRYER ON position at the time of
initial start-up and at all times when the hygrometer or humidity probe are removed for service.
25
Page 32
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3.4 SHORT-TERM SHUTDOWN
Follow this sequence when switching off the adsorption dryer:
First close all the shutoff valves up- and downstream of dryer
Then immediately switch DRYER OFF.
Danger!
Dryer will remain pressurized.
3.5 SHUTDOWN IN CASE OF A FAULT OR FOR MAINTENANCE
Follow this sequence when switching off the adsorption dryer:
First switch off the dryer. Make certain dryer is not in heating or cooling mode. The dryer electrical panel will still have power. The dryer disconnect must be turned off before opening electrical panel.
Close all the isolation valves upstream and downstream of the adsorption dryer.
Depressurize the dryer by using the hand valve mounted at the bottom of the
desiccant chamber.
Depressurize the filters by opening vent valves at the bottom of each filter vessel.
Danger!
Before any kind of maintenance or repair work is done, the dryer must be depressurized and disconnected from the power source.
3.6 RESTARTING
Close the hand valve mounted at the bottom of the afterfilter and at the bottom of each desiccant chamber
Slowly open the inlet isolation valve and pressurize the dryer up to the regular operating pressure by keeping the shutoff valve mounted behind the afterfilter closed.
Switch DRYER ON.
NOTE: If the dryer is restarted after a long standstill, proceed as for an initial
start-up (see paragraph 3.3).
26
Page 33
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
4. MAINTENANCE
4.1 CHECKLIST
These checks are to be carried out by the operator during the routine operations cycle.
4.1.1 DAILY CHECK
Operate prefilter drain ball valve as required to prevent excess accumulation. This may require frequent exercise depending on line moisture content. If the drain is automatic, check for functionality and blow down daily to remove accumulated fluids.
Check filter differential pressures. A filter differential pressure of 5 to 8 psi (or pointing in the red field) indicates a dirty filter element and it should be replaced. Filter elements should last between 6 to 12 months under normal use.
Check correct purge pressure.
Ensure dryer is cycling without alarms.
4.1.2 WEEKLY CHECK
Check all mufflers for backpressure. Replace if clogged or dirty.
Verify heater operation.
4.1.3 QUARTERLY CHECK (EVERY THREE MONTHS)
Check operating conditions, purge rate, line pressure, inlet flow.
Check dryer operating cycle for proper operation of valve operators, solenoid
valves, dump valves, heaters, pressure switches and temperature controller.
Check the outlet dewpoint.
Blow down relief valves.
Check heater outlet temperature is between 400°F and 425°F.
Verify pressure switch operation.
Inspect pilot air filter element. If element seems clogged, dirty or damaged,
replace it.
27
Page 34
USER MANUAL
ain pollutants as appropriate to their function.
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
4.1.4 ANNUAL CHECK
Disassemble, clean and inspect the inlet switching, purge exhaust and depressurization valves/actuators. Replace all worn or damaged parts.
Disassemble, clean and inspect the outlet and purge check valves. Replace all worn or damaged parts.
Inspect the desiccant through the chamber fill port. Replace desiccant if degraded or if oil is present (see paragraph 4.3).
Replace prefilter, afterfilter and pilot air filter elements at least once a year.
Replace the dewpoint sensor humidity probe.
NOTE: Should the need for spare parts or service arise during work on the
adsorption dryer, the dryer model and its serial number must be conveyed to Ingersoll-Rand. This information is given on the nameplate mounted on the control cabinet. Telephone Ingersoll-Rand to arrange for maintenance support (1-800-526-3615).
4.2 CHANGING THE FILTER ELEMENT
The filter element within the filter housing must be replaced annually
Depressurize the dryer and switch DRYER OFF
Danger!
Change filter elements only when the housing is fully depressurized
Separate the lower part of the housing from the upper part
Loosen and remove the element by hand
Install the new filter and the O-ring/gasket, making sure that the filter seats
perfectly
Refit the filter housing.
NOTE: Filter elements cannot be cleaned or reused.
Attention!
Filters may cont Dispose of used filters in accordance with your local, state and federal
28
Page 35
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
regulations.
4.3 REPLACEMENT OF THE DESICCANT
Desiccant life is determined by the care with which it is handled, the quality of filtered inlet air provided and by its time in use. Be careful to not abrade (i.e., wear down) the desiccant when installing it. Proper filtering of inlet air, and constant pressure and temperature, will also extend its life. In order to ensure trouble-free operation, we recommend replacing the desiccant every 10,000 operating hours, or every 3 years.
The following considerations determine the life expectancy of desiccant:
Care in installation
Quality of input gas (e.g., air)
Constancy of flow and temperature
Whether full-service cycling or low-demand usage
Time in service.
The following clues will suggest that you examine the desiccant and consider its replacement:
Discoloring of desiccant (e.g., oil residue, other contaminants): a brown or yellow tinge indicates that the adsorbancy capacity of the desiccant has been diminished
Frequent afterfilter replacement due to desiccant dust accumulation
Performance dew point rises.
Refer to paragraph 1.4 to determine the desiccant quantity required for your model of dryer.
Close dryer inlet/outlet isolation valves
Depressurize and switch DRYER OFF
Danger!
Wear protective equipment and clothing when handling desiccant.
Remove the drain plug and empty the old desiccant into a container
29
Page 36
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
4.3 REPLACEMENT OF THE DESICCANT (CONTINUED)
Screw the plug back in and fill with new desiccant from above (refer to paragraph
Start up the adsorption dryer in accordance with paragraph 3.3 for initial start-up.
Danger!
Desiccant may contain pollutants.
Desiccant is to be disposed of in accordance with local, state
and federal regulations.
1.4 regarding quantities for each chamber)
30
Page 37
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
5. PARTS LISTINGS
5.1 PARTS LIST FOR TZE400 TO TZE650
Description TZE400 TZE500 TZE650
Part # Qty Part # Qty Part # Qty
Consumables
Prefilter ( Element Only ) Afterfilter ( Element Only )
Muffler 38328167 2 38328167 2 38328167 2 Moisture Indicator 38016713 1 38016713 1 38016713 1 Activated Alumina – Pounds 38335253 544 38335253 700 38335253 866
Probe Recalibration
LDP Option
Activated Alumina – Pounds 38335253 364 38335253 470 38335253 580 Molecular Sieve 4A – Pounds
Inlet Valve
Inlet Valve Kit/ 38331666 2 38331666 2 38331666 2 Inlet Valve Solenoid Block 38331120 1 38331120 1 38331120 1 Gasket Consult factory
Outlet Valve
Valve Kit Consult factory Check Valve 38015855 2 38015855 2 38015855 2 Gasket 38049490 4 38049490 4 38049490 4
Purge
Purge Valve Kit 38331708 2 38331708 2 38331708 2 Purge Valve 38007076 1 38007076 1 38007076 1 Purge Exhaust Valve 38331716 2 38331716 2 38331716 2
3V Bypass Option
Ball Valve 38049540 3 38049540 3 38049540 3
EMS
Digital Panel Meter 38431730 1 38431730 1 38431730 1
Replacement Parts
Pressure Gauge 38006714 3 38006714 3 38006714 3 PLC 38028759 1 38028759 1 38028759 1 Power Supply 38328357 1 38328357 1 38328357 1 Text Display 38018065 1 38018065 1 38018065 1 Thermocouple 38031001 1 38031001 1 38031001 1 Relief Valve 38007084 2 38007084 2 38007084 2 Temperature Indicator 38006698 2 38006698 2 38006698 2 Heater 38028668 1 38028668 1 38028676 1 Gasket Consult factory Pressure Regulator 38015145 1 38015145 1 38015145 1 Pressure Switch 38006565 5 38006565 5 38006565 5 Light Bulb 38335212 2 38335212 2 38335212 2
Refer to filter
38049482
38340030 180 38340030 230 38340030 286
38331658 2 38331658 2 38331658 2
1
nameplate or
consult factory
38049482
1
38049482
1
31
Page 38
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
Description TZE400 TZE500 TZE650
Transformer Primary Fuse 38015244 2 38015244 2 38015244 2 Transformer Secondary Fuse 38006870 1 38006870 1 38006870 1 Heater Fuses 38006896 3 38006896 3 38006896 3 Control Fuses 38015236 1 38015236 1 38015236 1 Control Relay Consult factory Heater contactor 38049367 1 38049367 1 38049367 1
5.2 PARTS LIST FOR TZE820 TO TZE1225
Description TZE820 TZE1000 TZE1225
Part # Qty Part # Qty Part # Qty
Consumables
Prefilter ( Element Only ) Afterfilter ( Element Only )
Pilot Air Filter Element 38049474 1 38049474 2 38049474 2 Depressurization Muffler 38328167 2 38328167 2 38328167 2 Activated Alumina – Pounds 38335253 1320 38335253 1650 Probe Recalibration 38049482 1 38049482 1 38049482 1
LDP Option
Activated Alumina – Pounds 38335253 882 38335253 1106 Molecular Sieve 4A – Pounds 38340030 436 38340030 542 38340030 654
Inlet Valve
Inlet Valve Kit/ 38438875 2 38438875 2 38438875 2 Inlet Valve Solenoid Block 38015889 1 38015889 1 38015889 1 Gasket Consult factory
Outlet Valve
Valve Kit 38436879 1 38436879 1 38436879 Check Valve 38015715 2 38015715 2 38015715 2 Gasket 38027769 4 38027769 4 38027769 4
Purge
Purge Valve 38007068 2 38007068 2 38007068 2 Purge Valve Gasket 38049490 4 38049490 4 38049490 4 Exhaust Valve 38331690 2 38331690 2 38331690 2 Exhaust Valve Kit 38331708 2 38331708 2 38331708 2
3V Bypass Option
Manual Butterfly Valve Kit 38049599 3 38049599 3 38049599 3 Gasket, 3-inch 38027769 6 38027769 6 38027769 4 Bypass Valve 38049581 3 38049581 3 38049581 3
EMS
Digital Panel Meter 38431730 1 38431730 1 38431730 1
Replacement Parts
Pressure Gauge 38006714 3 38006714 3 38006714 3 PLC 38028759 1 38028759 1 38028759 1 Power Supply 38328357 1 38328357 1 38328357 1
Refer to filter
38438842 2 38438842 2 38438842 2
nameplate or
consult factory
38335253 1980
38335253 1326
32
Page 39
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
Description TZE820 TZE1000 TZE1225
Text Display 38018065 1 38018065 1 38018065 1 Thermocouple 38031001 1 38031001 1 38031001 1 Relief Valve 38007084 2 38007084 2 38026852 2 Temperature Indicator 38006706 2 38006706 2 38006706 2 Heater 38006953 1 38006938 1 38015475 1 Gasket Consult factory Pressure Regulator 38015145 1 38015145 1 38015145 Pressure Switch 38006565 1 38006565 5 38006565 5 Light Bulb 38335212 2 38335212 2 38335212 2 Transformer Primary Fuse 38015244 2 38015244 2 38015244 2 Transformer Secondary Fuse 38006870 1 38006870 1 38006870 1 Heater Fuses 38006821 3 38015293 3 38015335 3 Control Fuses 38015236 1 38015236 1 38015236 1 Control Relay Consult factory Heater Contactor 38049367 1 38049367 1 38049367 1
5.3 PARTS LIST FOR TZE1500 TO TZE2100
Description TZE1500 TZE1800 TZE2100
Part # Qty Part # Qty Part # Qty
Consumables
Prefilter ( Element Only ) Afterfilter ( Element Only )
Pilot Air Filter Element 38049474 1 38049474 2 38049474 2 Depressurization Muffler 38328167 2 38328167 2 38328175 2 Activated Alumina – Pounds 38335253 2110 38335253 2640 Probe Recalibration 38049482 1 38049482 1 38049482 1
LDP Option
Activated Alumina – Pounds Molecular Sieve 4A – Pounds 38340030 696 38340030 872 38340030 980
Inlet Valve
Inlet Valve Kit/ 38438875 2 38438883 2 38438883 2 Inlet Valve Solenoid Block 38015871 1 38015871 1 38015871 1 Gasket Consult factory
Outlet Valve
Valve Kit 38436879 1 38437299 1 38437299 Check Valve 38015715 2 38015764 2 38015764 2 Gasket 38027769 4 38329637 4 38329637 4
Purge
Purge Valve 38007019 2 38007019 2 38007019 2 Purge Valve Gasket 38027769 4 38027769 4 38027769 4 Exhaust Valve 38438842 2 38438842 2 38438842 2 Exhaust Valve Kit 38438875 2 38438875 2 38438875 2
3V Bypass Option
Refer to filter
38335253
38438842 2 38438859 2 38438859 2
1414
nameplate or
consult factory
38335253
1768
38335253 2970
38335253
1990
33
Page 40
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
Description TZE1500 TZE1800 TZE2100
Manual Butterfly Valve Kit 38049599 3 38049607 3 38049607 3 Gasket, 3-inch 38027769 6 38329637 6 38329637 4 Bypass Valve 38049581 3 Consult factory 3 Consult factory 3
EMS
Digital Panel Meter 38431730 1 38431730 1 38431730 1
Replacement Parts
Pressure Gauge 38006714 3 38006714 3 38006714 3 PLC 38028759 1 38028759 1 38028759 1 Power Supply 38328357 1 38328357 1 38328357 1 Text Display 38018065 1 38018065 1 38018065 1 Thermocouple 38031001 1 38031001 1 38031001 1 Relief Valve 38026852 2 38026852 2 38026852 2 Temperature Indicator 38006706 2 38006706 2 38006706 2 Heater 38028684 1 38006912 1 38028692 1 Gasket Consult factory Pressure Regulator 38015145 1 38015145 1 38015145 Pressure Switch 38006565 1 38006565 5 38006565 5 Light Bulb 38335212 2 38335212 2 38335212 2 Transformer Primary Fuse 38015244 2 38015244 2 38015244 2 Transformer Secondary Fuse 38006870 1 38006870 1 38006870 1 Heater Fuses 38015285 3 38006854 3 38006854 3 Control Fuses 38015236 1 38015236 1 38015236 1 Control Relay Consult factory Heater Contactor 38049383 1 38049409 1 38049409 1
5.4 PARTS LIST FOR TZE2500 TO TZE3500
Description TZE2500 TZE3000 TZE3500
Part # Qty Part # Qty Part # Qty
Consumables
Prefilter ( Element Only ) Afterfilter ( Element Only )
Pilot Air Filter Element 38049474 1 38049474 2 38049474 2 Depressurization Muffler 38328175 2 38328175 2 38328175 2 Activated Alumina – Pounds 38335253 3444 38335253 4620 Probe Recalibration 38049482 1 38049482 1 38049482 1
LDP Option
Activated Alumina – Pounds Molecular Sieve 4A – Pounds 38340030 1136 38340030 1524
Inlet Valve
Inlet Valve Kit/ 38438883 2 38438891 2 38438891 2 Inlet Valve Solenoid Block 38015871 1 38332391 1 38332391 1 Gasket Consult factory
Outlet Valve
Refer to filter
38335253
38438859 2 38438867 2 38438867 2
2308
nameplate or
consult factory
38335253
3096
38335253 5610
38335253 38340030 1852
3758
34
Page 41
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
Valve Kit 38437299 1 38437307 1 38437307 Check Valve 38015764 2 38015822 2 38015822 2 Gasket 38329637 4 38329645 4 38329645 4
35
Page 42
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
5.4 PARTS LIST FOR TZE2500 TO TZE3500 (CONTINUED)
Description TZE2500 TZE3000 TZE3500
Purge
Purge Valve 38007019 2 38007035 2 38007035 2 Purge Valve Gasket 38027769 4 38329637 4 38329637 4 Exhaust Valve 38438842 2 38438859 2 38438859 2 Exhaust Valve Kit 38438875 2 38438883 2 38438883 2
3V Bypass Option
Manual Butterfly Valve Kit 38049607 3 Consult factory 3 Consult factory 3 Gasket, 3-inch 38329637 6 Consult factory 6 Consult factory 4 Bypass Valve Consult factory Consult factory Consult factory
EMS
Digital Panel Meter 38431730 1 38431730 1 38431730 1
Replacement Parts
Pressure Gauge 38006714 3 38006714 3 38006714 3 PLC 38028759 1 38028759 1 38028759 1 Power Supply 38328357 1 38328357 1 38328357 1 Text Display 38018065 1 38018065 1 38018065 1 Thermocouple 38031001 1 38031001 1 38031001 1 Relief Valve 38026852 2 38026852 2 38026852 2 Temperature Indicator 38006706 2 38006706 2 38006706 2 Heater 38015467 1 38015418 1 38028700 1 Gasket Consult factory Consult factory Consult factory Pressure Regulator 38015145 1 38015145 1 38015145 Pressure Switch 38006565 1 38006565 5 38006565 5 Light Bulb 38335212 2 38335212 2 38335212 2 Transformer Primary Fuse 38015244 2 38015244 2 38015244 2 Transformer Secondary Fuse 38006870 1 38006870 1 38006870 1 Heater Fuses 38006862 3 38006847 3 38006847 3 Control Fuses 38015236 1 38015236 1 38015236 1 Control Relay Consult factory Consult factory Consult factory Heater Contactor 38338786 1 38049391 1 38049391 1
36
Page 43
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
37
Page 44
USER MANUAL
6. FAULTS AND TROUBLESHOOTING
6.1 DEWPOINT HAS DETERIORATED
POSSIBLE CAUSE REMEDY
Check compressor after cooler and cooling Incoming air temperature above design condition.
Incoming air flow too high
Inlet pressure below design pressure.
Liquid water entering dryer
system.
Adjust as necessary to reduce the inlet
temperature to dryer specification.
Problem external to dryer. Verify inlet flow
rate and reduce as necessary to dryer
specification.
Check compressed air system. Correct if
necessary
Check prefilter elements and seals for
damage. Replace if necessary.
Check operation of drain trap. Ensure
proper drainage. Repair or replace drain if
necessary.
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
Desiccant degraded or coated with oil.
Insufficient regeneration due to:
1. Heater failure
2. Heater contactor failure
3. Incorrect purge flow
4. Temperature setting incorrect
Leaks at piping/tubing connections downstream of the dryer.
Replace desiccant. Inspect prefilter if
desiccant is coated with oil.
1. Inspect and replace as necessary.
2. Inspect and replace as necessary.
3. Check purge flow setting.
4. Check setpoints of heater and purge exhaust.
Soap bubble test dryer and repair all leaks
38
Page 45
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
6.2 HIGH HUMIDITY ALARM OR SENSOR FAILURE
POSSIBLE CAUSE REMEDY
Hygrometer probe out of calibration Replace hygrometer probe.
Open circuit on probe electrical connection.
Inspect and repair.
Incorrect flow across sensor Refer to EMS start-up (paragraph 3.3.4).
Check sensor tubing and probe filter for
Excessive moisture on sensor.
buildup of moisture. Allow tubing to dry and replace filter element.
6.3 PRESSURE DROP TOO HIGH
POSSIBLE CAUSE REMEDY
Broken or fouled desiccant Inspect desiccant and replace if required.
Inlet flow exceeding design flow rate Reduce inlet flow as necessary
Pre or after filter element dirty or clogged
Depressurize filters and inspect elements. Replace if dirty or clogged.
6.4 SWITCHING FAILURE ALARM
If a switching failure alarm occurs, refer to paragraph 3.2.1 in order to determine where in the dryer cycle the alarm occurred. Also refer to the program step functions (paragraph 3.1.1) to assist in finding which component led to the switching failure.
POSSIBLE CAUSE REMEDY
Pilot air insufficient
Inlet air pressure below setpoint of pressure switches
39
Close pilot air isolation valve, depressurize pilot air filter and inspect element. If clogged or dirty, replace. Check that pilot air isolation valve is fully open. Check that pilot air regulator is set at 100 psig. Inspect pilot air tubing for kinks or breaks. Repair if necessary. Correct the low pressure problem to the dryer.
Page 46
USER MANUAL
Inspect purge and depressurization
closing or are leaking. Check solenoid
TZE400 to TZE3500 with EMS
6.4 SWITCHING FAILURE ALARM (CONTINUED)
POSSIBLE CAUSE REMEDY
Check operation of solenoid. Replace if not functioning.
Solenoid valve not energizing
Inlet or purge exhaust valves leaking
Check valve internals are worn or damaged
Check wiring from panel to the solenoid for an open or short circuit. Repair if necessary. Shut down and depressurize dryer. Inspect valve seats and seals for damage or wear. Repair or replace if necessary. While valve is disassembled, check the actuator stops to ensure that valve is fully closing ( butterfly valves only). Shut down and depressurize dryer. Repair or replace valves.
REV 10 – 23 February 2006
Switching failure on depressurization.
Switching failure on repressurization.
Pressure switch malfunction.
mufflers and replace if necessary. Off-line desiccant chamber inlet valve or outlet check valve leaking. Inspect as described above Regenerating chamber depress/exhaust valve failed to open. Check associated solenoid valve operation as described above. Online chamber outlet check valve leaking. Inspect and repair as described above. Excessive purge flow. Check the purge pressure setting. Exhaust or depressurization valves not
operation as listed above. Check valve failure as listed above. Insufficient purge flow. Check purge pressure settings. Check automatic purge isolation valve for correct operation. Check the setpoint of the pressure switches. Readjust if necessary. Check the operation of the pressure switches. Replace if needed.
40
Page 47
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
41
Page 48
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
7. DRAWINGS
42
Page 49
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
43
Page 50
Page 51
INGERSOLL-RAND COMPANY, 800-A BEATY STREET, DAVIDSON, NORTH CAROLINA, 28036 – USA TEL: (704) 896-4000 / FAX: (704) 896-4648 WWW.AIR.IRCO.COM
Loading...