Reading this user manual will fully familiarize you with the Ingersoll-Rand adsorption
dryer. You will be better able to run this equipment in accordance with its intended use.
This manual contains important information for safe, proper and economic dryer
installation, start-up, operation and maintenance. Always keep it within reach where the
adsorption dryer is being used.
It is necessary to follow all instructions as written. Careful reading will avert danger,
avoid unnecessary downtime, and minimize work for yourself and wear on the
equipment.
In addition to carefully reading this technical manual in its entirety, you must understand
your National, State and local rules and regulations regarding safety in the workplace,
their necessary precautions and procedures.
Each person responsible for the set-up, start-up, operation, maintenance or repair of
this adsorption dryer must have first read and understood this user manual – including
all the safety tips.
NOTE: Ingersoll-Rand recommends that installation, start-up and maintenance
be carried out by its factory-trained technicians in a regularly scheduled,
site-dedicated program. This will ensure the safety of personnel, the
integrity of equipment and the surety of warranty coverage.
1.3.1 Identification of Signs and Symbols in this Manual.....................................................................................2
1.3.2 General Safety Tips for Assembly, Inspection and Maintenance.................................................................3
1.4 TECHNICAL DATA SHEET ....................................................................................................................................4
1.4.1 Models TZE400 to TZE820 ..........................................................................................................................4
1.4.2 Models TZE1000 to TZE1800......................................................................................................................5
1.4.3 Models TZE2100 to TZE3500......................................................................................................................6
1.6 TRANSPORT .........................................................................................................................................................8
2.5 EMS CONTROL CONNECTION ...........................................................................................................................12
3.1 GENERAL OPERATING PRINCIPLES ....................................................................................................................13
3.1.1 Dryer Program Steps .................................................................................................................................14
3.2 OPERATOR CONTROLS / LOW-VOLTAGE CONTROL PANEL ...............................................................................16
3.2.1 Dryer Status ...............................................................................................................................................18
3.2.2Alarm Information .....................................................................................................................................19
3.2.4 Heater Sheath Information ........................................................................................................................20
3.2.5 Heater Outlet Information .........................................................................................................................21
3.2.6 Regeneration Outlet Information ...............................................................................................................21
3.2.7 Dryer Off, Dryer On, EMS On – 3-Position Switch..................................................................................21
3.2.8 Status Lamps..............................................................................................................................................22
4.2 CHANGING THE FILTER ELEMENT......................................................................................................................28
4.3 REPLACEMENT OF THE DESICCANT ...................................................................................................................29
5. PARTS LISTINGS ...............................................................................................................................................31
5.1 PARTS LIST FOR TZE400 TO TZE650................................................................................................................31
5.2 PARTS LIST FOR TZE820 TO TZE1225..............................................................................................................32
5.3 PARTS LIST FOR TZE1500 TO TZE2100............................................................................................................33
5.4 PARTS LIST FOR TZE2500 TO TZE3500.............................................................................................................34
6. FAULTS AND TROUBLESHOOTING .............................................................................................................38
6.1 DEWPOINT HAS DETERIORATED .............................................................................................................38
6.2 HIGH HUMIDITY ALARM OR SENSOR FAILURE ...................................................................................39
6.3 PRESSURE DROP TOO HIGH .......................................................................................................................39
This adsorption dryer includes the latest technology and safety features. Its use,
however, can endanger life and limb and can lead to considerable damage to the
equipment and other material assets if:
• it is operated by personnel not instructed in its use,
• it is improperly used,
• it is improperly maintained or serviced.
Furthermore, ignorance of its use and proper service can result in the loss of any claim
for damage.
This adsorption dryer is designed for neutral media (such as air or nitrogen) which is
free of aggressive water, oil and solid elements. Ingersoll-Rand accepts no liability for
corrosion damage or malfunctions caused by aggressive media.
Applications other than those mentioned in this manual must be agreed to by IngersollRand and confirmed in writing.
Ingersoll-Rand reserves the right to make changes at any time as may be necessary for
increasing safety or efficiency, or In the interests of further product development.
1.2 PRODUCT INFORMATION
The adsorption dryer is used for the purpose of drying compressed air and other gases
according to its contracted design. Depending on certain conditions at the inlet, it
provides pure, dry and oil-free compressed air or gases. The standard model of
adsorption dryer is equipped with two desiccant vessels and a prefilter and afterfilter.
This specific model of dryer includes an Energy Management System (EMS) that
provides automatic monitoring and control of the work/regeneration cycle to optimize
equipment efficiency. This manual includes references to optionally available Low Dew
Point (LDP) and 3-valve bypass (3V) systems/assemblies which may or may not be
provided. Selected options included with this dryer are indicated on the cover page by
an “X” mark in the box.
1
Page 8
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
1.2.1 PRESSURE VESSEL REGULATIONS
The pressure vessels are designed and built to meet the American Society of
Mechanical Engineers (ASME) standards. They fulfill the test of the certifying procedure
and carry the ASME symbols U or UM.
RANGE OF APPLICATION
Design Pressure Max: 150 psig
Design Temperature
Max: 500 °F (260 °C)
Min: -20 °F (-29 °C)
1.2.2 LEAK TEST
Each Ingersoll-Rand adsorption dryer is subjected to, and passes, a leak test prior to
shipment.
1.3 SAFETY INSTRUCTIONS
This manual contains basic tips which must be followed during set-up, operation and
servicing. It is of utmost importance that it be read by the assembly technician before
installation and start-up as well as by the specialist/operator in charge. It must always
be within reach at the place where the adsorption dryer is being used.
1.3.1 IDENTIFICATION OF SIGNS AND SYMBOLS IN THIS MANUAL
The safety tips contained in this manual, whose disregard could endanger people and
equipment, are indicated by a general danger sign and the additional markings Danger!
or Attention! or Warning!
Danger! / Attention!
Safety sign in accordance with DIN 4844 - W9
Warning – high voltage!
Safety sign in accordance with DIN 4844 - W8
Safety tips printed directly on the adsorption dryer must be heeded at all times and must
be kept completely legible.
2
Page 9
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
1.3.2 GENERAL SAFETY TIPS FOR ASSEMBLY, INSPECTION AND MAINTENANCE
The purchaser is to ensure that all assembly, maintenance and inspection work is
carried out by personnel qualified to do it.
The personnel involved in assembly, operation, maintenance and inspection must have
the corresponding qualifications to do this work. Areas of responsibility and supervision
of the personnel must be clearly established by the purchaser. Should the personnel
not possess the necessary knowledge, then they must be instructed. If need be, this
training may be carried out by the manufacturer/supplier at the request of the purchaser.
Further, the purchaser is to ensure that all personnel completely understand and follow
the content of this manual.
Attention!
• Never make structural changes to the adsorption dryer
• Only use recommended spare parts as listed in section 5
• Never weld on a pressure vessel or change it in any way
• Carry out maintenance only when the adsorption dryer is OFF,
depressurized and disconnected from the electric power supply.
Danger!
• Review the Material Safety Data Sheet (MSDS) provided with the
desiccant
• Wear protective clothing and goggles when working with the
desiccant
• If desiccant comes into contact with the eyes, rinse eyes
immediately with a lot of clear water
• If the desiccant is spilled, clean up without causing swirls of dust
• In case of fire, there is no restriction on the use of fire extinguishing
material; the reaction with water and foam is defined as strong
• A mask must be worn whenever handling desiccant.
Inlet Connection 3 in RF FLG 3 in RF FLG 3 in RF FLG 4 in RF FLG
Outlet Connection 3 in RF FLG 3 in RF FLG 3 in RF FLG 4 in RF FLG
Recommended Prefilter
Recommended Afterfilter
Pilot Air Filter
Standard Electric Rqmt 460 Vac/3-phase/60 Hz
Heater 17 kW 21 kW 25 kW 28 kW
Cycle Time
Outlet Pressure Dewpoint -40°F PDP (-100°F LDP)
EMS Control Setting -40°F PDP (-100°F LDP)
High Humidity Alarm -35°F PDP (-95°F LDP)
Pressure Switch Setpoints
Purge Pressure Setting 70 psig 60 psig 65 psig 70 psig
Low Purge Alarm Setpoint
Heater Outlet Set Point 425°F
End Heating Temperature 180°F
End Cooling Temperature 120°F
Heater Sheath Alarm 1000°F
Flow Directions Downward Drying - Upward Regeneration
The specific size/model of your dryer was selected to meet performance requirements
based on an analysis of air supply and demand capacities. The model selection chart
provided following should confirm that this dryer remains suitable for its intended use.
The table following is based on -40oF PDP, 8-hour cycle, activated alumina and average
inlet air flow for non-LDP-equipped dryers with EMS. Consult our factory for rated air
flows on LDP-equipped dryers.
Rated inlet air flow (scfm) at given pressures (psig)
(Based upon 100oF inlet air temperature)
Higher pressures are optionally available. Consult factory.
To correct for an inlet temperature other than 100oF, multiply dryer capacity by the
temperature correction factor listed below.
CORRECTION FACTOR FOR INLET TEMPERATURE
TEMPERATURE
DEGREES F
Correction Factor
Example: To size for an inlet flow of 950 SCFM @ 105 F and 110 psig.
1. Select model that produce at least 950 SCFM at 110 psig. This case would be the TZE1000 which
can dry 1140 SCFM.
2. Multiply pressure corrected flow by the temperature correction factor to obtain the flow of the dryer
corrected for pressure and temperature:
1140 X (0.85) = 969 SCFM
3. Confirm model selection. Model TZE1000 can flow 969 SCFM at the inlet conditions specified;
requirements of 950 SCFM are less: TZE1000 is correct.
80 90 100 105 110 115 120
1.1 1.1 1.0 0.85 0.69 0.565 0.455
7
Page 14
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
NOTE: Settings for EMS: Standard Dryers: EMS Control -40°F (-40°C)
High Humidity -35°F (-35°C)
LDP Dryers: EMS Control -100°F (-74°C) High Humidity -95°F (-69°C).
1.5 OVERLOADING
Attention! Protect the adsorption dryer from overloads!
The adsorption dryer can become overloaded if:
• The flow volume of the medium to be dried increases
• The temperature of the air at entry and, correspondingly, its
humidity increases
• The minimum operating pressure decreases
• The prefiltration and separation of impurities are not sufficient or the
filter drain fails
• Introduction of oil into the air stream.
1.6 TRANSPORT
Immediately upon delivery of the adsorption dryer, it must be checked for any damage
that may have occurred during transport. If necessary, the damage must be recorded
on the shipping waybill/receipt. Liability for such damage usually rests with the shipper.
Contact Ingersoll-Rand to arrange for any required service or replacement parts.
Attention!
For transport within your company site, only the skids of the adsorption
dryer may be used. Lifting at any other points on the equipment will void
the warranty and damage the equipment.
1.7STORAGE
If the adsorption dryer is to be stored for a long period of time, its place of storage must
be dry and free of dust. The ambient temperature cannot go below 33°F (+1°C).
1.8USE OF A PREFILTER AND AFTERFILTER
In order to prevent droplets of condensate, oil and dirt from getting into the desiccant, a
Ingersoll-Rand prefilter must be installed upstream of the adsorption dryer. An oil film
on the desiccant reduces the drying capacity and the dewpoint. In order to prevent
breakdown in downstream consumers caused by material that has been abraded from
the desiccant bed, a Ingersoll-Rand afterfilter must be mounted behind the adsorption
dryer. Since no condensate accumulates in the afterfilter, this filter is always equipped
with a manual vent valve.
8
Page 15
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
Both filters are equipped with a differential pressure indicator to ensure a direct display
of the degree of contamination of the filter elements.
2. INSTALLATION
2.1 GENERAL
Ensure that the installation site is free of dust, dirt and litter. The site floor must be level
and strong enough to support the equipment. The site itself must be an heated
environment (minimum 50°F) to ensure proper operation and warranty protection.
Ensure that the Ingersoll-Rand adsorption dryer is carried only by its skid base frame.
The adsorption dryer must be positioned so that the side from which it is to be operated
is easily accessible. The piping is to be connected at a slightly downward slope. Install
isolation valves on the inlet and outlet sides of the adsorption dryer. Also, a bypass
pipe with an additional isolation valve should be mounted onto the adsorption dryer to
allow for an uninterrupted supply of compressed air in case the adsorption dryer
requires maintenance or repair. The bypass assembly is optionally provided (see
paragraph 1.2) or can be customer furnished. If vibrations occur at the installation site,
the adsorption dryer skid frame is to be placed onto vibration dampers.
2.2 MECHANICAL ASSEMBLY
• The equipment should be located in an area with adequate clearances for
service. An overhead clearance of not less than two feet above each desiccant
tower is required for loading of the desiccant.
• Remove all protective shipping crates, flange covers, etc.
• Using the mounting holes provided on the skid, anchor the dryer to a solid, level
foundation designed to support the equipment.
• Do not hydrostatically test the pressure vessels. All TZE dryer pressure vessels
and welded piping are hydrostatically tested at one and one-half times the design
pressure after fabrication and before assembly.
• Desiccant for models TZE820 and up is shipped loose and must be installed on
site. Refer now to paragraph 4.3 for instructions on installing the desiccant.
• If the equipment is installed in a high traffic area, protective barriers may be
required to prevent possible damage of equipment and to prevent contact with
hot surfaces.
• Due to vibration during shipping some tube fittings may have loosened.
Therefore, inspect all connections and tighten if required.
9
Page 16
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
• Ensure that the inlet and outlet connections to and from the dryer are made using
the correctly rated fittings and piping to meet the design conditions.
NOTE: System isolation and by-pass valves should be installed. If not supplied
by Ingersoll-Rand as part of the equipment package (i.e., 3V option – see
paragraph 1.2), they should be supplied and installed by others. Ensure
that this bypass facility is installed so that future servicing of the dryer
system off-line may take place.
• Full flow relief valves to protect the system from over-pressure must be
customer-provided in accordance with local regulations.
• The purge exhaust on the TZE650 and smaller dryers is equipped with an
exhaust muffler. If required, the muffler can be removed and purge exhaust can
be connected to a vent header. Follow recommendations for pipe sizing listed
below.
• The purge exhaust connection on the TZE820 and larger dryers must be
connected to a vent header. To ensure satisfactory regeneration of the desiccant
chambers, the purge exhaust piping should be sized as follows to prevent backpressure build up.
EXTENDED LENGTH PIPE SIZE REQUIRED
TO 10 FEET SAME SIZE AS DRYER EXHAUST
TO 25 FEET 1 SIZE LARGER THAN DRYER EXHAUST
TO 50 FEET 2 SIZES LARGER THAN DRYER EXHAUST
TO 100 FEET 3 SIZES LARGER THAN DRYER EXHAUST
Caution!
The noise at the outlet of the exhaust header may exceed 100 dBa, and
the flow velocity will be high. Exhaust must be piped to an area where
these flow velocities and noise levels can be safely tolerated.
2.3 FILTER INSTALLATION
2.3.1 PREFILTER INSTALLATION (SHIPPED LOOSE)
• Mount prefilter in such a way as to allow clearance for the element installation
and removal.
• Locate the prefilter as close to the dryer inlet connection as possible.
• The filter must be piped so that the correct flow direction indicated on the filter is
followed.
10
Page 17
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
• Ensure that all piping and valves are equivalent or larger in size to the dryer inlet
connection.
• Connect drain port to a condensate collector. Use an easily visible collector to
aid in operational inspection.
2.3.2 AFTERFILTER INSTALLATION (SHIPPED LOOSE)
• Mount afterfilter in such a way as to allow clearance for the element installation
and removal.
• The filter must be piped so that the correct flow direction indicated on the filter is
followed.
• Ensure that all piping and valves are equivalent or larger in size to the dryer inlet
connection.
2.3.3 FILTER SKID WITH 3 VALVE BYPASS (IF DRYER INCLUDES 3V OPTION)
• Filters skid should be located as close to dryer as possible. Use the skid bolt
holes to secure the assembly.
• Ensure that the skid is located such that the 3-valve bypass will bypass the dryer
and filters when in use.
• Check the flow direction of each filter to ensure the prefilter is connected to the
inlet pipe of the dryer and afterfilter is connected to the outlet pipe of the dryer.
• Connect the filter skid piping and dryer skid piping using materials and fabrication
procedures that are suitable for compressed air pressure piping. All flanges are
ANSI B16.5 Class 150 raised face flanges.
2.4 ELECTRICAL CONNECTION
Warning – high voltage!
Be sure that power is removed from the line feed before making
• Connect the dryer to a correctly sized power supply. Refer to the dryer
nameplate or the electrical drawing (see section 7) for the supply voltage and
amperage requirement to properly size the electrical service. Only one electrical
connection is required. All internal wiring was done at the factory.
connection between the site drop and the equipment.
11
Page 18
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
NOTE: A disconnect switch is not provided with the dryer and must be supplied
by the customer in accordance with the local electrical code.
• Ground the frame of the dryer in accordance with the local electrical code.
• It is recommended that the common alarm relay, located in the dryer control
panel, be connected to the control room or operator station so that an immediate
response to the dryer alarm may be given when required.
• Before energizing the electrical circuit, the electrical heater assembly should be
inspected to determine that no moisture has accumulated in the heater enclosure
or terminations. A 1000V meg-ohmmeter should be used to determine the
phase-to-ground insulation resistance for each phase. A minimum value of 500
kOhms should exist.
2.5 EMS CONTROL CONNECTION
• A probe sample line must be run from downstream of the afterfilter.
• A 10-ft length of 1/8-in stainless steel tubing and necessary compression fittings
are provided.
• Tube fittings are to be installed downstream of the afterfilter at the differential
pressure indicator (DPI) port T-fitting on the afterfilter outlet nozzle
• Remove the hexagonal plug from the DPI T-fitting.
• Insert 1/8-in tubing into compression fitting and tighten.
• Run the tubing back to the hygrometer housing. Cut to necessary length and
connect to the upper connection fitting. Tubing is semi-flexible so care must be
taken when bending to ensure the tubing does not kink.
• If the sample port is installed at a distance longer than the tubing supplied,
contact your Ingersoll-Rand distributor for assistance.
12
Page 19
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3. EQUIPMENT OPERATION
3.1 GENERAL OPERATING PRINCIPLES
This dryer model has two parallel adsorption chambers filled with desiccant. While the
medium is being dried flowing top-down in one chamber, regeneration takes place from
the bottom up in the other chamber. The changeover from one chamber to the other is
controlled by the Energy Management System that monitors desiccant performance by
measuring the outlet air dew point. It can operate continuously and is fully automatic.
The standard dryer with EMS has a cycle time of eight hours. Half the cycle time is
dedicated to air drying work and the other half to desiccant regeneration, with one
chamber working to dry the air while the other regenerates. The dryer is configured at
the factory.
Wet air enters the working desiccant chamber (it can be either the left or right) at the
inlet switching valves (top) and is dried as it flows downward through the desiccant bed.
Dry air exits the dryer through the outlet check valve.
The regeneration of the off-line tower begins with a heating cycle. After having
depressurized the off-line tower, the purge orifice allows a portion of the dry outlet air to
flow across the regeneration heater. The heated regeneration air then passes upward
through the desiccant bed where it picks up previously adsorbed moisture from the
desiccant and is then evacuated to atmosphere through the purge exhaust valve.
At the completion of the regeneration heating cycle, the cooling cycle begins. The
regeneration heater is de-energized. The purge orifice allows a portion of the dry outlet
air to flow through the off-line tower. It is then evacuated to atmosphere through the
purge exhaust valve. When the cooling cycle is completed, the purge exhaust valve is
closed and the off-line tower is repressurized. Once at line pressure, the dryer is ready
to switch drying from one tower to the other. Dryer models TZE3000 and 3500 have
purge control valves which close once at line pressure and prior to switching from one
tower to the other.
The purge air is controlled by a purge adjusting valve and purge orifice located in the
purge line. Purge pressure is indicated on the purge pressure gauge.
Ingersoll-Rand high-efficiency prefilters and reverse-flow afterfilters are designed to
remove solids, oil and water condensate from compressed air and other neutral,
compressed gases. These filters provide high flows and low differential pressures.
13
Page 20
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
The prefilter is designed to flow from the inside to the outside. The afterfilter is designed
to flow from the outside to the inside. Solids are filtered out by impact or by the effect of
inertia, whereas oil particles and drops of moisture are filtered out by the effect of
coalescence. The contaminants collect at the bottom of the filter vessel and are drained
automatically or manually.
3.1.1 DRYER PROGRAM STEPS
This automatic dryer is equipped with a PLC which retains last-position data in the event
of a power failure or fast shutdown. The dryer will restart at the last position or can be
manually cycled on the operator interface to reset at step 1.
14
Page 21
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
STEP 1
OPEN LEFT CHAMBER
INLET VALVE
EV-1L & EV-11R (VALVE TO MOVE)
10-SEC TIMER/VALVE TO OPEN
10 SEC PASS, LEFT
CHAMBER ABOVE 60 psig
STEP 8
OPEN RIGHT CHAMBER
INLET VALVE
EV-1R & EV-11L (VALVE TO MOVE)
10-SEC TIMER/VALVE TO OPEN
10 SEC PASS, RIGHT
CHAMBER ABOVE 60 psig
STEP 2
5 SEC PASS
STEP 3
10 SEC PASS AFTER RIGHT
CHAMBER BELOW 30 psig
STEP 4
HEATING TIMER FINISH OR PURGE
OUTLET TEMP ABOVE 200-DEG F
STEP 5
IF COOLING TIMER DONE (100 MINUTES) OR PURGE
OUTLET TEMP BELOW 120-DEG F & 60 MINUTES PASSED
CLOSE RIGHT
CHAMBER INLET VALVE
EV-1L & EV-11R WAIT 5 SEC
FOR VALVE TO CLOSE
DEPRESSURIZE
RIGHT CHAMBER
EV-2R & EV-3R (IF R/C <10 psig)
ENERGIZE EV-1L & EV-11R
RIGHT CHAMBER
HEATING PERIOD
START R/C HEATING MODE
FOR 140 MINUTES MAXIMUM;
ENERGIZE EV-1L AND EV11R
RIGHT CHAMBER
COOLING PERIOD
START R/C COOLING MODE FOR
100 MINUTES MAXIMUM /
60 MINUTES MINIMUM;
ENERGIZE EV-1L & EV-11R
CLOSE LEFT CHAMBER
STEP 9
5 SEC PASS
STEP 10
10 SEC PASS AFTER LEFT
CHAMBER BELOW 30 psig
STEP 11
HEATING TIMER FINISH OR PURGE
OUTLET TEMP ABOVE 200-DEG F
STEP 12
IF COOLING TIMER DONE (100 MINUTES) OR PURGE
OUTLET TEMP BELOW 120-DEG F & 60 MINUTES PASSED
INLET VALVE
EV-1R & EV-11L WAIT 5 SEC FOR
VALVE TO CLOSE
DEPRESSURIZE
LEFT CHAMBER
EV-2L & EV-3L (IF L/C <10 psig)
ENERGIZE EV-1R & EV-11L
LEFT CHAMBER
HEATING PERIOD
START L/C HEATING MODE
FOR 140 MINUTES MAXIMUM
ENERGIZE EV-1R & EV11L
LEFT CHAMBER
COOLING PERIOD
START L/C COOLING MODE FOR
100 MINUTES MAXIMUM /
60 MINUTES MINIMUM
ENERGIZE EV-1R & EV-11L
STEP 6
120 SEC PASS & BOTH
CHAMBERS ARE ABOVE 60 psig
STEP 7
DRYER HALF-CYCLE COMPLETED (240
MINUTES) OR BAD DEWPOINT OR EMS OFF
& BOTH CHAMBERS ARE ABOVE 60 psig
GO TO STEP 8
REPRESSURIZE
RIGHT CHAMBER
ENERGIZE EV-1L & EV-11R
RIGHT CHAMBER
STANDBY
ENERGIZE EV-1L & EV-11R
STEP 13
120 SEC PASS & BOTH
CHAMBERS ARE ABOVE 60 psig
STEP 14
GO TO STEP 1
REPRESSURIZE
LEFT CHAMBER
ENERIZE EV-1R & EV-11L
LEFT CHAMBER
STANDBY
ENERGIZE EV-1R & EV11L
DRYER HALF-CYCLE COMPLETED (240
MINUTES) OR BAD DEWPOINT OR EMS OFF
& BOTH CHAMBERS ARE ABOVE 60 psig
Su
SD
E
FIGURE 1 – DRYER PROGRAMMED STEPS
15
Page 22
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3.2 OPERATOR CONTROLS / LOW-VOLTAGE CONTROL PANEL
The operator status display and control interface (i.e., monitor) is detailed in Figure 2. It
is provided to allow the operator to manually cycle through the programmed steps, and
to indicate system status. The system operating setpoints cannot be changed at this
panel.
16
Page 23
USER MANUAL
In order to choose one of the next four options, the SHIFT button
must be pressed first. An “s” in the lower right corner indicates the
shing
arrow on the right side of the screen indicates that more information is
available in the direction of the arrow and can be accessed by using
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
TEXT
DISPLAY
F1 – DRYER STATUS
F2 – MANUAL STEP AHEAD (MANUAL MODE ONLY)
F3 – DRYER ALARM STATUS
– ALARM RESET
F4
SHIFT –
upper row is now active.
F5 – DRYER OPERATING MODE MENU
F6 – HEATER SHEATH TEMPERATURE AND SETPOINT
F7 – HEATER OUTLET TEMPERATURE AND SETPOINTS
F8 – REGENERATION OUTLET TEMPERATURE AND SETPOINTS
Arrows allow user to scroll up or down within the display. A fla
the scroll arrows.
ESC – ACCESSES THE MENU MODE (ACCESS IS NOT REQUIRED).
ENTER – NO FUNCTIONALITY FOR THIS BUTTON.
FIGURE 2 – OPERATOR MONITOR
17
Page 24
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3.2.1 DRYER STATUS
The F1 key is pressed to display the present status of the dryer. This allows you to see
which step of the program cycle is currently engaged. A message can appear below
the dryer status at any time when in manual mode. A blinking arrow on the right side of
the display will indicate this. To access the messages, press the green arrow on the
right side of the interface.
MESSAGE IDENTIFICATION MESSAGE DESCRIPTION
SELECT LEFT CHAMBER DRYING
LEFT CHAMBER DRYING
R/C IN DEPRESS MODE
LEFT CHAMBER DRYING
R/C IN HEATING MODE
LEFT CHAMBER DRYING
R/C IN COOLING MODE
LEFT CHAMBER DRYING
R/C IN REPRESS MODE
LEFT CHAMBER DRYING
R/C IN STANDBY MODE
LEFT CHAMBER IN EMS MODE
R/C IN STANDBY MODE
SELECT RIGHT CHAMBER
DRYING
RIGHT CHAMBER DRYING
L/C IN DEPRESS MODE
RIGHT CHAMBER DRYING
L/C IN HEATING MODE
RIGHT CHAMBER DRYING
L/C IN COOLING MODE
RIGHT CHAMBER DRYING
L/C IN REPRESS MODE
RIGHT CHAMBER DRYING
L/C IN STANDBY MODE
RIGHT CHAMBER IN EMS MODE
L/C IN STANDBY MODE
Opening the left chamber (L/C) inlet valve.
Closing the right chamber (R/C) inlet valve.
Depressurizing the right chamber.
Heating the right chamber for regeneration.
Cooling the right chamber.
Pressurizing the right chamber.
Right chamber in standby until the end of the
half cycle.
The dryer is in EMS mode on the left
chamber. This will extend the half cycle for a
maximum of 12 hours or until the outlet
dewpoint goes higher than -40°F.
Opening the right chamber inlet valve.
Closing the left chamber inlet valve.
Depressurizing the left chamber.
Heating the left chamber for regeneration.
Cooling the left chamber.
Pressurizing the left chamber.
Left chamber in standby until the end of the
half cycle.
The dryer is in EMS mode on the right
chamber. This will extend the half cycle for a
maximum of 12 hours or until the outlet
dewpoint goes higher than -40°F.
18
Page 25
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3.2.2ALARM INFORMATION
The F3 button is pressed to display the status of the dryer alarms. If there is no alarm,
a NO ALARM message will appear. If more than one alarm is active, a flashing arrow
will appear on the right side of the display. To access the messages, press the green
arrow on the right side of the panel. In order to reset non-active alarms, press the F4
key. When all the alarm conditions have been cleared, the NO ALARM message will
appear.
MESSAGE IDENTIFICATION MESSAGE DESCRIPTION
HEATER OUTLET OVER TEMPERATURE
THERMOCOUPLE MODULE IN ERROR
THERMOCOUPLE OUT OF RANGE
HEATER FAILURE ALARM
FAIL REACH SETPOINT
OVERSHEATH ALARM
SHEATH TEMPERATURE TOO HIGH
DEPRESS FAILURE ON LEFT CHAMBER
DEPRESS FAILURE ON RIGHT CHAMBER
REPRESS FAILURE ON LEFT CHAMBER
REPRESS FAILURE ON RIGHT CHAMBER
HIGH HUMIDITY ALARM
NO ALARM Indicates no alarm is active.
Heater outlet temperature is above the
setpoint.
Indicates the thermocouple module
has lost it’s 24Vdc supply.
Indicates a thermocouple connected to
the module is defective or open.
The heater has failed to reach the
setpoint temperature within 15
minutes.
The heater sheath temperature is
above the setting.
The left chamber did not reach the low
setting of the pressure switch within
time limit.
The right chamber did not reach the
low setting of the pressure switch
within time limit.
The left chamber did not reach the
high setting of the pressure switch
within time limit.
The right chamber did not reach the
high setting of the pressure switch
within time limit.
Indicates the outlet dewpoint is above
alarm setpoint.
19
Page 26
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3.2.3 DRYER OPERATION MODES
The F5 button is pressed to display the dryer mode of operation. The actual mode will
be displayed whether it is in automatic or manual mode. To change the actual mode of
the dryer, press F2 when in the dryer mode screen. The actual mode will change from
one to the other each time the F2 button is pressed. If the dryer mode screen is left
unattended for thirty seconds, it will automatically switch to the dryer status screen. In
manual mode, the READY TO STEP AHEAD PRESS F2 TO CONTINUE message
will be shown when the dryer is ready to perform the next step. In order to go to the
next step in manual mode you must not be in the dryer operation mode screen. Failure
to do so will simply change the operating mode of the dryer.
MESSAGE IDENTIFICATION MESSAGE DESCRIPTION
The dryer is in automatic mode. The dryer
DRYER IN AUTO MODE
DRYER IN MANUAL MODE
READY TO STEP AHEAD
PRESS F2 TO CONTINUE
will perform its cycle without any external
intervention except in case of alarm.
The dryer is in manual mode. The dryer will
need external intervention in order to do to
the following step. If no external intervention
is provided the dryer will stay in that step.
The dryer is ready to go to the next step
when in manual mode. The user must wait
for this signal in order to press F2 for making
the dryer step ahead in its cycle.
3.2.4 HEATER SHEATH INFORMATION
The F6 button accesses heater sheath information. On this screen the actual sheath
temperature in degrees Fahrenheit is displayed and so is the temperature setpoint for
the sheath over-temperature alarm. The setpoint cannot be changed from the panel.
MESSAGE IDENTIFICATION MESSAGE DESCRIPTION
Displays temperature of the heater sheath
HEATER SHEATH XXXX F
ALARM SETPOINT YYYY F
20
(XXXX) and also at which temperature the
dryer will turn in alarm (YYYY).
Both temperatures are in degrees
Fahrenheit.
Page 27
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3.2.5 HEATER OUTLET INFORMATION
The F7 button accesses the heater outlet information. On this screen the actual
temperature in degrees Fahrenheit is displayed and so is the temperature setpoint for
the heater outlet over-temperature and heating failure alarm. The setpoint cannot be
changed at the panel.
MESSAGE IDENTIFICATION MESSAGE DESCRIPTION
Displays the heater outlet temperature
HEATER OUTLET XXXX F
HEAT CONTROL YYYY F
HEATER OUTLET XXXX F
HEAT FAIL AT ZZZZ F
HEATER OUTLET XXXX F
HEAT OVERTEMP VVVV F
(XXXX) and the regulation temperature
setting (YYYY) of the heater.
Both temperatures are in degrees F.
Displays the actual heater outlet temperature
(XXXX) and the heating failure alarm
temperature setting (ZZZZ).
Both temperatures are in degrees F.
Displays the actual heater outlet temperature
(XXXX) and the high outlet temperature
alarm setting (VVVV).
Both temperatures are in degrees F.
3.2.6 REGENERATION OUTLET INFORMATION
The F8 button accesses regeneration outlet information. On this screen the actual
temperature in degrees Fahrenheit is displayed and so are the control setpoints for end
of heating and end of cooling. The setpoints cannot be changed at the panel.
MESSAGE IDENTIFICATION MESSAGE DESCRIPTION
Displays the actual regeneration outlet
REGEN OUTLET XXXX F
HEAT SETPOINT YYYY F
temperature (XXXX) and the end of heating
mode temperature setting (YYYY).
Both temperatures are in degrees F.
Displays the actual regeneration outlet
REGEN OUTLET XXXX F
COOL SETPOINT ZZZZ F
temperature (XXXX) and the end of cooling
mode temperature setting (ZZZZ).
Both temperatures are in degrees F.
3.2.7 DRYER OFF, DRYER ON, EMS ON – 3-POSITION SWITCH
This 3-position switch provides for manual selection of dryer basic functions. Ensure
that the switch is set at DRYER OFF before beginning the initial startup procedure.
21
Page 28
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3.2.8 STATUS LAMPS
A green light announces that there is POWER at the control panel when lit. A red light
announces that there is an ALARM condition when lit. Refer to the operator monitor to
determine the cause.
3.2.9 PRESSURE GAGES
Three gages are mounted in a row above the low-voltage control panel. The two
outside read the pressure within each chamber (left side for left chamber, right for right)
and the middle gage shows the purge pressure.
3.3 INITIAL START-UP
Attention!
All pipes and wire connections must be tightened!
Furthermore, before start-up:
• The pipes must be checked for the presence of scale, abraded
material from the threading, or other similar impurities.
• All isolation valves on the prefilter, afterfilter and on the bypass line (if
installed) should be closed.
• The ambient temperature must not be less than 33°F.
NOTE: Breakdown resulting from faulty installation does not fall under the
Ingersoll-Rand warranty obligation.
3.3.1 PRESSURIZING DRYER
Prior to pressurizing the dryer system, verify the following:
• DRYER OFF/DRYER ON/EMS ON switch is in the DRYER OFF position
• System outlet block valve is closed
• Prefilter, afterfilter and pilot air filter vent valves are closed
• Desiccant chamber vent valve is closed
• Pilot air isolation valve is open
• Hygrometer adjustment/isolation valves are closed.
Slightly open the inlet isolation valve to slowly admit compressed air to the system.
When full system operating pressure has been reached, all connections should be soap
22
Page 29
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
bubble tested for leaks. Any leaks should be repaired and retested prior to placing the
equipment in service. If some gas other than the process air will be used for leak
testing, consult Ingersoll-Rand for its compatibility with system components before
proceeding.
Fully open the inlet isolation valve.
When the system is filled with process air and leak tight, slowly open the system outlet
valve to pressurize the downstream piping. During this procedure, ensure that the dryer
system pressure does not fall beyond 95% of its reading prior to opening the system
outlet valve. This will protect the equipment internal components (i.e., filter elements,
desiccant) from gas velocities above design conditions.
When pressurizing is complete, then fully open the system outlet valve to place the
equipment in service.
Verify that the system inlet pressure and temperature are at the design operating levels
(see paragraph 1.4)
Ensure that the pilot pressure regulator is set between 80 and 100 psig.
3.3.2 ENERGIZING DRYER CONTROLS
Turn 3-position switch to the DRYER ON position.
The operator monitor controls the dryer cycle. This should be used as a reference
guide to ensure dryer is cycling. A manual mode is included in the dryer program to
allow for fast cycling to verify to operation of the dryer.
Review the operational program of the dryer (paragraph 3.1.1) and the wiring schematic
(see section 7) before operating the dryer.
NOTE: The hygrometer will signal an open circuit (the ALARM light will
illuminate) until probe cable is connected to hygrometer probe. This
connection is described in paragraph 3.3.4 – leave it as is for now.
While dryer is in purge mode for either chamber, the regeneration pressure setting
should be checked. Refer to paragraph 3.3.3 for the correct blower flow setting.
Warning!
Failure to correctly set the purge pressure can lead to improper
regeneration of the desiccant bed, resulting in a dewpoint failure
when the chamber is returned to service.
23
Page 30
USER MANUAL
ADJUSTMENT
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3.3.3 PRESSURE SWITCH ADJUSTMENT
On the TZE dryer there are four pressure switches: PSH-1, PSL-1, PSH-2 and PSL-2.
The PSH pressure switches are set at 30 psig below the operating pressure of the
dryer, and use the normally open contact. When the adjustment is done, the contact
between C and NC should close when increasing to the desired pressure.
The PSL switches are set at 10 psig regardless of the operating pressure and use the
normally closed contact. When the adjustment is done, the contact between C and NC
should close when decreasing to the desired pressure.
To increase the pressure, screw the knob toward the pressure switch diaphragm (see
figure 3). To decrease the pressure, turn away from the pressure switch diaphragm.
KNOB
FIGURE 3 – PRESSURE SWITCH ADJUSTMENT
3.3.4 EMS START UP
Refer to the general assembly drawing provided in section 7, and to figure 4.
The EMS hygrometer probe has been shipped inside of its own sealed package to
ensure that the probe does not become saturated with ambient air during storage and
transport. Do not remove probe from the package until dryer system has been started
and probe is to be inserted into the sample cell.
24
Page 31
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
• Check that the sample line is connected from the dryer outlet to the inlet valve on
the humidity probe sample cell.
• Check that the humidity probe is installed into the sample cell.
• Connect the cable to the humidity probe.
• Fully open the inlet valve to the sample cell.
• Partially open the discharge valve of the sample cell to vent off a small amount of
sample air. Do not fully open discharge valve.
• Perform a soap bubble test to check for leaks on all parts of the sample line
connections and the humidity sample cell.
• The digital display will now read the dewpoint of the dryer system. It will take a
short period of time for a humidity probe to be purged of humidity.
FIGURE 4 – HYGROMETER PROBE ASSEMBLY
NOTE: The dryer should be operated in the DRYER ON position at the time of
initial start-up and at all times when the hygrometer or humidity probe are
removed for service.
25
Page 32
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
3.4 SHORT-TERM SHUTDOWN
Follow this sequence when switching off the adsorption dryer:
• First close all the shutoff valves up- and downstream of dryer
• Then immediately switch DRYER OFF.
Danger!
Dryer will remain pressurized.
3.5 SHUTDOWN IN CASE OF A FAULT OR FOR MAINTENANCE
Follow this sequence when switching off the adsorption dryer:
• First switch off the dryer. Make certain dryer is not in heating or cooling mode.
The dryer electrical panel will still have power. The dryer disconnect must be
turned off before opening electrical panel.
• Close all the isolation valves upstream and downstream of the adsorption dryer.
• Depressurize the dryer by using the hand valve mounted at the bottom of the
desiccant chamber.
• Depressurize the filters by opening vent valves at the bottom of each filter vessel.
Danger!
Before any kind of maintenance or repair work is done, the dryer
must be depressurized and disconnected from the power source.
3.6 RESTARTING
• Close the hand valve mounted at the bottom of the afterfilter and at the bottom of
each desiccant chamber
• Slowly open the inlet isolation valve and pressurize the dryer up to the regular
operating pressure by keeping the shutoff valve mounted behind the afterfilter
closed.
• Switch DRYER ON.
NOTE: If the dryer is restarted after a long standstill, proceed as for an initial
start-up (see paragraph 3.3).
26
Page 33
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
4. MAINTENANCE
4.1 CHECKLIST
These checks are to be carried out by the operator during the routine operations cycle.
4.1.1 DAILY CHECK
• Operate prefilter drain ball valve as required to prevent excess accumulation.
This may require frequent exercise depending on line moisture content. If the
drain is automatic, check for functionality and blow down daily to remove
accumulated fluids.
• Check filter differential pressures. A filter differential pressure of 5 to 8 psi (or
pointing in the red field) indicates a dirty filter element and it should be replaced.
Filter elements should last between 6 to 12 months under normal use.
• Check correct purge pressure.
• Ensure dryer is cycling without alarms.
4.1.2 WEEKLY CHECK
• Check all mufflers for backpressure. Replace if clogged or dirty.
• Verify heater operation.
4.1.3 QUARTERLY CHECK (EVERY THREE MONTHS)
• Check operating conditions, purge rate, line pressure, inlet flow.
• Check dryer operating cycle for proper operation of valve operators, solenoid
valves, dump valves, heaters, pressure switches and temperature controller.
• Check the outlet dewpoint.
• Blow down relief valves.
• Check heater outlet temperature is between 400°F and 425°F.
• Verify pressure switch operation.
• Inspect pilot air filter element. If element seems clogged, dirty or damaged,
replace it.
27
Page 34
USER MANUAL
ain pollutants as appropriate to their function.
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
4.1.4 ANNUAL CHECK
• Disassemble, clean and inspect the inlet switching, purge exhaust and
depressurization valves/actuators. Replace all worn or damaged parts.
• Disassemble, clean and inspect the outlet and purge check valves. Replace all
worn or damaged parts.
• Inspect the desiccant through the chamber fill port. Replace desiccant if
degraded or if oil is present (see paragraph 4.3).
• Replace prefilter, afterfilter and pilot air filter elements at least once a year.
• Replace the dewpoint sensor humidity probe.
NOTE: Should the need for spare parts or service arise during work on the
adsorption dryer, the dryer model and its serial number must be
conveyed to Ingersoll-Rand. This information is given on the nameplate
mounted on the control cabinet. Telephone Ingersoll-Rand to arrange for
maintenance support (1-800-526-3615).
4.2 CHANGING THE FILTER ELEMENT
• The filter element within the filter housing must be replaced annually
• Depressurize the dryer and switch DRYER OFF
Danger!
Change filter elements only when the housing is fully depressurized
• Separate the lower part of the housing from the upper part
• Loosen and remove the element by hand
• Install the new filter and the O-ring/gasket, making sure that the filter seats
perfectly
• Refit the filter housing.
NOTE: Filter elements cannot be cleaned or reused.
Attention!
Filters may cont
Dispose of used filters in accordance with your local, state and federal
28
Page 35
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
regulations.
4.3 REPLACEMENT OF THE DESICCANT
Desiccant life is determined by the care with which it is handled, the quality of filtered
inlet air provided and by its time in use. Be careful to not abrade (i.e., wear down) the
desiccant when installing it. Proper filtering of inlet air, and constant pressure and
temperature, will also extend its life. In order to ensure trouble-free operation, we
recommend replacing the desiccant every 10,000 operating hours, or every 3 years.
The following considerations determine the life expectancy of desiccant:
• Care in installation
• Quality of input gas (e.g., air)
• Constancy of flow and temperature
• Whether full-service cycling or low-demand usage
• Time in service.
The following clues will suggest that you examine the desiccant and consider its
replacement:
• Discoloring of desiccant (e.g., oil residue, other contaminants): a brown or yellow
tinge indicates that the adsorbancy capacity of the desiccant has been
diminished
• Frequent afterfilter replacement due to desiccant dust accumulation
• Performance dew point rises.
Refer to paragraph 1.4 to determine the desiccant quantity required for your model of
dryer.
• Close dryer inlet/outlet isolation valves
• Depressurize and switch DRYER OFF
Danger!
• Wear protective equipment and clothing when handling
desiccant.
• Remove the drain plug and empty the old desiccant into a container
29
Page 36
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
4.3 REPLACEMENT OF THE DESICCANT (CONTINUED)
• Screw the plug back in and fill with new desiccant from above (refer to paragraph
• Start up the adsorption dryer in accordance with paragraph 3.3 for initial start-up.
Danger!
• Desiccant may contain pollutants.
• Desiccant is to be disposed of in accordance with local, state
and federal regulations.
1.4 regarding quantities for each chamber)
30
Page 37
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
5. PARTS LISTINGS
5.1 PARTS LIST FOR TZE400 TO TZE650
Description TZE400 TZE500 TZE650
Part # Qty Part # Qty Part # Qty
Consumables
Prefilter ( Element Only )
Afterfilter ( Element Only )
Depressurize filters and inspect elements.
Replace if dirty or clogged.
6.4 SWITCHING FAILURE ALARM
If a switching failure alarm occurs, refer to paragraph 3.2.1 in order to determine where
in the dryer cycle the alarm occurred. Also refer to the program step functions
(paragraph 3.1.1) to assist in finding which component led to the switching failure.
POSSIBLE CAUSE REMEDY
Pilot air insufficient
Inlet air pressure below setpoint of
pressure switches
39
Close pilot air isolation valve, depressurize
pilot air filter and inspect element. If
clogged or dirty, replace.
Check that pilot air isolation valve is fully
open.
Check that pilot air regulator is set at 100
psig.
Inspect pilot air tubing for kinks or breaks.
Repair if necessary.
Correct the low pressure problem to the
dryer.
Page 46
USER MANUAL
Inspect purge and depressurization
closing or are leaking. Check solenoid
TZE400 to TZE3500 with EMS
6.4 SWITCHING FAILURE ALARM (CONTINUED)
POSSIBLE CAUSE REMEDY
Check operation of solenoid. Replace if
not functioning.
Solenoid valve not energizing
Inlet or purge exhaust valves leaking
Check valve internals are worn or
damaged
Check wiring from panel to the solenoid for
an open or short circuit. Repair if
necessary.
Shut down and depressurize dryer. Inspect
valve seats and seals for damage or wear.
Repair or replace if necessary.
While valve is disassembled, check the
actuator stops to ensure that valve is fully
closing ( butterfly valves only).
Shut down and depressurize dryer. Repair
or replace valves.
REV 10 – 23 February 2006
Switching failure on depressurization.
Switching failure on repressurization.
Pressure switch malfunction.
mufflers and replace if necessary.
Off-line desiccant chamber inlet valve or
outlet check valve leaking. Inspect as
described above
Regenerating chamber depress/exhaust
valve failed to open. Check associated
solenoid valve operation as described
above.
Online chamber outlet check valve leaking.
Inspect and repair as described above.
Excessive purge flow. Check the purge
pressure setting.
Exhaust or depressurization valves not
operation as listed above. Check valve
failure as listed above.
Insufficient purge flow. Check purge
pressure settings. Check automatic purge
isolation valve for correct operation.
Check the setpoint of the pressure
switches. Readjust if necessary.
Check the operation of the pressure
switches. Replace if needed.
40
Page 47
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
41
Page 48
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
7. DRAWINGS
42
Page 49
USER MANUAL
TZE400 to TZE3500 with EMS
REV 10 – 23 February 2006
43
Page 50
Page 51
INGERSOLL-RAND COMPANY, 800-A BEATY STREET, DAVIDSON, NORTH CAROLINA, 28036 – USA
TEL: (704) 896-4000 / FAX: (704) 896-4648
WWW.AIR.IRCO.COM
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.