Ingersoll-Rand NVC 200, NVC 300, NVC 400 Operator's Manual

Page 1
Nirvana Cycling Refrigerated Dryer
ENGLISH
PORTUGUESE
PRINT LANGUAGE
FRENCH
SPANISH
Models 200-400
Operator’s Manual
EN
Operator’s Manual
Manual Del Operador
FR
Manuel De L’opérateur
PT
Manual do Operador
80442775
Revision E
July 2012
Save These Instructions
Page 2

1.0 CONTENTS

CONTENTS PAGE CONTENTS PAGE
1.0 CONTENTS 2
2.0 INTRODUCTION 3
3.0 WARRANTY 3
4.0 REFRIGERATED DRYER NOMENCLATURE 3
5.0 RECEIVING AND INSPECTION 4
5.1 INSPECTION 4
5.2 UNPACKING AND HANDLING 4
6.0 SAFETY AND OPERATION PRECAUTIONS 4
7.0 PRINCIPLES OF OPERATION 6
7.1 INTRODUCTION 6
7.2 AIR SYSTEM 6
7.3 MOISTURE REMOVAL SYSTEM 6
7.3.1 SOLENOID DRAIN STANDARD 6
7.3.2 NO AIR LOSS DRAIN OPTIONAL 7
7.4 REFRIGERATION SYSTEM 7
7.5 THERMAL MASS CIRCULATING SYSTEM 7
7.6 CONTROLS 7
7.6.1 BASIC USER INTERFACE 8
7.6.2 EXCHANGER TEMPERATURE SET POINT AND ALARMS 8
7.6.3 ADJUSTING SET POINTS 9
7.6.4 ALARMS AND THEIR FUNCTIONS 9
7.6.5 ALERT MESSAGES 9
7.6.6 START MODES 9
7.6.6.1 MANUAL MODE 9
7.6.6.2 REMOTE MODE OPTIONAL 9
7.6.6.3 AUTO RESTART 10
8.0 INSTALLATION AND INITIAL STARTUP 10
8.1 LOCATION AND MOUNTING 10
8.2 PIPING AND VALVES 10
8.3 FILTRATION 10
8.4 ELECTRICAL CONNECTION 11
8.5 INITIAL STARTUP 11
8.5.1 START UP SEQUENCE 11
9.0 SCHEDULED MAINTENANCE 12
9.1 INTRODUCTION 12
9.2 REFRIGERANT CONDENSER 12
9.3 CONDENSATE DISCHARGE SYSTEM 12
9.3.1 SOLENOID DRAIN STANDARD 12
9.3.1.1 CLEANING INSTRUCTIONS  SOLENOID DRAIN 12
9.3.2 NO AIR LOSS DRAIN OPTIONAL 13
9.4 PANEL FILTER ELEMENT 13
9.5 PREFILTERS AND POSTFILTERS 13
10.0 TROUBLESHOOTING 14
10.1 INTRODUCTION 14
10.2 PROBLEM / ACTION GUIDE 14
11.0 WIRING DIAGRAMS 17
12.0 GENERAL ARRANGEMENT 21
13.0 REPLACEMENT PARTS 22
13.0 REPLACEMENT PARTS 23
14.0 ENGINEERING SPECIFICATIONS 23
2 NIRVANA CYCLING REFRIGERATED DRYER MODELS 200-400 ingersollrandproducts.com
Page 3

2.0 INTRODUCTION

Ingersoll Rand Nirvana™ Cycling refrigerated air dryer
removes moisture, oil vapor, and other contaminants from compressed air. These contaminants are detrimental to pneumatically operated appliances, controls, instruments, machinery and tools. This removal is accomplished by cooling the air with a refrigeration unit to a temperature at which moisture in the air is condensed and separated

3.0 WARRANTY

The Company warrants that the equipment manufactured by it and delivered hereunder will be free of defects in material and workmanship for a period of twelve months from the date of placing the Equipment in operation or eighteen months from the date of shipment from the factory, whichever shall rst occur. The Purchaser shall be obligated to promptly report any failure to conform to this warranty, in writing to the Company in said period, whereupon the Company shall, at its option, correct such nonconformity, by suitable repair to such equipment or, furnish a replacement part F.O.B. point of shipment, provided the Purchaser has stored, installed, maintained and operated such Equipment in accordance with good industry practices and has complied with specic recommendations of the Company. Accessories or equipment furnished by the Company, but manufactured by others, shall carry whatever warranty the manufacturers have conveyed to the Company and which can be passed on to the Purchaser. The Company shall not be liable for any repairs, replacements, or adjustments to the Equipment or any costs of labor performed by the Purchaser or others without Company’s prior written approval.
The eects of corrosion, erosion and normal wear and tear are specically excluded. Performance warranties are limited to those specically stated within the Company’s proposal. Unless responsibility for meeting such
from the air stream. The temperature the air is cooled to, normally between 34° and 38°F (1° and 3°C), is known as dew point. This dryer can be easily installed into various pneumatic systems in which dry air is required or desired. Please refer to Principles of Operation for complete operating details.
performance warranties are limited to specied tests, the Company’s obligation shall be to correct in the manner and for the period of time provided above.
THE COMPANY MAKES NO OTHER WARRANTY OR REPRESENTATION OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE HERBY DISCLAIMED.
Correction by the Company of nonconformities whether patent or latent, in the manner and for the period of time provided above, shall constitute fulllment of all liabilities of the Company for such nonconformities whether based on contract, warranty negligence, indemnity, strict liability or otherwise with respect to or arising out of such Equipment.
The Purchaser shall not operate Equipment which is considered to be defective, without rst notifying the Company in writing of its intention to do so. Any such use of Equipment will be at Purchaser’s sole risk and liability.
Note that this is Ingersoll Rand standard warranty. Any warranty in force at the time of purchase of the equipment or negotiated as part of the purchase order may take prec-
edence over this warranty.

4.0 REFRIGERATED DRYER NOMENCLATURE

PREFIX NOMINAL*
FLOW
NVC 200-400 A = AIR
* Nominal Flows indicated are for 100°F inlet temperature, 100°F ambient temperature and 100 psig compressed air pressure.
ingersollrandproducts.com 3
CONDENSER
TYPE
W = WATER
POWER RATING
2 = 230-1-60 4 = 460-3-60 5 = 230-3-60 6 = 575-3-60 7 = 380-3-50 8 = 220-3-50
0 = NEMA 1 H = NEMA 4
Page 4

5.0 RECEIVING AND INSPECTION

5.1 INSPECTION

Upon receiving your Ingersoll Rand air dryer, please inspect the unit closely. If rough handling has been detected, please note it on your delivery receipt, especially if the dryer will not be uncrated immediately. Obtaining the delivery person’s signed agreement to any noted damages will facilitate any insurance claims.

5.2 UNPACKING AND HANDLING

WARNING
Under no circumstances should any person attempt to lift heavy objects without proper lifting equipment (i.e., crane, hoist, slings or fork truck). Lifting any unit without proper lifting equipment, may cause serious injury.

6.0 SAFETY AND OPERATION PRECAUTIONS

Because an air dryer is pressurized and contains rotating parts, the same precautions should be observed as with any piece of machinery of this type where carelessness in operation or maintenance could be hazardous to personnel. In addition to obvious safety rules that should be followed with this type of machinery, safety precautions as listed below must be observed:
Only qualied personnel shall be permitted to adjust,
1. perform maintenance or repair this air dryer.
To facilitate handling during shipment, all dryer packages have been mounted on a base that provides for forklifting between two base channels. Forks should extend all the way through forklift channels to reduce unnecessary forces to the dryer during moving. Slings can be used to lift the crates, but spreader bars must be used to prevent the slings from exerting a force against the sides of the crates or the dryer.
OSHA Heading Descriptions
WARNING
“Warning” is used to indicate a hazardous situation which has some probability of death or severe injury. Warning should not be considered for property damage accidents unless personal injury risk is present.
Read all instructions completely before operating
2. unit.
Pull main electrical disconnect switch and
3. disconnect any separate control lines, if used, before attempting to work or perform maintenance on the unit.
Do not attempt to service any part while machine is
4. in an operational mode.
Do not attempt to remove any parts without rst
5. relieving the entire air system of pressure.
Do not attempt to remove any part of the
6. refrigeration system without removing and containing refrigerant in accordance with the EPA and local regulations.
Do not operate the dryer at pressures in excess of its
7. rating.
Do not operate the dryer without guards, shields and
8. screen in place.
Inspect unit daily to observe and correct any unsafe
9. operating conditions.
CAUTION
“Caution” is used to indicate a hazardous situation which may result in minor or moderate injury.
NOTICE
“Notice” is used to indicate a statement of company policy as the message relates directly or indirectly to the safety of personnel or protection of property. Notice should not be associated directly with a hazard or hazardous situation and must not be used in place of “Danger,” “Warning,” or “Caution.”
NOTICE
The user of any air dryer manufactured by Ingersoll Rand, is hereby warned that failure to follow the above Safety and Operation Precautions may result in personal injury or equipment damage. However, Ingersoll Rand does not state as fact, nor does it mean to imply, that the preceding list of Safety and Operating Precautions is all inclusive, and further, that the observance of this list will prevent all personal injury or equipment damage.
4 ingersollrandproducts.com
Page 5
6.0 SAFETY AND OPERATION PRECAUTIONS
Air Under Pressure Will Cause Injury, Death Or Property Damage.
• Do Not Exceed Pressure Rating.
• Relieve Press. Before Servicing.
• Do Not Modify/Repair/Rework ASME Coded Pressure Vessels As Insurance Rating Aected.
READ TECHNICAL MANUAL
ELECTRICAL CONNECTION BOX
All Customer Connections To Be Made At This Location. See Terminal Connection Diagrams, below. Be Certain To Follow All NEC, State, Local and Other Applicable Codes During Installation.
1
2
3
4
5
6
GRN
WHT
BLK
G
N
L1
FACTORY
WIRING
INCOMING
LINE VOLTAGE
100-125VAC 1PH/50-60HZ (BY OTHERS)
(REFER TO UNIT
NAMEPLATE FOR
POWER
REQUIREMENTS)
100-125VAC / 1 PH
1
2
3
4
5
6
GRN
BLK
G
L1
RED
L2
FACTORY
WIRING
INCOMING
LINE VOLTAGE
200-240VAC 1PH/50-60HZ (BY OTHERS)
(REFER TO UNIT
NAMEPLATE FOR
POWER
REQUIREMENTS)
200-240VAC / 1 PH
1
2
3
4
5
6
GRN
RED
WHT
G
L1
L2
BLK
L3
FACTORY
WIRING
INCOMING
LINE VOLTAGE
200-575VAC 3PH/50-60HZ (BY OTHERS)
(REFER TO UNIT
NAMEPLATE FOR
POWER
REQUIREMENTS)
200-575VAC / 3 PH
ELECTRICAL CONNECTION BOX
CONTAINS HIGH VOLTAGE
• Turn O Power And Lock Out At ALL Sources Before Opening To Perform Service.
• Remote Alarm Contact Wiring Has Control Power From Separate Source.
READ TECHNICAL MANUAL
Air Under Pressure Will Cause Injury, Death Or Property Dam age.
• Relieve Press. Before Servicing.
• Condensate Drain Discharges Under Pressure.
• Drain Requires Periodic Cleaning (Service).
READ TECHNICAL MANUAL
Removing fuses will not disconnect power from dryer. Always disconnect power from ALL sources before performing service.
READ TECHNICAL MANUAL
HIGH VOLTAGE
This unit is charged with
refrigerant under high pressure.
FAN MAY AUTOMATICALLY
START AT ANY TIME
ingersollrandproducts.com 5
Page 6

7.0 PRINCIPLES OF OPERATION

7.1 INTRODUCTION

Ingersoll Rand Nirvana™ Cycling dryers remove moisture
from compressed air by cooling the air temperature to between 34° and 38°F (1 and 3°C). This causes vapors to condense into liquid droplets which can then be easily removed from the air. The major systems of the dryer which contribute to its operation are the Air System, the Moisture Removal System, the Refrigeration System, the Thermal Mass Circulating System and the Controls. The following paragraphs describe each of the systems in greater detail.

7.2 AIR SYSTEM

The air system consists of the dryer components which are in contact with the compressed air. Referring to Figure 1 and following the bold “AIR FLOW,” hot saturated
air from the compressor enters the precooler/reheater where the air temperature is reduced prior to entering the chiller by the cool air exiting the air/moisture separator. This precooling allows for the use of a smaller refrigeration system. The air then goes into the chiller section where it is further cooled to the desired dew point by a thermal mass uid. The temperature of the thermal mass uid is maintained by the refrigeration circuit and controls. The air continues to the separator where moisture is removed, thereby, allowing the cool, dry air to return back to the precooler/reheater to be heated by the incoming moist hot air. The air exiting the “reheater” portion of the dryer should be approximately 15°- 20°F lower than the inlet air temperature based on standard conditions at full rated ow.
FAN MOTOR
AIR INLET
PRECOOLER / REHEATER
CHILLER
EVAPORATOR
CONDENSATE
DRAIN
LEGEND
AIR OUTLET
SEPARATOR
AIR FLOW REFRIG (R404A) FLOW THERMAL MASS FLUID CONDENSATE LINE WATER FLOW
CHILLER (EXCHANGER) TEMPERATURE
DIGITAL DISPLAY
CONTROL ENCLOSURE
FIGURE 1  FLOW DIAGRAM

7.3 MOISTURE REMOVAL SYSTEM

Ingersoll Rand condensate drains discharge condensed
moisture and lubricants (condensate) from compressed air equipment.
Liquid droplets are removed from the air stream in the separator. As the air and liquid mixture passes through the separator it spins, slows down and then changes direction. This causes condensate to fall out of the air stream and collect in the bottom of the separator. The collected liquid is removed from the separator by a timed electric drain(standard) which is controlled by the Controller OR an optional No-Air Loss drain.
WATER-COOLED CONDENSER
WATER IN
WATER OUT
CIRCULATING PUMP
WATER REGULATING VALVE
FILTER DRYER
AIR COOLED CONDENSER
THERMAL MASS RESERVOIR
REFRIGERANT MATERING
DEVICE
REFRIG
COMPRESSOR
PROCESS AND INSTRUMENTATION DIAGRAM NVC200-400 AIR AND WATERCOOLED
550032-D
7.3.1 SOLENOID DRAIN (STANDARD)
The Drain Open time and Drain Closed time are accessed by depressing the appropriate button and using the up and down arrows to change the value. The Drain Open value is seconds; the Drain Closed value is minutes.
To obtain the optimum time values for operation of
the electric drain valve, set the drain closed time to ve minutes and the open time to ten seconds.
After running the unit under full rated ow for
approximately 30 minutes, verify that when the electric drain opens, all of the accumulated liquid is discharged and then followed by a small burst of air.
6 ingersollrandproducts.com
Page 7
7.0 PRINCIPLES OF OPERATION
If a small amount of liquid and a large amount of
air is discharged, decrease the on-time setting or increase the o-time setting. If there is all liquid and no air has been discharged, increase the on-time setting or decrease the o-time setting.
The on/o-time settings will vary accordingly to
seasonal conditions. During the summer when more moisture is present in the air system, a shorter ontime that increases the valve opening frequency is required. A longer o-time may be used during the winter months when moisture levels are lower.
7.3.2 NO AIR LOSS DRAIN (OPTIONAL)
The condensate drain operates as a zero-air-loss drain, returning air that is displaced in the drain bowl back into the compressed air system. Consistent discharging of condensate from compressed air equipment is essential for proper equipment operation and performance.
The condensate drain uses a unique sensing method to determine the level of condensate in the drain bowl. A transducer located in the drain bowl continuously sends out a signal 50 times per second. Once the transducer determines that the level of condensate has reached a predetermined level within the drain bowl, a signal is sent to the no-loss drain valve to open. This operation permits removal of condensate of up to 80 gallons per hour.
tube (expansion valve on water-cooled dryers) meters the refrigerant for introduction into the evaporator. The refrigerant pressure is reduced upon entering the evaporator where as it evaporates, removes heat from the thermal mass uid.

7.5 THERMAL MASS CIRCULATING SYSTEM

The thermal mass uid in a Ingersoll Rand Nirvana™ Cycling dryer is continuously circulated in a closed pump loop system. Referring to Figure 1 and following the dashed “THERMAL FLUID” line, the heat is removed from the uid in the evaporator by the refrigeration system. The thermal mass reservoir is sized to minimize refrigeration cycles during reduced air load periods. The thermal mass uid is pulled from the bottom of the reservoir and pumped through the chiller, removing heat from the air and then returned to the evaporator. The pump utilized on the Ingersoll Rand Nirvana™ Cycling dryer is a maintenance­free, quiet cartridge circulator pump similar to those used in residential water systems. While the refrigeration system cycles on and o based on loading conditions, the circulating pump runs continuously to maintain ow through the chiller at all times. Note that when the power switch is set to the o position, the circulating pump will not operate.

7.6 CONTROLS

The drain also features a test button that permits manual operation of the no-loss drain valve. Depressing the test button illuminates the LED and energizes the solenoid valve. The LED illuminates to indicate “POWER ON” and goes o when the no-loss drain valve is operated by the transducer or manual test button.
The condensate ows through the feed line into the drain unit and accumulates in the container. A capacitive sensor continuously registers the liquid level and passes a signal to the electronic control as soon as the container is lled. The pilot valve is then activated and the diaphragm opens the outlet line for discharging the condensate. When the drain unit has been emptied, the outlet line is closed again quickly and tightly without wasting compressed air.”

7.4 REFRIGERATION SYSTEM

The Refrigeration System consists of all the components which handle R-404A. This is a hermetically sealed closed­loop system. Referring to Figure 1 and following the phantom “REFRIG(R-404A) FLOW,” refrigerant is shown leaving the evaporator section where, in the process of removing heat, it is changed from a low pressure liquid into a low pressure gas. This gas enters the suction side of the compressor where it is compressed into a high pressure gas. The high pressure gas is cooled in the condenser section until it becomes a high pressure liquid. It then goes through a permanent lter dryer that ensures the refrigeration system is free of contaminants. A small diameter capillary
The Ingersoll Rand NVC200-400 Series dryers incorporate automatic controls for proper operation. The thermal mass uid temperature is maintained by a microprocessor control that monitors the temperature and cycles the refrigeration system in response to varying air ow and temperature. Upon an increase in the temperature of the thermal mass uid, the refrigeration compressor is cycled on. When the uid is cooled to two deg.F below its control set point, the refrigerant compressor is cycled o. The thermal mass uid functions as a thermal storage mass in the NVC Series dryer.
A low pressure cut out (LPCO) switch is provided for all NVC series dryers. This switch is factory set to open at 20 psig. If the refrigerant suction pressure draws below 20 psig, the LPCO opens to shut o the refrigerant compressor. Once the switch has opened, it will prevent the compressor from running until the suction pressure rises above 60 psig and the LPCO has been manually reset.
All water cooled units come with a high pressure cut out (HPCO) switch. This switch is set to open at 320 psig and close at 270 psig. To compensate for water temperature variation, it may be necessary to adjust the water regulating valve to maintain a 250 psig discharge pressure. Adjustment can be done by rotating the adjusting screw counterclockwise for an increase in discharge pressure. For conditions where low water temperature and/or high water pressure are expected it is advisable to install a water pressure regulator ahead of the condenser.
ingersollrandproducts.com 7
Page 8
ADJUSTMENT SCREW
7.0 PRINCIPLES OF OPERATION
FIGURE 2  WATER REGULATING VALVE
7.6.1 BASIC USER INTERFACE
The Controller provides the user with information about the dryer’s operation and alarms.
The following illustration summarizes the keypad functions.
TYPICALMAY VARY WITH DRAIN
BUTTONS
ON / OFF
Toggles the dryer operation between “On Line” and “O Line” status; Energizes glycol pump. Note that the refrigeration system will operate based on temperature.
EXCH SET
When depressed, will display the current exchanger set point in the LCD window. While the exchanger set point is displayed, the up and down arrows may be used to increase or decrease the exchanger set point temperature.
ALARM RESET
Pressing once clears the local alarm indication and de-energizes the remote alarm contact. Should the alarm condition persist, the alarm will return after the alarm inhibit time has expired.
% SAVINGS
Depressing once changes LCD display to indicate ratio of refrigeration system running time vs. total dryer ON time.
°F / °C
Toggles the LED temperature indicators between Fahrenheit and Celsius units of measure.
+ / -
Allows user to modify set point values. Set point values cycle through a xed range.
DRAIN OPEN (SOLENOID DRAIN ONLY)
Press this button to set the length of time in seconds that the condensate drain will be open. This is adjustable from one (1) to sixty (60) seconds.
DRAIN CLOSED (SOLENOID DRAIN ONLY)
Press this button to set the amount of time in minutes that the condensate drain will be closed. This is adjustable from one (1) to sixty (60) minutes.
DRAIN TEST (SOLENOID DRAIN ONLY)
Press this button to open the drain to verify operation.
LIGHTS
LCD Display
Displays exchanger temperature during normal operation. Also used to display exchanger temperature set point, alarm condition and timing functions.
SYSTEM ENERGIZED
Indicates when power is applied to unit.
DRYER ON
Illuminated when the On/O switch has been pressed to place the unit in operation. The refrigerant system may start at any time when the light is on.
REFRIGERATION COMPRESSOR ON
Indicates that the refrigeration system is operating.
DEGREES F / DEGREES C
Indicates the temperature units of measure.
HIGH TEMP ALARM
Indicates that the exchanger temperature has risen to 10°F or 5°C above the exchanger temperature set point.
LOW TEMP ALARM
When activated, indicates that the exchanger temperature has dropped below 29°F or -2°C. This condition stops the compressor. The compressor will not restart until the temperature has risen two degrees above exchanger set point.
DRAIN OPEN (SOLENOID DRAIN ONLY)
This light comes on when power is applied to open the time solenoid drain.
7.6.2 EXCHANGER TEMPERATURE SET POINT AND ALARMS
The Controller allows the user to congure the dryer’s Exchanger Temperature Setpoint to operate according to site conditions. The Controller is shipped from the factory with the exchanger temperature having a default value of 38 deg.
8 ingersollrandproducts.com
Page 9
EXCH.
SET
36
37
38
38
P F
C D
7.0 PRINCIPLES OF OPERATION
7.6.3 ADJUSTING SET POINTS
Accessing and manipulating the Exchanger Temperature Setpoint is accomplished as follows.
Pressing EXCHANGER SETPOINT button will change the display to show the current setpoint.
Pressing the UP or DOWN arrows modies the EXCHANGER SETPOINT in one degree increment.
Pressing the UP or DOWN arrows modies the EXCHANGER SETPOINT in one degree increment.
The Controller accepts the last setpoint. After 5 seconds, the readout will return to displaying the current Exchanger Temperature.
CAUTION
Do not set the Exchanger Temperature greater than 50 deg.F. Running dryer at an Exchanger Temperature higher than 50 deg.F may damage refrigeration system.
7.6.4 ALARMS AND THEIR FUNCTIONS
condition may not necessarily damage the dryer when subjected to long-term exposure. It may, however, have a signicant impact on downstream processes and thus should be investigated upon detection. Note that this alarm will not shut down the dryer. This alarm will activate the remote alarm contact and reset automatically once the alarm condition is rectied.
LOW TEMPERATURE SAFETY ALARM
If the dryer chiller temperature falls below the factory set point, the alarm routine will activate. This alarm condition may cause damage to the dryer when subjected to continuous or long-term exposure. Note that this alarm will shut down the dryer after a response time delay. This alarm will activate the remote alarm contact and reset automatically once the alarm condition is rectied.
7.6.5 ALERT MESSAGES
The Controller features the following readouts to communicate the status of the dryer’s operation.
Indicates a probe failure. This condition is usually caused by a probe being unplugged, damage to the probe lead or a defective probe.
Indicates that the refrigerant compressor will not start until the end of a three minute safety delay. The display of “cd” is immediately followed by the number of minutes left in the delay. This is a normal function of the controller and not a fault indication.
7.6.6 START MODES
The NCV200-400 dryers are capable of starting in one of the following start modes:
The Controller indicates critical alarms to alert the user of an out of tolerance condition. Once each alarm condition is detected, the appropriate LED indicator will illuminate and the remote alarm contact will close.
Alarm Display Alarm Set Point HIGH TEMPERATURE ALARM LOW TEMPERATURE ALARM
The alarm names and a brief description of each are described in detail below.
HIGH TEMPERATURE ALARM
When the thermal mass (glycol) temperature reaches the alarm set point, the alarm will be activated. This alarm
HI TEMP ALARM EXCH SETPOINT +
10 °F
LOW TEMP ALARM 28 °F
7.6.6.1 Manual Mode
After power is supplied to the dryer, the LCD display will indicate the chiller temperature as well as the time remaining for the safety delay. Once the delay has timed out, depressing the On/O button will permit the refrigeration system to operate. Should the chiller temperature be greater than the set point, the refrigeration system will energize. Should the chiller temperature be below the set point, the refrigeration system will remain o until the chiller temperature rises to the setpoint.
7.6.6.2 Remote Mode (Optional)
This mode of operation allows the user to control the dryer remotely and requires the installation of a customer­supplied contact. With power applied to the dryer and once the safety delay has timed out, the dryer will start once the remote switch is closed. In addition, this mode of operation
ingersollrandproducts.com 9
Page 10
7.0 PRINCIPLES OF OPERATION
still permits manual control of the dryer via the On/O pushbutton on the local control panel. Note that if the dryer was turned “On” from the remote switch and then turned “O” via the local control panel, the remote switch must be turned “O” and then “On” to reinstate the dryer.
8.0 INSTALLATION AND INITIAL STARTUP

8.1 LOCATION AND MOUNTING

The dryer should not be located in an area where ambient temperature is likely to exceed 113°F (45°C) or be less than 50°F (10°C). The dryer must be located in an area that provides sucient clearance from walls and other adjoining equipment to allow easy access for servicing and maintenance requirements. A minimum of 18 inches is required to allow free ow of air to the condenser inlet.
On installations with a relatively steady ow rate, the dryer is normally connected after the air receiver. If loads uctuate widely, the dryer should be positioned ahead of the receiver and sucient storage capacity downstream is necessary to prevent excessive air ow through the dryer.
7.6.6.3 Auto Restart
Should the dryer lose power while in the “On” mode, the dryer will revert to the “On” mode once power is restored. Similarly, should power be removed from the dryer while the dryer is in the “O” mode, the dryer will remain in the “O” mode once power is restored until the On/O switch is depressed or the remote switch is closed.

8.2 PIPING AND VALVES

Install piping, ttings and accessories as required for specic site conditions and requirements. Figure 3 indicates a typical piping arrangement for a refrigerated dryer, including dryer and lter bypasses. This gure can be used as a guide for valve and accessory placement in the system.
Ingersoll Rand NVC200-400 models come factory installed with a drain isolation valve (D). The isolation valve permits maintenance of the automatic drain without isolating air ow to the dryer. To operate dryer, all valves shown in Figure 3 are to be closed except valves (B), (C) and (D). Valve (A) is used for bypass purposes and valve (E) is for test and manual drain purposes.
When installed after any compressor that causes signicant vibration or air pulsation, such as reciprocating compressors, proper vibration isolation and pulsation dampening devices should be added to protect the dryer.
NOTICE
Failure to comply to the above instructions may result in equipment malfunction and will void warranty.
NOTICE
Always use a backup wrench when making any threaded connection to the dryer. Failure to use a backup wrench may result in damaged tubing and components internal to the cabinet.

8.3 FILTRATION

To protect the air dryer from gross contamination associated with compressor oil and debris and ensure maximum dryer performance, a pre-lter is recommended. Pre-lters and post-lters sized to your drying application can be provided by Ingersoll Rand and are available factory installed. Call your local distributor to select the lter that best suits your ltration requirements. In addition to air ltration, condensate discharge oil/water separators are also available to address stringent EPA regulations.
10 ingersollrandproducts.com
Page 11
B
A
C
UNIT AS DELIVERED
OPTIONAL ACCESSORY ITEMS
NOTE:
DRAIN TUBE MUST NOT RISE OR BE CONNECTED TO EXCESSIVELY LONG PIPE WHICH MAY CREATE BACK PRESSURE A CONNECTION TO OPEN FLOOR DRAIN IS REQUIRED
DE
AIR IN
PRE-FILTER
AIR
DRYER
AIR OUT
OIL
SEPERATOR
DRAIN VALVE
DRAIN VALVE
CHECK
VALVE
CHECK
VALVE
CHECK
VALVE
CHECK
VALVE
8.0 INSTALLATION AND INITIAL STARTUP
FIGURE 3  TYPICAL PIPING ARRANGEMENT

8.4 ELECTRICAL CONNECTION

Equipment is available in various electrical congurations. All customer connections can be made at the terminal connections located in the customer electrical connection box on the rear of the dryer. (Refer to General Arrangement and appropriate Wiring Diagrams.)
A suitable fused disconnect switch or circuit breaker, in accordance with national and local code requirements, is recommended for all Ingersoll Rand equipment. Refer to Section 13 for voltage requirements and load.
CAUTION
Never wire directly or connect any additional wires to the compressor junction box. This will cause severe system malfunction.

8.5 INITIAL START-UP

NOTICE
For water cooled models, the water valve must be manually opened to ensure that the condenser is full of water prior to start-up.
8.5.1 START- UP SEQUENCE
Apply power to dryer. LCD Panel will illuminate. The
Anti- Short Cycle delay will commence counting down.
NOTICE
After installation or a prolonged shutdown, start the dryer with no air load (no air ow). This enables the dryer to reach its proper operating temperature in the shortest time possible (typically within 30 minutes for Nirvana™ Cycling dryers).
Start Dryer, using one of the following methods,
depending on Start Mode setting:
Manual Mode - Press the ON pushbutton.
Auto Restart Mode - No additional action required
Remote Automatic Mode - Close the remote contact.
ingersollrandproducts.com 11
Page 12

9.0 SCHEDULED MAINTENANCE

PROFILE GASKET
ELECTRICAL CONNECTOR
SCREW
APPLIANCE SOCKET
SEAL
WASHER
CABLE GLAND
SOLENOID VALVE
SPRING WASHER
RETAINER NUT
WASHER
D.I.N. UNIT SOLENOID
PLUNGER TUBE ASSY.
ORIFICE CUP
BEVELLED WASHER
STRAINER
BODY
THREADED FLANGE GASKET
PLUNGER W/ SPRING ASSEMBLY
8
9
9
5
6
7
1
6
2
4
1
3
10
8 9
5
7
1
3
2
4

9.1 INTRODUCTION

Ingersoll Rand Nirvana™ Cycling refrigerated air dryers
require little maintenance. These dryers utilize hermetically sealed compressors which do not require any lubrication. Fan motors require lubrication at both oil ports every six months. Ingersoll Rand recommends component inspection and service at regular intervals to obtain maximum performance from your dryer.

9.2 REFRIGERANT CONDENSER

For standard dryers, regular inspection and cleaning of the condenser is recommended. Ingersoll Rand dryers may be equipped with an optional ambient air lter designed to protect the condenser from dirt and debris that can accumulate on the condenser. For proper operation with this option, it is imperative that this lter be inspected and cleaned on a regular basis. Annual replacement of the lter is recommended. For applications where excessive dirt, dust or debris is encountered, more frequent inspection and cleaning may be required.

9.3 CONDENSATE DISCHARGE SYSTEM

9.3.1 SOLENOID DRAIN (STANDARD)
been cleaned and inspected. Reposition the orice hole on the rubber gasket of the orice cup in the line and closest to the arrow indicated on the valve body.
Reassemble valve and install in reverse order as
described above.
On a minimum of a monthly basis, the operation of the drain should be checked. Periodically, the drain should be removed and cleaned to ensure no debris from the system is trapped inside. Ingersoll Rand dryers are equipped with
FIGURE4 SOLENOID DRAIN ASSEMBLY
a drain isolation valve, enabling the valves to be cleaned during dryer operation after the drain isolation valve has been manually closed. The drain valve is located near the solenoid valve and requires a quarter turn to isolate the drain from system pressure.
9.3.1.1 Cleaning Instructions - Solenoid Drain
Be sure dryer is depressurized or isolation valve is
closed.
Disconnect drain body from lter stop.
Loosen connector screw to allow the electrical
connector assembly to be removed from the D.I.N. unit solenoid.
Remove retainer nut and separate the valve body
from the D.I.N. unit solenoid. Unthread the plunger tube assembly in a counterclockwise direction until plunger separates from valve body.
Clean beveled washer, thread gasket, spring
assembly and strainer with soap and water. Do NOT use solvents of any kind, as failure to the seals will occur. Be especially careful to clean the center brass orice and the rubber gasket orice on the orice cup with a straight pin.
Reassemble all drain components after the drain has
FIGURE5 NO AIR LOSS DRAIN
12 ingersollrandproducts.com
Page 13
9.0 SCHEDULED MAINTENANCE
1
2
3
4
5
6
7
2
5
4
3
2
1
6
4
3
1
1
2
3
4
9.3.2 NO AIR LOSS DRAIN (OPTIONAL)
WARNING
Before drain maintenance work, always close the drain isolation ball valves and ensure that the device is pressureless and de-energized.
Maintenance recommendations
Replace service unit (5) annually.
Remove control unit (1) by pressing latching
hook (2).
Detach Drain from outlet (3).
Remove design shell (4) (where applicable) using
a screw driver (10).
Remove service unit (5) from pipe at inlet by undoing union nut
or by undoing screws (6) at elbow connector (7)
or by undoing screws (8) at intermediate adapter (9)
which is then detached from the service unit by
downward movement.
Check if new service unit (5) matches control unit (1)
- type designation and colour of latching hook (2)
Fit new service unit (5) in reverse order
Open drain isolation ball valve. Press drain test
button to verify proper drain operation.
Fit latching hook (6) of control unit (1) into
sensor tube plate (5).
Press control unit (1) against service unit (3) and
snap into place
Open drain isolation ball valve. Press drain test
button to verify proper drain operation.

9.4 PANEL FILTER ELEMENT

Annual replacement of the panel lter element is recommended. To replace the panel lter element, remove the panel lter by pulling up and out of its slots, then t the new element in.

9.5 PRE-FILTERS AND POST-FILTERS

WARNING
Depressurize the system before disassembling lters. Failure to do so may result in injury or death.
Filter elements should be changed as indicated on the pressure dierential gauge. Change carbon elements when hydrocarbons are rst detected downstream or every six months, whichever comes rst.
Certain lters contain multiple elements. When replacing lter elements, all elements should be replaced simultaneously. Mixing new and old elements can result in reduced air quality.
Assembly Control unit onto service unit:
Check if service unit (3) matches control unit (1) (type designation and colour of latching hook)
Check if sensor tube plate (5) with contact springs (4) is clean, dry and free from foreign matter.
Insert sensor (2) into sensor tube plate (5).
ingersollrandproducts.com 13
Page 14

10.0 TROUBLESHOOTING

10.1 INTRODUCTION

Ingersoll Rand Nirvana™ Cycling dryers are designed for
reliable, trouble-free operation. In the event of any dryer malfunction, the guide below has been developed to facilitate problem identication and corrective actions.
WARNING
Prior to working on the unit, make sure that all circuit breakers or disconnected switches are tagged “Out of Service.”
WARNING
An air dryer always operates under pressure. Any maintenance procedure that involves disassembly of pipe ttings, valves or any other components requires the dryer be isolated from the compressed air stream and fully depressurized.

10.2 PROBLEM / ACTION GUIDE

PROBLEM SYMPTOM(S) POSSIBLE CAUSE CORRECTIVE ACTION
Moisture down stream Dryer is properly cooling air
stream (Check Chiller. Temp on controller)
Inlet and outlet temperatures are the same.
Moisture down stream Inlet and outlet
temperatures are the same.
Compressor and fan are running, exchanger temp high, pump not running.
Condensate drain failure caused by defective service unit.
Excessive ow Check inlet and outlet pressure
Dryer by-pass valve not closed Close by-pass valve No power to the dryer Check power supply and fuses/
High suction pressure Check and clean condenser. Refrigerant leak Check suction pressure gauge if
Compressor not running and fan is running
Compressor and fan not running.
Compressor and fan not running. Controller indicates compressor is ON.
Defective Pump Contact your local distributor
Replace service unit.
and system design capacity. Correct cause of excessive ow.
circuit breakers
reading is 0 psig, turn dryer o and contact your distributor
Check and clean condenser. Check ambient temperature
and reduce below 113°F Check Chiller Temperature Check MAIN CONTROL fuse. Compressor relay may be bad,
replace relay Check for loose wire
connections at contactor or loss of power at control board
Defective control board ­replace as necessary
Contact your local distributor for further assistance.
for further assistance.
14 ingersollrandproducts.com
Page 15
10.0 TROUBLESHOOTING
PROBLEM SYMPTOM(S) POSSIBLE CAUSE CORRECTIVE ACTION
Apparent controller display malfunction
High pressure drop across dryer
Condensate drain does not re
Display Blank Blown Fuse Check Fuses
Board Failure Contact your local distributor
for further assistance.
Unrealistic temperature displayed
Erratic or inaccurate temperature readings
Unrealistic pressure displayed
Outlet pressure substantially lower than inlet pressure System operating temperature is above 32°F
Outlet pressure substantially lower than inlet pressure System operating temperature is below 32°F
Probe loose, o connection or defective probe
Probe not completely in thermal well
Defective probe Replace probe Transducer loose, o
connection or defective transducer
Inlet and outlet valves not completely open
Inlet and outlet lters blocked up.
Compressor relay / contactor stuck.
Microprocessor Control relay bad
Probe not completely in thermal well
Problem persists Turn dryer o and consult your
Inlet / outlet pipe internal diameter too small causing air-lock or back pressure.
Excessive use of bends / elbows in inlet / outlet pipe work causing air-lock/ back pressure.
Outlet pipe too long / too high causing back pressure.
More than one condensate source connected providing alternative path for condensate.
Inspect probe cable and terminal connection Replace probe
Inspect probe and check readings against independent source (eg. temperature analyzer/pyrometer/ice bath) both in temperature well and to ambient
Inspect transducer cable and terminal connection
Replace transducer Open valves
Change lter elements
Replace relay / contactor.
Replace relay
Inspect probe and check readings against independent source (eg. temperature analyzer/pyrometer/ice bath) both in exchanger well and to ambient
local distributor for further assistance
Check installation is in accordance with this manual. Revise installation accordingly.
Replace with larger diameter piping.
Reduce the amount of bends and elbows.
Recongure condensate piping.
Reroute condensate to eliminate secondary path. Install check valves as required.
ingersollrandproducts.com 15
Page 16
10.0 TROUBLESHOOTING
PROBLEM SYMPTOM(S) POSSIBLE CAUSE CORRECTIVE ACTION
Condensate drain LED is o (Optional-No Air Loss Drain)
Air bleed from condensate drain outlet port (Optional­No Air Loss Drain)
Condensate drain bowl does not seem to ll with condensate, drain does not seem to work due to air locking (Optional-No Air Loss Drain)
Debris trapped under seal. Damage to seal.
Check power supply. Press test button for minimum 2 seconds and observe. Locate and eliminate supply fault.
Press and hold the test button to clear (drain valve will open). Replace seal with Service Kit.
If bottom inlet is used, top port must be used as air bleed. Make sure Connect the top inlet to a higher point in system, which will function as an air bleed for the drain.
16 ingersollrandproducts.com
Page 17

11.0 WIRING DIAGRAMS

MICROPROCESSOR BOARD
WHT
RED
RED
WHT
DRAIN SV (SV)
CONNECTIONS
TO REMOTE ALARM BY OTHERS (OPTIONAL)
5A/120VAC MAX
REMOTE ALARM CONTACT
REMOTE START/STOP
CUSTOMER SUPPLIED
{
SWITCH
{
3
TS-3
1 2
WHT
PUMP (PM)
CONNECTIONS
GND
RED
WHT
GRN
5
4
TS-2
1 2 3 4
YEL
RED
YEL
WHT
RED
6
DRYER ELECTRICAL COMPARTMENT FRONT PANEL
DRYER ELECTRICAL COMPONENTS
RED
WHT RED BLK BLK
YELLOW
YELLOW
DRYER ELECTRICAL COMPARTMENT
* SEE NOTE 3
BLK
FAN
BLK
SEE NOTE 2.
GRN
(C1)
L1
CONTACTOR
RED
H2H1
200V
TRANSFORMER
WHT
GRN
RED
XFMR1
115V
GRN
LUG
GROUND
SIDE
THRU
480V
SIDE
H4
H3
WHT
RED
RED
FU2
FU1
PRIMARY
FUSES
XFMR SECONDARY
FUSE - FU3-250V
CUT OUT SW.
LOW PRESS
LPCO
GRN
GRN
RED
RED
3
CONNECTIONS
CUSTOMER
TS-1
4
1
2
GRND SCREW
GRN
BLK
GRN
{
208-230 VAC/1PH/60HZ
BY OTHERS
INCOMING LINE VOLTAGE
200-220 VAC/1PH/50HZ
BLK
RED
BLK
NVC200A & W - CSR TYPE
ZEKS# 682558 EMBRACO# J9232GK BOM# 963ND
5
GR
O
UN
D
4
BLK
COMP
OL
3
C
RS
WHT
RED
GND
230V/1PH/60HZ
COMPRESSOR
CONNECTIONS
1
START
RUN
4
1
COMPRESSOR
CAPACITOR
ENCLOSURE
RELAY AND
2
RED
RED
RED
BLK
ELEC. PLUG
G
MAX LOAD 0.50 A
SEE NOTE 4
N L1
GRN
WHT
WHT
WHT
WHT
5
6
L1
L2
GRNG
RED
RED
CR1
RED
RED
RED
SHIELDED PAIR
TEMPERATURE
TO EXCHANGER
THERMOWELL
PROBE
CUT OUT SW.
HIGH PRESS
HPCO
BLK
BLK
RED
BLK
RED
NOTES:
1. CUSTOMER POWER HOOK UP AT THE TERMINAL STRIP IN THE ELECTRICAL CONNECTION BOX IN THE
DRYER REAR ON L1, L2 & GND.
2. HPCO INCLUDED WITH WATERCOOLED UNITS ONLY.
3. FAN MOTOR NOT INCLUDED ON WATERCOOLED UNITS.
4. OUTLET NOT PROVIDED ON NEMA 4 OR WEATHERPROOF OPTIONS.
5. -------- DENOTES OPTIONAL EQUIPMENT.
200VAC THRU
380VAC THRU
CONNECTION
CONNECTION
WARNING: DISCONNECT POWER TO DRYER
AT CUSTOMER SOURCE BEFORE SERVICING
SHOCK HAZARD: SOME CIRCUITS MAY BE
LIVE WHEN DRYER IS TURNED OFF
DRAIN/PUMP HOT
COMPR HOT
COMPR
ALARM HOT
PUMP/DRAIN
DRAIN TIMER
24VAC
H
POWER
N
J1
SENSORS
J4
ALARM
J5
240VAC
480VAC
(TYPICAL)
HOLES IN
ELECTRICAL
COMPARTMENT
GROMMETED
WIRING DIAGRAM
NVC200 AIR AND WATERCOOLED
230/1/60, 220/1/50
550037B
OPTIONAL-NO AIR LOSS DRAIN ONLY
ingersollrandproducts.com 17
Page 18
WIRING DIAGRAM NVC200
AIR AND WATERCOOLED WITH SOLENOID
230/1/60, 220/1/50
550180A
11.0 WIRING DIAGRAMS
18 ingersollrandproducts.com
Page 19
11.0 WIRING DIAGRAMS
WIRING DIAGRAM
NVC200-400 AIR AND WATERCOOLED
208-575V/3PH/60HZ, 200-440V/3PH/50HZ
WIRING DIAGRAM
NVC200-400 AIR AND WATERCOOLED
208-575V/3PH/60HZ, 200-440V/3PH/50HZ
550031D
OPTIONAL-NO AIR LOSS DRAIN ONLY
ingersollrandproducts.com 19
Page 20
11.0 WIRING DIAGRAMS
NVC200-400 AIR AND WATERCOOLED
208-575V/3PH/60HZ, 200-440V/3PH/50HZ
WIRING DIAGRAM
NVC200-400 AIR AND WATERCOOLED
WITH SOLENOID DRAIN
208-575V/3PH/60HZ, 200-440V/3PH/50HZ
550181
20 ingersollrandproducts.com
Page 21

12.0 GENERAL ARRANGEMENT

550030E
GENERAL ARRANGEMENT
NVC200-400
AIR AND WATERCOOLED
CONTROL PANEL
OPTIONAL CONDENSATE
DRAIN
AIR OUTLET CONNECTION
1) 1 1/2" MPT FOR 200-250 SCFM MODELS
2) 2" FOR 300-400 SCFM MODELS
AIR INLET CONNECTION
1) 1 1/2" MPT FOR 200-250 SCFM MODELS
2) 2" FOR 300-400 SCFM MODELS
CUSTOMER ELECTRICAL
CONNECTIONS ACCESS
GLYCOL PUMP ACCESS
PANEL FILTER LOCATION
(FOR AIRCOOLED UNITS ONLY, NOT SHOWN)
WATER COOLED INLET CONNECTION
1/2" FPT FOR 250-400 SCFM MODELS
3/8" FPT FOR 200 SCFM MODELS
WATER COOLED OUTLET CONNECTION
1/2" FPT FOR 250-400 SCFM MODELS
3/8" FPT FOR 200 SCFM MODELS
OUTFLOW VALVE
ADJUSTMENT
ACCESS
MICROPROCESSOR CONTROL
(SEE TECHNICAL MANUAL FOR
OPERATION DETAILS)
FRONT VIEWLEFT SIDE VIEW
TOP VIEW
25.00
30.38
23.38
2.50
57.75
REAR VIEW
32.56
28.12
2.38
51.19
CONDENSER AIIR
DISCHARGE
CONDENSER AIR
INLET
CONDENSER AIR
DISCHARGE
CONDENSER AIR
INLET
STANDARD SOLENOID
VALVE DRAIN
ASSEMBLY
STANDARD DRAIN
OUTLET
RIGHT SIDE VIEW
55.25
ingersollrandproducts.com 21
Page 22
MISCELLANEOUS PARTS

13.0 REPLACEMENT PARTS

PART # DESCRIPTION
697187 BLADE, CONDENSER FAN 1 681867 BOARD, CONTROL 1 1 1 1 697290 CONTACTOR, COMPRESSOR 1 1 1 1
684234 DRAIN, CONDENSATE (OPTIONAL-NO AIR LOSS DRAIN) 1 38448239 DRAIN, SERVICE UNIT (NO AIR LOSS DRAIN ONLY) 1 22612931 DRAIN, SOLENOID VALVE 1/4” 115V 1
600384 DRYER, REFRIGERANT FILTER 1
800866 FAN GUARD KIT FOR NVC200A-400A 1
699808 FUSE, TRANSFORMER PRIMARY 2 2 2 4
682646 FUSE, TRANSFORMER SECONDARY (EXCEPT NVC200) 1 1 1 2
684463 OVERLAY, CONTROL BOARD 1
682948 PANEL FILTER ELEMENT 1
682955C PROBE, EXCHANGER TEMPERATURE 1 1 1 1
682439 PUMP, GLYCOL 1
681663 SWITCH, LOW REFRIGERANT PRESSURE 1
600191 TRANSFORMER, CONTROL - 0.15 KVA (EXCEPT NVC200) 1
680029 VALVE, DRAIN SHUT OFF 1
682618 VALVE, GLYCOL PUMP ISOLATION 1
QTY/ UNIT
1 2 3
SPARES
Spare. Quantities under this heading reect the number of each item which we recommend be kept on hand for
maintenance or repair.
The appropriate quantity for your application will depend on how critical interruptions in service are to your operation.
Class Quantity Suggested for
1 Minimum Domestic service where interruptions in service are acceptable. 2 Average Domestic service where some interruptions in service are acceptable. 3 Maximum Export service or for domestic service where interruptions in service are unacceptable.
PARTS FOR AIR COOLED DRYERS
NVC
MODEL
200 697168 681803 681803 681802 681802 300 697169 681803 681803 681802 681802 400 697169 681803 681803 681802 681802
CONDENSERS
NEMA 1 230V NEMA 4 230V NEMA 1 460V NEMA 4 460V
FAN MOTORS
22 ingersollrandproducts.com
Page 23

13.0 REPLACEMENT PARTS

PARTS FOR WATER COOLED DRYERS
NVC MODEL CONDENSERS VALVES
200 683492 600561 300 683493 600562 400 683493 600562
COMPRESSORS
NVC MODEL 230/1/60 230/3/60 230/3/50 380/3/50 460/3/60 575/3/60
200 682558 682595 682605 682559 682559 682559 300 - 682560 682561 682562 682443 682443 400 - 682606 682563 682564 682562 682562

14.0 ENGINEERING SPECIFICATIONS

AIR COOLED CONDENSERS
MODEL
NO.
VOLTS/
PH/HZ
WEIGHT R-404A
LBS. KG. LB-OZ KG. HP RLA LRA QTY HP RLA LRA
NVC200 230/1/60 540 245 2-4 1.02 20 13.7 1 9.7 40 1 1/6 1 3 NVC200 460/3/60 540 245 2-4 1.02 6 3.9 1 2.4 13 1 1/6 0.5 1.2 NVC200 230/3/60 540 245 2-0 .907 15 9.6 1 6.4 38 1 1/6 1 3 NVC200 575/3/60 540 245 2-4 1.02 5 3.0 1 2.4 13 1 1/6 0.5 1.2 NVC250 460/3/60 570 259 3-8 1.588 8 5.3 1 1/2 3.6 16 1 1/6 0.5 1.2 NVC250 230/3/60 570 259 3-8 1.588 15 9.6 1 1/2 6.4 38 1 1/6 1 3 NVC250 575/3/60 570 259 3-8 1.588 7 4.3 1 1/2 3.6 16 1 1/6 0.5 1.2 NVC300 460/3/60 630 286 4-0 1.814 10 6.2 2 4.3 16 1 1/6 0.5 1.2 NVC300 230/3/60 630 286 4-0 1.814 18 11.5 2 7.9 38 1 1/6 1 3 NVC300 575/3/60 630 286 4-0 1.814 8 4.9 2 4.3 16 1 1/6 0.5 1.2 NVC400 460/3/60 670 304 4-0 1.814 12 7.6 2 1/2 5.4 23 1 1/6 0.5 1.2 NVC400 230/3/60 670 304 4-0 1.814 25 15.9 2 1/2 11.4 57 1 1/6 1 3 NVC400 575/3/60 670 304 4-0 1.814 10 6.0 2 1/2 5.4 23 1 1/6 0.5 1.2
MAXIMUM ALLOWABLE WORKING PRESSURE: 230 psig
MAX. FUSE
SIZE
MIN.
CIRCUIT
AMPACITY
COMPRESSOR
RATINGS
FAN RATINGS
NOTICE
Specication information above accurate at time of publication. Refer to equipment
serial label for actual refrigerant charges and specications for units.
ingersollrandproducts.com 23
Loading...