Ingersoll-Rand M801P080BU48AA, M801P100CU48AA, M801P060AU36AA, M801P140DU60AA, M801P120DU60AA Installer's Manual

...
Page 1
18-CD34D1-5-EN
Upflow/Horizontal — Downflow/Horizontal, Gas-Fired Furnaces, “Fan Assisted Combustion System”
M801P040AU24AA M801P060AU24AA M801P060AU36AA M801P080BU36AA M801P080BU48AA
ALL phases of this installation must comply with
IMPORTANT — This Document is customer property and is to
remain with this unit. Please return to service
information pack upon completion of work.
M801P100BU36AA M801P100CU48AA M801P100CU60AA M801P120DU60AA M801P140DU60AA
M801P060AD24AA M801P060AD36AA M801P080BD45AA M801P100CD48AA
M801P100CD60AA M801P120DD60AA M801P140DD60AA
NATIONAL, STATE AND LOCAL CODES
For VENT SIZING INFORMATION see:
USA —
National Fuel Gas Code ANSI Z223.1/ NFPA 54 (latest version)
CANADA—
Natural Gas Installation Code CAN/ CGA-B149.1 (latest version) Propane Installation Code CAN/ CGA-B149.2 (latest version)
OPTIONAL ACCESSORIES
Model Number Description
BAYBASE205 Downflow subbase for downflow models
only
BAYFLTR200 External side filter rack
BAYFLTR203 Filter kit horizontal for 17.5" cabinet
BAYFLTR204 Filter kit horizontal for 21" cabinet
BAYFLTR205 Filter kit horizontal for 24.5" cabinet
BAYFLTR317 Cleanable filter for 17.5" cabinet upflow
only
BAYFLTR321 Cleanable filter for 21" cabinet upflow
only
BAYFLTR324 Cleanable filter for 24.5" cabinet upflow
only
BAYLPKT210B Propane conversion kit
BAYLPSS210B LP kit with stainless steel burners
BAYRACK960A Internals filter rack kit for upflow models
BAYVENT800B Masonry chimney vent kit for upflow only
KIT09224 Filter clip kit
BAYBRCKFLT10 Downflow bracket kit
FLR01185 Filter for 14-1/2" cabinet downflow only
FLR01186 Filter for 17-1/2", 21", 24-1/2" cabinet
downflow only
Upflow/ Horizontal* Downflow/ Horizontal*
*Horizontal Conversion for these furnaces may be left
or right side rotation.
A341789P12
Page 2
INSTALLER’S GUIDE
WARNING
SAFETY SECTION
The following safety practices and precautions must be followed during the installation, servicing, and operation of this furnace.
1. Use only with the type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as
specied in “Location and Clearances” in this document.
3. Provide adequate combustion and ventilation air to the
furnace space as specied in “Air for Combustion and Ventilation” in this document.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specied in the “Venting” section in this document.
5. Never test for gas leaks with an open ame. Use a commercially available soap solution made specically
for the detection of leaks to check all connections, as
specied in “Gas Piping” in this document.
6. Always install the furnace to operate within the furnace’s intended temperature-rise range with a duct system which has an external static pressure within the allowable
range, as specied on the unit rating plate. Airow with temperature rise for CFM versus static is shown in this
document.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
8. A gas-red furnace for installation in a residential
garage must be installed as specied in “Location and Clearances” section in this document.
9. The furnace may be used for temporary heating of buildings or structures under construction only when the following conditions have been met:
a. The furnace venting system must be complete and
installed per manufacturer’s instructions.
b. The furnace is controlled only by a room thermostat
(no eld jumpers).
c. The furnace return air duct must be complete and
sealed to the furnace and clean air lters are in place.
d. The furnace input rate and temperature rise must be
veried to be within nameplate marking.
e. 100% of the furnace combustion air requirement must
come from outside the structure.
f. The furnace return air temperature range is between
55 and 80 degrees Fahrenheit.
g. Clean the furnace, duct work, and components upon
substantial completion of the construction process, and verify furnace operating conditions including ignition, input rate, temperature rise and venting,
according to the manufacturer’s instructions.
10. This product must be gas piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Massachusetts.
Safety signal words are used to designate a degree or level of seriousness associated with a particular hazard. The signal words for safety markings are WARNING and CAUTION.
b. WARNING indicates a potentially hazardous
situation which, if not avoided, could result in death
or serious injury.
c. CAUTION indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate
injury. It is also used to alert against unsafe practices
and hazards involving only property damage.
GENERAL INSTALLATION INSTRUCTIONS
The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation. It is recommended
that Manual J of the Air Conditioning Contractors Association (ACCA) or A.R.I. 230 be followed in estimating heating
requirements. When estimating heating requirements for
installation at Altitudes above 2000 ft., remember the gas input must be reduced (See GAS INPUT ADJUSTMENT).
Material in this shipment has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in shipment. Unpack carefully after moving equipment to approximate location. If damage to contents is found, report the damage immediately to the delivering agency.
Codes and local utility requirements governing the installation of gas red equipment, wiring, plumbing, and ue connections must
be adhered to. In the absence of local codes, the installation must
conform with latest edition of the National Fuel Gas Code ANSI Z223.1 • National Installation Code, CAN/CGA B149.1. The latest code may be obtained from the American Gas Association Laboratories, 400 N. Capitol St. NW, Washington D.C. 20001,
1-800-699-9277 or www.aga.org
These furnaces have been classied as Fan Assisted Combustion system CATEGORY I furnaces as required by ANSI Z21.47 “latest edition” and CAN/CGA 2.3. Therefore they do not require
any special provisions for venting other than what is indicated in these instructions.
!
▲
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Improper servicing could result in dangerous operation, serious injury, death, or property damage.
© 2015 Ingersoll Rand — All Rights Reserved 18-CD34D1-5-EN
Page 3
WARNING
INSTALLER’S GUIDE
!
▲
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
Seal any unused openings in the venting
system.
1. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
2. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other deficiencies which could cause an unsafe condition.
3. Close fireplace dampers.
4. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
5. Follow the lighting instructions. Place the appliance be-ing inspected into operation. Adjust the thermostat so appliance is operating continuously.
6. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149 Installation Codes.
7. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas
-fired burning appliance to their previous conditions of use.
Contents
Safety Section ..................................................................2
General Installation Instructions ....................................... 2
Location and Clearances .................................................. 4
Outline Drawings ..............................................................5
Upflow Installation ............................................................7
Downflow Installation ........................................................ 7
Horizontal Installation ....................................................... 7
Air for Combustion and Ventilation .................................... 8
Duct Connections ........................................................... 10
Return Air Filter .............................................................. 11
General Venting Instructions ........................................... 12
Venting into a Masonry Chimney .................................... 13
Field Wiring Diagrams .................................................... 15
Electrical Connections .................................................... 16
Gas Piping ...................................................................... 17
Sequence of Operation ...................................................17
Start-up and Adjustment ................................................. 17
Combustion and Input Check .........................................17
High Altitude Derate .......................................................19
Lighting Instructions ....................................................... 20
Control and Safety Switch Adjustment ...........................20
Operating Information ..................................................... 20
Integrated Furnace Control Error flash Codes ................ 21
Periodic Servicing Requirements ...................................22
Airflow Tables .................................................................. 23
18-CD34D1-5-EN 3
Page 4
INSTALLER’S GUIDE
CAUTION
WARNING
!
▲
To prevent shortening its service life, the furnace should not be used as a “Construction Heater” during the finishing phases of construction until the requirements listed in item 9, a-g of the safety section of this publication have been met. Condensate in the presence of chlorides and fluorides from paint, varnish, stains, adhesives, cleaning compounds, and cement create a corrosive condition which may cause rapid deterioration of the heat exchanger.
!
WARNING
▲
These furnaces are not approved or intended for installation in manufactured (mobile) housing, trailers, or recreational vehicles. Failure to follow this warning could result in property damage, personal injury, or death.
!
CAUTION
▲
Do NOT install the furnace in a corrosive or contaminated atmosphere.
!
WARNING
▲
Do NOT install the furnace directly on carpeting, tile or other combustible material other than wood flooring. For vertical downflow application, subbase (BAYBASE205) must be used between the furnace and combustible flooring. When the downflow furnace is installed vertically with a cased coil, a subbase is not required.
!
▲
EXPLOSION HAZARD!
PROPANE GAS IS HEAVIER THAN AIR AND MAY COLLECT IN ANY LOW AREAS OR CONFINED SPACES. IN ADDITION, ODORANT FADE MAY MAKE THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE. IF THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED AREA OR A CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO CONTACT A GAS SUPPLIER TO INSTALL A GAS DETECTING WARNING DEVICE IN CASE OF A GAS LEAK.
NOTE: The manufacturer of your furnace does not test any detectors and makes no representations regarding any brand or type of detector
LOCATION AND CLEARANCES
The location of the furnace is normally selected by the architect, the builder, or the installer. However, before the furnace is moved into place, be sure to consider the following requirements:
1. Is the location selected as near the chimney or vent and as centralized for heat distribution as practical?
2. Do all clearances between the furnace and enclosure
equal or exceed the minimums stated in Clearance Table on the Outline Drawings.
3. Is there sufcient space for servicing the furnace and other equipment? A minimum of 24 inches front accessibility to the furnace must be provided. Any access door or
panel must permit removal of the largest component.
4. Are there at least 3 inches of clearance between the furnace combustion air openings in the front panel and any closed panel or door provided?
5. Are the ventilation and combustion air openings large enough and will they remain unobstructed? If outside air is used, are the openings set above the highest snow
accumulation level? (See the Air for Combustion and
Ventilation section)
6. Allow sufcient height in supply plenum above the furnace to provide for cooling coil installation, if the cooling coil is not installed at the time of this furnace installation.
7. A furnace shall be installed so electrical components are protected from water.
8. If the furnace is installed in a residential garage, it must be installed so that the burners, and the ignition source
are located not less than 18 inches above the oor and the
furnace must be located or protected to avoid physical damage from vehicles.
4 18-CD34D1-5-EN
Page 5
Ø 1-5/8” HOLE WITH PLUG
INSTALLER’S GUIDE
14-1/2" 9-5/8" 13-1/4" 13"
17-1/2" 9-5/8" 16-1/4" 16"
OUTLINE DRAWINGS - UPFLOW/HORIZONTAL
For the M801P Series Furnaces
Ø 7/8” HOLE WITH PLUG
ELECTRICAL CONNECTION
Ø 1-5/8” HOLE WITH PLUG
(ALTERNATE)
MODEL DIM "A" DIM "B" DIM "C" DIM "D"
M801P040AU24AA, M801P060AU24AA
M801P060AU36AA
M801P080BU36AA, M801P080BU48AA
M801P100BU36AA
M801P100CU48AA, M801P100CU60AA 21" 13-1/16" 19-3/4" 19-1/2"
M801P120DU60AA, M801P140DU60AA 24-1/2" 15-5/16" 23-1/4" 23"
18-CD34D1-5-EN 5
Page 6
INSTALLER’S GUIDE
Ø 7/8” HOLE WITH PLUG
ELECTRICAL CONNECTION
(ALTERNATE)
Ø 1-5/8” HOLE WITH PLUG
M801P OUTLINE DRAWING - DOWNFLOW\HORIZONTAL
For the M801P Series Furnaces
1-1/2” X 2-1/2” OVAL
GAS CONNECTION
MODEL DIM "A" DIM "B" DIM "C" DIM "D"
M801P060AD24AA, M801P060AD36AA 14-1/2" 9-5/8" 13-1/4" 13"
M801P080BD45AA 17-1/2" 9-5/8" 16-1/4" 16"
M801P100CD48AA, M801P100CD60AA 21" 13-1/16" 19-3/4" 19-1/2"
M801P120DD60AA, M801P140DD60AA 24-1/2" 15-5/16" 23-1/4" 23"
6 18-CD34D1-5-EN
Ø 1-5/8” HOLE
WITH PLUG (3)
Page 7
UPFLOW
FURNACE
CASED
COIL
INSTALLER’S GUIDE
UPFLOW INSTALLATION
The coil is always placed downstream of the furnace airow. Apply gasket material (duct seal eld supplied) to ALL mating
surfaces between the furnace and the coil case.
NOTE: The top flanges on the furnace must be bent 90 degrees upward to allow the coil attachment.
1
Seal with field
supplied sealant
or gasket
Required floor opening: (DOWNFLOW)
Figure 3 and Table 1
3
A (width)
FURNACE
FRONT
CABINET
WIDTH
14-1/2" 13-1/4" 13-5/8" 20-1/8" 12-5/8" 19-3/8" 17-1/2" 16-1/4" 16-5/8" 20-1/8" 15-5/8" 19-3/8"
21" 19-3/4" 20-1/8" 20-1/8" 19-1/8" 19-3/8"
24-1/2" 23-1/4" 23-5/8" 20-1/8" 22-5/8" 19-3/8"
RETURN
DUCT
WIDTH
FLOOR OPENING PLENUM OPENING
B (depth)
D
C
"A" "B" "C" "D"
HORIZONTAL INSTALLATION
The coil and furnace must be fully supported when used in the horizontal position. Three brackets (with screws) are included
with downow furnaces for installation to stabilize and secure the furnace and cased coil in the horizontal position. See Figure 4.
VERTICAL
INSTALLATIONS:
DOWNFLOW INSTALLATION
!
WARNING
▲
Do not install the furnace directly on carpeting, tile or other combustible material other than wood flooring. For vertical downflow application, subbase (BAYBASE205) must be used between the furnace and combustible flooring. When the downflow furnace is installed vertically with a cased coil, a subbase is not required.
2
IMPORTANT: The cased coil must be placed downstream of the furnace. In horizontal installations, the apex of the coil may point either toward or away from the furnace. See the coil Installer's Guide for more details.
The cased coil is secured to the furnace and both the furnace and the cased coil must be properly supported. The brackets mount using the rear screws on the coil case and use the screws provided to secure the bracket to the furnace. The remaining bracket is placed as close to center as possible (horizontally) between the
coil case front and the furnace bottom channel (for downow/
horizontal furnace). Use four of the screws provided to secure the
bracket. The upow furnace,
4
CASED COIL CONNECTION
BRACKET FOR DOWNFLOW
FURNACE IN HORIZONTAL
DOWNFLOW ONLY
converted to horizontal, aligns and attaches the coil as in Figure 1.
However, the coil requires additional support. This furnace may be installed in an attic or crawl space in the horizontal position by placing the furnace on the left or right side (as viewed from the front in the upright position). The horizontal furnace installation in an attic should be on a service platform large enough to allow for proper clearances on all sides and service access to the front
of the furnace (See Clearance Table on Outline Drawings and Figure 5).
18-CD34D1-5-EN 7
Page 8
INSTALLER’S GUIDE
If the furnace is suspended using perforated steel strap (plumber’s
strap), it must be supported at all four corners and in the middle at the front of the furnace. The forward most screw on the side
of the furnace may be used to connect the strapping (See Figure
6). Line contact is only permissible between lines formed by the
intersection of the top and two sides of the furnace casing and the
building joists, studs, or framing.
5
TYPICAL UPFLOW/HORIZONTAL ATTIC INSTALLATION
A cutout is provided on both sides of the downow furnace
cabinet to allow a 90° elbow to be attached inside the cabinet
and the vent piping to connect there. In horizontal, the downow
furnace may be vented through the top of the cabinet if needed.
In vertical conguration, the downow furnace may be vented using the side cabinet cutouts. This venting conguration could
be used if an electronic air cleaner is installed.
When the downow furnace is vented through the left side of the furnace cabinet in horizontal or vertical conguration,
Type B vent pipe must be used within the cabinet.
6
AIR FOR COMBUSTION AND VENTILATION
Adequate ow of combustion and ventilating air must not be obstructed from reaching the furnace. Air openings provided in
the furnace casing must be kept free of obstructions which restrict
the ow of air. Airow restrictions affect the efciency and safe
operation of the furnace. Keep this in mind should you choose to remodel or change the area which contains your furnace.
Furnaces must have a free ow of air for proper performance.
Provisions for combustion and ventilation air shall be made
in accordance with “latest edition” of Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1, or Sections 7.2, 7.3 or 7.4 of CAN/ CGA B149 Installation Codes, and applicable provisions of the local building
codes. Special conditions created by mechanical exhausting of
air and replaces must be considered to avoid unsatisfactory
furnace operation.
Furnace locations may be in “conned space” or “unconned space”. Unconned space is dened in Table 2 and Figure 7. These spaces may have adequate air by inltration to provide air for combustion, ventilation, and dilution of ue gases. Buildings
with tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), may need additional air
provided as described for conned space.
Conned spaces are installations with less than 50 cu. ft. of space per 1000 BTU/hr input from all equipment installed. Air for
combustion and ventilation requirements can be supplied from
inside the building as in Figure 9 or from the outdoors, as in Figure 10.
CONFINED
8
LESS THAN 50 CU. FT. PER 1000 BTU/ HR. INPUT ALL EQUIP INSTALLED
Typical Suspended Upow/Horizontal Furnace
7
UNCONFINED
50 CU. FT. OR MORE PER 1000 BTU/HR. INPUT ALL EQUIP. INSTALLED
8 18-CD34D1-5-EN
1. All air from inside the building as in Figure 9: The conned space shall be provided with two permanent
openings communicating directly with an additional
room(s) of sufcient volume so that the combined volume of all spaces meets the criteria for an unconned space.
The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Refer to Table 3, for minimum open areas required.
2. All air from outdoors as in Figure 10: The conned space shall be provided with two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Refer to Table 3, for minimum open areas required.
Page 9
TABLE 2
MINIMUM AREA IN SQUARE FEET FOR
UNCONFINED SPACE INSTALLATIONS
FURNACE MAXIMUM
BTUH / INPUT RAT-
ING
40,000 60,000
80,000 100,000 120,000 140,000
TABLE 3
MINIMUM FREE AREA IN SQUARE INCHES
EACH OPENING (FURNACE ONLY)
Furnace
Maximum
BTUH/INPUT
Rating
40,000 60,000
80,000 100,000 120,000 140,000
WITH 8 FOOT CEILING
MINIMUM AREA IN SQUARE
FEET OF UNCONFINED SPACE
250 375 500 625 750 875
Air From
Inside
100 100 100 100 120 140
Air From Outside
Vertical
Duct
10 15 20 25 30 35
INSTALLER’S GUIDE
0
Horizontal
Duct
20 30 40 50 60 70
9
3. The following types of installations will require use
of OUT DOOR AIR for combustion, due to chemical
exposures:
* Commercial buildings
* Buildings with indoor pools
* Furnaces installed in commercial laundry rooms
* Furnaces installed in hobby or craft rooms
* Furnaces installed near chemical storage areas.
* Exposure to the following substances in the
combustion air supply will also require OUTDOOR AIR for combustion:
* Permanent wave solutions
* Chlorinated waxes and cleaners
* Chlorine based swimming pool chemicals
* Water softening chemicals
* Deicing salts or chemicals
* Carbon Tetrachloride
* Halogen type refrigerants
* Cleaning solvents (such as perchloroethylene)
* Printing inks, paint removers, varnish, etc.
* Hydrochloric acid
* Cements and glues
* Antistatic fabric softeners for clothes dryers
* Masonry acid washing materials
18-CD34D1-5-EN 9
Page 10
INSTALLER’S GUIDE
DUCT CONNECTIONS
NOTE: The top anges on the furnace must be bent 90 degrees upward to allow connection to the ducting.
Air duct systems should be installed in accordance with standards for air conditioning systems, National Fire Protection Association Pamphlet No. 90. They should be sized in accordance with ACCA Manual D or whichever is applicable.
Central furnaces, when used in connection with cooling units,
shall be installed in parallel or on the upstream side of the cooling units to avoid condensation in the heating element, unless
the furnace has been specically approved for downstream installation. With a parallel ow arrangement, the dampers or other means used to control ow of air shall be adequate to
prevent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in full heat or cool position.
On any job, exible connections of nonammable material
may be used for return air and discharge connections to prevent transmission of vibration. Though these units have been
specically designed for quiet, vibration free operation, air ducts
can act as sounding boards and could, if poorly installed, amplify the slightest vibration to the annoyance level.
When the furnace is located in a utility room adjacent to the
living area, the system should be carefully designed with returns which minimize noise transmission through the return air grille.
Although these winter air conditioners are designed with large
blowers operating at moderate speeds, any blower moving a high volume of air will produce audible noise which could be
objectionable when the unit is located very close to a living area. It is often advisable to route the return air ducts under the oor
or through the attic. Such design permits the installation of air return remote from the living area (i.e. central hall).
When the furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace and terminating outside the space containing the furnace.
Minimum return air/“air entering” temperature for the furnace is 55° F.
Where there is no complete return duct system, the return connection must be run full size from the furnace to a location outside the utility room, basement, attic, or crawl space.
Do not install return air through the back of the furnace cabinet.
Return Air Duct Connection
All return air duct systems should provide for installation of return air lters.
NOTE: For Upow 5 ton airow models, if the airow requirement exceeds 1800 CFM, these models will require return air openings and lters on both sides; or 1 side and the bottom; or just the bottom.
1. Set the furnace in place.
2. For side return installations on upow models, remove
the insulation around the opening in the blower compartment.
3. The side panels on upow furnaces include locating
notches which may be used as guides for cutting an
opening for return air. Refer to Figure 11 and the outline
drawing in this document for duct connection dimensions for various furnaces.
4. If a 3/4" ange is to be used for attaching the air inlet duct,
add to cut where indicated by solid lines in Figure 11. Cut corners diagonally and bend outward to form ange.
5. If anges are not required, and a lter frame is installed,
cut along knockout guidelines.
6. Upow Furnaces: Filter brackets are available for
lter use within the furnace cabints. Order RTR00133 and CLP00359. If bottom return opening is not used,
fabricate and install a sheet metal plate in the bottom of the furnace cabinet
q
LOCATING NOTCHES PROVIDED FOR SIDE
UPFLOW FURNACE ONLY
CUT
*
OUT FOR
*
SIDE FILTER
RETURN CUTOUT
FURNACE
*SEE OUTLINE
*
*
FRONT
DRAWING
Downow Furnaces: Brackets must be eld supplied. Order BAYBRCKFLT10. Also 2 FLR01185 for 14.5" models, or 2 FLR01186 for 17.5", 21.0" and 24.5" models must be
ordered.
When the upow furnace is installed in the horizontal right
or left application and a return duct is attached to the top
side as shown in Figure 12, the lter must be installed in a
remote location.
Do not install the lter in the return duct directly above the
furnace in horizontal applications.
10 18-CD34D1-5-EN
Page 11
WARNING
WARNING
INSTALLER’S GUIDE
!
▲
Do NOT install the filter in the return duct directly above the furnace in horizontal applications. Install the filter remotely. Installing the filter directly above the furnace in horizontal applications may cause property damage, serious injury or death.
!
▲
TO PREVENT INJURY OR DEATH DUE TO CONTACT WITH MOVING PARTS, TURN THE POWER TO THE FURNACE OFF BEFORE SERVICING FILTERS.
When the upow furnace is installed in the horizontal right or left application and a close coupled (less than 36") return
duct is attached to the bottom side of the furnace as shown
in Figure 12, securely attach a 1/2" mesh metal hardware cloth protective screen to the inside bottom of the lter grill
to prevent personal injury from contacting moving parts when reaching into the return opening to replace the
lter.
REMOVE FILTER FROM UPFLOW FURNACE WHEN RETURN DUCT IS ATTACHED TO FURNACE TOP SIDE (HORIZONTAL LEFT OR RIGHT APPLI­CATIONS) AS SHOWN.
Close coupled (less than 36") return (filter directly beneath bottom side return) not recommended due to noise considerations. If used, securely attach 1/2" mesh metal hardware cloth protective screen to the inside bottom of filter grill.
FILTER
w
RETURN AIR FILTER
These furnaces require high velocity type air lters which may be located within the furnace blower compartment for UPFLOW furnaces in either a BOTTOM or SIDE (left side or right side) return air inlet. See Figures 13 and 14. Some lters may need to be trimmed for side or bottom lter use.
NOTE: On upow 5 ton airow models, if the airow requirement exceeds 1800 CFM, these models will require return air openings and lters on both sides; OR 1 side and the bottom; OR just the bottom.
NOTE: Upow models only - Installation of the alternate bottom lter kit requires the bottom ange to be bent at.
Optional downow furnace lters must be located outside the furnace cabinet. Typical installations are shown in Figures 14 and
15. Tables 5 and 6 provide information for installation of the lter retaining brackets shipped with downow furnaces. TABLE 4
MODEL CABINET WIDTH
M801P040AU24AA M801P060AU24AA M801P060AU36AA
M801P080BU36AA M801P080BU48AA M801P100BU36AA
M801P100CU48AA M801P100CU60AA
M801P120DU60AA M801P140DU60AA
M801P060AD24AA M801P060AD36AA
M801P080BD45AA 17-1/2"
M801P100CD48AA M801P100CD60AA
M801P120DD60AA M801P140DD60AA
14-1/2" 1 - 14 X 25 X 1
17-1/2" 1 - 17 X 25 X 1
21" 1 - 20 X 25 X 1
24-1/2" 1 - 24 X 20 X 1
14-1/2"
21"
24-1/2"
REQUIRED FILTER
SIZE FOR BOTTOM
BAYBRCKFLT10
2 - FLR01185
BAYBRCKFLT10
2 - FLR01186
BAYBRCKFLT10
2 - FLR01186
BAYBRCKFLT10
2 - FLR01186
Close coupled (less than 36") return (lter directly beneath
bottom side return) is not recommended due to noise considerations.
7. Connect the duct work to the furnace. See Outline
Drawing for supply and return duct size and location. Flexible duct connectors are recommended to connect
both supply and return air ducts to the furnace.
If only the front of the furnace is accessible, it is recommended that both supply and return air plenums are removable.
8. When replacing a furnace, old duct work should be cleaned out. Thin cloths should be placed over the registers and the furnace fan should be run for 10 minutes.
Don’t forget to remove the cloths before you start the
furnace.
18-CD34D1-5-EN 11
e
BAYBRCKFLT10
Airflow
Typical Filters of Upflow in Horizontal
Page 12
INSTALLER’S GUIDE
Important: When using the supplied high velocity filters, the filter support base must be installed into the furnace duct flange prior to ductwork installation.
Remove the brackets from the blower compartment. They are wrapped in foam and taped to the side of the downflow unit.
Remove the four screws securing the top panel. Save screws.
Slide the top panel forward approximately 1”.
With support tabs facing up, install the filter base by inserting one end tab into the duct flange at the rear of the furnace.
Slide the top panel back to its original position, engaging the other end tab in the slot. Replace screws.
Remove brackets
TABLE 6
CABINET
WIDTH
14-1/2" 13-1/4" 12" 14" 17-1/2" 16-1/4" 15" 14"
21" 19-3/4" 19-1/2" 14"
24-1/2" 23-1/4" 22" 14"
RETURN
DUCT
WIDTH
FILTER ACCESS
OPENING -
DIMENSION "A"
FILTER
ACCESS
OPENING -
DIMENSION
"B"
GENERAL VENTING INSTRUCTIONS
VENT PIPING
These furnaces have been classied as Fan-Assisted Combustion System, Category I furnaces under the “latest edition” provisions of ANSI Z21.47 and CAN/CGA 2.3 standards. Category I
furnaces operate with a non-positive vent static pressure and with
a ue loss of not less than 17 percent.
NOTE: If desired, a side wall termination can be accomplished through the use of an “add-on” draft inducer. The inducer must be installed according to the inducer manufacturer’s instructions. Set the barometric pressure relief to achieve
-0.02 inch water column.
Screw locations
Flanges upward
TABLE 5
CABINET
WIDTH
14-1/2" 2 - 14X20X1 12-7/8" 17-1/2" 2 - 16X20X1 14-3/8"
21" 2 - 16X20X1 13-1/8"
24-1/2" 2 - 16X20X1 11-5/8"
* Location dimension is from end of duct to the screw holes for the
FILTER
SIZE
bracket.
FILTER BRACKET
LOCATION *
NOTE: When the downow furnace is vented through the left side of the furnace cabinet using the provided cutout, Type B vent piping must be used.
DOWNFLOW
r
Airflow
DOWNFLOW/ HORIZONTAL
Airflow
t
12 18-CD34D1-5-EN
Page 13
WARNING
WARNING
WARNING
INSTALLER’S GUIDE
!
▲
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149 Installation Codes.
8. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas­fired burning appliance to their previous conditions of use.
The furnace shall be connected to a factory built chimney or vent complying with a recognized standard, or a masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction.
!
WARNING
▲
Furnace venting into an unlined masonry chimney or concrete chimney is prohibited.
Failure to follow this warning could result in property damage, personal injury, or death.
VENTING INTO A MASONRY CHIMNEY
If the chimney is oversized, the liner is inadequate, or ue-
gas condensation is a problem in your area, consider using the
chimney as a pathway or chase for type “B” vent or exible vent liner. If exible liner material is used, size the vent using the “B”
vent tables, then reduce the maximum capacity by 20% (multiply
0.80 times the maximum capacity).
Internal Masonry Chimneys
Venting of fan assisted appliances into a lined, internal masonry chimney is allowed only if it is common vented with at least one
natural draft appliance; OR, if the chimney is lined with type “B”, double wall vent or suitable exible liner material (See Table 7).
!
▲
The chimney liner must be thoroughly inspected to insure no cracks or other potential areas for flue gas leaks are present in the liner. Liner leaks will result in early deterioration of the chimney.
Failure to follow this warning could result in carbon monoxide poisoning or death.
TABLE 7
MASONRY CHIMNEY VENTING
Tile Lined Chimney Chimney Lining
Type Furnace Internal External “B” Vent
Single Fan
Assist
Fan Assist
+ Fan Assist
Fan Assist
+ Natural
* Flexible chimney liner size is determined by using the type “B” vent size for the available BTUH input, then reducing the maximum capacity by 20% (multiply maximum capacity times 0.80). The minimum capacity is the same as shown in the “B” vent tables.
No No Ye s Yes*
No No Ye s Yes*
Ye s No Ye s Yes*
External Masonry Chimney
!
▲
CARBON MONOXIDE POISONING HAZARD
This masonry chimney kit shall NOT be installed on any furnaces with 40,000 BTU/H inputs or any downflow models. Failure to follow this warning could result in carbon monoxide poisoning, personal injury, or death.
NOTE: Masonry Chimney Kit BAYVENT800B may be used
with these furnaces (Upow model furnaces 60,000 BTU/H and above only) to allow venting into an external masonry chimney. Refer to BAYVENT800B Installer's Guide for application requirements. The following section does not apply if BAYVENT800B (Masonry Chimney Kit) is used. All instructions with the kit must be followed.
Flexible
Metal Liner
18-CD34D1-5-EN 13
Page 14
INSTALLER’S GUIDE
WARNING
Venting of fan assisted appliances into external chimneys (one or more walls exposed to outdoor temperatures), requires the
chimney be lined with type “B”, double wall vent or suitable exible chimney liner material. This applies in all combinations
of common venting as well as for fan assisted appliances vented alone.
The following installation practices are recommended to
minimize corrosion caused by condensation of ue products in the furnace and ue gas system.
!
▲
CARBON MONOXIDE POISONING HAZARD
Failure to follow the installation instructions for the venting system being placed into operation could result in carbon monoxide poisoning or death.
1. Avoid an excessive number of bends.
2. Horizontal runs should pitch upward at least 1/4" per foot.
3. Horizontal runs should be as short as possible.
4. All vent pipe or connectors should be securely supported and must be inserted into, but not beyond the inside wall at the chimney vent.
5. When vent connections must pass through walls or partitions of combustible material, a thimble must be used and installed according to local codes.
6. Vent pipe through the roof should be extended to a height
determined by National Fuel Gas Code or local codes.
It should be capped properly to prevent rain water from entering the vent. Roof exit should be waterproofed.
7. Use type “B” double wall vent when vent pipe is routed
through cool spaces (below 60° F.).
8. Where long periods of airow are desired for comfort, use long fan cycles instead of continuous airow.
9. Apply other good venting practices as stated in the venting section of the National Fuel Gas Code ANSI Z223.1 “latest edition”.
10. Vent connectors serving appliance vented by natural draft or non-positive pressure shall not be connected into any portion of a mechanized draft system operating under positive pressure.
11. Horizontal pipe runs must be supported by hangers, straps or other suitable material in intervals at a minimum of every 3 feet of pipe.
12. A furnace shall not be connected to a chimney or ue serving a separate appliance designed to burn solid fuel.
13. The ow area of the largest section of vertical vent or chimney shall not exceed 7 times the smallest listed
appliance categorized vent area, ue collar area, or draft
hood outlet area unless designed in accordance with approved engineering methods.
Maximum Vent or Tile
= X 7
Lined Chimney Flow Area
*Drafthood outlet diameter, ue collar diameter, or listed appliance categorized vent diameter.
π(D*)
4
2
TABLE 8
GAS VENT TERMINATION
ROOF PITCH MINIMUM HEIGHT
FLAT TO 7/12 OVER 7/12 TO 8/12 OVER 8/12 TO 9/12 OVER 9/12 TO 10/12 OVER 10/12 TO 11/12 OVER 11/12 TO 12/12 OVER 12/12 TO 14/12 OVER 14/12 TO 16/12 OVER 16/12 TO 18/12 OVER 18/12 TO 20/12 OVER 20/12 TO 22/12
* THIS REQUIREMENT COVERS MOST INSTALLATIONS
1.0 FEET *
1.5 FEET
2.0 FEET
2.5 FEET
3.25 FEET
4.0 FEET
5.0 FEET
6.0 FEET
7.0 FEET
7.5 FEET
8.0 FEET
Carbon monoxide, re or smoke can cause serious bodily injury, death, and/ or property damage.
A variety of potential sources of carbon monoxide can be found in a building or dwelling such as gas-red clothes dryers, gas cooking stoves, water heaters, furnaces and replaces. The U.S. Consumer Product Safety Commission recommends that users of
gas-burning appliances install carbon monoxide detectors as well
as re and smoke detectors per the manufacturer’s installation instructions to help alert dwelling occupants of the presence of
re, smoke or unsafe levels of carbon monoxide. These devices should be listed by Underwriters Laboratories, Inc. Standards
for Single and Multiple Station Carbon Monoxide Alarms, UL 2034 or CSA International Standard, Residential Carbon Monoxide Alarming Devices, CSA 6.19.
NOTE: The manufacturer of your furnace does not test any detectors and makes no representations regarding any brand or type of detector.
y
14 18-CD34D1-5-EN
Page 15
OUTDOOR UNIT
(NO TRANSFORMER)
SEE
NOTE 5
From drawing B342023 Rv 0
FURNACE
B/C
B/C
TO 115 V 1 PH., 60 HZ., POWER SUPPLY PER LOCAL CODES
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE
1 STAGE HEATING, 1 STAGE COOLING
USING A 1 STAGE HEATING, 1 STAGE COOLING THERMOSTAT
(OUTDOOR SECTION WITHOUT TRANSFORMER)
SEE
NOTE 5
From drawing B342026 Rv 0
FURNACE
SEE
NOTE 6
B/C
B/C
TO 115 V 1 PH., 60 HZ., POWER SUPPLY PER LOCAL CODES
FIELD WIRING DIAGRAM FOR 1 STAGE FURNACE
1 STAGE HEATING
USING A 1 STAGE HEATING THERMOSTAT
NO COOLING
FIELD WIRING DIAGRAMS
INSTALLER’S GUIDE
18-CD34D1-5-EN 15
Page 16
INSTALLER’S GUIDE
WARNING
CAUTION
WARNING
WARNING
DRIP LEG
TOP VIEW
AUTOMATIC GAS VALVE WITH MANUAL SHUTOFF
DRIP LEG
ELECTRICAL CONNECTIONS
!
▲
The cabinet must have an uninterrupted or unbroken ground according to National Electrical Code, ANSI/NFPA 70 - “latest edition” and Canadian Electrical Code, CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. Failure to follow this warning could result in an electrical shock, fire, injury, or death.
!
▲
The integrated furnace control is polarity sensitive. The hot leg of the 115 VAC power must be connected to the BLACK field lead.
!
▲
To prevent injury or death due to electrical shock or contact with moving parts, lock unit disconnect switch in the open position before servicing the unit. Failure to follow this warning could result in electrical shock, personal injury, or death.
!
▲
TO PREVENT AN EXPLOSION OR POSSIBLE INJURY, DEATH AND EQUIPMENT DAMAGE, DO NOT STORE COMBUSTIBLE MATERIALS, GASOLINE OR OTHER FLAMMABLE VAPORS OR LIQUIDS NEAR THE UNIT.
IMPORTANT:
A sediment trap must be installed in the gas line before the furnace gas valve. The sediment trap must be located as close to the furnace cabinet as practical.
u
LEFT SIDE PIPING (STANDARD)
Make wiring connections to the unit as indicated on enclosed wiring diagram. As with all gas appliances using electrical
power, this furnace shall be connected into a permanently live electric circuit. It is recommended that it be provided with a
separate “circuit protection device” electric circuit. The furnace
must be electrically grounded in accordance with local codes or
in the absence of local codes with the National Electrical Code, ANSI/ NFPA 70 “latest edition” or Canadian Electrical Code, CSA C22.1, if an external electrical source is utilized.
All eld supplied wiring must conform with the temperature limitation for Type T wire [63° F (35° C)], when installed in
accordance with these instructions and wiring diagrams supplied
with the furnace. A disconnecting means must be located within
sight from, and readily accessible to, the furnace. Refer to the
SERVICE FACTS literature for unit wiring diagrams in addition
to the diagram inside the blower door.
!
WARNING
▲
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury, or loss of life.
RIGHT SIDE PIPING (OPTIONAL)
TOP VIEW OF RIGHT SIDE PIPING
16 18-CD34D1-5-EN
Page 17
WARNING
WARNING
WARNING
INSTALLER’S GUIDE
GAS PIPING
!
▲
FIRE - EXPLOSION HAZARD
DO NOT RUN FLEXIBLE GAS LINE THROUGH THE FURNACE CABINET WALL. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN PROPERTY DAMAGE, SERIOUS PERSONAL INJURY, OR DEATH.
This unit is shipped standard for left side installation of gas
piping. A piping cutout is also provided in the right side for an
alternate piping arrangement. The installation of piping shall be in accordance with piping codes and the regulations of the
local gas company. Pipe joint compound must be resistant to the chemical reaction with liqueed petroleum gases. Refer to piping
Table 9 for delivery sizes.
NOTE: Refer to local codes and the National Fuel Gas Code, current edition, for gas pipe requirements.
The furnace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of
that system at test pressures in excess of 1/2 psig.
The furnace must be isolated from the gas supply piping by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to
or less than 1/2 psig.
!
CAUTION
▲
that the pressure switch contacts are open and the limit switch(es) contacts are closed, the draft blower will be energized.
As the induced draft blower comes up to speed, the pressure
switch contacts will close and the ignitor warm up period will begin. The ignitor will heat for approx. 17 seconds, then the gas
valve is energized to permit gas ow to the burners. The ame sensor conrms that ignition has been achieved within the 6
second ignition trial period.
After the ame sensor conrms that ignition has been achieved, the delay fan ON period (xed at 45 seconds) begins timing. After the delay of 45 seconds, the indoor blower motor will be
energized and will continue to run during the heating cycle.
When the thermostat is satised, R and W thermostat contacts open, the gas valve will close, the ames will extinguish, and the
induced draft blower will be de-energized. The indoor blower
motor will continue to run for the fan off period (xed at 100
seconds), then will be de-energized by the control module.
!
▲
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury, or loss of life
Use a backup wrench on the gas valve when installing gas piping to prevent damage to the gas valve and manifold assembly.
NOTE: Maximum pressure to the gas valve for natural gas is 13.8" W.C. Minimum pressure is 5.0" W.C. Maximum pressure to the gas valve for propane is 13.8" W.C. Minimum pressure is 11.0" W.C.
All gas ttings must be checked for leaks using a soapy solution before lighting the furnace.
DO NOT CHECK WITH AN OPEN FLAME!
The following warning complies with the State of California law, Proposition 65.
!
▲
HAZARDOUS GASES!
EXPOSURE TO FUEL SUBSTANCES OR BY PRODUCTS OF INCOMPLETE FUEL COMBUSTION IS BELIEVED BY THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS, OR OTHER REPRODUCTIVE HARM.
SEQUENCE OF OPERATION
Thermostat call for heat
R and W thermostat contacts close signaling the control module
to run its self-check routine. After the control module has veried
START-UP AND ADJUSTMENT
Preliminary Inspections
With gas and electrical power “OFF”
1. Duct connections are properly sealed
2. Filters are in place
3. Venting is properly assembled
4. Blower door is in place
Turn knob on main gas valve within the unit to the “OFF” position. Turn the external gas valve to “ON”. Purge the air from the gas lines. After purging, check all gas connections for leaks
with a soapy solution – DO NOT CHECK WITH AN OPEN FLAME. Allow 5 minutes for any gas that might have escaped
to dissipate. LP Gas, being heavier than air, may require forced
ventilation. Turn the knob on the gas valve in the unit to the
“ON” position.
COMBUSTION AND INPUT CHECK
1. Make sure all gas appliances are off except furnace.
2. Clock the gas meter with the furnace operating (determine
the dial rating of the meter) for one revolution.
3. Match the “Sec” column in the gas ow (in cfh) Table 12
with the time clocked.
4. Read “Flow” column opposite number of seconds
clocked.
18-CD34D1-5-EN 17
Page 18
INSTALLER’S GUIDE
CAUTION
5. Use the following factors if necessary:
For 1 Cu. Ft. Dial Gas Flow CFH = Chart Flow Reading ÷ 2 For 1/2 Cu Ft. Dial Gas Flow CFH = Chart Flow Reading ÷ 4 For 5 Cu. Ft. Dial Gas Flow CFH = 10X Chart Flow Reading ÷ 4
6. Multiply the nal gure by the heating value of the gas obtained from the utility company and compare to the nameplate rating. This must not exceed the nameplate rating.
Gas Valve Adjustment
Changes can be made by adjusting the manifold pressure (See Table 14), or changing orices (orice change may not always be required). To adjust the manifold pressure:
1. Turn off all electrical power to the system.
2. Attach a manifold pressure gauge with exible tubing
to the outlet pressure boss marked “OUT P” on White­Rodgers gas valve model 36J. See Figure 18 for White­Rodgers gas valve model 36J.
3. Loosen (Do Not remove) the pressure tap test set screw one turn with 3/32" hex wrench.
a. The pressure tap adjustment kit (KIT07611) contains
a 3/32" hex wrence, a 5/16" hose and a connector and can be ordered through Global Parts.
4. Turn on system power and energize valve.
5. Adjust gas heat by removing adjustment regulator cover screw.
a. To increase outlet pressure, turn regulator adjust
screw clockwise.
b. To decrease outlet pressure, turn the regulator adjust
screw counterclockwise.
c. Adjust regulator until pressure shown on mano meter
matches pressure specied in Table 14.
d. The input of no more than nameplate rating and no
less than 93% of the nameplate rating, unless the unit is derated for high altitude.
e. Replace and tighten regulator cover screw securely.
6. Cycle valve several times to verify regulator setting.
a. Repeat steps 5-6 if needed.
7. Turn off all electrical power to the system.
8. Remove the manometer and exible tubing and tighten the pressure tap screw.
9. Using a leak detection solution or soap suds, check for leaks at the pressure outlet boss and pressure tap test screw.
10. Turn on system power and check operation of unit.
!
▲
Replace and/ or tighten all plugs removed or loosened when adjusting gas pressure. Leak check the fittings before placing the furnace into regular service. Failure to follow this warning could result in fire, explosion, or property damage.
For LP gases, the nal manifold pressure setting shall be 10.5" W.C. with an input of no more than the nameplate rating and no
less than 93% of the nameplate rating, unless the unit is derated
for altitude. Table 10 lists the main burner orices shipped with the furnace. If a change of orices is required to correct the input
rate, refer to Table 11.
Input ratings (BTUH) of these furnaces are based on sea level
operation and should not be changed at elevations up to 2,000 ft.
If the installation is 2,000 ft. or above, the furnace input rate
(BTUH) shall be reduced 4% for each 1,000 ft. above sea level.
The furnace input rate shall be checked by clocking the gas
ow rate (CFH) and multiplying by the heating value obtained
from the local utility supplier for the gas being delivered at the
TABLE 9
NATURAL GAS ONLY
TABLE OF CUBIC FEET PER HOUR OF GAS
FOR VARIOUS PIPE SIZES AND LENGTHS
PIPE SIZE
1/2 132 92 73 63 56 50 46
3/4 278 190 152 130 115 105 96
1-1/4 1050 730 590 520 440 400 370
This table is based on pressure drop of 0.3 inch W.C. and 0.6 SP.GR. gas
10 20 30 40 50 60 70
1 520 350 285 245 215 195 180
LENGTH OF PIPE
TABLE 10
ORIFICE SIZES
INPUT
RATING
BTUH
40,000 60,000
80,000 100,000 120,000 140,000
NUMBER
OF
BURNERS
2 3 4 5 6 7
MAIN BURNER ORIFICE
DRILL SIZE
NAT. GAS LP GAS
45 45 45 45 45 45
56 56 56 56 56 56
TABLE 11
PART NUMBERS FOR REPLACEMENT ORIFICES
DRILL
SIZE
44 45 46 47 48 49 50
PART
NUMBER
ORF00501 ORF00644 ORF00909 ORF00910 ORF01099 ORF00503 ORF00493
DRILL
SIZE
54 55 56 57 58 59
PART
NUMBER
ORF00555 ORF00693 ORF00907 ORF00908 ORF01338 ORF01339
18 18-CD34D1-5-EN
Page 19
INSTALLER’S GUIDE
TABLE 12
GAS FLOW IN CUBIC FEET PER HOUR
SEC. FLOW SEC. FLOW SEC. FLOW SEC. FLOW
8 900 29 248 50 144 82 88
9 800 30 240 51 141 84 86 10 720 31 232 52 138 86 84 11 655 32 225 53 136 88 82 12 600 33 218 54 133 90 80 13 555 34 212 55 131 92 78 14 514 35 206 56 129 94 76 15 480 36 200 57 126 96 75 16 450 37 195 58 124 98 73 17 424 38 189 59 122 100 72 18 400 39 185 60 120 104 69 19 379 40 180 62 116 108 67 20 360 41 176 64 112 112 64 21 343 42 172 66 109 116 62 22 327 43 167 68 106 120 60 23 313 44 164 70 103 124 58 24 300 45 160 72 100 128 56 25 288 46 157 74 97 132 54 26 277 47 153 76 95 136 53 27 267 48 150 78 92 140 51 28 257 49 147 80 90 144 50
2 CUBIC FOOT DIAL
HIGH ALTITUDE DERATE
TABLE 13
Orifice
Twist
Drill
Size If
Installed
At Sea
Level
42 43 44 45 46 47
54 55 56 57 58
2000 3000 4000 5000 6000 7000 8000 9000 10000
From National Fuel Gas Code - Table F-4
ALTITUDE ABOVE SEA LEVEL
and Orifice Required At Other Elevations
42
43
43
43
44
44
45
46
44
44
44
45
45
46
47
47
45
45
45
46
47
47
48
48
46
47
47
47
48
48
49
49
47
47
47
48
48
49
49
50
48
48
49
49
49
50
50
51
54
55
55
55
55
55
56
56
55
55
55
56
56
56
56
56
56
56
57
57
57
58
59
59
58
59
59
60
60
61
62
63
59
60
60
61
62
62
63
63
47 48 50 50 51 52
56 57 60 63 64
Outlet Pressure Boss
i
Regulator
Adjust-
ment
Inlet Pressure Boss (opt.)
On/Off Switch
White-Rodgers 36J gas valve
Table 14
FINAL MANIFOLD PRESSURE SET-
NATURAL GAS 3.5" W.C.
If the desired input rate cannot be achieved with a change
in manifold pressure, then the orices must be changed. LP installations will require an orice change.
DO NOT attempt to manually light the burner. Failure to follow this warning could result in property damage, personal injury or death.
IMPORTANT: Re-install the propane orices to the same depth as the orices supplied with the equipment.
See Table 13 for help in selecting orices if orice change is required. Furnace input rate and temperature rise should be checked again after changing orices to conrm the proper rate
for the altitude.
Installations above 4,000 feet may require a pressure switch
change. If required, use the BAYHALT*** Kit (High Altitude Accessory Kit) listed in PRODUCT DATA.
TINGS (inches w.c.)
FUEL PRESSURE
LP GAS 10.5" W.C.
!
WARNING
▲
installed altitude. Input rate changes can be made by adjusting the manifold pressure (min 3.0 - max 3.7 in. W.C. - Natural Gas) or changing orices (orice change may not always be required).
Installation of this furnace at altitudes above 2,000 ft. (610m) must be in accordance with local codes, or in the absence of
local codes, the National Fuel Gas Code, ANSI Z223.1/ NFPA 54 or National Standard of Canada, Natural Gas and Propane Installation Code, CSA B149.1, and must be made in accordance with the listed high Altitude Conversion Kit available with this
furnace.
18-CD34D1-5-EN 19
Page 20
INSTALLER’S GUIDE
WARNING
WARNING
LIGHTING INSTRUCTIONS
Lighting instructions appear on each unit. Each installation must be checked out at the time of initial start up to insure proper operation of all components. Check out should include putting the unit through one complete cycle as outlined below.
Turn on the main electrical supply and set the thermostat above the indicated temperature. The ignitor will automatically heat,
then the gas valve is energized to permit the ow of gas to the burners. After ignition and ame is established, the ame control module monitors the ame and supplies power to the gas valve until the thermostat is satised.
To shut off
For complete shutdown: Move the control switch on the main gas valve to the “OFF” position (See Figures 18). Disconnect the
electrical supply to the unit.
!
CAUTION
▲
If this is done during the cold weather months, provisions must be taken to prevent freeze-up of all water pipes and water receptacles.
Whenever your house is to be vacant, arrange to have someone inspect your house for proper temperature. This is very important in below freezing weather. If for any reason your furnace should fail to operate damage could result, such as frozen water pipes.
CONTROL AND SAFETY SWITCH ADJUSTMENT
LIMIT SWITCH CHECK OUT
The limit switch is a safety device designed to close the gas valve should the furnace become overheated. Since proper operation of this switch is important to the safety of the unit, it must be checked out on initial start up by the installer.
To check for proper operation of the limit switches, set the thermostat to a temperature higher than the indicated temperature
to bring on the gas valve. Restrict the airow by blocking the
return air or by disconnecting the blower. When the furnace reaches the maximum outlet temperature as shown on the rating plate, the burners must shut off. If they do not shut off after a reasonable time and overheating is evident, a faulty limit switch
is probable and the limit switch must be replaced. After checking
the operation of the limit control, be sure to remove the paper or cardboard from the return air inlet, or reconnect the blower.
AIRFLOW ADJUSTMENT
Check inlet and outlet air temperatures to make sure they are within the ranges specied on the furnace rating nameplate. If the airow needs to be increased or decreased, see the wiring
diagram for information on changing the speed of the blower motor.
!
▲
Disconnect power to the unit before removing the blower door. Failure to follow this warning could result in property damage, personal injury or death.
This unit is equipped with a blower door switch which cuts power to the blower and gas valve causing shutdown when the door is
removed. Operation with the door removed or ajar can permit the escape of dangerous fumes. All panels must be securely closed at
all times for safe operation of the furnace.
NOTE: Direct drive motors have bearings which are permanently lubricated and under normal use, lubrication is not recommended
INDOOR BLOWER TIMING
The control module controls the indoor blower. The blower starts
approximately 45 seconds after ignition. The FAN-OFF period is approximately 100 seconds from the interruption of gas ow.
ROOM AIR THERMOSTAT HEAT ANTICIPATOR ADJUSTMENT
Set the thermostat heat anticipator according to the current ow
measured, or the settings found in the notes on the furnace wiring diagram (found inside the furnace casing).
INSTRUCTIONS TO THE OWNERS
In the event that electrical, fuel, or mechanical failures occur, the owner should immediately turn the gas supply off at the manual gas valve, located in the burner compartment (See Figure 17). Also turn off electrical power to the furnace and contact the service agency designated by your dealer.
!
▲
Should overheating occur, or the gas supply fail to shut off, shut off the gas valve to the unit before shutting off the electrical supply. Failure to follow this warning could result in property damage, personal injury, or death.
OPERATING INFORMATION
FLAME ROLL-OUT DEVICE
All models are equipped with a thermal control device on the burner cover. In case of ame roll-out, the device will cause the circuit to open which shuts off all ow of gas.
Abnormal Conditions
1. EXCESSIVE COMBUSTION VENT PRESSURE OR FLUE BLOCKAGE
If pressure against the induced draft blower outlet becomes excessive, the pressure switch will shut off the gas valve until acceptable combustion pressure is again available.
2. LOSS OF FLAME OR GAS SUPPLY FAILURE
If loss of ame occurs during a heating cycle (when ame is
not present at the sensor), the control module will retry the
20 18-CD34D1-5-EN
Page 21
Failure to follow safety warnings exactly, could result in a fire or explosion causing property damage, personal injury or loss of life.
—
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier,
call the fire department.
— Installation and service must be performed by
a qualified installer, service agency or the gas supplier.
▲
WARNING
!
▲
WARNING
!
The following warning complies with State of California law, Proposition 65.
This product contains fiberglass wool insulation!
Fiberglass dust and ceramic fibers are believed by the State of California to cause cancer through inhalation. Glasswool fibers may also cause respiratory, skin, or eye irritation.
PRECAUTIONARY MEASURES
● Avoid breathing fiberglass dust.
● Use a NIOSH approved dust/mist respirator.
● Avoid contact with the skin or eyes. Wear long-
sleeved, loose-fitting clothing, gloves, and eye protection.
● Wash clothes separately from other clothing: rinse washer thoroughly.
● Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respirator in these situations.
FIRST AID MEASURES
Eye Contact – Flush eyes with water to remove dust.
If symptoms persist, seek medical attention.
Skin Contact – Wash affected areas gently with soap
and warm water after handling.
ignition sequence up to two times after the sensor cools. If ignition is not achieved, it will lockout the furnace.
3. POWER FAILURE
If there is a power failure during a heating cycle, the system will restart the ignition sequence automatically when power is restored, if the thermostat still calls for heat.
4. INDUCED DRAFT BLOWER FAILURE
If pressure is not sensed by the pressure switch, it will not allow the gas valve to open, therefore the unit will not start. If failure occurs during a running cycle, the pressure switch will cause the gas valve to close and shut the unit down.
INSTALLER’S GUIDE
INTEGRATED FURNACE CONTROL ERROR FLASH CODES
Flashing Slow --- Normal - No call for Heat
Flashing Fast --- Normal - Call for Heat
Continuous ON --- Replace IFC
Continuous OFF --- Check Power
2 Flashes --- System Lockout (Retries or Recycles exceeded)
Draft Pressure Error - Possible problems:
3 Flashes ---
4 Flashes --- Open Temperature Limit Circuit
5 Flashes --- Flame sensed when no ame should be present
6 Flashes --- 115 volt AC power reversed, poor grounding or system voltage too low
7 Flashes --- Gas valve circuit error
8 Flashes --- Low ame sense signal
18-CD34D1-5-EN 21
a) Venting problem
b) Pressure switch problem
c) Inducer problem
Page 22
INSTALLER’S GUIDE
22 18-CD34D1-5-EN
Ingersoll Rand 11819 N. Pennsylvania Street Carmel, IN 46032
The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and
specications without notice.
Loading...