Ingersoll-Rand SM132, SH90, SH132, SL110, SM150 Installation, Operation And Maintenance Manual

...
80448574
Revision A
May 2015
Save These Instructions
Oil-Free Rotary Screw Air Compressor
Installation, Operation and Maintenance
SL90, SM90, SH90, SL110, SM110, SH110 SL132, SM132, SH132, SL150, SM150, SH150 SL200, SM200, SH200, SL250, SM250, SH250, SH300 L125, H125, HH125, L150, H150, HH150 L200, H200, HH200, L250, H250, HH250 L300, H300, HH300, L350, H350, HH350, HH400
61115.10.33
2 80448574 Rev A
FOREWORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . 6
GENERAL OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
DESIGN PRESSURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
DESIGN TEMPERATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
COMPRESSED AIR SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
CONDENSATE REMOVAL SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . .6
LUBRICATION SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
COOLING SYSTEM (AIRCOOLED) . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
COOLING SYSTEM (WATERCOOLED) . . . . . . . . . . . . . . . . . . . . . . . .7
ELECTRICAL SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
CAPACITY CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
AUTOMATIC START/STOP CONTROL OPTION . . . . . . . . . . . . . . .7
REMOTE LOAD/UNLOAD OPTION . . . . . . . . . . . . . . . . . . . . . . . . . .8
REMOTE START/STOP OPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
POWER OUTAGE RESTART OPTION . . . . . . . . . . . . . . . . . . . . . . . . .8
SEQUENCER CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
TIMED LEAD/LAG OPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
SCHEDULED START/STOP OPTION . . . . . . . . . . . . . . . . . . . . . . . . .8
HIGH CONDENSATE LEVEL SWITCH . . . . . . . . . . . . . . . . . . . . . . . . .8
RECEIPT / HANDLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
RECEIPT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
UNPACKING AND HANDLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
LONG TERM STORAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
LOCATION IN THE PLANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
DISCHARGE AND CONDENSATE PIPING . . . . . . . . . . . . . . . . . . 10
PRIOR TO STARTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
ELECTRICAL CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
COOLING WATER PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
VENTING THE WATER SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
DRAINING THE WATER SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
WATER QUALITY RECOMMENDATIONS . . . . . . . . . . . . . . . . . . . 12
ROTATION CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
DRIVE MOTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
FAN MOTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . 14
BASIC OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
PRIOR TO STARTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
INITIAL CHECK SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
START SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
STOP SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
EMERGENCY STOPPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
RESTARTING AFTER EMERGENCY STOPPING . . . . . . . . . . . . . . 14
INTERFACE DATA AND KEYS . . . . . . . . . . . . . . . . . . . . . . . 15
Xe–90M/145M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
LED STATUS ICONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
COMMAND KEYS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
NAVIGATION KEYS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
DISPLAY LAYOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
SIERRA COMPRESSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
HOME FOLDER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
OPERATOR SETTINGS FOLDER . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
EVENTS FOLDER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
WARNING EVENTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
TRIP EVENTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
TRIP HISTORY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
GRAPHING FOLDER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
MAINTENANCE FOLDER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
GENERAL SETTINGS FOLDER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
INTEGRAL SEQUENCING FOLDER . . . . . . . . . . . . . . . . . . . . . . . . . 26
STATUS FOLDER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
FACTORY SETTINGS FOLDER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
WEB ACCESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
COMMISSIONING PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . 30
CONNECTING TO A PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
ETHERNET CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
LOGIN PROCESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
DEFAULT ACCOUNTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
NAVIGATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
TAB NAVIGATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
COMMAND BUTTONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
DASHBOARD ICONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
HOME PAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
EVENT LOG UTILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
PERFORMANCE LOG UTILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
GRAPHING UTILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
MAINTENANCE UTILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
INSPECTION LOG UTILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
COMPRESSOR INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
COMPRESSOR IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . 51
EMAIL (SMTP) SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
CONTENTS
61115.10.33
80448574 Rev A 3
COMPRESSOR DETAILS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
UNIT TYPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
ACCOUNT MANAGEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
ADD ACCOUNT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
MODIFY THE ACCESS LEVEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
ROUTINE MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
AIR FILTER CHANGE PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . 58
OIL CHANGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
OIL FILTER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
GEARCASE BREATHER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
CONDENSATE DRAIN FUNCTIONALITY . . . . . . . . . . . . . . . . . . . 58
CONDENSATE STRAINERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
AIREND BEARINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
COMPRESSOR MODULE INPUT SHAFT SEAL REPLACEMENT 58
MOTOR BEARINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
MOTOR BEARING LUBRICANT SPECIFICATION . . . . . . . . . . . . . 59
CLEANING/INSTALLING PACKAGE PRE-FILTER [90-160Kw(125-
200Hp)NEW ENCLOSURE ONLY] . . . . . . . . . . . . . . . . . . . . . . . . . . 59
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
CONTENTS
61115.10.33
4 80448574 Rev.A
FOREWORD
The contents of this manual are considered to be proprietary and condential to Ingersoll Rand and should not be reproduced without the prior written permission of Ingersoll Rand.
Nothing contained in this document is intended to extend any promise, warranty or representation, expressed or implied, regarding the Ingersoll Rand products described herein. Any such warranties or other terms and conditions of sale of products shall be in accordance with the standard terms and conditions of sale for such products, which are available upon request.
This manual contains instructions to cover all routine operation and scheduled maintenance tasks by operation and maintenance sta. Major overhauls are outside the scope of this manual and should be referred to an authorised Ingersoll Rand service department.
Any modication to any part is absolutely prohibited and would result in the CE Certication and marking being rendered invalid.
All components, accessories, pipes and connectors added to the compressed air system should be:
of good quality, procured from a reputable manufac­turer and, wherever possible, be of a type approved by Ingersoll Rand.
clearly rated for a pressure at least equal to the ma­chine maximum allowable working pressure.
compatible with the compressor lubricant/coolant. accompanied with instructions for safe installation,
operation and maintenance.
Details of approved equipment are available from Ingersoll Rand Service departments.
The use of non-genuine spare repair parts other than those included within the Ingersoll Rand approved parts list may create hazardous conditions over which
Ingersoll Rand has no control. Therefore Ingersoll Rand does not accept any liability for losses
caused by equipment in which non-approved repair parts are installed. Standard warranty conditions may be aected.
Ingersoll Rand reserves the right to make changes and improvements to products without notice and without incurring any obligation to make such changes or add such improvements to products sold previously.
The intended uses of this machine are outlined below and examples of unapproved usage are also given, however Ingersoll Rand cannot anticipate every application or work situation that may arise.
IF IN DOUBT CONSULT SUPERVISION.
This machine has been designed and supplied for use only in the following specied conditions and applications:
Compression of normal ambient air containing no known or detectable additional gases, vapours. or particles.
Operation within the ambient temperature range specied in the PRODUCT SPECIFICATION SHEET.
The use of the machine in any of the situation types listed in table 1:−
a) Is not approved by Ingersoll Rand, b) May impair the safety of users and other persons,
and
c) May prejudice any claims made against
Ingersoll Rand.
TABLE 1
Use of the machine to produce compressed air for:
a) direct human consumption.
b) indirect human consumption, without suitable ltration and purity checks.
Use of the machine outside the ambient temperature range specied in the PRODUCT SPECIFICATION SHEET.
Use of the machine where there is any actual or foreseeable risk of hazardous levels of ammable gases or vapours.
THIS MACHINE IS NOT INTENDED AND MUST NOT BE USED IN POTENTIALLY EXPLOSIVE ATMOSPHERES, INCLUDING SITUATIONS WHERE FLAMMABLE GASES OR VAPOURS MAY BE PRESENT.
Use of the machine tted with non Ingersoll Rand approved components.
Use of the machine with safety or control components missing or disabled.
The company accepts no responsibility for errors in translation of this manual from the original English version.
61115.10.33
80448574 Rev.A 5
SAFETY
Locate, read, understand and follow all Danger, Warning, Caution, and Operating Instructions on the product and in all Manuals. Failure to comply with safety precautions described in the manuals supplied with the product, this manual or any of the labels and tags attached to the product may result in death, serious injury or property damage.
Check that all labels, tags and data (name) plates are in place and legible.
It is your responsibility to make this information available to others.
If you have any questions about safety or procedures not included in this manual, ask your supervisor or contact any Ingersoll Rand oce or qualied Ingersoll Rand distributor.
61115.10.33
6 80448574 Rev A
GENERAL INFORMATION
GENERAL OPERATION
The Sierra compressor is an electric motor driven, two stage, dry screw compressor complete with accessories piped, wired and baseplate mounted. It is a totally self–contained oil free air compressor package. A standard compressor is composed of the following:
Inlet air ltration Compressor and motor assembly Pressurised oil system with cooler ON/OFF line capacity control system Motor starting control system Instrumentation Safety provisions Intercooler Aftercooler Moisture separation rst and second stage Automatic condensate removal rst and second stage.
The motor and airend are integrally mounted. This assembly is isolated from the base by rubber isolation mounts. Flexible pipe connections are utilised where necessary to isolate the main base and customer connections.
DESIGN PRESSURES
The normal operating pressures for Ingersoll Rand Sierra compressors are 7.0 bar, 8.5 bar and 10.0 bar (100 psi, 125 psi and 150 psi). The maximum allowable pressure is 0.2 bar (3 psi) above the normal operating pressure and is shown on the compressor name plate.
The inter–stage safety valve is set at 3.1 barg (45 psi) 90–150 kW, 125–200 hp or 3.8 barg (55 psi) 200–300 kW, 250–400 hp. The second stage safety valve is set at
11.4 barg (165 psi) max. The design of the pressurised system is well above the safety valve settings.
DESIGN TEMPERATURES
The standard compressor is designed for operation in an ambient range of 2 °C to 46 °C (35 °F to 115 °F). When conditions other than the design levels described are encountered, we recommend you contact your nearest Ingersoll Rand Distributor or Air Centre for additional information.
COMPRESSED AIR SYSTEM
The compressor air enters the compressor through an opening at the right end of the enclosure. It travels through a passageway lined with sound–absorbing material to the air lter. Via a round exible hose, the air passes through the inlet/unloading valve into the rst stage of the compressor.
The helical rotors compress the air to a pressure of between
1.7 to 2.6 barg (25 to 38 psig). It is discharged into a venturi, which dampens any pressure pulsations that may be present.
The intercooler then reduces the air temperature before it enters the second stage. A safety relief valve is also positioned in this system to guard against an abnormally high inter­stage pressure. A moisture separator is supplied immediately
following the intercooler to remove any condensation that may occur under certain conditions of ambient humidity and temperature.
An expansion joint is utilised between the moisture separator and the second stage.
The second stage further compresses the air to the desired pressure. The pressure pulsations being dampened in a venturi. An expansion joint prevents transmitted vibrations. A poppet type check valve is provided to prevent any backow of air into the compressor. The aftercooler cools the air to a suitable temperature, while the discharge moisture separator removes signicant amounts of condensation.
During unloaded operation, the inlet/unloading valve closes, via mechanical linkage, the blowdown valve opens, expelling any compressed air from the package.
CONDENSATE REMOVAL SYSTEM
A moisture separator is located immediately after the intercooler and aftercooler to collect and eject any condensation formed from the compressed air.
The condensate is drained through electrically operated solenoid valves. The opening duration is preset at three (3) adjustable between 2 and 20 seconds, the interval between openings may be altered between 60 and 360 seconds, depending on ambient conditions. If the environment consists of high temperature and/or high humidity, then the interval may have to be reduced. The factory set interval is 180 seconds.
The bosses for the manual valves are located on the outside and rear of the sub–base. These valves are supplied loose inside the compressor enclosure and need to be connected to the ports as indicated in the general arrangement drawing. To check operation of solenoid valves, open the manual bypass valves momentarily once per day. For extended shutdown periods, the manual valves should be opened and left open.
Strainers are provided upstream of the condensate valves to prevent any particles from plugging the solenoid valves. Before any maintenance is performed on the strainers or solenoid valves, the strainer service valves should be closed, in order to isolate from possible high pressure.
LUBRICATION SYSTEM
The oil sump is integral within the gearcase. The oil pump is a positive displacement gear–type pump, and is driven by the compressor driven shaft. Therefore, it rotates at the main motor speed.
See MAINTENANCE section for lubricant specication.
From the pump, the oil travels past a pressure relief valve to the oil cooler. The pressure relief valve’s function is to prevent over–pressure of the system. It also regulates oil pressure and may divert some oil ow back to sump.
At the discharge side of the oil cooler is a thermostatic valve. This valve mixes the cold oil with hot oil that bypasses the cooler to provide oil at the optimum temperature to the bearings and gears.
61115.10.33
80448574 Rev A 7
The oil then passes through a lter to a distribution manifold. An orice from the manifold determines the oil pressure (2.8 to 3.5 barg) (40 to 50 psig), at normal operating temperature (54 °C to 68 °C) (129 °F to 154 °F).
The gearcase is vented to a mounted breather. The breather prevents oil vapour from escaping the sump area. The breather exhaust is piped to the plenum area of the package.
COOLING SYSTEM (AIRCOOLED)
The intercooler, aftercooler, oil-cooler, fan and motor are an integral assembly. The heat exchanger and fan are mounted directly above the compressor assembly. Cooling air ows through the end of the enclosure, through the heat exchangers and discharges through the top of the package.
COOLING SYSTEM (WATERCOOLED)
The intercooler, aftercooler and oil-cooler are shell and tube type heat exchangers. The intercooler and aftercooler are ”water in the shell” design. The oil-cooler employs ”water in the tube”.
Cooling water ows through each of the three components in parallel. A water solenoid shut o valve is provided in the water discharge line from the package.
The tube bundles are removable for ease of cleaning.
ELECTRICAL SYSTEM
The electrical system of the compressor utilises the microprocessor–based Xe controller. The standard electrical/ electronic components, contained within a readily accessible enclosure include:
Xe controller
Star–Delta compressor motor starter, with auxiliary contacts and overload relays
Cooling fan manual motor starter and circuit breaker or fuses
Power supply board
Main motor overload relay
Control relay control transformer, and fuses.
Star–Delta type starter
By use of the Star–Delta type starter, the compressor motor can be started and accelerated using a greatly reduced ”inrush” electric current. The starter is completely automatic and controlled by the Xe controller. Refer to the electrical schematic.
CAPACITY CONTROL
Automatic unloaded start
The compressor will always start in the unload mode. When unloaded, the inlet valve is nearly closed, the blowdown valve is open and the compressor is operating at minimum power.
1.
2.
3.
4.
5.
6.
On–O line control
On–O line control will deliver air at full capacity (compressor maximum eciency condition) or will operate at zero capacity (compressor minimum power condition). The compressor is controlled by the Xe controller responding to changes in plant air pressure. The Xe controller energises the load solenoid valve (1SV) to actuate the hydraulic cylinder and load the compressor whenever plant air pressure drops below the online pressure set point. The compressor will then operate to deliver full capacity air to the plant system. If the plant air system pressure rises to the o line set point of the Xe, the load solenoid valve is de–energised, the hydraulic cylinder is de–actuated allowing the machine to unload. The compressor will continue to run with minimum power draw.
AUTOMATIC START/STOP CONTROL OPTION
Many plant air systems have widely varying air demands or large air storage capacity which allows for automatic standby air capacity control.
The Xe system has been designed to carry out this function utilising a software module. Automatic Start–Stop is standard on all Sierra compressors.
During periods of low air demand, if the line pressure rises to the oine set point, the Xe controller begins to time out. If the line pressure remains above the online set point for as long as the set time, the compressor will stop. At the same time, the Automatic Restart warning message will appear in the display to indicate the comdpressor has shut down automatically and will restart automatically. An automatic restart will occur when the line pressure drops to the online set point.
The oine and online set points and shutdown delay time are set on the control panel. There is a 10 second delay after shutdown during which the compressor will not restart even if line air pressure drops below the online set point. This is to allow the motor to come to a complete stop and the controller to collect current data of operating condition. If line air pressure is below the online set point at the end of 10 seconds, the unit will start unless the load delay timer is set greater than 10 seconds.
Delay load time
This is the amount of time the line pressure must remain below the online set point before the compressor will load or start (if the unit was stopped due to an auto start/stop situation). This timer will not delay loading after a start or if the time is set to 0. When the delay load timer becomes active, the display will switch to line pressure (if not displaying line pressure at that time) and then display the delay load countdown. Once the countdown reaches 0, the unit will load or start and the display will return to line pressure. The display select arrows are inactive during the delay load countdown.
GENERAL INFORMATION
61115.10.33
8 80448574 Rev A
Automatic start/stop operation
When in operation, the compressor must meet two specic timing intervals before the Xe controller will stop the unit in an Automatic Start/Stop situation.
A timer prevents the compressor from automatically starting more than 6 times an hour by requiring the unit to run at least 10 minutes after each automatic start.
This 10 minute run period can be loaded, unloaded or a combination of the two and allows dissipation of heat generated within the motor windings at start.
When the compressor has completed the settings of the timer, the controller stops the compressor, turns on the automatic restart light and displays AUTO-RESTART in the message display.
Pressure sensor 4APT continues to monitor the package discharge pressure and sends information to the controller which automatically restarts the compressor when the pressure falls to the online setting.
REMOTE LOAD/UNLOAD OPTION
This option allows the operator to remotely load and unload the machine.
With the option enabled, two dierent switches can be wired (refer to the electrical schematic for wiring locations). The switches are customer supplied.
REMOTE START/STOP OPTION
The remote start/stop option allows the operator to control the compressor from a remote mounted start/stop station. This option may be selected from the customer set–up routine.
With the option enabled, two dierent switches can be wired to the Xe for remote start/stop. (Refer to the electrical schematic for wiring locations.) The switches are customer supplied and must be of momentary type. The stop switch contacts are normally closed / the start switch contacts are normally open.
The following notice must be permanently xed to the unit in a prominent position.
(Factory tted on 60Hz machines).
WARNING
This machine is remote start and stop equipped. Disconnect power before servicing.
May start or stop at any time. Lock and tag out.
Can cause severe injury or death. See Operators / Instruction Manual.
POWER OUTAGE RESTART OPTION
The Power Outage Restart option is for installations that have interruptions in their incoming power supply to the compressor and must maintain an uninterrupted supply of compressed air. When turned on, the option allows the compressor to automatically restart and load 10 seconds after incoming power is restored after a power interruption. Suitable visible and audible warnings are given before restart.
SEQUENCER CONTROL
Sequencer control capability can be added to the electronic control system by utilising a sequencer interface. This option is available as a eld installation kit.
TIMED LEAD/LAG OPTION
When two or more machines are set up in a Lead/Lag situation. This option allows the machines to be switched from Lead to Lag at certain time of day.
SCHEDULED START/STOP OPTION
Allows the machine to be started or stopped at certain times of the day.
HIGH CONDENSATE LEVEL SWITCH
This option prevents high condensate levels in the inter­stage moisture separator, providing added protection against condensate carryover into the second stage compression module. If the condensate drain system becomes clogged or inoperative, this switch would signal the controller to shut the unit down and display a HIGH I/C CONDENSATE trip. The option may be factory installed or ordered as a eld installation kit.
GENERAL INFORMATION
61115.10.33
80448574 Rev A 9
RECEIPT / HANDLING
RECEIPT
Before signing the delivery receipt, inspect for damage and missing parts. If damage or missing parts are apparent, make the appropriate notation on the delivery receipt, then sign the receipt. Immediately contact the carrier for an inspection.
All material shall be held in the receiving location for the carrier’s inspection.
Delivery receipts that have been signed without a notation of damage or missing parts are considered to be delivered “clear.” Subsequent claims are then considered to be concealed damage claims. Settle damage claims directly with the transportation company.
If you discover damage after receiving the compressor (concealed damage), the carrier shall be notied within 15 days of receipt and an inspection shall be requested by telephone with conrmation in writing. On concealed damage claims, the burden of establishing that the compressor was damaged in transit reverts back to the claimant.
Read the compressor nameplate to verify it is the model ordered, and read the motor nameplate to verify it is compatible with your electrical conditions.
Make sure electrical enclosures and components are appropriate for the installation environment.
UNPACKING AND HANDLING
The compressor will normally be delivered with a polyethylene or other cover. If a knife has to be used to remove this cover, ensure that the exterior paintwork of the compressor is not damaged.
Incorporated within the base of the compressor are slots to enable a fork lift truck to move the compressor. Ensure truck forks are fully engaged on both sides. Alternatively a special lifting frame can be used to enable a crane or hoist to move the compressor. Use only marked lifting points.
Once the packaging and pallet are discarded and the compressor is in its nal position, remove the yellow painted transit brackets from the resilient mounts and store for future use or discard.
IMPORTANT Remove any shipping brackets particularly the soft
mount transit braces painted in yellow.
LONG TERM STORAGE
If the product will not be commissioned within six months of receipt, it should be prepared for long term storage. Please contact Ingersoll Rand for details.
61115.10.33
10 80448574 Rev A
INSTALLATION
LOCATION IN THE PLANT
Key
1. Compressor
2. Air Receiver Dry Tank
3. Air Dryer
4. Compressed Air Filters
5. System Demand Points
6. Vent/Drain Trap
7. Isolation Valve
8. Air Receiver (“Wet Tank”)
The compressor can be installed on any level oor capable of supporting it. A dry, well ventilated area where the atmosphere is as clean as possible is recommended.
The area selected for the location of the compressor should be free of dust, chemicals, metal lings, paint fumes and overspray.
Hard surfaces may reect noise with an apparent increase in the decibel level. When sound transmission is important, a sheet of rubber or cork can be installed beneath the compressor to reduce noise. Flexible piping may be required.
See the general arrangement drawing for minimum space requirements for normal operation and maintenance.
Minimum space in front of the control panel door as required by national or local codes shall be maintained.
Ambient temperatures higher than 46 °C (115 °F) shall be avoided, as well as areas of high humidity.
CAUTION
A minimum of 1 m (3.3ft) all round the compressor is recommended. If headroom is restricted, then the exhaust should be ducted or deected away from the machine.
Screw type compressors [1] should not be installed in air systems with reciprocating compressors without means of isolation such as a common receiver tank. It is recommended that both types of compressor be piped to a common receiver using individual air lines.
NOTICE
If ducting is tted, the sump breather needs to be piped outside the enclosure to avoid back pressure into the compression module.
1
5
4
2
3
4
6
7
DISCHARGE AND CONDENSATE PIPING
It is essential when installing a new compressor [1], to review the total air system. This is to ensure a safe and eective total system. One item which should be considered is liquid carryover. Installation of air dryers [3] is always good practice since properly selected and installed they can reduce any liquid carryover to zero.
To assure long trouble free operation of a compressor operating with ON-LINE OFF-LINE control, the system volume must be large enough to keep the load/unload cycles to a minimum (greater than 2 minutes).
A receiver [2], installed before the feeder lines [5], may be necessary to ensure that the total system volume is not less than 2.0 U.S.Gallons per rated delivery C.F.M.
Discharge piping should be at least as large as the discharge connection of the compressor. All piping and ttings should
be suitably rated for the discharge pressure.
It is important to install an isolation valve [7] within 3 feet (1 meter) of the compressor.
It is good practice to install line lters [4].
Include a means [6] to vent the discharge pipework downstream from the machine’s check valve and upstream of the rst system isolation valve [7].
When two rotary units are operated in parallel, provide an isolation vaIve and drain trap for each compressor before the common receiver.
The built−in intercooler and aftercooler reduce the discharge air temperature below the dew point (for most ambient conditions), therefore, considerable water vapor is condensed. To remove this condensation, each compressor with built−in aftercooler is furnished with two moisture separator/solenoid valve combinations. Since these solenoid valves discharge
61115.10.33
80448574 Rev A 11
at dierent pressures, it is extremely important that they are piped separately into an open drain.
A dripleg assembly and isolation valve should be mounted near the compressor discharge. A drain line should be connected to the condensate drain in the base.
IMPORTANT: The drain line must slope downward from the base to work properly. For ease of inspection of the automatic drain trap operation, the drain piping should include an open funnel.
CAUTION
The use of plastic bowls on line lters and other plastic air line components without metal guards can be hazardous. Their safety can be aected by either synthetic oils or the additives used in mineral oils. From a safety standpoint, metal bowls should be used on any pressurized system.
NOTICE
Do not use the compressor to support the discharge pipe.
PRIOR TO STARTING
If the electric motor/control wiring should become exposed or saturated with moisture/water deposits, it must be safely dried o before attempting to make any part or conductor electrically live.
Ensure all persons concerned are suitably competent with electrical installations.
Ensure that there is a safe working procedure which has been issued by supervisory personnel, and that it is understood by all persons concerned with the operation of the compressor.
Ensure that the safety procedure to be applied is based on the appropriate national regulations.
Ensure that the safety procedure is followed at all times.
ELECTRICAL CONNECTION
Feeder cables should be sized by a competent electrical engineer to meet all power requirements.
IMPORTANT Ensure that the control circuit is connected to the
transformer tapping that matches the supply voltage.
COOLING WATER PIPING
NOTICE
Water piping to and from the compressor package shall be atleast as large as the package connection size. Do not undersize the water piping.
Isolation valves with side drains should be installed on both the inlet and outlet lines. To maintain cooler cleanliness and reliability, it is important to install a strainer of 2 mm mesh size on the inlet line. Strainers are available from
Ingersoll Rand.
The air compressor has a normally closed solenoid valve that is tted to the water outlet side within the package. The valve is wired into the air compressor control circuit and closes when the compressor stops.
Carefully inspect the water system before installing the air compressor package. Ensure that the piping is free of scale and deposits that may restrict water ow to the air compressor package. If water cleanliness is poor, ltration installed on the water inlet pipe line is recommended.
Proper operation of the compressor requires that the cooling water ow be provided at a maximum supply temperature of 46 °C (115 °F). See the compressor engineering data sheets for cooling water ow rates.
Water temperature and pressure gauges should be installed in the water piping for use in any fault nding of the water system. Water pressure should ideally be between 3 and 5 bar (43.5 and 72.5 psi) but shall not be above 10 bar (145 psi).
Water cleanliness is also extremely important. Cleaning of coolers as a result of fouling is a customer responsibility. Therefore, it is highly recommended that proper water quality shall meet the requirements listed in WATER QUALITY RECOMMENDATIONS later in this section.
VENTING THE WATER SYSTEM
At the initial installation, or for startup after draining the water system, proceed to vent the system as follows:
Locate the water system vent cock on top of the intercooler.
Open the water valve(s) allowing water to ow to the package.
Open the vent cock and allow all air to escape from the system. When water is observed at the vent cock, close it.
The system is now properly vented.
1.
2.
3.
INSTALLATION
61115.10.33
12 80448574 Rev A
DRAINING THE WATER SYSTEM
Should it become necessary to completely drain the water system, proceed as follows:
Disconnect the inlet and discharge water lines from the connections located at the rear of the unit.
Locate the oil cooler by removing the left and centre rear panels. Remove the two drain plugs located at the end of the cooler.
Allow the system to completely drain.
WATER QUALITY RECOMMENDATIONS
Water quality is often overlooked when the cooling system of a water-cooled air compressor is examined. Water quality determines how eective the heat transfer rate, as well as the ow rate will remain during the operation life of the unit. It should be noted that the quality of water used in any cooling system does not remain constant during the operation of the system. The water make–up is eected by evaporation, corrosion, chemical and temperature changes, aeration, scale and biological formations. Most problems in a cooling system show up rst in a reduction in the heat transfer rate, then in a reduced ow rate and nally with damage to the system.
There are many constituents in the water system that must be balanced to have a good, stable system. The following major components should be monitored:
SCALE: Scale formation inhibits eective heat transfer, yet it does help prevent corrosion. Therefore, a thin uniform coating of calcium carbonate is desired in the inner surfaces. Perhaps the largest contributor to scale formation is the precipitation of calcium carbonate out of the water. This is dependent on temperature and pH. The higher the pH value, the greater the chance of scale formation. Scale can be controlled with water treatment.
CORROSION: In contrast to scale formation is the problem of corrosion. Chlorides cause problems because of their size and conductivity. Low pH levels promote corrosion, as well as high levels of dissolved oxygen.
FOULING: Biological and organic substances (slime) can also cause problems, but in elevated temperature environments such as cooling processes they are not a major concern. If they create problems with clogging, commercial shock treatments are available.
To ensure good operation life and performance of the compressor cooling system, the recommended acceptable ranges for dierent water constituents are included below:
Corrosivity (Hardness, pH, Total dissolved solids, Temperature at inlet and Alkalinity should be analysed monthly, or if stable for 3 to 4 months, analysed quarterly.
Acceptable concentration: Langelier Index 0 to 1
1.
2.
Iron content should be analysed monthly. Acceptable concentration: 2 mg/l (2 ppm)
Sulphate content should be analysed monthly. Acceptable concentration: 50 mg/l (50 ppm)
Chloride content should be analysed monthly. Acceptable concentration: 50 mg/l (50 ppm)
Nitrate content should be analysed monthly. Acceptable concentration: 2 mg/l (2 ppm)
Silica content should be analysed monthly. Acceptable concentration: 100 mg/l (100 ppm)
Dissolved Oxygen content should be analysed daily, or if stable, analysed weekly. Acceptable concentration: 0 mg/l (0 ppm) (as low as possible)
Oil and Grease content should be analysed monthly. Acceptable concentration: 5 mg/l (5 ppm)
Ammonia content should be analysed monthly. Acceptable concentration: 1 mg/l (1 ppm).
ROTATION CHECK
CAUTION
If the compressor is operated in the opposite direction of rotation, airend damage may result and is not warrantable.
Locate the rotation decal on each motor.
DRIVE MOTOR
The correct motor rotation is clockwise when viewed from the rear or non–drive end of the motor.
For the compressor motor rotation check, the running of the motor must be as short a time as possible.
After depressing the start button, IMMEDIATELY depress the ”EMERGENCY STOP” BUTTON. Should the motor rotation be incorrect, put the main isolator in the OFF position.
Open the starter box door.
Interchange any two line connections (L1, L2 or L3) at the starter. Close and fasten the starter box door. Recheck for correct rotation.
INSTALLATION
61115.10.33
80448574 Rev A 13
FAN MOTOR
Observe the compressor cooling fan. The rotation should be in accordance with the fan rotation decal axed to the fan motor. Cooling air should exhaust from the top of the compressor enclosure.
Should the motor rotation not be correct, put the main isolator in the OFF position.
Interchange any two fan motor leads at the fan manual motor starter (MMS). Close and fasten the starter box door. Recheck for correct rotation.
CAUTION
Do not operate the machine with the panels removed as this may cause overheating and operators to be exposed to high noise levels.
Do not start or operate the machine in temperatures below or approaching 0 °C (32 °F), because the operation of the regulation system, the unloader valve, the safety valve, will be compromised. Your Ingersoll Rand distributor will advise on low ambient modications.
ELECTRICAL DATA
An independent electrical isolator should be installed adjacent to the compressor.
Feeder cables should be sized by the customer/electrical contractor to ensure that the circuit is balanced and not overloaded by other electrical equipment. The length of wiring from a suitable electrical feed point is critical as voltage drops may impair the performance of the compressor.
Feeder cable connections to studs L1–L2–L3 on isolator should be tight and clean.
The applied voltage must be compatible with the motor and compressor data plate ratings.
The control circuit transformer has dierent voltage tappings. Ensure that these are set for the specic applied voltage prior to starting.
CAUTION
Never test the insulation resistance of any part of the machines electrical circuits, including the motor without completely disconnecting the Xe controller.
INSTALLATION
61115.10.33
14 80448574 Rev A
OPERATING INSTRUCTIONS
BASIC OPERATION
NOTICE
The language and compressors of measure displayed on the controller will be preset before leaving the factory. If these are required to be changed, contact your local Ingersoll Rand service provider.
PRIOR TO STARTING
Check that the lubricant level is at least visible in the center of the sight glass and add lubricant if necessary. Refer to the maintenance procedures for setting the correct level.
Ensure that the discharge air isolation valve is open. Switch on the main electrical isolation switch. The control panel will illuminate, indicating that the line and control voltages are available.
INITIAL CHECK SEQUENCE
The controller will perform an initial check sequence if the compressor receives initial power to the controller or has experienced an trip reset. While the initial check sequence occurs, the controller will display a “Checking Machine” message.
During the initial check sequence, the controller will check the control system for proper operation. During this time, if any items are found inoperative, a trip will occur and the compressor will not start.
After completion of the initial check sequence, the controller will then display “READY TO START’. This process should be completed within 10 seconds.
START SEQUENCE
The compressor will initially start by the operator pressing the local start button or receiving a remote start command. The compressor will start loaded at the end of star delta transition period for a star delta starter or wait for a period of time equal to the starter time set point for a remote starter.
STOP SEQUENCE
The compressor can be stopped by a local or remote stop, a shutdown due to a trip, or an emergency stop. All of the above conditions will cause the compressor to stop immediately, except the local or remote stop. A local or remote stop will open the blowdown valve and the compressor will run for up to 10 seconds. The compressor will stop if the system pressure reaches the oine pressure setpoint. However, if the compressor stops for this reason, it will automatically restart when the system pressure falls below the online pressure set point.
NOTICE
If the compressor has to be stopped in an emergency depress the emergency stop button located underneath the instrument panel.
EMERGENCY STOPPING
If the compressor has to be stopped in an emergency press the emergency stop button located underneath the instrument panel.
This will over-ride the normal unload/stop button and will immediately stop the compressor.
RESTARTING AFTER EMERGENCY STOPPING
If the compressor has been switched o because of a compressor malfunction, identify and correct the fault before attempting to restart.
If the compressor has been switched o for reasons of safety, ensure that the compressor can be operated safely before restarting.
Refer to the PRIOR TO STARTING and START SEQUENCE instructions earlier in this section before restarting the compressor.
61115.10.33
80448574 Rev A 15
INTERFACE DATA AND KEYS
Xe–90M/145M
The standard user interface conguration of the controller consists of the membrane and the LCD display. The membrane consists of ve command keys (Start, Stop, Load, Unload, and Reset), four navigation keys (Up, Right, Left and Down), and an Edit mode selection key (Enter). These keys, in conjunction with the color graphics display and the LED icons, make up the user interface to the compressor.
Xe–90M/145M
LED STATUS ICONS
Three LED icons are used to indicate the current status of the control system from a distance and are located on the upper left side of the user interface.
Icon Name Function
OK
Illuminates when no Warnings or Trips are sensed. Can be in a Ready or Not Ready state. This icon will ash when the machine is Running Unloaded.
Alert
Illuminates when a Warning (ashes) or Trip (constant on) is sensed. Can be in a Ready (Warning) or Tripped state.
Auto
Illuminates when the compressor stops in auto restart.
COMMAND KEYS
These keys command the controller to perform actions as specied in the following table. When any of these keys are pressed the action below will be initiated and logged in the event log.
Key Name Function
--- None
Load
Puts the compressor into the selected mode of operation. Unit will load if the pressure conditions are right.
Unload
Puts the compressor into an unloaded state. Unit will run unloaded indenitely.
Reset
Clears Warnings and Trips once the condition is corrected.
Start Starts the compressor.
Stop
Stops the compressor. This button should be pressed instead of the E-Stop for normal stopping operation.
Enter
Toggles the display between the Navigation mode and the Edit mode.
Xe–90M/145M Command Keys
NAVIGATION KEYS
There are four navigation keys (UP, RIGHT, DOWN and LEFT). While the ENTER key is not considered a navigation key, it is used in conjunction with the navigation keys to make or conrm a selection.
Xe–90M/145M’s Navigation Keys
OPERATING INSTRUCTIONS
61115.10.33
16 80448574 Rev A
The navigation keys roll over. Pressing one of the navigation keys will lead the user down a navigation path. Each time the key is pressed, another step in the path is taken. Once the end of a navigation path is reached, pressing the key one more time will bring the user back to the beginning of the path. Pressing the opposite key will move the user through the navigation path in the opposite direction. Once the beginning is reached, pressing the opposite key will take the user to the end of the path.
DISPLAY LAYOUT
Xe–90M/145M’s Display Layout
Folder Bar: Uses tabs to graphically identify each
folder.
Title Bar: Identies current folder and page
(underlined).
Page Content: Content of the current page. Dashboard: Displays system status.
FOLDER NAVIGATION AND ICONS
To move among the tabbed folders shown on the LCD display, press the RIGHT and LEFT keys. The navigation rolls over from the last to the rst folder and vice-versa.
Folder
Name
Icon Description
Home
System performance and status main information. The rst page of this folder is the default page when the controller rst powers up.
Operator
Settings
System options and conguration settings.
Events System events log.
Trip History Details on the most recent trips.
Graphing
On-board graphing of system data (Xe–145M Only).
Maintenance
Status and notication setup for compressor maintenance items.
Folder
Name
Icon Description
General
Settings
General settings such as Language, Time, and Units of Measure.
Integral
Sequencing
Intergral Sequencing communication status and conguration.
Status
Measurements or status from/of all analog and digital I/O.
Factory
Settings
Compressor tuning parameters. Also displays hardware and software versions.
Folder Bar Icons
PAGE NAVIGATION
Once the desired folder is selected, press the DOWN key to move to the page selection area and then use the RIGHT and LEFT keys to select the desired page. Use the UP key to get back to the folder tabs.
Icon Description
Start of the page selection area.
Indicates that there are more pages available by navigating right.
Indicates that there are more pages available by navigating left.
Title Bar Page Icons
ACCESSING PARAMETERS
After the desired page is selected, the page’s parameters can be selected by using the DOWN key. The cursor will move to the next parameter each time the DOWN key is pressed. Use the UP key to go back to the previous one.
The cursor rolls over, so once the last parameter is selected, pressing the DOWN key will navigate the cursor to the Folder Bar. If the rst parameter is selected, pressing the UP key will move the cursor to the page selection area.
Once selected, access parameters by pressing the ENTER key. Make changes using the NAVIGATION keys and then enter the setting by pressing the ENTER key again. After a parameter is accessed, pressing the ENTER key will enter the current setting into the control program and navigate the cursor back to the selected parameter on the page.
When the cursor is on a parameter that has an enabled/ disabled box, pressing the ENTER key will cause the setting to toggle.
OPERATING INSTRUCTIONS
61115.10.33
80448574 Rev A 17
The icon appears on numeric entry windows (see gure below). Placing the cursor on it and then pressing the ENTER key will cancel the entry and any changes that were made.
Not all pages have adjustable parameters. Some just have read-only information.
DASHBOARD ICONS
The dashboard is intended to be a quick at-a-glance view of system status. The following table lists standard dashboard icons and their denition. Note that the color of these icons changes based on the state set by the application while running.
Name Icon Description
Remote Control
Remote control is enabled. This can be Remote Start/Stop, COM Control, Integral Sequencing or Web Control.
Service Required
A service reminder is nearing or has expired (i.e.: an air or oil lter needs to be changed).
Unloaded
or
Loaded
Compressor is in the unloaded state.
Compressor is in the loaded state.
Xe–90M/145M’s Dashboard Icons
DASHBOARD STATUS MESSAGES
The dashboard also displays the current operating state of the compressor. The following states can be encountered during machine operation:
Ready to Start – The compressor currently has no trip or start inhibit conditions present. The machine can be started by pressing the start button at any time.
Starting – A start command has been given to the
compressor and the start sequence is being performed. The time period for this state can vary depending on the starter type of the machine.
Load Delay – The compressor is waiting for a small period of time after starting before allowing the machine to load. This ensures the machine is at operating conditions before loading
Running Loaded – The compressor is operating and producing air. The inlet valve is open and the blowo valve is closed.
Running Unloaded – The compressor is operating, but not producing air. The inlet valve is closed and the blowo valve is open.
Auto-Restart – The compressor has stopped due to pressure rising above the oine or auto-stop setpoints and auto-restart being enabled. The compressor will automatically restart when pressure falls to the online or target pressure setpoint.
Stopping – The compressor has received a stop command and the stop sequence is being performed.
Blowdown – The compressor must wait for a brief period of time after stopping its motor before it is allowed to start again.
Not Ready – The compressor has detected a condition that will not allow the compressor to start. The condition must be cleared before a start is allowed, but does not need to be acknowledged.
Tripped – The compressor has detected an abnormal operational condition that has stopped the machine. A trip must be acknowledged by hitting the reset button before the compressor can start.
Processor Init – The controller is being initialized.
OPERATING INSTRUCTIONS
61115.10.33
18 80448574 Rev A
SIERRA COMPRESSOR
HOME FOLDER
PAGE 1 – SYSTEM OVERVIEW
This is the factory default display after powering up the system.
Load Pressure – indicated in the white box and by the white arrow, which is always left of center on the gauge. The compressor will load when package discharge pressure falls below this value.
Unload Pressure – indicated in the white box and by the white arrow, which is always right of center on the gauge. The compressor will unload when package discharge pressure rises above this value.
Package Discharge Pressure – indicated by the large numbers centred below the gauge and by the red arrow. This is the air pressure that the compressor is supplying to the plant.
Pressure Unit of Measure – indicated below the Package Discharge Pressure. This is selectable from the GENERAL SETTINGS folder.
Package Discharge Temperature – indicated by the numbers in the lower right of the display. This is the temperature of the compressed air/at the discharge of the compression module. The Package Discharge Temperature is only displayed if the Hot Discharge option is disabled.
Second Stage Discharge Temperature – indicated by the numbers in the lower right of the display. This is the temperature of the compressed air at the discharge of the 2nd stage compression module.
Temperature Unit of Measure – indicated to the right of the Airend Discharge Temperature. This is selectable from the GENERAL SETTINGS folder.
Run Hours – indicate the number of hours the compressor has been running.
All information on this page is read only.
PAGE 2 – COUNTERS
Hour Meters – Indicates the hours that: the controller has been powered up, the compressor has been running, and the compressor has running loaded.
Starts – Indicates the number of times a start is attempted on the compressor.
Date and Time – Indicates the current date and time. This is adjustable and congurable in the GENERAL SETTINGS folder.
All information on this page is read only.
PAGES 3 THRU 4 – ANALOG INPUTS
Pressure is indicated by this icon.
Temperature is indicated by this icon.
Any sensor that is not installed or is reporting a failure will show an X symbol.
All information on these pages is read only.
The following analog inputs are displayed in this section:
Package Discharge Pressure – The pressure the compressor is delivering to the plant.
Package Discharge Temperature – The temperature of the air after passing through the After-cooler.
1st Stage Discharge Temperature – The temperature of the air at the discharge of the 1st stage of the compression module.
OPERATING INSTRUCTIONS
61115.10.33
80448574 Rev A 19
2nd Stage Inlet Pressure – The pressure of the air at the intake of the 2nd stage of the compression module.
2nd Stage Inlet Temperature – The temperature of the air at the intake of the 2nd stage of the compression module.
2nd Stage Discharge Pressure – The pressure of the air at the discharge of the 2nd stage of the compression module.
2nd Stage Discharge Temperature – The temperature of the air at the discharge of the 2nd stage of the compression module.
Bearing Oil Temperature – The temperature of the coolant oil at the bearings of the compression module shaft.
Bearing Oil Pressure – The pressure of the coolant oil at the bearings of the compression module shaft.
Inlet Vacuum – Vacuum reading at the inlet valve.
Remote Pressure (optional) – An optional pressure sensor
that reads pressure at a point outside of the compressor package. Usually this would be on a common tank.
Oil Filter Pressure Drop – Dierential pressure across the lter. Higher values indicate an older or clogged lter.
OPERATOR SETTINGS FOLDER
PAGE 1–2 OPERATOR SETTINGS
The below values are all setpoints:
Oine Pressure – The compressor will unload when package discharge pressure rises above this value. Range (in PSI): 75 to Rated Pressure +3.
Online Pressure – The compressor will load when the package discharge pressure falls below this value. Range (in PSI): 65 to Oine Pressure -10.
Lead/Lag – When this box is checked the compressor is operating as a lead machine. Unchecking the box causes the machine to run as a lag machine.
Lag Oset – If the machine is running as a lag compressor, the lag oset will be subtracted from the online and oine setpoints. Range (in PSI): 0–45, depending on the online and oine setpoints. The Lag Oset will never allow you to exceed the minimum or maximum values of the online and oine setpoints.
Condensate Release Time – Time period that determines how long the condensate drain valve will remain open every cycle. Range: 2–20 seconds.
Condensate Interval Time – Time period that determines how long the condensate drain will remain closed every cycle. Range: 90–270 seconds.
Starter Time – Time period that the compressor needs in order to come up to operating speed after a start command before being able to produce air. Range (in seconds): 5–30.
Max 1st Stage Temperature – Setting that determines at what temperature the compressor will trip if the 1st Stage Discharge Temperature exceeds it. Range (in °F): 300–440.
Max 2nd Stage Temperature – Setting that determines at what temperature the compressor will trip if the 2nd Stage Discharge Temperature exceeds it. Range (in °F): 328–428.
The parameters on these pages are adjustable any time.
PAGES 3–5 OPERATOR OPTIONS
The below values are all setpoints:
Auto-Restart Time – The time period the compressor must run unloaded before stopping in auto-restart. This time period begins the moment that package discharge pressure rises above the oine setpoint. Both this time period and the minimum motor run timer (10 minutes) must be satised before the compressor will stop in auto restart. Range (in seconds): 120–900.
Auto-Restart Delay – The time period after the package discharge pressure has fallen below the online setpoint before the compressor can automatically restart. Range (in seconds): 0–60.
COM Control – Enabling this setpoint allows the compressor to be controlled by a serial or Ethernet device, such as an X8I. This is equivalent to the “Sequencer” option on older Intellisys controllers.
Remote Start/Stop – Enabling this setpoint allows the compressor to be started and stopped using the digital inputs on the controller.
Enable PORO – Enabling this setpoint will allow the
OPERATING INSTRUCTIONS
61115.10.33
20 80448574 Rev A
compressor to automatically restart after a power outage has been restored if the compressor was running loaded at the time of the outage. PORO is an option and the option module must be purchased and installed before this feature can be turned on.
PORO Time – Time after the controller power has been restored and controller has nished booting before the compressor will perform a PORO start. During this time the PORO Horn will sound. Range (in seconds): 10–600.
Condensate Level Installed – Setpoint to enable the level switch used to detect a blocked condensate drain.
Lead/Lag Cycle Length – The time period that controls how long the compressor will remain in the lead position before switching to lag. Setting this to 0 will disable this function. Range: 0–750 hours.
Scheduled Start Day – Day (or days) of the week for which a scheduled start will be performed. The compressor will start when its onboard clock matches the day, hour, and minute of the scheduled start setpoints. Scheduled Start/Stop is an option and the option module must be purchased and installed before this feature can be turned on.
Scheduled Start Hour – Hour of the day for which a scheduled start will be performed. Scheduled Start/Stop is an option and the option module must be purchased and installed before this feature can be turned on.
Scheduled Start Minute – Minute of the hour for which a scheduled start will be performed. Scheduled Start/Stop is an option and the option module must be purchased and installed before this feature can be turned on.
Scheduled Stop Day – Day (or days) of the week for which a scheduled stop will be performed. The compressor will stop when its onboard clock matches the day, hour, and minute of the scheduled stop setpoints. Scheduled Start/Stop is an option and the option module must be purchased and installed before this feature can be turned on.
Scheduled Stop Hour – Hour of the day for which a scheduled stop will be performed. Scheduled Start/Stop is an option and the option module must be purchased and installed before this feature can be turned on.
Scheduled Stop Minute – Minute of the hour for which a scheduled stop will be performed. Scheduled Start/Stop is an option and the option module must be purchased and installed before this feature can be turned on.
Enable High Dust Filter – Enabling this when a high dust lter is installed will adjust the change inlet lter warning and high inlet vacuum trip thresholds to a higher value.
Enable Remote Pressure Sensor – Enabling this allows the compressor to load and unload based o a sensor reading installed in a remote location.
Please note that in order to disable Scheduled Start/Stop, the Scheduled Start and Stop days, hours, and minutes must
match exactly.
PAGES 6 CALIBRATE SENSORS
Sensor calibration can only take place when the machine is stopped and there is no pressure on the sensor. Calibration only needs to take place after a sensor is replaced, the controller is replaced, the controller software is upgraded, or the operator suspects the sensor reading is in error. Calibrate a sensor by selecting the checkbox beside the sensor name.
Each of the sensors listed below can be calibrated:
Inlet Vacuum (1AVPT) 2nd Stage Inlet Pressure (2APT) 2nd Stage Discharge Pressure (3APT) Package Discharge Pressure (4APT) Oil Filter Inlet Pressure (5OPT) Bearing Oil Pressure (6OPT) Remote Pressure (10APT) – Only on units with the
remote sensor option.
Please note that if a sensor is currently reading a value that is +/-10% of its range from zero, the sensor will not be able to be calibrated and an warning will be logged in the event log. Please make sure the sensor is being exposed to atmosphere before attempting calibration.
EVENTS FOLDER
PAGES 1 TO A MAX OF 50
The pages in the Events folder document up to the last 250 events that the controller has experienced, with the time and date of the occurrence. The events are recorded in sequence, with number one being the newest and 250 being the oldest. When a new event occurs, it becomes number one and all others are shifted up in number.
The page numbers in the Title Bar are used to scroll through
OPERATING INSTRUCTIONS
61115.10.33
Loading...
+ 44 hidden pages