Ingersoll-Rand DXR Series, DXR800, DXR1000, DXR425, DXR600 Operator's Instruction Manual

DXR SERIES
REFRIGERATED AIR DRYERS
OPERATOR'S
INSTRUCTION MANUAL
DXR425 DXR600 DXR800
English: 1-1 Español: 2-1
Before installation or starting the dryer for the first time, study this manual carefully to obtain a clear knowledge of the dryer and of the duties to be performed while operating and maintaining the dryer.
RETAIN THIS MANUAL WITH DRYER.
This technical manual contains IMPORTANT SAFETY DATA and should be kept with the dryer at all times.
Bulletin 553 Revision M (2/00) Copyright ©2000 Ingersoll-Rand Company Printed in USA
Table of Contents
INTRODUCTION ...............................1-1
SAFETY ....................................1-1
Safety Instructions ............................1-1
Safety Labels ...............................1-1
Data Plate and Labels ..........................1-1
RECEIVING AND INSPECTION ......................1-1
INSTALLATION ...............................1-2
Ambient Air Temperature ........................1-2
Location and Clearance .........................1-2
System Arrangement ...........................1-2
Piping and Connections .........................1-2
Drains ..................................1-2
Electrical Connections ..........................1-2
Cooling Water ..............................1-2
Air-Cooled Models............................1-3
HOW IT WORKS ...............................1-3
Air Flow .................................1-3
Refrigeration System...........................1-3
INSTRUMENTATION ............................1-4
Power Signal ...............................1-4
System Operation Monitor ..........................1-4
AUTOMATIC DRAIN VALVES ......................1-7
ADV Adjustment.............................1-8
START-UP ...................................1-8
SHUTDOWN .................................1-8
MAINTENANCE ...............................1-9
General ..................................1-9
Daily Maintenance ............................1-9
Weekly Maintenance...........................1-9
Monthly Maintenance ..........................1-9
Service Due Indicator ..........................1-9
Returns to Manufacturer .........................1-9
Ambient Air Filter Replacement ....................1-10
Automatic Drain Valve Disassembly and Servicing ..........1-10
Prefilter Element Replacement .....................1-10
FIELD SERVICE GUIDE ..........................1-12
REPLACEMENT PARTS ..........................A-1
SCHEMATICS ................................A-1
INTRODUCTION
DXR Series refrigerated air dryers use mechanical re frigeration to dry compressed air to pressure dew points as low as 33°F-39°F. They deliver the required dew point at specified inlet air temperature, pressure and air flow. Any change in these operating conditions may af fect performance. See Table 9 for rated capacity and other dryer specifications.
To ensure continuing good performance and safe opera tion of the dryer, everyone who installs, uses or main tains it must read and carefully follow the instructions in this manual.
-
-
SAFETY
DXR Series dryers are designed and built with safety as a prime consideration; industry-accepted safety factors have been used in the design. Each dryer is checked at the factory for safety and operation. All necessary ad justments are made before shipment.
Follow the maintenance schedules outlined in this man­ual for good performance and safe operation. Mainte­nance should be done only by qualified personnel with proper tools.
Carefully read the following safety rules before pro­ceeding with installation, operation or maintenance. The rules are essential to ensure safe dryer operation. Failure to follow these rules may void the warranty or result in dryer damage or personal injury.
1. Do not install or try to repair a dryer that has been damaged in shipment. See Receiving and Inspec tion for instructions.
2. Compressed air and electricity have the potential to cause personal injury or equipment damage. Before doing any work on the dryer, be sure the electrical supply has been locked and tagged and the internal pressure of the dryer has been vented to the atmos phere.
3. Do not operate the dryer at pressures or tempera tures above the maximum conditions shown on the data plate.
4. Always supply electrical power that complies with the voltage shown on the data plate.
5. Do not readjust the dryer without factory authoriza tion.
6. Work on the refrigeration system must be done only by a competent refrigeration mechanic.
-
-
-
-
7. Use only manufacturer's genuine replacement parts. The manufacturer bears no responsibility for haz ards caused by the use of unauthorized parts.
-
Safety Instructions
-
-
-
Safety instructions in this manual are boldfaced for em phasis. The signal words DANGER, WARNING and CAUTION are used to indicate hazard seriousness lev els as follows:
DANGER—Immediate hazard which WILL result in severe injury or death.
WARNING—Hazard or unsafe practice which COULD result in severe injury or death.
CAUTION—Hazard or unsafe practice which COULD result in minor injury or in product or property damage.
-
-
Safety Labels
Dryer labels providing important safety information are included in this manual near corresponding text. If any of the labels is missing or damaged, contact your local distributor, request the label by its part number and ap­ply it to the dryer.
Data Plate and Labels
The dryer data plate and dryer labels contain critical safety and identification information. If any label or data plate is missing or damaged, contact your local dis­tributor and request a replacement.
RECEIVING AND INSPECTION
Inspect the dryer closely when it is received. Record any indication of damage on the delivery receipt, espe cially if the dryer will not be immediately uncrated. Ob tain the delivery person's signed agreement to recorded damages to facilitate future insurance claims.
Since the dryer is shipped F.O.B. New Castle, Dela ware, the manufacturer's responsibility for the shipment ceases when the carrier signs the bill of lading.
If goods are received short or in damaged condition, no tify the carrier and insist on a notation of the loss or damage across the face of the freight bill. Otherwise no claim can be enforced against the carrier.
If concealed loss or damage is discovered, notify your carrier at once and request an inspection. This is abso
-
lutely necessary. Unless you do this the carrier will not consider any claim for loss or damage. The carrier will make an inspection and may grant a concealed damage notation. If you give the carrier a clear receipt for goods that have been damaged or lost in transit, you do so at your own risk and expense.
-
-
-
-
-
DXR Series Dryers (Bulletin 553) 1-1
The manufacturer is willing to assist you in collecting claims for loss or damage. Willingness does not make the manufacturer responsible for collecting claims or re placing material. Claim filing and processing is your re sponsibility.
Compressed air systems commonly require filters to re
­move compressor oils, particulates, condensed liquids and other contaminants. When an oil-removal filter is
-
-
used, install the filter downstream of the DXR Series dryer. At this location, the life of the replaceable filter element is prolonged since some of the entrained oil is removed by the dryer and drained through the separator.
INSTALLATION
Ambient Air Temperature
Locate the dryer indoors where the ambient air tempera ture will be between 40°F and 100°F. Intermittent op eration at ambient temperatures up to 120°F will not damage the dryer but may result in a higher dew point or dryer shutdown due to high refrigerant discharge pressure (see Field Service Guide). Call your local dis tributor if prolonged operation at ambient temperatures above 100°F or below 40°F is unavoidable.
Do not operate air-cooled dryers at ambient air tempera tures below 40°F. Such operation may result in low suc tion pressure, causing freeze-up.
Location and Clearance
Mount the dryer on a level base and bolt down if base vibrates. If the dryer is air cooled, install it in a clean, well-ventilated area to reduce fouling of the condenser coils with dirt and dust. Allow 24 inches clearance on the sides and front of the dryer for cooling airflow on air-cooled dryers and for service access on both air­cooled and water-cooled dryers.
System Arrangement
Liquid water adversely affects dryer performance. To prevent “slugging” the dryer with liquid water, locate the dryer downstream of an and a separator. Install drain valves to discharge condensate that collects in these areas.
If the airflow is relatively constant and will not cause short term overloading of the dryer, it is recommended that the dryer be located downstream of the receiver tank. If the nature of the application is such that the air demand regularly exceeds the dryer flow rating, it is recommended that the dryer be located upstream of the receiver.
For safety and convenience, install inlet and outlet shut off valves and depressurization valves at the locations indicated. These valves allow the dryer to be isolated and depressurized for servicing. Bypass piping may be installed around the dryer for uninterrupted airflow when the dryer is serviced. If the compressed air opera tion cannot tolerate undried air for short periods, install a second dryer in the bypass line.
-
Piping and Connections
Piping must be furnished by the user unless otherwise specified. Connections and fittings must be rated for the
­maximum operating pressure given on the dryer data
plate and must be in accordance with applicable codes. Support all piping; do not allow the weight of any pip
-
ing to stress the dryer or filters. Proper sizing of piping
-
should be determined using good engineering practice. See Table 8 for dryer inlet and outlet connections.
Drains
­Condensate must be drained from the dryer to prevent
­its reentrainment. The dryers are equipped with an auto
­matic drain valve. A condensate hose is coiled and se­cured inside the dryer cabinet for shipping. Uncoil the hose and run it to a waste disposal collection system that meets applicable regulations. Install the discharge lines so that condensate can be seen as it drains.
Pipe or copper tubing densate discharge lines. Do not use
1
-inch is recommended for con-
2
1
-inch or
4
5
16
-inch O.D. flexible tubing unless the discharge line is shorter than 10 feet.
Electrical Connections
Standard models are constructed according to NEMA Type 1 electrical standard. Field wiring must comply with local and national fire, safety and electrical codes. Installation must be in accordance with the National Electrical Code. Confirm that your line voltage is the same as the voltage listed on the data plate.
Dryers are wired so that the crankcase heaters (if sup
­plied) and drain valves are energized when power is supplied, even if the power switch is turned off. See the electrical schematics for wiring details.
Cooling Water
-
-
Water-cooled condensers are optional on some models. The suffix W on the model number indicates water­cooled. The user is responsible for piping the water to and from the condenser. A factory-installed water regu lating valve in the condenser inlet connection is stan
-
dard.
Required water flow rate depends on water temperature (refer to Table 1). The valve supplied with the dryer automatically adjusts the flow to compensate for varia
-
-
1-2 DXR Series Dryers (Bulletin 553)
tions in water temperature, water pressure and dryer air load.
Operating the dryer with inadequate condenser cooling water (temperatures above or pressures below those in Table 1) will cause a rise in dew point unless the dryer inlet airflow is reduced. The refrigerant discharge pres
­sure control will shut down the refrigerant compressor if cooling water is inadequate.
If the cooling water is dirty, install a strainer ahead of the condenser inlet. Install shutoff valves so that the strainer can be drained and cleaned at regular intervals.
COOLING WATER REQUIREMENTS
DRYER
MODEL
DXR425-W
DXR600-W
DXR800-W
DXR1000-W
a
Minimum water pressure is 25 psig for city water and 35 psig for
tower water. Maximum water pressure is 150 psig.
WATER
CONN.
(in NPT)
3
3
1
1
Table 1

COOLING WATER

REQUIRED
60°F 70°F 80°F 85°F 90°F
GPM GPM GPM GPM GPM
8
8
2
2
0.6 1.0 2.1 2.7 4.2
1.6 2.0 2.8 3.8 5.5
1.5 2.0 3.7 5.4 10.0
2.5 3.0 4.5 5.7 9.0
a
Air-Cooled Models
Cooling air must be drawn from a clear, well-ventilated area to reduce dust and dirt accumulation on the con­denser coils. Air temperature should not exceed 100°F. Required air flow rates are shown in Table 2.
COOLING AIR REQUIREMENTS
MODEL
DXR425 3000
DXR600 2700
DXR800 5200
DXR1000 4800
Table 2
COOLING AIR
(cfm)
The cold, dry air is reheated by incoming warm air as it passes back through the air-to-air heat exchanger. Using the outgoing air to pre-cool the inlet air condenses up to 65 percent of the moisture out of the inlet air before it reaches the chiller. Pre-cooling the inlet air reduces the heat load on the refrigerant compressor, permitting the use of a smaller refrigerant compressor.
Refrigeration System
The refrigeration system is designed and fabricated in accordance with recognized commercial/industrial prac tices. It consists of a compressor and the controls, safety interlocks and associated equipment necessary for safe performance.
A thermostatic expansion valve (TEV) and a hot gas by pass valve (HGBV) are used to modulate the refrigerant flow. The TEV adjusts the flow of liquid refrigerant to the chiller. A temperature sensor downstream of the chiller opens and closes the TEV in response to the tem perature of the refrigerant leaving the chiller to maintain the proper cooling rate under all load conditions. The HGBV delivers hot refrigerant gas to the chiller in re­sponse to changes in refrigerant pressure. This prevents icing in the chiller and short cycling in the refrigerant compressor during extended periods of system opera­tion at low load.
All refrigerant valves are adjusted at the factory; opera­tion is fully automatic.
-
-
-
HOW IT WORKS
Air Flow
DXR Series dryers use refrigeration cooling to condense entrained moisture out of the airstream (see Figure 2). Warm saturated air enters the air- to-air heat exchanger where it is cooled by outgoing cold air. The inlet air is further cooled in the refrigeration chiller. Cooling con denses entrained moisture. The condensate is removed by a centrifugal separator and an automatic drain valve.
DXR Series Dryers (Bulletin 553) 1-3
-
Figure 2.
Air and refrigerant flow schematic.
INSTRUMENTATION
Power Signal
All dryers are equipped with an ON-OFF switch located on the front panel. A white light signals when power is on.
System Operation Monitor
A System Operation Monitor measures and displays critical air and refrigerant temperatures, signals operat ing conditions which may affect dryer performance, and enables panel adjustment of the automatic drain valve. There is also a light to indicate the need for routine service.
The monitor consists of (refer to Figure 4):
indicating lights
alphanumeric display
• controls (push buttons) that provide access to critical air and refrigerant temperatures
• schematic with lights that correspond to the locations of the temperature sensors in the system
• drain valve controls
• temperature sensor probes
-
Indicating lights
The System Operation Monitor has four indicating lights: NORMAL OPERATION, CHECK OPERAT ING CONDITIONS, SERVICE DUE and SYSTEM ALARM. Table 3 provides instructions for using the in dicating lights to monitor dryer operation .
NORMAL OPERATION—The green NORMAL OP ERATION indicator will light when the temperature in side the evaporator (chiller) is normal.
CHECK OPERATING CONDITIONS —The red CHECK OPERATING CONDITIONS indicator will light when the temperature inside the evaporator is too high.
SERVICE DUE—The yellow SERVICE DUE indica tor will light under two conditions: as a reminder to per form routine maintenance after 4,500 hours of dryer service (approximately six months) and when a tem perature sensor probe fails.
SYSTEM ALARM—The red SYSTEM ALARM indi cator signals air system or dryer operating conditions that may affect dew point performance or cause damage to the dryer.
Temperature SCAN/SEEK push button
The SCAN/SEEK push button on the System Operation Monitor provides a readout on the alphanumeric display of the following temperatures:
-
-
-
-
-
-
-
-
• inlet air
System Operation Monitor
Figure 4.
1-4 DXR Series Dryers (Bulletin 553)
INDICATING
LIGHT
NORMAL OPERATION
CHECK OPERATING CONDITIONS
SERVICE DUE
SYSTEM ALARM
SYSTEM OPERATION MONITOR INDICATING LIGHTS
INDICATES ACTION REQUIRED NOTES
The temperature inside the evaporator (chiller) is normal.
The temperature inside the evaporator (chiller) is too high.
1. 4,500 hours of dryer service (approximately six months) has passed; routine maintenance should be performed.
2. A temperature sensor probe is sensing temperature outside of normal range or probe has failed. The probe may sense temperatures outside of normal range for up to two minutes after startup or in extreme temperature conditions. (The alphanumeric display will read T1, T2, T3, T4 or T5 MALFUNCTION. T1 = inlet air, T2 = refrigerant suction, T3 = refrigerant discharge, T4 = ambient air, T5 = evaporator.)
1. Inlet air temperature is too high.
2. Refrigerant suction temperature is too low.
3. Ambient air temperature is too low.
4. Ambient air temperature is too high.
Table 3
This indicator should light within 30 minutes of start-up, after the refrigeration system has stabilized. It should remain on when the dryer is operating.
It is normal for this light to be on when the dryer is first turned on and remain on until dryer has reached normal operating temperatures (about 30 minutes).
If the CHECK OPERATING CONDITIONS indicator turns on during normal operation, turn the dryer off to avoid compressor damage. Have a refrigeration mechanic identify and correct the malfunction. If the dryer is under warranty, call your local distributor for authorization before servicing
1. See maintenance section in this manual for further instructions.
2. Check sensor probe. Replace if necessary.
Determine which temperature(s) is out of range. See Table 5 and the Field Service Guide in this manual for possible causes/remedies
Indicator will go off if the CHECK OPERATING CONDITIONS indicator comes on or when a temperature sensor probe has failed.
Indicator will remain illuminated until problem has been corrected.
See maintenance section in this manual for instructions on resetting indicator.
Indicator will go off when the dryer is turned off. This will not affect the 4,500 hour routine maintenance indicator.
Indicator will not stop flashing until the problem has been corrected.
refrigerant suction
refrigerant discharge
ambient air
The display can be programmed to automatically scan each temperature for five seconds in sequence or to con tinuously display any selected reading. The correspond ing light on the system schematic will illuminate when the temperature is displayed.
To scan the temperatures (normal mode): press and hold the SCAN/SEEK button for three seconds. Each temperature will then be displayed for five seconds in the following sequence: inlet air, refrigerant suction, re frigerant discharge and ambient air. To stop the scan
-
-
To display any selected temperature (seek/test mode): press the SCAN/SEEK button once. The display
will read the same temperature until the button is pressed again. When in seek mode, it will continue to monitor for abnormal conditions.
-
Critical Air and Refrigerant Temperatures
Table 4 provides the normal range for each displayed temperature when the dryers are operated in accordance with specified conditions. If a temperature reaches the warning set point indicated in the table, the correspond ing light on the system schematic will flash during the 5-second display. If the temperature reaches the alarm set point indicated in the table, the System Alarm indi cator will flash. Refer to the Field Service Guide in this
-
mode push the TIME ADJUST button once.
DXR Series Dryers (Bulletin 553) 1-5
-
manual if any temperature readout falls outside the nor mal range.
Inlet Air Temperature—If the inlet air temperature falls outside the normal range, the dryer may fail to achieve the required dew point. Check the compressor aftercooler and adjust aftercooler operation to ensure specified inlet air temperature to the dryer.
Refrigerant Suction Temperature—If the dryer has been operating for more than 20 minutes and the refrig erant suction light flashes, there may be a malfunction in the refrigeration system. Turn the dryer off and have a refrigeration mechanic identify and correct the mal
­function. If the dryer is under warranty, call your local distributor for authorization before servicing.
Refrigerant Discharge Temperature—This tempera ture is used by service personnel to analyze the perform ance of the refrigeration system.
-
able range, the dryer may fail to achieve the required dew point or dryer shutdown may result due to high re
-
frigerant temperature.
Intermediate Air Temperature
This temperature is used by service personnel to analyze the performance of the refrigeration system. Intermedi
­ate air temperature is displayed by putting monitor in Scan mode then pushing and holding down the TIME
-
ADJUST and CLOSED/OPEN buttons simultaneously for three seconds. The intermediate air temperature will be displayed for 5 seconds. The digital display will then return to its last temperature readout.
Intermediate air temperature varies with operating con ditions and ambient air temperature. Table 5 lists ap
-
proximate normal ranges of this temperature at various inlet flows and dew point classes.
-
-
-
Ambient Air Temperature—If the ambient air tem
­perature falls outside the acceptable range, the dryer may fail to achieve the required dew point or dryer shut­down may result due to high refrigerant discharge pres­sure.
Inlet Condensing Water Temperature (Water-cooled models) — If the cooling water falls outside the accept-
AIR AND REFRIGERANT TEMPERATURES
DIGITAL
DISPLAY
Inlet Air Inlet air piping
Refrigerant Suction
Refrigerant Discharge
Ambient Air (Air-Cooled Only)
Inlet Condensing Water (Water-Cooled Only)
Intermediate Air
a
Normal temperature range is indicated by a 3-second red light. The red light flashes when temperatures are outside the normal range. Dew points 50°F or higher may cause the REFRIG. SUCTION signal to flash. See the Field Service Guide if red lights flash.
TEMPERATURE
PROBE
LOCATION
Refrigerant line upstream of compressor
Refrigerant line downstream of compressor
Outside the condenser
Inlet pipe of the condenser
Outside surface of chiller discharge piping
Inlet air temperature varies with changes in aftercooler cooling medium temperature and air compressor unloading. Inlet temperatures higher than 100°F reduce drying capacity.
These refrigerant temperatures vary with the refrigeration load and are controlled by refrigeration valve settings. These readings are used primarily by service personnel to analyze refrigeration system performance.
Ambient air temperatures higher than 100°F will reduce drying capacity.
Cooling water temperatures in excess of 100°F will reduce drying capacity.
Intermediate air temperature varies with inlet air pressure, ambient temperature and airflow. This reading is used primarily by service personnel to analyze refrigeration system performance.
Table 4
COMMENTS
NORMAL
TEMPERATURE
RANGE
40°F – 120°F >115°F >120°F
32°F – 55°F N.A. 25°F
140°F – 240°F N.A. N.A.
35°F – 120°F
35°F – 120°F
Variable;
see Table 5
a
WARNING
SET
POINT
> 115°F/
< 35°F
> 115°F/
< 35°F
N.A. N.A.
ALARM
SET
POINT
> 120°F/
< 35°F
> 120°F/
< 35°F
1-6 DXR Series Dryers (Bulletin 553)
INTERMEDIATE AIR TEMPERATURE
DRYER INLET
AIRFLOW
(% of rated
capacity)
80 - 100 35°F - 45°F 50°F - 60°F
50 - 79 45°F - 55°F 60°F - 70°F 25 - 49 55°F - 65°F 70°F - 80°F 10 - 24 65°F - 75°F 80°F - 90°F
No airflow 75°F - 100°F 90°F - 100°F
a
Based on 90°F - 100°F dryer inlet air temperature and 100°F ambient
air temperature. These ranges are approximate and may vary with changes in inlet air pressure, ambient temperature and inlet airflow.
Table 5
APPROXIMATE NORMAL RANGE
33°F - 39°F
Dew Point
50° - 54°F
Dew Point
a
RS-232 Serial Port
The RS-232 serial communications port allows for mon itoring of current temperature and error flags. Commu nication is via a series of ASCII characters sent every second. The data format is shown below. The baud rate is 4800, 8 bits, no parity.
Message format:
DS version:
:Ixxx,Sxxx,Dxxx,Axxx,Oxxx,Nxxx,Lyy,Syy<cr><lf>
Where:
** Intermediate or Glycol is displayed, based on
version.
The alarm bits are preceded with either:
L = Alarm bits
S = Service Due indication
The HEX characters that follow “L” or “S” convey an eight-bit field which indicates the source of the alarm or service due indicator. A value of all zeros (0x00) indi
-
cates that no alarm or service due condition exists.
Version Program
-
1
-
svc = > 4500 hours operating time
DS inlet
Remote Alarm Contacts (Optional)
Dry (unpowered) contacts including one normally open set and one normally closed set are provided to signal remote indication if the CHECK OPERATING CON
­DITIONS or SYSTEM ALARM indicators are acti­vated. The contacts are 2½ Amps max., unfused and 120/240 VAC max.
• “:” = colon character
• “,” = comma character
• <cr> = carriage return
• <lf> = line feed
xxx = temperature in BCD, leading zeros are sup pressed (replaced with spaces. Out-of-range val ues are displayed as “---”.)
yy = alarm bits in ASCII HEX format
Each numerical temperature value is preceded with a single alphabetic identifier:
I = Inlet air
S = Suction
D = Discharge
W = Water*
A = Ambient*
O = Operation
G = Glycol**
N = Intermediate**
* Water or Ambient is displayed, based on ver
sion.
AUTOMATIC DRAIN VALVES
All dryers are equipped with an electronic drain valve that automatically discharges condensate from the dryer.
Drain valve controls are on the system operation moni­tor. The ADV controls allow the period of drain open-
-
-
-
ing to be set from 1 second to 10 seconds and the drain closed (cycle) time to be set from 0.5 minutes to 10 minutes. A test push button helps to check ADV opera tion. When the button is pushed, the drain port clicks open with a clearly audible sound.
To set the drain closed (cycle) time:
The monitor must be in the Scan mode. Press the CLOSED/OPEN button once. The display will show the current setting for the ADV closed time.
Press and hold the TIME ADJUST button. Release the button when the display reads the desired time. The se
-
lected time will be locked into memory.
To set the drain open time:
The monitor must be in the Scan mode. If monitor is not already in the mode for adjusting drain closed time, slowly push the CLOSED/OPEN button once. Allow a few seconds for monitor to set up, then push the button a second time. The display will show the current setting for the ADV open time.
-
DXR Series Dryers (Bulletin 553) 1-7
Press and hold the TIME ADJUST button. Release the button when the display reads the desired time. The se lected time will be locked into memory.
-
ADV Adjustment
To minimize air losses, the ADV timer should be ad justed to open the drain port just long enough to dis charge accumulated condensate. Set the timer so that only air discharges at the end of the open period. Rec ommended initial settings are a 3-second drain opening and a 3-minute drain closed time (cycle). The separator or filter bowl is likely to fill with water if the drain cy cle is too long. If liquid discharges as the port is closing, set the timer for a shorter cycle or a longer opening.
-
-
-
-
START-UP
Follow the procedure below to start your dryer. Failure to follow the prescribed start-up procedure will invali date the warranty. If problems arise during start-up, call your local distributor.
Before you start the dryer:
1. Turn off the dryer ON/OFF switch.
2. Verify the main electrical supply voltage matches the voltage specified on the dryer data plate.
3. Turn on the main electrical power to the dryer.
The crankcase heater is wired to be on when power is supplied to the dryer. The crankcase heater
must be warmed up for 4 hours before starting the dryer. This warm-up heats the compressor oil and boils off liquid refrigerant to prevent damage to the compressor.
During the warm-up period:
Do not turn the dryer switch on.
Compressed air may flow through the dryer dur ing warm-up but drain valves will not be func tional.
After the main electrical power to the dryer has been on for 4 hours, the dryer may be started.
To start the dryer:
-
-
-
a collection tank or an environmentally-approved disposal system.
3. Check ADV timing. See Automatic Drain Valve section for ADV adjustment procedure.
4. Check customer-supplied circuit breakers or fuses. Reset or replace as required.
5. Check proper connection and support of com pressed air lines to the dryer; check bypass valving system, if installed.
6. Ensure adequate ventilation for air-cooled dryers.
7. For water-cooled models, verify the water supply is connected to the water regulating valve on the con denser. Confirm that the cooling water supply meets the required flow and temperature (see Table
1).
8. Confirm that the inlet air temperature, pressure and airflow to the dryer meet the specified requirements (see Tables 8 and 9).
9. After 30 minutes of operation, check the CHECK OPERATING CONDITIONS indicator. If this in­dicator is lit, turn the dryer off and call your local distributor.
10. If the CHECK OPERATING CONDITIONS indi­cator has turned off after 30 minutes of operation, check the following temperatures on the System Operation Monitor:
• Refrigerant discharge (head) temperature should be within the range of 140°F to 220°F.
Refrigerant suction temperature should be within the range of 32°F to 55°F.
If either temperature is out of range, see the Field Service Guide for correction.
The dryer is designed to run continuously. Let the dryer run even when the demand for compressed air is inter rupted; the dryer will not freeze up. If the supply power has been turned off for more than four hours, supply power to the dryer; warm up the crankcase heater (if applicable) for 4 hours before starting the dryer to vaporize any accumu lated liquid refrigerant from the compressor oil.
-
-
-
-
1. Turn the power switch to ON. The refrigerant com pressor will turn on. The monitor will turn on and the CHECK OPERATING CONDITIONS indica tor may turn on. If the dryer does not start in this way, call your local distributor.
2. Confirm that condensate is discharging from the automatic drain valves and that the condensate lines from the automatic drain valve discharge into
1-8 DXR Series Dryers (Bulletin 553)
-
SHUTDOWN
­When the dryer must be shut down for maintenance or
other reasons, use the following procedures.
If electrical repairs must be made:
1. Turn off the power switch.
2. Disconnect the main power supply.
3. Lock out and tag the power supply in accordance with OSHA requirements.
Refer to the Instrumentation section and the Field Serv ice Guide for further information.
-
DANGER Portions of the control circuit remain energized when the power switch is in the OFF position. Disconnect supply powerto the dryer before performing maintenance on the electrical system.
If mechanical repairs must be made, vent the internal pressure of the dryer to atmospheric pressure.
Restart the dryer according to the start-up instructions.
MAINTENANCE
DXR Series dryers require little maintenance for satis factory operation. Good performance can be expected if the following routine maintenance steps are taken.
DANGER Dismantling or working on any component of the compressed air system under pressure may cause equipment failure and serious personal injury. Before dismantling any part of the dryer or compressed air system, completely vent the internal pressure to the atmosphere.
General
For continued good performance of your refrigerated dryer, all refrigeration system maintenance should be performed by a competent refrigeration mechanic. Bef ore corrective maintenance is done during the warranty period, call your local distributor and proceed according to instructions. Refer to the warranty for limits of your coverage.
Daily Maintenance
Check the operation of the automatic drain valve at least once during each 8-hour shift. See the Field Service Guide for remedies to drain valve malfunctions. See the Instrumentation section for drain valve adjustment.
Check the following readouts on the system operation monitor.
high evaporator temperature
refrigerant suction temperature
refrigerant discharge temperature
alarm lights
-
-
Weekly Maintenance
Check prefilter (if installed) differential pressure gauge. Replace filter element when pointer reaches red zone of gauge (approx. 7 to 10 psid). Failure to change element at least once a year or when the gauge reaches the red zone will adversely affect dryer performance. See Filter Element Replacement procedure.
Monthly Maintenance
For air-cooled condensers, inspect the condenser coils. Remove dust, dirt or other particles with a soft brush or with compressed air from an OSHA-approved air nozzle that limits its discharge pressure to 30 psig. If the coils are coated with oil, grease or other substances that re duce the cooling efficiency, clean the coil.
Replace the ambient air filter. See Ambient Air Filter Replacement procedure.
-
Service Due Indicator
On dryers equipped with the System Operation Monitor, the yellow SERVICE DUE indicator will light after 4,500 hours (six months) of dryer operation. At this time, complete the following:
• Disassemble and clean automatic drain valve.
• Disassemble and clean separator bowl.
• For air-cooled condensers, inspect the condenser coils; clean if necessary. Lubricate fan motors with 20 wt motor oil (if necessary).
For water-cooled condensers, clean customer­supplied strainer.
To reset the SERVICE DUE INDICATOR:
1. Turn the power switch to the OFF position.
2. Hold down the PUSH TO TEST and CLOSED/OPEN buttons simultaneously.
3. Turn the power switch to the ON position.
4. Wait two seconds. Release the PUSH TO TEST and CLOSED/OPEN buttons. The indicator is now reset.
Returns to Manufacturer
If the dryer or a component of the dryer must be re turned to the manufacturer, first call your local distribu tor for a return authorization number and shipping address. Your distributor will inform you whether the dryer or only a component must be returned. Mark the package with the return authorization number and ship freight prepaid as directed by your local distributor.
-
-
DXR Series Dryers (Bulletin 553) 1-9
Ambient Air Filter Replacement
For units equipped with the optional ambient air filter (designated by the suffix F in the model number), in spect the filter element. If necessary, replace the ele ment by lifting it out and slipping in a replacement. See the replacement parts lists for replacement element model numbers.
-
-
Automatic Drain Valve Disassembly and Servicing
All DXR Series dryers have a timer-controlled auto matic drain valve.The valve body is mounted on the frame bottom; a hose connects the valve body to the separator.
CAUTION Do not disassemble drain valve timer or attempt to repair electrical parts. Replace timer if defective.
The drain valves discharge condensate through a full-port drain opening.
The valve body may need to be cleaned under condi­tions of gross particulate contamination. To disassemble the drain valve body for cleaning or other maintenance (see Figure 6):
1. Turn power switch off.
2. Disconnect main power supply to dryer.
3. Lock out and tag power supply in accordance with
OSHA requirements.
-
Once the drain valve is disassembled, the following maintenance can be performed.
1. Inspect diaphragm; clean or replace as required.
2. Remove debris from valve body.
3. Wipe solenoid core components with a clean cloth or blow out debris with compressed air from an OSHA-approved air nozzle that limits its discharge pressure to 30 psig.
4. Check that small port in diaphragm assembly is clear and solenoid coil moves freely in housing. Vi ton diaphragm seals are compatible with commonly used synthetic lubricants.
5. If timer is attached to valve body, check electrical continuity across timer assembly.
To reassemble the drain valve, reverse the sequence of the preceding steps. After the drain valve is reassem bled, connect the main power supply to the dryer. When the dryer is returned to service, check the drain valve for air or condensate leaks; tighten connections as required to correct leaks. Check the drain cycle; adjust the timer according to the procedure in the Automatic Drain Valve Adjustment section.
-
Prefilter Element Replacement
On models equipped with the cold coalescing option (C option), the filter element must be replaced at least once a year or when the differential pressure gauge on top of the filter is in the red zone.
To replacing the coalescing prefilter element:
-
WARNING If power supply is not disconnected before disassembly, serious personal injury and valve damage may result.
4. Remove hoses that connect the drain valve to the
separator.
5. Remove screw and washer from front of the drain
valve.
6. Remove the power supply connector and gasket
(with timer assembly if attached) from the solenoid coil housing. Do not damage or lose the gasket.
7. Remove 13mm nut and spring washer from top of
solenoid coil housing.
8. Lift solenoid coil housing off solenoid core in valve
body.
9. Unscrew solenoid core from valve body.
1-10 DXR Series Dryers (Bulletin 553)
Vent internal pressure to atmospheric pressure before performing anymaintenance.
1. Vent the internal pressure to the atmosphere. Refer to the shutdown instructions on page 8.
2. Disconnect drain lines at manual and automatic drain valves (if installed).
A “hissing” sound while the bowl is being removed indicates the filter has not been properly depressurized. DO NOT continue to remove the bowl until the filter has been completely vented to atmospheric pressure.
Filter bowls may be heavy. Caution should be taken when removing the bowl.
DANGER
DANGER
CAUTION
Automatic Drain Valve Components
Figure 6
3. Remove the bottom bowl by unscrewing it from the head. A strap wrench may be needed.
4. Remove the element from the filter head with a brisk downward pull, or by working the element back and forth until it snaps free. Discard the ele
­ment in accordance with applicable regulations. Used elements typically hold contaminants, such as compressor lubricants and particulate matter.
Note: The element may be unsnapped by DPin normal operation. This will not affect filtration, as the O-ring on the element maintains a positive seal.
5. Clean accumulated debris from the bowl with soap and water, and dry thoroughly.
CAUTION Lubricate the O-ring with a petroleum-based lubricant compatible with your application.
6. Lightly lubricate the new element O-ring before in
stalling the new element.
7. Insert new element, snapping it into place with a
firm push up into the head. The element will hang from the head until the bowl is installed.
CAUTION Lubricate the O-ring with a petroleum-based lubricant compatible with your application.
8. Lightly lubricate the filter bowl O-ring.
-
Side view of coalescing filter
DXR Series Dryers (Bulletin 553) 1-11
Figure 7
CAUTION Do not use a pipe wrench to tighten the filter bowl to the head.
9. Reattach bowl to head and hand tighten. As the
bowl is threaded onto the head, supports in the bot tom of the bowl ensure a proper seal between the element and the filter head.
10. Reattach drain lines (if applicable).
11. Record the date of the element change in a record book or on the provided “Maintenance Reminder” label. The maintenance reminder label with the updated information should be applied over
MAINTENANCE REMINDER
Date Element Changed: Changed By: Next Scheduled Change:
Additional elements available from your local Ingersoll-Rand Compressed Air System supplier
Telephone:
Fax:
the previous label each time the element is replaced.
Restart the dryer according to the Start-up instructions on page 8.
FIELD SERVICE GUIDE
Problems most frequently encountered with refrigerated dryers are water downstream of the dryer and excessive pressure drop. Most causes can be identified and reme­died by following this guide.
DANGER Closed refrigeration systems are potentially dangerous. Work on the refrigeration system must be done only by a competent refrigeration mechanic.
the dryer. While the dryer is operating, the suction pres
­sure/temperature may fluctuate slowly with changes in the refrigeration load. To determine the suction pres
­sure/temperature, a refrigeration mechanic should attach a set of gauges to the unit. Gauge readings should be as follows:
-
SUCTION PRESSURE/TEMPERATURE
REFRIGERANT
R-22 58 psig/33°F 68 psig/40°F
Do not adjust refrigerant valves without factory authori
Table 6
WITHOUT AIRFLOW
WITH
AIRFLOW
­zation. Adjustments must be made only with no airflow into the dryer.
REFRIGERANT PRESSURE SWITCH SETTINGS
Pressure Switch Setting
Model
DXR425 DXR600 DXR800
DXR1000
Refrigerant Compressor Control
Pressure Switch Setting
Sensor Location Cut out Cut In
Compressor
Discharge
Compressor
Suction
Table 7
Fan Cycle Control
R-22
On Off
275 195
405 280
40 60
Do not release fluorocarbon refrigerants indoors; do not discharge liquid refrigerants into floor drains. Refrigerant vapors may accumulate in low places. Inhalation of high concentrations may be fatal. All refrigerants must be recovered per EPA requirements.
Do not smoke while working on the refrigeration system or when a refrigerant leak is suspected. Burning materials may decompose refrigerants, forming toxic gas or acids that may cause serious injury and property damage.
The refrigerant valves are adjusted at the factory with the refrigerant system operating and no airflow through
1-12 DXR Series Dryers (Bulletin 553)

FIELD SERVICE GUIDE

PROBLEM SYMPTOM(S) POSSIBLE CAUSE REMEDY
No discharge from auto matic drain valves.
Inlet air temperature is outside normal range or reaches alarm set point.
Liquid water entering dryer.
Excessive airflow (may also cause high pres sure drop).
Drain valve failure or accumulation
­of dirt in valve.
Dismantle drain valve; clean, repair or re place. See Maintenance section.
Aftercooler malfunction. Check aftercooler discharge temperature.
Reduce temperature to 120°F max.; reduce airflow if temperature is above 100°F.
Aftercooler drain valve malfunction. Dismantle aftercooler drain valve; clean, re
pair or replace.
Dryer improperly sized. Check airflow and dryer capacity (see Table
-
8). Reduce airflow or resize and replace dryer.
1. Condenser fouled or clogged. 1. Clean condenser coils (see Mainte
nance, Monthly).
2. Fan motor stopped. 2. Repair or replace fan motor.
3. Inlet air temperature too high. 3. Check aftercooler discharge temperature.
Reduce temperature to 120°F max.; reduce
Refrigerant compressor cut out by high refrigerant discharge pressure control.
4. Air in refrigeration system. 4. Have refrigeration mechanic locate and
airflow if temperature is higher than 100°F (see Airflow section).
repair leak. Recharge. Refer to data plate for refrigerant type and quantity.
5. Ambient air temperature too high
5. Vent compressor room to outside.
for air-cooled compressor.
6. Aftercooler coolant air blowing
6. Baffle or vent to outside air.
on air-cooled condenser.
1. Inadequate ventilation of air­cooled compressor.
1. Ensure adequate ventilation of the con­densing unit (see Clearance). Motor will re­start automatically when compressor is
cool. Water downstream of dryer.
Compressor cuts out on internal overload.
2. Insufficient cooling water for water-cooled compressor.
2. Ensure adequate cooling water (see Ta-
ble 1). Motor will re- start automatically
when compressor is cool.
3. Leak in refrigeration system. 3. Locate leak. Repair and recharge. Motor will restart automatically when compressor is cool.
4. Incorrect adjustment of refrigera
-
4. Call your local distributor.
tion control valves.
Compressor windings read open or shorted.
Compressor burned out. Have refrigeration mechanic check and re
place.
1. Leak in refrigeration system. 1. Locate leak; repair and recharge.
2. Improper adjustment of HGBV. 2. Remove cap from HGBV and screw out
HIGH EVAP light on or Dew point indicator in red zone
3. Air or noncondensables in refrig
eration system. Possible leak in chiller.
HGBV ½-turn with an allen wrench to lower suction temperature to the level listed in the Refrigerant Flow section.
-
3. Locate leak; repair and recharge. If chiller must be replaced, consult your local dis tributor.
1. Improper adjustment of HGBV. 1. Remove cap from HGBV and screw out HGBV ½-turn with an allen wrench to lower suction temperature to the level listed in the Refrigerant Flow section.
Suction temperature higher than 65°F.
2. Inlet air temperature higher than
130°F.
2. Reduce aftercooler discharge tempera ture to design conditions (120°F max.).
3. Excessive airflow 3. Check airflow and system capacity. Re duce airflow or resize and replace system.
4. Leak in refrigeration system. 4. Locate leak; repair and recharge.
Refrigerant discharge
Low ambient temperature. Consult your local distributor. temperature lower than 140°F.
-
-
-
-
-
-
-
DXR Series Dryers (Bulletin 553) 1-13
Loading...
+ 33 hidden pages