All-in-one touchscreen
interface and logic controller
FT1A Touch
The FT1A SmartAXIS Touch combines operator interface
and control in a single compact package, all programmable
with IDEC’s PC-based software. The FT1A Touch is
available in 12 I/O and 14 I/O configurations with analog I/O
expansion capability suitable for advanced analog
monitoring and control.
KEY F E AT U R E S
• 3.8” HMI+PLC
• Models with 12 or 14 I/O
• Embedded RJ45 Ethernet Port
• Modbus TCP or RTU
• Built-in 2 analog inputs
• Built-in 2 analog outputs
• Optional Analog Cartridges
• PID Controls
• USB Maintenance Port
• Seamless interface with other PLCs
• Class 1 Div. 2 Hazardous Locations
• -20 to 55 degree C operating temp.
• IP66f, Nema 4X (indoor), 13
General Specifications
Part No.FT1A-*12RA-*FT1A-*14KA-* / FT1A-*14SA-*
OutputRelay outputTransistor output
Rated Power Voltage/
Power Supply Isolation
Allowable Voltage Range20.4 to 28.8V DC (including ripple)
Power Consumption9.2 W maximum11W maximum
Allowable Momentary
Power Interruption
Dielectric Strength
EMC ImmunityIEC/EN 61131-2:2007 compliant
Inrush Current50A maximum (5ms maximum)
Operating TemperatureColor display: –20 to +55°C, Monochrome display: 0 to +55°C (Note 1) (Note 2)
Storage Temperature–20 to +60°C (no freezing)
Relative Humidity10 to 95% RH (no condensation)
Pollution Degree2 (IEC 60664-1)
Corrosion ImmunityAtmosphere free from corrosive gases
Degree of ProtectionIP66F TYPE 4X TYPE 13 (Panel front) (Note 3), IP20 (Rear)
GroundFunctional grounding
Protective grounding
conductor
Vibration Resistance
Shock Resistance147 m/s
Mounting StructurePanel mount
Weight (approx.)300g250g
Note 1: FT1A-*12RA-* hardware version V130 (indicated on hardware) and earlier is UL, c-UL listed at 50°C (maximum operating temperature).
Note 2: See SmartAXIS Touch User’s Manual FT9Y-B1390(2) for I/O derating.
Note 3: Operation not guaranteed when used with certain types of oils.
24V DC/Not isolated
10 ms maximum
Between power terminal and FE terminal: 500V AC, 5 mA, 1 minute
Between power terminal and output terminal: 2,300V AC, 5 mA, 1 minute
UL1007 AWG16
2
5 to 8.4 Hz half amplitude 3.5 mm, 8.4 to 150 Hz, acceleration 9.8 m/s
2 hours per axis on each of three mutually perpendicular axis (IEC 61131-2)
2
, 11 ms, X, Y, Z directions 3 times (IEC 61131-2)
(1G),
Between power terminal and FE terminal: 500V AC, 5 mA, 1 minute
Between power terminal and output terminal: 500V AC, 5 mA, 1 minute
Function Specifications
Part NumberFT1A-*12RA-*FT1A-*14KA-*FT1A-*14SA-*
Control SystemStored program system
Instruction
Words
Program CapacityProgram size: 47.4 kB, Configuration memory capacity: 5 MB
Processing
Time
Ladder Program
FB37 types
Program CapacityProgram size: 38kB, Configuration memory capacity: 5MB
No. of FB
FBD
Processing
Time
User Program StorageFlash ROM (100,000 times)
I/O Points
Analog Input
Analog Output—2 (4 max. can be added with analog cartridge)
Internal Relays1,024
Shift Registers128
Data Registers2000
Special Data Registers200
Counters200
Timer (1ms, 10 ms, 100 ms, 1s)200
ClockPrecision: ±30 seconds/month (25°C, typical)
Backup DataInternal relays, shift registers, counters, data registers, clock data
Backup DurationApproximately 30 days (typical) at 25°C after backup battery is fully charged
BatteryLithium secondary battery
Charging TimeApproximately 15 hours required to charge from 0 to 90%
RAM Backup
ReplaceabilityNot possible
Self-Diagnostic Functions
Input FilterNo filter, 3 to 15 ms (selectable in increments of 1 ms)
Catch Input/Interrupt Input4/4
Maximum Counting
Frequency and Points
Counting Range0 to 4,294,967,295 (32 bits)
Counter
High-speed
Operation ModeRotary encoder mode and adding counter mode
Analog Voltage
Inputs
Number of Relay Outputs 10A relay: 4—
Number of Transistor Outputs—4 (sink)4 (source)
Analog Output
USB-mini B (Note 2)
USB-A (Note 2)
RS232C (Note 2)
RS485/422 (Note 2)
Ethernet
Expansion Communication Ports
Memory Cartridge—
SD Memory Card—
Analog Cartridge Interface
Note 1:
Except for timer, counter, input FB, and output FB.
Note 2: Not isolated from internal circuits.
Basic Instructions42 types
Advanced Instructions98 types99 types
Basic Instruction1850μs/1,000 steps
END Processing5 msec minimum
FB (Note 1)1,000
Timer (T)200
Counter (C)200
Basic Instruction4ms/100
END Processing5ms minimum
Inputs
Outputs
Single/two-phase selectable1 (5 kHz, multiple 2/4, single-phase cannot be used)
Single-phase4 (x 10 kHz)
Built-in Points2
Input Range0 to 10V DC 0 to 10V DC (voltage input) /4 to 20 mA (current input)
Drawings, bit button, word button, goto screen button, key button, multi-button, keypad, selector switch, potentiometer, numerical input, character input, pilot lamp, picture
Functions
Note 1: The up-to-date information on the connectable PLC can be obtained from http://www.idec.com/language.
display, message display, message switching display, alarm list display, alarm log display, numerical display, bar chart, line chart, pie chart, meter, calendar, bit write
command, word write command, goto screen command, timer, script command, multi-command, system area, start time, Auto Backlight OFF, O/I Link, user communication,
maintenance communication, DM Link Communication, PLC Link Communication (Note 1), alarm log, data log, operation log, data storage area, preventive maintenance,
recipe, text group, global script, user account, project data transfer using external memory, downloading logged data in external memory, USB auto-run function
Loading...
+ 6 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.