All-in-one touchscreen
interface and logic controller
FT1A Touch
The FT1A SmartAXIS Touch combines operator interface
and control in a single compact package, all programmable
with IDEC’s PC-based software. The FT1A Touch is
available in 12 I/O and 14 I/O configurations with analog I/O
expansion capability suitable for advanced analog
monitoring and control.
KEY F E AT U R E S
• 3.8” HMI+PLC
• Models with 12 or 14 I/O
• Embedded RJ45 Ethernet Port
• Modbus TCP or RTU
• Built-in 2 analog inputs
• Built-in 2 analog outputs
• Optional Analog Cartridges
• PID Controls
• USB Maintenance Port
• Seamless interface with other PLCs
• Class 1 Div. 2 Hazardous Locations
• -20 to 55 degree C operating temp.
• IP66f, Nema 4X (indoor), 13
General Specifications
Part No.FT1A-*12RA-*FT1A-*14KA-* / FT1A-*14SA-*
OutputRelay outputTransistor output
Rated Power Voltage/
Power Supply Isolation
Allowable Voltage Range20.4 to 28.8V DC (including ripple)
Power Consumption9.2 W maximum11W maximum
Allowable Momentary
Power Interruption
Dielectric Strength
EMC ImmunityIEC/EN 61131-2:2007 compliant
Inrush Current50A maximum (5ms maximum)
Operating TemperatureColor display: –20 to +55°C, Monochrome display: 0 to +55°C (Note 1) (Note 2)
Storage Temperature–20 to +60°C (no freezing)
Relative Humidity10 to 95% RH (no condensation)
Pollution Degree2 (IEC 60664-1)
Corrosion ImmunityAtmosphere free from corrosive gases
Degree of ProtectionIP66F TYPE 4X TYPE 13 (Panel front) (Note 3), IP20 (Rear)
GroundFunctional grounding
Protective grounding
conductor
Vibration Resistance
Shock Resistance147 m/s
Mounting StructurePanel mount
Weight (approx.)300g250g
Note 1: FT1A-*12RA-* hardware version V130 (indicated on hardware) and earlier is UL, c-UL listed at 50°C (maximum operating temperature).
Note 2: See SmartAXIS Touch User’s Manual FT9Y-B1390(2) for I/O derating.
Note 3: Operation not guaranteed when used with certain types of oils.
24V DC/Not isolated
10 ms maximum
Between power terminal and FE terminal: 500V AC, 5 mA, 1 minute
Between power terminal and output terminal: 2,300V AC, 5 mA, 1 minute
UL1007 AWG16
2
5 to 8.4 Hz half amplitude 3.5 mm, 8.4 to 150 Hz, acceleration 9.8 m/s
2 hours per axis on each of three mutually perpendicular axis (IEC 61131-2)
2
, 11 ms, X, Y, Z directions 3 times (IEC 61131-2)
(1G),
Between power terminal and FE terminal: 500V AC, 5 mA, 1 minute
Between power terminal and output terminal: 500V AC, 5 mA, 1 minute
Function Specifications
Part NumberFT1A-*12RA-*FT1A-*14KA-*FT1A-*14SA-*
Control SystemStored program system
Instruction
Words
Program CapacityProgram size: 47.4 kB, Configuration memory capacity: 5 MB
Processing
Time
Ladder Program
FB37 types
Program CapacityProgram size: 38kB, Configuration memory capacity: 5MB
No. of FB
FBD
Processing
Time
User Program StorageFlash ROM (100,000 times)
I/O Points
Analog Input
Analog Output—2 (4 max. can be added with analog cartridge)
Internal Relays1,024
Shift Registers128
Data Registers2000
Special Data Registers200
Counters200
Timer (1ms, 10 ms, 100 ms, 1s)200
ClockPrecision: ±30 seconds/month (25°C, typical)
Backup DataInternal relays, shift registers, counters, data registers, clock data
Backup DurationApproximately 30 days (typical) at 25°C after backup battery is fully charged
BatteryLithium secondary battery
Charging TimeApproximately 15 hours required to charge from 0 to 90%
RAM Backup
ReplaceabilityNot possible
Self-Diagnostic Functions
Input FilterNo filter, 3 to 15 ms (selectable in increments of 1 ms)
Catch Input/Interrupt Input4/4
Maximum Counting
Frequency and Points
Counting Range0 to 4,294,967,295 (32 bits)
Counter
High-speed
Operation ModeRotary encoder mode and adding counter mode
Analog Voltage
Inputs
Number of Relay Outputs 10A relay: 4—
Number of Transistor Outputs—4 (sink)4 (source)
Analog Output
USB-mini B (Note 2)
USB-A (Note 2)
RS232C (Note 2)
RS485/422 (Note 2)
Ethernet
Expansion Communication Ports
Memory Cartridge—
SD Memory Card—
Analog Cartridge Interface
Note 1:
Except for timer, counter, input FB, and output FB.
Note 2: Not isolated from internal circuits.
Basic Instructions42 types
Advanced Instructions98 types99 types
Basic Instruction1850μs/1,000 steps
END Processing5 msec minimum
FB (Note 1)1,000
Timer (T)200
Counter (C)200
Basic Instruction4ms/100
END Processing5ms minimum
Inputs
Outputs
Single/two-phase selectable1 (5 kHz, multiple 2/4, single-phase cannot be used)
Single-phase4 (x 10 kHz)
Built-in Points2
Input Range0 to 10V DC 0 to 10V DC (voltage input) /4 to 20 mA (current input)
Drawings, bit button, word button, goto screen button, key button, multi-button, keypad, selector switch, potentiometer, numerical input, character input, pilot lamp, picture
Functions
Note 1: The up-to-date information on the connectable PLC can be obtained from http://www.idec.com/language.
display, message display, message switching display, alarm list display, alarm log display, numerical display, bar chart, line chart, pie chart, meter, calendar, bit write
command, word write command, goto screen command, timer, script command, multi-command, system area, start time, Auto Backlight OFF, O/I Link, user communication,
maintenance communication, DM Link Communication, PLC Link Communication (Note 1), alarm log, data log, operation log, data storage area, preventive maintenance,
recipe, text group, global script, user account, project data transfer using external memory, downloading logged data in external memory, USB auto-run function
Input Specifications
Part Number*12RA-**14KA-**14SA-*
Input Points6
Input TypeSinkSourceSink
Input Voltage Range0 to 28.8V DC
Rated Input Current4.4 mA5.2 mA4.4 mA
Input Impedance5.5 kΩ4.7 kΩ5.5 kΩ
Input Delay Time
Isolation
Input TypeType 1 (IEC 61131-2)
Digital Input
External Load for I/O InterconnectionNot needed
Operating Level
Input Points2
Input TypeVoltage inputVoltage/Current input
Input Range0 to 10.0 VDC0 to 10.0 VDC / 4 to 20 mA
Sampling Duration Time2 ms maximum
Total Input System Transfer Time3 ms + sampling time + scan time
Digital Resolution0 to 1,000 (10 bits)
Input Error
Analog Input
Isolation
When used as digital
input
External Power for Input
OFF ON
ON OFF
Between input terminalsNot isolated
Internal circuitNot isolated
OFF voltage
ON voltage
OFF current
ON current
25°C±3% of full scale
Total±5% of full scale
Between input terminalsNot isolated
Internal circuitNot isolated
Digital I/OType 1 (not conforming to IEC 61131-2 digital I/O type)
Operation Level
Input Voltage Range—
Output Current Capacity—
2.5 μs + soft filter setting
5 μs + soft filter setting
Sink type: 5V DC max.
Source type: 15V DC min.
Sink type: 15V DC min.
Source type: 5V DC max.
Sink type: 0.9 mA max.
Source type: –1.0 mA min.
Sink type: 2.7 mA min.
Source type: –3.0 mA max.
3 ms + sampling time + scan time
(voltage input)
12 ms + sampling time + scan time
(current input)
OFF voltage: 5V maximum
ON voltage: 15V minimum
OFF current: 0.06 mA maximum
ON current: 0.20 mA minimum
Output Specifications
Part Number*12RA-**14KA-**14SA-*
Output Points
Rated Load Voltage24V DC
Input Voltage Range20.4 to 28.8V DC
Maximum Load
Current
Voltage Drop (ON Voltage)1V maximum (voltage between COM and output terminals when output is ON)
Inrush Current1A
Leakage Current0.1 mA maximum
Clamping Voltage39V ± 1V
Maximum Lamp Load8 W maximum
Transistor Output
Inductive LoadL/R = 10 ms (28.8V DC, 1 Hz)
External Current Draw100 mA maximum, 24V DC
Isolation
Output Delay
Electrical Life
Mechanical Life
Common
Dielectric Strength
Relay Output
Output Points
Analog Output Signal TypeVoltage/Current output (Selectable)
Analog Output Range0 to 10V DC / 4 to 20mA
Load Impedance2kΩ min (voltage input) / 500 Ω max (current input)
Applicable Load TypeResistive Load
Maximum Deviation at 25°C±0.3% of full scale
Temperature Coefficient±0.02%/°C of full scale
Repeatability After Stabilization Time±0.4% of full scale
Non-linearity±0.01% of full scale
Output Ripple30mV max. (spike noise not included)
Analog Output
Overshoot0% (Note 2)
Total Error±1.0% of full scale including ripple
Effect of Improper Output ConnectionNo damage
Digital Resolution0 to 1,000 (10 bits)
Output Value of LSB10mV (0-10V) / 16μA (4-20mA)
Monotonicity Yes
Current loop openNot detectable
Note 1: High-speed output terminal (100 kHz pulse output terminal): 5 μs max. Normal output terminal (including 5kHz pulse output terminal): 100 μs max.
Note 2: Overshoot may occur under light load conditions. Overshoot can be suppressed by inserting a damping resistor. Damping resistor value: approx. 150Ω including
the input impedance.
Transistor Sink Output
Transistor Source Output—4
1 point0.3A maximum
1 common1A maximum
—
Between output terminal
and internal circuit
Between output terminalsNot isolated
OFF ON100μS max.
ON OFF200μS max.
Between output terminal
and internal circuit
Between output terminals
(between COMs)
100,000 operations minimum
1,800 operations/h)
20 million operations minimum (no load
18,000 operations/h)
J: –200 to 1000°C
R: 0 to 1760°C
S: 0 to 1760°C
B: 0 to 1820°C
E: –200 to 800°C
T: –200 to 400°C
N: –200 to 1300°C
C: 0 to 2315°C
±0.1% of full scale
Cold junction compensation accuracy ±4.0°C or less
Exceptions
R, S thermocouple error:
±6.0°C (0 to 200 °C range only)
B thermocouple error: Not guaranteed
(0 to 300 °C range only)
K, J, E, T, N thermocouple error:
±0.4% of full scale
(0°C or lower range only)