Revision History
Date Manual No. Description
November, 2008 B-1090(0)
First print
December, 2008 B-1090(1)
Sensor connections for IDEC SmartRelay: FL1E-H12RCA / FL1E-B12RCA / FL1E-H12RCE / FL1E-B12RCE / FL1E-H12SND
February, 2009 B-1090(2)
• Compatibility (FL1C-PM3 memory cartridge in FL1E)
• Compatibility (FL1E-PM4 memory cartri dg e in ol d er IDEC SmartRelay modules)
July, 2009 B-1090(3) Deleting the circuit program and passwor d “Note”
September, 2009 B-1090(4)
• 1. The analog output module (FL 1D-K 2B M 2) stru c ture
• 1. How to identify the IDEC SmartRelay (Analog output module )
• 2.1.2 Setup with different voltage classes
• 2.1.3 Compatibility (F L1D-K2BM2)
• 2.2.3 Mounting the Text Display
• 2.3.4 Connecting outputs, Output Internal Circuit
(FL1D-K2BM2)
• 3.6.5 Password
• 3.6.5 Changing IDEC SmartRelay fr om RUN to STOP
mode from the Text Display
• 4.4.20 Analog amplifier (Analog output )
• 6. Compatibility (FL1C-PM3 memory cartrid ge i n FL1E)
• 6. Compatibility (FL1E-PM4 memory cartrid ge in older
IDEC SmartRelay modules)
• A.1 General technical data (Degree of protection)
• A.11 T echnical data: FL1D-K2BM2
• E: Type Number (FL1D-K2BM 2)
July, 2010 B-1090(5)
• 1. How to identify the IDEC SmartRelay (Base module)
• 4.4.11 Seven-day time switch
• 4.4.12 Twelve-month time switch
• A.4 Technical data: FL1E-H12SND
(Backup of the real-time clock at 25°C, Accuracy of the real-time clock)
• E: Type Number (FL1E-H12SND)
December, 2011 B-1090(6)
• 7. IDEC SmartRelay software
Adding Windows 7 to the supporting OS.
• Deleting the description for LONWORKS.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
IDEC SmartRelay Manual i
Safety guidelines
This manual contains notices you have to observe in order to ensure
your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring to property damage only have no safety alert symbol. The notices shown below are graded according to the degree of danger.
If more than one degree of danger is present, the warning notice representing
the highest degree of danger will be used.
A no
tice warning of injury to persons with a safety alert symbol
may also include a warning relating to property damage.
!
Danger
indicates that death or severe personal injury will result if proper precautions are not taken.
!
Warning
indicates that death or severe personal injury may result if proper precautions are not taken.
!
Caution
with a safety alert symbol indicates that minor personal injury can result if proper precautions are not taken.
Caution
without a safety alert symbol indicates that property damage can result if proper precautions are not taken.
Note
indicates that an unintended result or situation can occur if the cor­responding notice is not taken into account.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
ii IDEC SmartRelay Manual
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning and operation of a device/system may only be performed by qualified personnel. Within the context of the safety notices in this documentation qualified persons are defined as persons who are authorized to commission, ground and label devices, systems and circuits in accordance with established safety practices and standards.
Prescribed Usage
Note the following:
Copyright IDEC
CORPORATION
All rights reserved
The reproduction, distribution or use of this document or its contents
is not permitted without express written authority. Offenders will be liable for damages. All rights reserved, in particular in the event of patents being granted or the registration of a utility model or design.
Disclaim of Liability
We have reviewed the contents of this publication to ensure co
nsiste
ncy with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly an d an y ne cessa ry corrections are included in subsequent editions.
!
Warning
This device and its components may only be used for the applications described in the catalog or the technical description, and only in connection with devices or components from other manufacturers which have been approved or recommended by IDEC. Correct, reliable operation of the product requires proper transport, storage, positioning and assembly as well as careful operation and maintenance.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Preface
IDEC SmartRelay Manual iii
Preface
Dear customer We thank you for purchasing IDEC SmartRelay and
congratulate you on y
our decision. With IDEC SmartRelay you have acquired a logic module that meets the stringent quality requirements of ISO 9001. IDEC SmartRelay can be used in ma
ny fiel
ds of applications. Due to its high functionality and easy operation, IDEC SmartRelay offers you the utmost efficiency for almost any application.
Purpose of this manual
This IDEC SmartRelay manual provides you with information ab
out the cre
ation of circuit programs, about the installation and use of FL1E IDEC SmartRelay base m odules, th e Te xt Display and the IDEC SmartRelay exp ansion mo dules , and about their compatibility with the previous FL1A–FL1D versions (FL1x are the last four characters of the order number of the base modules and differentiate the device series).
IDEC SmartRelay’s place in information technology
The wiring information in your IDEC SmartRelay manual is also found in the
IDEC SmartRe
lay Product Info included with all devices. For further information on programming the IDEC SmartRelay on your PC, refer to the Online Help for WindLGC. WindLGC is the programming software for PCs. It runs
un
der Win
dows
. It helps you to get started with IDEC SmartRelay and to write, test, print out and archive your programs, independent of the IDEC SmartRelay.
Guide
The manual is divided into 8 chapters:
Getting started with IDEC SmartRelay
IDEC SmartRelay installation and wiring
Programming IDEC SmartRelay
IDEC SmartRelay functions
Configuring IDEC SmartRelay
IDEC SmartRelay memory and battery cartridges
IDEC SmartRelay software
Applications
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Preface
iv IDEC SmartRelay Manual
Valid range of this manual
The manual applies to devices of series FL1E.
New features of the FL1E IDEC SmartRelay device series
The Text Display provides an additional display device for me
ssages, a
nd contains four cursor keys and four functions
keys that can be used in the circuit program.
An additional password protection function is available in the
Te
xt Display (version 4 or later) and can only be enabled when the Text Display is used together with IDEC SmartRelay Base modules (version 4 or later).
The new IDEC SmartRelay Battery cartridge and the IDEC Smar
tRel
ay Combined Memory/Battery cartridge provide up to two years of backup time for the real-time clock. The new IDEC SmartRelay Memory cartridge and the Combined Memory/Battery cartridge provide 32 Kbytes memory space.
Additional optional analog inputs and fast digital inputs are available on
some of the F
L1E IDEC SmartRelay base
modules.
FL1E IDEC SmartRelay configuration menus can be d
isp
layed in ten supported languages. You have a configuration choice to specify the language for IDEC SmartRelay menus.
New instruction blocks are available: Pulse Width Modulator (PWM), Ana
lo
g Math, and Analog Math Error Detection.
Message texts can tick on and off the display; can include bar
graphs, can switch between two character sets, and can be displayed on either the IDEC SmartRelay Display, the Text Display, or both. Full editing capabilities are available from WindLGC; editing from the IDEC SmartRelay base module is limited to simple text. See section 2.1.3 for further details.
USB PC cable between a PC and IDEC SmartRelay base mo
dule is ava
ilable as an option.
You can now have up to 200 program blocks in your circuit prog
ram.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Preface
IDEC SmartRelay Manual v
Additional differences compared to previous devices (FL1A to FL1D)
Extended set of reference parameters for function blocks.
Enhancements to up/down counter, Operating hours counter,
Twelve-month time switch and analog watchdog
instruction blocks.
You can find information on compatibility
of IDEC Smart-
Relay FL1
E to previous devices at section 2.1.3.
Additional support
At our Internet address you can quickly and easily find answers to your queries about IDEC SmartRelay.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Preface
vi IDEC SmartRelay Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
IDEC SmartRelay Manual vii
Contents
Preface.....................................................................iii
Contents.................................................................vii
1 Getting started with IDEC SmartRelay...................1
2 IDEC SmartRelay installation and wiring ............17
2.1 Modular IDEC SmartRelay setup...................................................20
2.1.1 Maximum setup................ ............................................... ..............20
2.1.2 Setup with different voltage classes ..............................................22
2.1.3 Compatibility..................................................................................24
2.2 Installing/removing IDEC SmartRelay...........................................25
2.2.1 DIN rail mounting.......................................... ......................... ........26
2.2.2 Wall-mounting................................................................................29
2.2.3 Mounting the Text Display .............................................................30
2.3 Wiring IDEC SmartRelay ................................................................32
2.3.1 Connecting the power supply........................................................33
2.3.2 Connecting the Text Display power supply....................................34
2.3.3 Connecting IDEC SmartRelay inputs.............................................35
2.3.4 Connecting outputs........................................................................44
2.3.5 Connecting the AS interface bus...................................................49
2.4 Putting into operation............................................ ... ......................51
2.4.1 Switching on the IDEC SmartRelay/Power On..............................51
2.4.2 Operating states............................................................................54
3 Programming IDEC SmartRelay ..........................57
3.1 Connectors......................................................................................58
3.2 Blocks and block numbers............................................................60
3.3 From circuit diagram to IDEC SmartRelay program....................63
3.4 The four golden rules for operating IDEC SmartRelay................66
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
viii IDEC SmartRelay Manual
3.5 Overview of IDEC SmartRel ay me nu s .............................. .. ... ... ... .68
3.6 Writing and starting the circuit program......................................69
3.6.1 Selecting programming mode ....................................................... 69
3.6.2 The first circuit program .................................................................70
3.6.3 Circuit program input........................................................... .......... 72
3.6.4 Assigning a circuit program name.................................................77
3.6.5 Password.......................................................................................78
3.6.6 Switching IDEC SmartRelay to RUN mode...................................84
3.6.7 Second circuit program .................................................................86
3.6.8 Deleting a block................................................................... ... ....... 92
3.6.9 Deleting block groups................ ....................................................93
3.6.10 Correcting programming errors.....................................................94
3.6.11 Selecting analog output values for RUN/STOP transition............. 94
3.6.12 Defining the type of analog outputs............................................... 95
3.6.13 Deleting the circuit program and password...................................96
3.6.14 Summertime/wintertime conversion..............................................97
3.6.15 Synchronization...........................................................................101
3.7 Memory space and circuit program size....................................103
4 IDEC SmartRelay functions ................................109
4.1 Constants and conn ec tors - Co..................... ... ... .. ......................110
4.2 Basic functions list - GF............................................................... 114
4.2.1 AND..............................................................................................115
4.2.2 AND with Edge Detection.............................................................116
4.2.3 NAND (not AND).........................................................................116
4.2.4 NAND with Edge Detection..........................................................117
4.2.5 OR................................................................................................118
4.2.6 NOR (not OR)..............................................................................119
4.2.7 XOR (exclusive OR).................................................................... 120
4.2.8 NOT (Negation, Inverter).............................................................120
4.3 Special functions.......................................................................... 121
4.3.1 Designation of the inputs.............................................................121
4.3.2 Time response ............................................................................. 122
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
IDEC SmartRelay Manual ix
4.3.3 Backup of the real-time clock .......................................... ... .........123
4.3.4 Retentivity....................................................................................123
4.3.5 Parameter protection.......................................................... .........124
4.3.6 Calculating the gain and offset of analog values............. ... .........125
4.4 Special functions list - SF ............................................................128
4.4.1 On-delay......................................................................................131
4.4.2 Off-delay......................................................................................135
4.4.3 On-/Off-delay...............................................................................136
4.4.4 Retentive on-delay.......................................................................138
4.4.5 Interval time-delay relay/Pulse output .........................................139
4.4.6 Edge-triggered interval time-delay rela y......................................140
4.4.7 Asynchronous pulse generator........................................ ............142
4.4.8 Random generator.......................................................................144
4.4.9 Stairwell Light Switch...................................................................146
4.4.10 Dual-function switch ....................................................................148
4.4.11 Seven-day time switch....................................... ... .......................150
4.4.12 Twelve-month time switch ...........................................................155
4.4.13 Up/down counter ................................. ......................... ...............161
4.4.14 Operating hours counter..............................................................164
4.4.15 Frequency trigger ........................................................................168
4.4.16 Analog trigger ..............................................................................171
4.4.17 Analog differential trigger.............................................................174
4.4.18 Analog comparator ......................................................................177
4.4.19 Analog watchdog.........................................................................182
4.4.20 Analog amplifier...........................................................................185
4.4.21 Latching relay ...................................... ... ......................... ............190
4.4.22 Current impulse relay .................................................................191
4.4.23 Message texts..............................................................................193
4.4.24 Softkey.........................................................................................205
4.4.25 Shift register.................................................................................208
4.4.26 Analog Multiplexer.......................................................................210
4.4.27 Analog Ramp Control..................................................................212
4.4.28 PI controller .................................................................................216
4.4.29 Pulse Width Modulator (PWM)....................................................222
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
x IDEC SmartRelay Manual
4.4.30 Analog math................................................................................225
4.4.31 Analog math error detection........................................................ 230
5 Configuring IDEC SmartRelay............................233
5.1 Selecting parameter assignment mode...................................... 234
5.1.1 Parameters..................................................................................235
5.1.2 Selecting the parameters.............................................................236
5.1.3 Modifying parameters..................................................................237
5.2 Setting the default values for IDEC SmartRelay........................ 239
5.2.1 Setting the time of day and date (FL1E-H12RC...)...................... 240
5.2.2 Setting the display contrast and backlight choice........................241
5.2.3 Setting the menu language ......................................................... 243
5.2.4 Setting the number of AIs in the base module ............................ 244
5.2.5 Setting the start screen................................................................245
6 IDEC SmartRelay memory
and battery cartridge (card)................................247
6.1 Security function (CopyProtect)..................................................250
6.2 Inserting and removing memory and battery cartridges .......... 252
6.3 Copying data from IDEC SmartRelay
to the memory cartridge............................................................... 254
6.4 Copying data from the memory cartridge
to IDEC SmartRelay....................... ... ......................... ... ... ... .......... 256
7 IDEC SmartRelay software..................................259
7.1 Connecting IDEC SmartR e lay to a PC ........................... ... .. ... ... ..261
8 Applications .........................................................263
8.1 Stairway or corridor lighting........................................................ 265
8.1.1 Requirements for a stairway lighting system....................... ... ..... 265
8.1.2 Previous solution........................................... ... ...........................265
8.1.3 Lighting system with IDEC SmartRelay............................... ... ..... 266
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
IDEC SmartRelay Manual xi
8.1.4 Special features and expansion options......................................268
8.2 Automatic door .............................................................................269
8.2.1 Requirements of an automatic door.............. ......................... ......269
8.2.2 Conventional solution ..................................................................270
8.2.3 Door control system with IDEC SmartRelay................................270
8.2.4 Special features and expansion options......................................273
8.2.5 Extended solution with FL1E-H12RCC .......................................273
8.3 Air-conditioning sys te m....................... ... ......................... ... ... ......276
8.3.1 Requirements for an air-conditioning system ............................. .276
8.3.2 Advantages of using IDEC SmartRelay........................... ............279
8.4 Factory door..................................................................................281
8.4.1 Requirements for a gate control system......................................281
8.4.2 Previous solution.........................................................................282
8.4.3 Extended IDEC SmartRelay solution...........................................284
8.5 Centralized control and monitoring of several factory doors. .. 285
8.5.1 Requirements for a gate control system......................................286
8.6 Luminous rows ............................. ... .. .......................... .. ...............289
8.6.1 Requirements for a lighting system.............................................289
8.6.2 Previous solution.........................................................................290
8.6.3 Luminous row control system with FL1E-H12RCC......................291
8.7 Service water pump............. ... ... ... ......................... ... ... .................293
8.7.1 Requirements for a control system of a service water pump.......294
8.7.2 Previous solution.........................................................................294
8.7.3 Service water pump system with FL1E-H12RCC........................295
8.7.4 Special features and expansions.................................................296
A Technical data......................................................297
A.1 General technical da ta.............................................. ... .. ...............297
A.2 Technical data: FL1E-H12RCC/FL1E-B1 2RCC .............. ............. 299
A.3 Technical data: FL1B-M08C2R2 ..................................................302
A.4 Technical data: FL1E-H12SND.....................................................305
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
xii IDEC SmartRelay Manual
A.5 Technical data: FL1B-M08B1S2 ................................................. 307
A.6 Technical data: FL1E-H12RCA/FL1E-B12RCA........................... 309
A.7 Technical data: FL1B-M08D2R2.................................................. 312
A.8 Technical data: FL1E-H12RCE/
FL1E-B12RCE and FL1B-M08B2R2.............................................314
A.9 Switching capacity and serv ice life of the relay outputs .......... 317
A.10 Technical data: FL1B-J2B2.......................................................... 318
A.11 Technical data: FL1D-K2B2, FL1D-K2BM2.................................319
A.12 Technical data: Text Display .......................................................320
B Determining the cycle time.................................321
C IDEC SmartRelay without display .....................325
D IDEC SmartRelay menu structure ......................329
D.1 IDEC SmartRelay base module ...................................................329
D.2 Text Display................................................................................... 331
E Type Numbers...... ............ ........... ............ ........... ..333
Index......................................................................335
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
IDEC SmartRelay Manual 1
1
Getting started with IDEC SmartRelay
Here’s IDEC SmartRelay
IDEC SmartRelay is a universal logic module made by IDEC that integrate
s:
Controls
Operator and display panel with background lighting
Power supply
Int er fa ce fo r exp a nsion modules
Interface for a memory cartridge, battery cartridge, combined
memory/battery cartridge, IDEC SmartRelay
PC cable or USB PC cable
Int er fa ce fo r an opti onal te xt disp la y (T D) mo d ule
Pre-configured standard functions, for example, on-and off-delays, cur
rent impulse relay and softkey
•Timers
Digital and analog memory markers
Inputs and outputs, according to the device type
What IDEC SmartRelay can do for you
IDEC SmartRelay offers solutions for domestic and installa
tion
engineering applications such as stairway lighting, external lighting, sun blinds, shutters, shop window lighting and more; switch cabinet engineering, as well as for mechanical and apparatus engineerin g such as gate control systems, air-conditioning systems, rand ainwater pumps.
IDEC SmartRelay can also be implemented for special contr
ol syste
ms in conservatories or greenhouses, for control signal processing and, by connecting a communication module such as an AS-i module, for distributed local controlling of machines and processes.
Special versions without operator panel a nd display unit are a
va
ilable for series production applications in small machine,
apparatus, switching cabinet and installation engineering.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Getting started with IDEC SmartRelay
2 IDEC SmartRelay Manual
Which devices are available?
IDEC SmartRelay Base is available in two voltage classes:
Class 1 24 V, i.e.
12 V DC, 24 V DC, 24 V AC
Class 2 > 24 V, i.e. 100...240 V AC/DC IDEC SmartRelay Base is available in two versions:
With display:
8
inputs and 4 outputs
Without display (”
IDEC SmartRelay Pure”): 8 inputs and
4 outputs
Each version is integrated into four subunits, is equipped with an e
xpansion interface and Text Display interface and provides 39 pre-configured standard and special function blocks for the creation of your circuit program.
Which expansion modules are available?
IDEC SmartRelay digital modules are available for
o
peration
with 12 V DC, 24 V AC/DC and 100...240 V AC/
DC, and are equipped with four inputs and four outputs.
IDEC SmartRelay analog modules are available for
o
peration
with 24 V DC and some with 12 V DC, depending on the specific module. Each is equipped with two analog inputs or two analog outputs.
The digital/analog modules are integrated in two or four sub
un
its. Each one is equipped with two expansion
interfaces for connecting additional modules.
Which display modules are available?
IDEC SmartRelay Base with display
Text Display
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Getting started with IDEC SmartRelay
IDEC SmartRelay Manual 3
Features of the Text Display
The Text Display is available with the FL1E series. It provides an additional display that is wider than the Base module. It has four function keys that you can program in your circuit program as inputs. Like the IDEC SmartRelay Base module, it has four cursor keys, an ESC key and an OK key that you can also program in your circuit program and use for navigation on the Text Display.
You can create and download a power-up screen for the Tex
t D
isplay from WindLGC. This screen displays briefly when you initially power on the Text Display. You can also upload the power-up screen from the Text Display to WindLGC.
The menus for the Text Display are shown in Appendix sect
ion D.2. You
configure the settings for the Text Disp
lay independently from the IDEC SmartRelay Base module . The settings can be d
ifferent.
Which communication modules are available?
IDEC SmartRelay communication module (CM) AS
interface, which is described
in more detail in a separate
documentation. The communication module has four virtual inputs and
outputs, and
acts as an interface between an AS­Interface system and an IDEC SmartRelay system. The module enables four data bits to be transferred from the IDEC SmartRelay base module to the AS-Interface system and vice versa.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Getting started with IDEC SmartRelay
4 IDEC SmartRelay Manual
It’s your choice
The various IDEC SmartRelay Base versions, expansion modules, Text Display and communication modules offer you a highly flexible and adaptive system to suit your specific tasks.
The IDEC SmartRelay system offers you many solutions such as
for small domes
tic installations, simple automation tasks, and even complex engineering tasks involving its integration into a bus system (e.g. communication mod ule AS interface).
Note
IDEC SmartRelay base module may only be equipped with expansion modules of the same voltage class. Mechanical encoding pins in the housing prevent you from connecting devices of a different voltage class.
Exception: The left-hand interface of an analog module or communication module is galvanically isolated.
This type of expansion module can therefore be connected to devices of a different voltage class. See also Chapter 2.1.
A Text Display, if used, can be connected only to an FL1E IDEC SmartRelay base module.
Each IDEC SmartRelay base module supports the following connections for the creation of the circuit program, regardless of the number of connected modules:
Inputs 11 to I24
Analog inputs AI1 to AI8
Outputs Q1 to Q16
Analog outputs AQ1 and AQ2
Memory Markers M1 to M27:
- M8: Startup marker
- M25: Backlight flag: IDEC SmartRelay Display
- M26: Backlight flag: Text Display
- M27: Message text character set flag
Analog Memory Markers AM1 to AM6
Shift register bits S1 to S8
4 cursor keys
16 blank outputs X1 to X16
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
I7 I8
Q1 Q2 Q3 Q4
4
L1 N
09
I5 I6I2 I3 I4I1
72
55
53
1 2 1 2 1 2 1 2
6
IDEC SmartRelay Base
(e.g.: FL1E-H12RCC)
Q4
Q1 Q2
L1 N I2 I3 I4I1
36
09
53
4
Q3
RUN/STOP
53
1 2 1 2
1 2 1 2
IDEC SmartRelay
expansion module
(e.g.: FL1B-M08C2R2)
Getting started with IDEC SmartRelay
IDEC SmartRelay Manual 5
The IDEC SmartRelay structure
Power supply Control panel
(not for FL1E­B12...)
Mechanical coding pins
Inputs LCD
(not for FL1E­B12...)
Mechanical coding sockets
Outputs RUN/STOP
indicator
Slide
Module slot with cap
Expansion interface
Text Display cable connector
Version number
(example:
represents Version 1.)
15926103711481213
X 2 3 4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
I7 I8
Q1 Q2 Q3 Q4
4
L+ M
4
6
5
09
I5 I6I2 I3 I4I1
72
55
53
1 2 1 2 1 2 1 2
IDEC SmartRelay Base
(e.g.: FL1E-H12RCE)
Q3 Q4
Q1 Q2
L+ M I2 I3 I4I1
09
4
36
53
53
RUN/STOP
1 2 1 2
1 2 1 2
IDEC SmartRelay
expansion module
(e.g.: FL1B-M08B2R2)
Getting started with IDEC SmartRelay
6 IDEC SmartRelay Manual
Power supply Control panel
(not for FL1E­B12...)
Mechanical coding pins
Inputs LCD
(not for FL1E­B12...)
Mechanical coding sockets
Outputs RUN/STOP
indicator
Slide
Module slot with cap
Expansion interface
Text Display cable connector
Version number
15926103711481213
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Getting started with IDEC SmartRelay
IDEC SmartRelay Manual 7
FL1B-J2B2
I1
PE
INPUT2x(0..10V/0..20mA)
L+ M
09
M1U1 M2U2I2
4
L+ M
RUN/STOP
36 53
53
FL1D-K2B2
Power supply Mechanical
coding pins
PE terminal, for connecting earth and the shielding of analog measuring cables.
Inputs Mechanical
coding sockets
RUN/STOP indicator
Slide Version number
Expansion interface
Power supply Expansion
interface
Slide
Outputs Mechanical
coding pins
PE terminal, for connecting earth
Version number
RUN/STOP indicator
Mechanical coding sockets
191221071113818112912710
13
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Getting started with IDEC SmartRelay
8 IDEC SmartRelay Manual
FL1D-K2BM2
V1+
OUTPUT 2x(0..10V or 0/ 4..20mA)
L+M
36
RU N / ST O P
1
7
9
9
88
M1PEM2V2+
4
L+M
2
11
10
12
53
90
35
13
I2I1
Power supply Expansion
interface
Slide
Outputs Mechanical
coding pins
PE terminal, for connecting earth
Version number
RUN/STOP indicator
Mechanical coding sockets
1811291271013
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Getting started with IDEC SmartRelay
IDEC SmartRelay Manual 9
Text Display
Communication interfacePower supply
The Text Display includes a wid
er
display area than the IDEC SmartRelay Display. It includes four programmable cursor keys, four programmable function keys, and a n ESC and OK key. You use the included Text Display cable to connect from the communication interface on the right side of the Text Display to the corresponding interface on the left side of the IDEC SmartRelay base module.
How to identify the IDEC SmartRelay
The IDEC SmartRelay identifier informs you of various pr
operties
. Base module FL1E- B: Base module without display
H: Base module with display
Number of Inputs and OutputsR: Relay output S: Tr. (source) outputC: With clock N: Without clockD: 24V DC E: 12/24V DC A: 24V AC/DC
B: 100...240V AC C: 100...240V AC/DC
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Getting started with IDEC SmartRelay
10 IDEC SmartRelay Manual
Expansion module Digital module FL1B-M
Number of Inputs and OutputsB1: 24V DC B2: 12/24V DC
C2: 100...240V AC/DC D2: 24V AC/DC
S: Tr. (source) output R: Relay outputTerminal type 2: non-removable terminal
Analog input module FL1B-J Number of Inputs
Resolution B: 10bitTerminal type 2: non-removable terminal
Analog output module FL1D-K Number of Outputs
Resolution B: 10bitblank: 0 ... 10V M: 0 ... 10V, 0/4 ... 20 mATerminal type 2: non-removable terminal
Communication module FL1B- C: Communication module
AS: AS-Interfaceblank: AS-Interface rated voltage (30V DC) C1: 24V AC/
DC
Terminal type 2: non-removable terminal Text Display
FL1E- RD: Remote Display Version type
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Getting started with IDEC SmartRelay
IDEC SmartRelay Manual 11
Symbols
Version with display unit is equipped with 8 inputs and 4 outputs
Version without display unit is equipped with 8 inputs and 4 outputs
The digital module is equipped with 4 digital inputs and 4 digital outputs
The analog module is equipped with 2 analog inputs or two analog outputs, according to the device type
The communication module (CM); for example, AS Interface is equipped with 4 virtual inputs and 4 virtual outputs
The Text Display
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Getting started with IDEC SmartRelay
12 IDEC SmartRelay Manual
Versions
The following IDEC SmartRelay versions are available:
(1): Of those can be used alternatively: 4 analog inputs (0 ... 10V) and 4 fast inputs. (2): AC versions: Two groups consisting of 4 inputs each. Each input within a group
must be connected to the same phase. It is possible to interconnect groups with a different phase.
(3): The digital inputs can be operated with P or N action.
Symbol Designation Supply
volta
ge
I
nputs Outputs Properties
FL1E-H12RCE 12/24 V DC 8 digital
(1)
4 relays (10 A)
FL1E-H12SND 24 V DC 8 digital
(1)
4 solid state 24V / 0.3A
no clock
FL1E-H12RCA
(3)
24 V AC/ 24 V DC
8 digital 4 relays
(10A)
FL1E-H12RCC
(2)
100...240 V AC/DC
8 digital 4 relays
(10A)
FL1E-B12RCE 12/24 V DC 8 digital
(1)
4 relays (10A)
no display unit no keyboard
FL1E-B12RCA
(3)
24 V AC / 24 V DC
8 digital 4 relays
(10A)
no display unit no keyboard
FL1E-B12RCC
(2)
100...240 V AC/DC
8 digital 4 relays
(10A)
no display unit no keyboard
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Getting started with IDEC SmartRelay
IDEC SmartRelay Manual 13
Expansion modules
The following expansion modules can be con nected to IDEC SmartRelay:
(1): Different phases are not allowed within the inputs. (2): 0 ... 10 V, 0 ... 20 mA can be connected optionally. (3): Digital inputs can be operated either with P or with N action. (4): 0 ... 10 V, 0/4 ... 20 mA can be connected optionally.
Communication modules
The following communication modules can be co nnected to IDEC
SmartRelay:
   
Text Display Module
The following Text Display module is available:
Symbol Name Power supply Inputs Outputs
FL1B-M08B2R2 12/24 V DC 4 digital 4 relays (5A) FL1B-M08B1S2 24 V DC
4 digital 4 solid state 24V
/ 0.3A
FL1B-M08D2R2
(3)
24 V AC/DC 4 digital 4 relays (5A)
FL1B-M08C2R2 100...240 V
AC/DC
4 digital
(1)
4 relays (5A)
FL1B-J2B2 12/24 V DC 2 analog
0 ... 10V or 0 ... 20mA
(2)
none
FL1D-K2B2 24 V DC none 2 analog
0 ... 10 V DC
FL1D-K2BM2 24 V DC none 2 analog
0 ... 10 V DC, 0/4 ... 20 mA
(4)
Symbol Name Power supply Inputs Outputs
IDEC Smart­Relay CM AS Interface
30 V DC the
next four inputs after the physical inputs of IDEC SmartRelay (I
n
... I
n+3
)
the next four outputs after the physical outputs of IDEC SmartRelay (Q
n
... Q
n+3
)
Symbol Name Supply voltage Display
Text Display 24 V AC/DC
12 V DC
LCD (128 x 64) 4-row display
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Getting started with IDEC SmartRelay
14 IDEC SmartRelay Manual
Certification and approvals
IDEC SmartRelay is certified to cULus and FM.
cULus Haz. Loc. Underwriters Laboratories Inc. (UL) to
- UL 508 (Industrial Control Equipment)
- CSA C22.2 No. 142 (Process Control Equipment)
- UL 1604 (Hazardous Location)
- CSA–213 (Hazardous Location) APPROVED for use in Class I, Division 2, Group A, B, C, D Tx Class I, Zone 2, Group IIC Tx
FM Approval Factory Mutual Research (FM) to Appro
val Standard Class Number 3611, 3600, 3810 APPROVED for use in Class I, Division 2, Group A, B, C, D Tx Class I, Zone 2, Group IIC Tx For further information, see our Internet address
Note
You will find current approvals on the rating plate of the relevant module.
IDEC SmartRelay is issued with the CE Certificate of Conformity. It is compliant with IEC 60730 -1 and IEC 61131­2 and interference-proof to EN 55011, Limit Class B.
Marine certification has been requested.
ABS (American Bureau of Shipping)
BV (Bureau Veritas)
DNV (Det Norske Veritas)
GL (Germanischer Lloyd)
LRS (Lloyds Register of Shipping)
Class NK (Nippon Kaiji Kyokai) IDEC SmartRelay modules are there
fore suitable for
use in industrial and residential areas. Use in Class I, Division 2, Group A, B, C and D locations or in non- hazardous locations is supported.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Getting started with IDEC SmartRelay
IDEC SmartRelay Manual 15
Marine certification requires the surge protective device what manufactured by DEHN+SÖHNE GmbH+Co., in a case of 12/24V DC or 24V DC power line. The required Type No. and Part No.: BVT AD 24, 918 402. See Note on page 298. For further information, see our Internet address
ID for Australia
Recycling and Disposal
IDEC SmartRelay units can be fully recycled , du e to the ir low-
pollutant equip
ment. Contact a certified electronic waste disposal center for environmentally accept able recycling and disposal of your old devices.
Our products carrying the label shown at the side are compliant with AS/NZS 2064:1997 (Class A) standard.
!
Warning
Risk of death, personal injury or property damage can occur if you do not follow safety precautions for hazardous locations.
In potentially explosive atmospheres, do not disconnect connectors when the system is in RUN. Always switch off the power supply to IDEC SmartRelay and its components before you disconnect any connectors or components.
Substitution of components can impair suitability for Class I, Division 2 locations. Combinations of equipment are subject to investigation by the local authority having jurisdiction at the time of installation.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Getting started with IDEC SmartRelay
16 IDEC SmartRelay Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com