• 3.6.5 Changi ng IDEC SmartRelay from RUN to STOP
mode from the Text Display
• 4.4.20 Analog amplifier (Analog output)
• 6. Compatibility (FL1C-PM3 memory cartridge in FL1E)
• 6. Compatibility (FL1E-PM4 memory cartridge in olde r
IDEC SmartRelay modules)
• A.1 General technical data (Degree of protection)
• A.11 T echnical data: FL1D-K2BM2
• E: Type Number (FL1D-K2BM2)
• 1. How to identify the IDEC SmartRelay
(Base module)
• 4.4.11 Seven-day time switch
• 4.4.12 Twelve-month time switch
• A.4 Technical data: FL1E-H12SND
(Backup of the real-time clock at 25°C,
Accuracy of the real-time clock)
• E: Type Number (FL1E-H12SND)
• 7. IDEC SmartRelay software
Adding Windows 7 to the supporting OS.
• Deleting the description for LONWORKS.
Safety guidelines
!
!
!
This manual contains notices you have to observe in order
to ensure your personal safety, as well as to prevent damage
to property. The notices referring to your personal safety are
highlighted in the manual by a safety alert symbol, notices
referring to property damage only have no safety alert
symbol. The notices shown below are graded according to
the degree of danger.
Danger
indicates that death or severe personal injury will result if proper
precautions are not taken.
Warning
indicates that death or severe personal injury may result if proper
precautions are not taken.
Caution
with a safety alert symbol indicates that minor personal injury can
result if proper precautions are not taken.
Caution
without a safety alert symbol indicates that property damage can
result if proper precautions are not taken.
Note
indicates that an unintended result or situation can occur if the corresponding notice is not taken into account.
If more than one degree of danger is present, the warning
notice representing the highest degree of danger will be used.
A notice warning of injury to persons with a safety alert symbol
may also include a warning relating to property damage.
IDEC SmartRelay Manuali
Qualified Personnel
!
The device/system may only be set up and used in
conjunction with this documentation. Commissioning and
operation of a device/system may only be performed by
qualified personnel. Within the context of the safety notices
in this documentation qualified persons are defined as
persons who are authorized to commission, ground and
label devices, systems and circuits in accordance with
established safety practices and standards.
Prescribed Usage
Note the following:
Warning
This device and its components may only be used for the
applications described in the catalog or the technical description,
and only in connection with devices or components from other
manufacturers which have been approved or recommended by
IDEC.
Correct, reliable operation of the product requires proper transport,
storage, positioning and assembly as well as careful operation and
maintenance.
Copyright IDEC CORPORATION All rights reserved
The reproduction, distribution or use of this document or its
contents is not permitted without express written authority.
Offenders will be liable for damages. All rights reserved, in
particular in the event of patents being granted or the
registration of a utility model or design.
Disclaim of Liability
We have reviewed the contents of this publication to ensure
consistency with the hardware and software described.
Since variance cannot be precluded entirely, we cannot
guarantee full consistency. However, the information in this
publication is reviewed regularly and any necessary
corrections are included in subsequent editions.
iiIDEC SmartRelay Manual
Preface
Dear customer
We thank you for purchasing IDEC SmartRelay and
congratulate you on your decision. With IDEC SmartRelay
you have acquired a logic module that meets the stringent
quality requirements of ISO 9001.
IDEC SmartRelay can be used in many fields of applications.
Due to its high functionality and easy operation, IDEC
SmartRelay offers you the utmost efficiency for almost any
application.
Purpose of this manual
This IDEC SmartRelay manual provides you with information
about the creation of circuit programs, about the installation
and use of FL1E IDEC SmartRelay base modules, the Text
Display and the IDEC SmartRelay expansion modules, and
about their compatibility with the previous FL1A–FL1D
versions (FL1x are the last four characters of the order
number of the base modules and differentiate the device
series).
IDEC SmartRelay’s place in information technology
The wiring information in your IDEC SmartRelay manual is
also found in the IDEC SmartRelay Product Info included
with all devices. For further information on programming the
IDEC SmartRelay on your PC, refer to the Online Help for
WindLGC.
WindLGC is the programming software for PCs. It runs
under Windows
SmartRelay and to write, test, print out and archive your
programs, independent of the IDEC SmartRelay.
Guide
The manual is divided into 8 chapters:
•Getting started with IDEC SmartRelay
•IDEC SmartRelay installation and wiring
•Programming IDEC SmartRelay
•IDEC SmartRelay functions
•Configuring IDEC SmartRelay
•IDEC SmartRelay memory and battery cartridges
•IDEC SmartRelay software
•Applications
. It helps you to get started with IDEC
Preface
IDEC SmartRelay Manualiii
Preface
Valid range of this manual
The manual applies to devices of series FL1E.
New features of the FL1E IDEC SmartRelay device series
•The Text Display provides an additional display device for
messages, and contains four cursor keys and four functions
keys that can be used in the circuit program.
•An additional password protection function is available in
the Text Display (version 4 or later) and can only be enabled
when the Text Display is used together with IDEC
SmartRelay Base modules (version 4 or later).
•The new IDEC SmartRelay Battery cartridge and the
IDEC SmartRelay Combined Memory/Battery cartridge
provide up to two years of backup time for the real-time
clock. The new IDEC SmartRelay Memory cartridge and
the Combined Memory/Battery cartridge provide 32
Kbytes memory space.
•Additional optional analog inputs and fast digital inputs are
available on some of the FL1E IDEC SmartRelay base
modules.
•FL1E IDEC SmartRelay configuration menus can be
displayed in ten supported languages. You have a
configuration choice to specify the language for IDEC
SmartRelay menus.
•New instruction blocks are available: Pulse Width Modulator
(PWM), Analog Math, and Analog Math Error Detection.
•Message texts can tick on and off the display; can include
bar graphs, can switch between two character sets, and
can be displayed on either the IDEC SmartRelay Display,
the Text Display, or both. Full editing capabilities are
available from WindLGC; editing from the IDEC
SmartRelay base module is limited to simple text. See
section
2.1.3 for further details.
•USB PC cable between a PC and IDEC SmartRelay base
module is available as an option.
•You can now have up to 200 program blocks in your
circuit program.
ivIDEC SmartRelay Manual
Additional differences compared to previous devices
(FL1A to FL1D)
•Extended set of reference parameters for function blocks.
•Enhancements to up/down counter, Operating hours
counter, Twelve-month time switch and analog watchdog
instruction blocks.
•You can find information on compatibility of IDEC SmartRelay FL1E to previous devices at section 2.1.3.
Additional support
At our Internet address
http://smart.idec.com/
you can quickly and easily find answers to your queries
about IDEC SmartRelay.
Preface
IDEC SmartRelay Manualv
Preface
viIDEC SmartRelay Manual
Contents
Preface..................................................................... iii
Contents ................................................................. vii
1Getting started with IDEC SmartRelay................... 1
2IDEC SmartRelay installation and wiring ............ 17
IDEC SmartRelay is a universal logic module made by IDEC
that integrates:
•Controls
•Operator and display panel with background lighting
•Power supply
•Interface for expansion modules
•Interface for a memory cartridge, battery cartridge,
combined memory/battery cartridge, IDEC SmartRelay
PC cable or USB PC cable
•Interface for an optional text display (TD) module
•Pre-configured standard functions, for example, on-and
off-delays, current impulse relay and softkey
•Timers
•Digital and analog memory markers
•Inputs and outputs, according to the device type
What IDEC SmartRelay can do for you
IDEC SmartRelay offers solutions for domestic and
installation engineering applications such as stairway
lighting, external lighting, sun blinds, shutters, shop window
lighting and more; switch cabinet engineering, as well as for
mechanical and apparatus engineering such as gate control
systems, air-conditioning systems, rand ainwater pumps.
IDEC SmartRelay can also be implemented for special
control systems in conservatories or greenhouses, for
control signal processing and, by connecting a
communication module such as an AS-i module, for
distributed local controlling of machines and processes.
Special versions without operator panel and display unit are
available for series production applications in small machine,
apparatus, switching cabinet and installation engineering.
1
IDEC SmartRelay Manual1
Getting started with IDEC SmartRelay
Which devices are available?
IDEC SmartRelay Base is available in two voltage classes:
•Class 1 24 V, i.e. 12 V DC, 24 V DC, 24 V AC
•Class 2 > 24 V, i.e. 100...240 V AC/DC
IDEC SmartRelay Base is available in two versions:
•With display: 8 inputs and 4 outputs
•Without display (”IDEC SmartRelay Pure”): 8 inputs and
4 outputs
Each version is integrated into four subunits, is equipped
with an expansion interface and Text Display interface and
provides 39 pre-configured standard and special function
blocks for the creation of your circuit program.
Which expansion modules are available?
•IDEC SmartRelay digital modules are available for
operation with 12 V DC, 24 V AC/DC and 100...240 V AC/
DC, and are equipped with four inputs and four outputs.
•IDEC SmartRelay analog modules are available for
operation with 24 V DC and some with 12 V DC,
depending on the specific module. Each is equipped with
two analog inputs or two analog outputs.
The digital/analog modules are integrated in two or four
subunits. Each one is equipped with two expansion
interfaces for connecting additional modules.
Which display modules are available?
•IDEC SmartRelay Base with display
•Text Display
2IDEC SmartRelay Manual
Getting started with IDEC SmartRelay
Features of the Text Display
The Text Display is available with the FL1E series. It
provides an additional display that is wider than the Base
module. It has four function keys that you can program in
your circuit program as inputs. Like the IDEC SmartRelay
Base module, it has four cursor keys, an ESC key and an OK
key that you can also program in your circuit program and
use for navigation on the Text Display.
You can create and download a power-up screen for the
Text Display from WindLGC. This screen displays briefly
when you initially power on the Text Display. You can also
upload the power-up screen from the Text Display to
WindLGC.
The menus for the Text Display are shown in Appendix
section
D.2. You configure the settings for the Text Display
independently from the IDEC SmartRelay Base module. The
settings can be different.
Which communication modules are available?
•IDEC SmartRelay communication module (CM) AS
interface, which is described in more detail in a separate
documentation.
The communication module has four virtual inputs and
outputs, and acts as an interface between an ASInterface system and an IDEC SmartRelay system. The
module enables four data bits to be transferred from the
IDEC SmartRelay base module to the AS-Interface
system and vice versa.
IDEC SmartRelay Manual3
Getting started with IDEC SmartRelay
It’s your choice
The various IDEC SmartRelay Base versions, expansion
modules, Text Display and communication modules offer
you a highly flexible and adaptive system to suit your specific
tasks.
The IDEC SmartRelay system offers you many solutions
such as for small domestic installations, simple automation
tasks, and even complex engineering tasks involving its
integration into a bus system (e.g. communication module
AS interface).
Note
IDEC SmartRelay base module may only be equipped with
expansion modules of the same voltage class. Mechanical
encoding pins in the housing prevent you from connecting devices
of a different voltage class.
Exception: The left-hand interface of an analog module or
communication module is galvanically isolated.
This type of expansion module can therefore be connected to
devices of a different voltage class. See also Chapter 2.1.
A Text Display, if used, can be connected only to an FL1E IDEC
SmartRelay base module.
Each IDEC SmartRelay base module supports the following
connections for the creation of the circuit program, regardless of the
number of connected modules:
•Inputs 11 to I24
•Analog inputs AI1 to AI8
•Outputs Q1 to Q16
•Analog outputs AQ1 and AQ2
•Memory Markers M1 to M27:
-M8: Startup marker
-M25: Backlight flag: IDEC SmartRelay Display
-M26: Backlight flag: Text Display
-M27: Message text character set flag
•Analog Memory Markers AM1 to AM6
•Shift register bits S1 to S8
•4 cursor keys
•16 blank outputs X1 to X16
4IDEC SmartRelay Manual
I7 I8
Q1Q2Q3Q4
4
L1 N
09
I5 I6I2 I3 I4I1
72
55
53
1 2 1 2 1 2 1 2
6
IDEC SmartRelay Base
(e.g.: FL1E-H12RCC)
Q4
Q1Q2
L1 NI2 I3 I4I1
36
09
53
4
Q3
RUN/STOP
53
1 2 1 2
1 2 1 2
IDEC SmartRelay
expansion module
(e.g.: FL1B-M08C2R2)
Getting started with IDEC SmartRelay
15926103711481213
X 2
3 4
The IDEC SmartRelay structure
Power supplyControl panel
(not for FL1E-
Mechanical coding
pins
B12...)
InputsLCD
(not for FL1E-
Mechanical coding
sockets
B12...)
OutputsRUN/STOP
Slide
indicator
Module slot
with cap
IDEC SmartRelay Manual5
Expansion
interface
Text Display
cable connector
Version number
(example:
represents Version 1.)
I7 I8
Q1Q2Q3Q4
4
L+ M
4
6
5
09
I5 I6I2 I3 I4I1
72
55
53
1 2 1 2 1 2 1 2
IDEC SmartRelay Base
(e.g.: FL1E-H12RCE)
Q3Q4
Q1Q2
L+ MI2 I3 I4I1
09
4
36
53
53
RUN/STOP
1 2 1 2
1 2 1 2
IDEC SmartRelay
expansion module
(e.g.: FL1B-M08B2R2)
Getting started with IDEC SmartRelay
15926103711481213
Power supplyControl panel
(not for FL1E-
Mechanical coding
pins
B12...)
InputsLCD
(not for FL1E-
Mechanical coding
sockets
B12...)
OutputsRUN/STOP
Slide
indicator
Module slot
with cap
6IDEC SmartRelay Manual
Expansion
interface
Text Display
cable connector
Version number
FL1B-J2B2
191221071113818112912710
13
Getting started with IDEC SmartRelay
L+ M
L+ M
4
Power supplyMechanical
coding pins
InputsMechanical
coding sockets
RUN/STOP
SlideVersion number
indicator
Expansion interface
FL1D-K2B2
RUN/STOP
PE
INPUT2x(0..10V/0..20mA)
I1
M1 U1 M2 U2I2
3653
53
PE terminal, for
connecting earth and
the shielding of
analog measuring
cables.
09
Power supplyExpansion
Slide
interface
OutputsMechanical
coding pins
RUN/STOP
indicator
Mechanical
coding sockets
PE terminal, for
connecting earth
Version number
IDEC SmartRelay Manual7
Getting started with IDEC SmartRelay
V1+
OUTPUT 2x(0..10V or 0/4..20mA)
L+M
36
RU N / ST O P
1
7
9
9
88
M1PEM2V2+
4
L+M
2
11
10
12
53
90
35
13
I2I1
1811291271013
FL1D-K2BM2
Power supplyExpansion
Slide
interface
OutputsMechanical
coding pins
RUN/STOP
indicator
Mechanical
coding sockets
PE terminal, for
connecting earth
Version number
8IDEC SmartRelay Manual
Text Display
Communication interface
Power supply
The Text Display includes a wid
IDEC SmartRelay Display. It includes four programmable
cursor keys, four programmable function keys, and an ESC
and OK key. You use the included Text Display cable to
connect from the communication interface on the right side
of the Text Display to the corresponding interface on the left
side of the IDEC SmartRelay base module.
Getting started with IDEC SmartRelay
er display area than the
How to identify the IDEC SmartRelay
The IDEC SmartRelay identifier informs you of various
pr
operties.
Base module
FL1E- B: Base module without display
H: Base module with display
Number of Inputs and Outputs
R: Relay output S: Tr. (source) output
C: With clock N: Without clock
D: 24V DC E: 12/24V DC A: 24V AC/DC
B: 100...240V AC C: 100...240V AC/DC
IDEC SmartRelay Manual9
Getting started with IDEC SmartRelay
Expansion module
Digital module
FL1B-M
Number of Inputs and Outputs
B1: 24V DC B2: 12/24V DC
C2: 100...240V AC/DC D2: 24V AC/DC
S: Tr. (source) output R: Relay output
Terminal type 2: non-removable terminal
Analog input module
FL1B-J Number of Inputs
Resolution B: 10bit
Terminal type 2: non-removable terminal
Analog output module
FL1D-K Number of Outputs
Text Display
FL1E- RD: Remote Display
Version type
10IDEC SmartRelay Manual
Symbols
Getting started with IDEC SmartRelay
Version with display unit is equipped with 8 inputs and 4 outputs
Version without display unit is equipped with 8 inputs and 4 outputs
The digital module is equipped with 4 digital inputs and 4 digital
outputs
The analog module is equipped with 2 analog inputs or two analog
outputs, according to the device type
The communication module (CM); for example, AS Interface is
equipped with 4 virtual inputs and 4 virtual outputs
The Text Display
IDEC SmartRelay Manual11
Getting started with IDEC SmartRelay
Versions
The following IDEC SmartRelay versions are available:
SymbolDesignationSupply
voltage
FL1E-H12RCE12/24 V DC 8 digital
FL1E-H12SND24 V DC8 digital
FL1E-H12RCA
(3)
24 V AC/
24 V DC
FL1E-H12RCC
(2)
100...240 V
AC/DC
FL1E-B12RCE12/24 V DC 8 digital
FL1E-B12RCA
(3)
24 V AC /
24 V DC
FL1E-B12RCC
(2)
100...240 V
AC/DC
(1): Of those can be used alternatively: 4 analog inputs (0 ... 10V) and 4 fast inputs.
(2): AC versions: Two groups consisting of 4 inputs each. Each input within a group
must be connected to the same phase. It is possible to interconnect groups with
a different phase.
(3): The digital inputs can be operated with P or N action.
InputsOutputsProperties
(1)
4 relays
(10 A)
(1)
4 solid state
no clock
24V / 0.3A
8 digital4 relays
(10A)
8 digital4 relays
(10A)
(1)
4 relays
(10A)
8 digital4 relays
(10A)
8 digital4 relays
(10A)
no display unit
no keyboard
no display unit
no keyboard
no display unit
no keyboard
12IDEC SmartRelay Manual
Getting started with IDEC SmartRelay
Expansion modules
The following expansion modules can be connected to IDEC
SmartRelay:
SymbolNamePower supplyInputsOutputs
FL1B-M08B2R212/24 V DC4 digital4 relays (5A)
FL1B-M0
FL1B-M08D2R2
FL1B-M08C2R2100...240 V
FL1B-J2B212/24 V DC2 analog
FL1D-K2B224 V DCnone2 analog
FL1D-K2BM224 V DCnone2 analog
(1): Different phases are not allowed within the inputs.
(2): 0 ... 10 V, 0 ... 20 mA can be connected optionally.
(3): Digital inputs can be operated either with P or with N action.
(4): 0 ... 10 V, 0/4 ... 20 mA can be connected optionally.
8B1S224 V DC4 digital4 solid state 24V
/ 0.3A
(3)
24 V AC/DC4 digital4 relays (5A)
(1)
4 digital
4 relays (5A)
AC/DC
none
0 ... 10V or
0 ... 20mA
(2)
0 ... 10 V DC
0 ... 10 V DC,
0/4 ... 20 mA
(4)
Communication modules
The following communication modules can be connected
o IDEC SmartRelay:
t
SymbolNamePower supplyInputsOutputs
IDEC Smart-
y CM AS
Rela
Interface
30 V DCthe next four inputs
after the physical
inputs of IDEC
SmartRelay
... I
(I
)
n
n+3
the next four
outputs after the
physical outputs of
IDEC SmartRelay
... Q
n+3
)
(Q
n
Text Display Module
The following Text Display module is
SymbolNameSupply voltageDisplay
Text Display24 V AC/DC
12 V DC
IDEC SmartRelay Manual13
available:
128 x 64)
LCD (
4-row display
Getting started with IDEC SmartRelay
Certification and approvals
IDEC SmartRelay is certified to cULus and FM.
•cULus Haz. Loc.
Underwriters Laboratories Inc. (UL) to
-UL 508 (Industrial Control Equipment)
-CSA C22.2 No. 142 (Process Control Equipment)
-UL 1604 (Hazardous Location)
-CSA–213 (Hazardous Location)
APPROVED for use in
Class I, Division 2, Group A, B, C, D Tx
Class I, Zone 2, Group IIC Tx
•FM Approval
Factory Mutual Research (FM) to
Approval Standard Class Number 3611, 3600, 3810
APPROVED for use in
Class I, Division 2, Group A, B, C, D Tx
Class I, Zone 2, Group IIC Tx
For further information, see our Internet address
(URL: http://www.idec.com/usen)
Note
You will find current approvals on the rating plate of the relevant
module.
IDEC SmartRelay is issued with the CE Certificate of
Conformity. It is compliant with IEC 60730-1 and IEC 611312 and interference-proof to EN 55011, Limit Class B.
Marine certification has been requested.
•ABS (American Bureau of Shipping)
•BV (Bureau Veritas)
•DNV (Det Norske Veritas)
•GL (Germanischer Lloyd)
•LRS (Lloyds Register of Shipping)
•Class NK (Nippon Kaiji Kyokai)
IDEC SmartRelay modules are therefore suitable for use in
industrial and residential areas. Use in Class I, Division 2,
Group A, B, C and D locations or in non-hazardous locations
is supported.
14IDEC SmartRelay Manual
Marine certification requires the surge protective device what
✔
!
manufactured by DEHN+SÖHNE GmbH+Co., in a case of
12/24V DC or 24V DC power line. The required Type No. and
Part No.: BVT AD 24, 918 402. See Note on page 298.
For further information, see our Internet address
(URL: http://www.idec.com/usen)
ID for Australia
Our products carrying the label shown at the side are compliant
with AS/NZS 2064:1997 (Class A) standard.
Warning
Risk of death, personal injury or property damage can occur if you
do not follow safety precautions for hazardous locations.
In potentially explosive atmospheres, do not disconnect
connectors when the system is in RUN. Always switch off the
power supply to IDEC SmartRelay and its components before you
disconnect any connectors or components.
Substitution of components can impair suitability for Class I,
Division 2 locations. Combinations of equipment are subject to
investigation by the local authority having jurisdiction at the time of
installation.
Getting started with IDEC SmartRelay
Recycling and Disposal
IDEC SmartRelay units can be fully recycled, due to their
pollutant equipment. Contact a certified electronic waste
lowdisposal center for environmentally acceptable recycling and
disposal of your old devices.
IDEC SmartRelay Manual15
Getting started with IDEC SmartRelay
16IDEC SmartRelay Manual
IDEC SmartRelay installation
and wiring
General guidelines
Please note the following guidelines for installing and wiring
your IDEC SmartRelay:
•Always ensure that the wiring of your IDEC SmartRelay
is compliant with current rules and standards. Also,
conform with all national and regional regulations when
you install and operate the devices. For information on
standards and regulations that apply to your specific
case, contact your local authorities.
•Always switch off power before you wire or install/remove
a module.
•Always use cables with appropriate conductor crosssections for the relevant current. You can wire IDEC
SmartRelay with cable conductor cross-sections from
1.5
mm2 to 2.5 mm2; see Chapter 2.3.
•Do not exceed the screw torque of the terminals. The
maximum torque is: 0.5 Nm, see Chapter 2.3.
•Keep the cabling as short as possible. If longer cables are
necessary, you should use shielded versions. You should
always route your cables in pairs: i.e. one neutral
conductor plus one phase conductor or signal line.
•Always keep separate:
-The AC wiring
-High-voltage DC circuits with high-frequency
switching cycles
-Low-voltage signal wiring
•Ensure that the wires are installed with appropriate strain
relief.
•Provide a suitable lightning surge arrester for cables
installed in hazardous areas.
•Do not connect an external power supply in parallel to the
output load of a DC output. This could develop a reverse
current at the output if you have not installed a diode or
similar barrier device.
•Reliable functioning of the equipment is only ensured with
certified components!
2
Note
IDEC SmartRelay devices may only be installed and wired by
skilled personnel who are familiar with and follow general
engineering rules and relevant regulations and standards.
IDEC SmartRelay Manual17
IDEC SmartRelay installation and wiring
!
What you must note when installing
IDEC SmartRelay is designed for fixed and enclosed
installation in the housing or the control cabinet.
Warning
Death, serious bodily injury or considerable damage to property
can occur.
Modules of an IDEC SmartRelay are open facilities. This means
that you must install IDEC SmartRelay only in a housing or cabinet.
Allow access to the housings or cabinets only with the use of a key
or a tool and only allow access to authorized or approved
personnel.
It is permissible to operate IDEC SmartRelay from the front at any
time.
Safety of electronic control equipment
Introduction
The notes below apply regardless of the type or
manufacturer of the electronic control.
Reliability
Maximum reliability of IDEC SmartRelay devices and
components is achieved by implementing extensive and
cost-effective measures during development and
manufacture.
This includes the following:
•Use of high-quality components
•Worst-case design of all circuits
•Systematic and computer-aided testing of all
components
•Burn-in of all large-scale integrated circuits (e.g.
processors, memory, etc.)
•Measures preventing static charge when handling MOS
ICs
•Visual checks at different stages of manufacture
•Continuous heat-run test at elevated ambient
temperature over a period of several days
•Careful computer-controlled final testing
•Statistical evaluation of all returned systems and
components to enable the immediate initiation of suitable
corrective measures
•Monitoring of major control components, using online
tests (cyclic interrupt for the CPU, etc.)
18IDEC SmartRelay Manual
IDEC SmartRelay installation and wiring
These measures are referred to as basic measures.
Carrying out tests
You must, however, ensure safety in your plant.
Before finally commissioning a system, carry out complete
functional testing as well as all the necessary safety testing.
In testing, also include any predictable faults that can occur.
This means that you will avoid any danger to the plant or to
people during operation.
Risks
In all cases where the occurrence of failures can result in
material damage or injury to persons, special measures
must be taken to enhance the safety of the installation – and
therefore also of the situation. System-specific and special
regulations exist for such applications. They must be
observed on installing the control system (for example, VDE
0116 for burner control systems).
For electronic control equipment with a safety function, the
measures that have to be taken to prevent or rectify faults
are based on the risks involved in the installation. Beyond a
certain degree of hazard the basic measures mentioned
above are not sufficient. Additional measures must be
implemented and approved for the controller.
Important information
The instructions in the operating manual must be followed
exactly. Incorrect handling can render measures intended to
prevent dangerous faults ineffective, or generate additional
sources of danger.
IDEC SmartRelay Manual19
IDEC SmartRelay installation and wiring
FL1B-M08 FL1B-M08FL1B-M08FL1B-M08
FL1B-J2B2
FL1B-J2B2
I9...I12I13...I16I17...I20I21...I24
AI5, AI6
AI7, AI8
I1, I2, I3 ... I6 I7, I8
Q1...Q4Q5...Q8Q13...Q16Q9...Q12
AI3, AI4,AI1, AI2
IDEC SmartRelay
base module
FL1D-K2B2
AQ1, AQ2
FL1D-K2BM2
FL1B-J2B2
AI3, AI4
FL1B-M08 FL1B-M08FL1B-M08FL1B-M08
FL1B-J2B2
FL1B-J2B2
I9...I12I13...I16I17...I20I21...I24
AI5, AI6
AI7, AI8
I1, I2, I3 ... I6 I7, I8
Q1...Q4Q5...Q8Q13...Q16Q9...Q12
AI1, AI2
IDEC SmartRelay
base module
FL1D-K2B2
AQ1, AQ2
FL1D-K2BM2
2.1 Modular IDEC SmartRelay setup
2.1.1Maximum setup
As defined in Chapter 1, IDEC SmartRelay supports a
maximum of 24 digital inputs, 8 analog inputs, 16 digital
outputs, and 2 analog outputs. You can achieve the
maximum setup in different ways as shown below:
Maximum setup of an IDEC SmartRelay with an
in use
(FL1E-H12RCE/FL1E-B12RCE and FL1E-H12SND)
IDEC SmartRelay base module, 4 digital modules, 2 analog
m
odules and 1 analog output module (example)
Maximum setup of an IDEC SmartRelay with analog inputs - two
in use
(FL1E-H12RCE/FL1E-B12RCE and FL1E-H12SND)
IDEC SmartRelay base module, 4 digital modules, 3 analog
m
odules and 1 analog output module (example)
alog inputs - four
Maximum setup of an IDEC SmartRelay without analog inputs
(FL1E-H12RCA/FL1E-B12RCA and FL1E-H12RCC/FL1E-B12RCC)
I1, I2, I3 ... I6 I7, I8
IDEC SmartRelay
base module
20IDEC SmartRelay Manual
IDEC SmartRelay base module, 4 digital modules, 4 analog
m
odules and 1 analog output module (example)
I9...I12I13...I16I17...I20I21...I24
FL1B-M08 FL1B-M08 FL1B-M08 FL1B-M08
Q1...Q4Q5...Q8Q13...Q16Q9...Q12
FL1B-J2B2
AI1, AI2
AI3, AI4
FL1B-J2B2
AI5, AI6
FL1B-J2B2
AI7, AI8
FL1B-J2B2
FL1D-K2B2
FL1D-K2BM2
AQ1, AQ2
IDEC SmartRelay installation and wiring
With any setup, you can plug in an analog output module,
which has the maximum of two analog outputs.
For FL1E-H12RCE/FL1E-B12RCE and FL1E-H12SND
modules, you can configure whether the module uses two or
four of the four possible analog inputs. AI inputs are
numbered consecutively depending on how many you
configure the base module to use. If you configure two
inputs, they are numbered AI1 and AI2, and correspond to
the I7 and I8 input terminals. Subsequent AI expansions
modules would begin numbering at AI3. If you configure four
inputs, they are numbered AI1, AI2, AI3, and AI4, and
correspond to I7, I8, I1, and I2 in that order. Subsequent AI
expansions modules would begin numbering at AI5. See
sections 4.1 and 5.2.4.
High-speed/optimal communication performance
For optimal and high-speed communication performance
between IDEC SmartRelay base module and the various
modules, we recommend that you install the digital modules
first, then the analog modules (examples above). (The
special function PI controller is an exception: the AI used for
the value PV should be on the IDEC SmartRelay base
module or an analog input module adjacent to the IDEC
SmartRelay base module).
We recommend that you position the CM AS Interface on
the far right-hand side. (If the AS Interface voltage fails,
communication between the IDEC SmartRelay system and
expansion modules that are arranged to the right of the IDEC
SmartRelay CM AS Interface expansion module is
interrupted).
The Text Display module is installed separately. You
connect it to the IDEC SmartRelay base module with the
included Text Display cable.
IDEC SmartRelay Manual21
IDEC SmartRelay installation and wiring
2.1.2Setup with different voltage classes
Rules
Digital modules can only be directly connected to devices of
the same voltage class.
You can connect analog and communication modules to
devices of any voltage class.
Overview: Connecting an expansion module to IDEC SmartRelay
base module
In the following tables, “X” means that the connection is
possible; “-” means that the connection is not possible.
When setting up expansion modules of different power voltages, take the following restrictions into consideration.
Note
When you use a 24V DC power supply to supply power to 12/24V
DC power type base module and 24V DC power type expansion
I/O modules, use a 24V DC power supply which starts up within 10
seconds, otherwise the base module does not recognize the
expansion I/O modules. When the power supply voltage varies
while the base module and the expansion I/O modules are
operating, they normally operate within the permissible operating
voltage range.
When using different power supplies, supply power to the base
module and expansion modules at the same time, or supply power
to expansion modules before the base module.When supplying
power to expansion modules after the base module, expansion
modules may not be recognized by the base module.
When using different power supplies, the fast transient/burst
immunity (IEC61000-4-4) will be 1 kV (power supply).
A 100 to 240V AC/DC module cannot be connected to the right side
of a 12/24V DC, 24V DC, or 24V AC/DC module.
For analog input module and AS-Interface communication module,
a module of any voltage can be connected to the left side. To the
right side, however, a 100 to 240V AC/DC module cannot be
connected.
IDEC SmartRelay Manual23
IDEC SmartRelay installation and wiring
2.1.3Compatibility
The Text Display module can only be used with equipment
series FL1E.
You cannot edit message texts from the IDEC SmartRelay
base module that contain any of the following parameters:
•Par
•Time
•Date
•EnTime
•EnDate
You can only edit such message texts from WindLGC.
When using FL1D-K2B2 and FL1D-K2BM2 with equipment
series FL1C or FL1D, the functions are limited to the ones
available on this equipment. You cannot use the module with
equipment series FL1B or earlier.
All other expansion modules are completely compatible with
the basic modules of equipment series FL1B, FL1C, FL1D,
and FL1E.
24IDEC SmartRelay Manual
IDEC SmartRelay installation and wiring
!
2.2 Installing/removing IDEC SmartRelay
Dimensions
The IDEC SmartRelay installation dimensions are compliant
with DIN
IDEC SmartRelay can be snap–mounted to 35 mm DIN rails
to EN
IDEC SmartRelay width:
•Text Display has a width of 128.2 mm, which corresponds
•IDEC SmartRelay base modules have a width of 72 mm,
•IDEC SmartRelay expansion modules have a width of
Note
The figure below shows you an example of the installation and
removal of a FL1E-H12RCC and a digital module. The measures
shown apply to all other IDEC SmartRelay Base versions and
expansion modules
Warning
43880.
50022 or on the wall.
to
8 subunits
which corresponds to 4 subunits
36
mm, which corresponds to 2 or 4 subunits
Always switch off power before you “remove” and “insert” an
expansion module.
IDEC SmartRelay Manual25
IDEC SmartRelay installation and wiring
1
2
3
4
5
6
2.2.1DIN rail mounting
Mounting
How to mount
digital module onto a DIN rail:
IDEC SmartRelay base module:
1. Hook the IDEC SmartRelay base module onto the rail.
2. Push down the lower end to snap it on. The mounting
in
terlock at the rear must engage.
an IDEC SmartRelay base module and a
IDEC SmartRelay digital module:
3. On the right side of the IDEC SmartRelay base module/
IDEC Smar
connector cap.
4. Place the digital module onto the DIN rail on the righth
and side of the IDEC SmartRelay base module.
5. Slide the digital module towards the left
the IDEC SmartRelay base module.
tRelay expansion module, remove the
until it contacts
26IDEC SmartRelay Manual
IDEC SmartRelay installation and wiring
6. Using a screwdriver, push the interlock to the left. In its
end position the slide interlock engages in IDEC
SmartRelay base module.
Repeat steps 3 through 6 to mount further expansion
modules.
Note
The expansion interface on the last expansion module must be
covered.
IDEC SmartRelay Manual27
IDEC SmartRelay installation and wiring
1
2
1
2
3
4
AB
Removal
To remove IDEC SmartRelay:
....... if you have installed only one
module:
A
Part
1. Insert a screwdriver into the eyelet at the bottom of the
slide interlock and move the latch downward.
2. Swing the IDEC SmartRelay base module off the DIN rail.
IDEC SmartRelay base
....... if you have connected at least one expansion
module to IDEC SmartRelay base module:
B
Part
1. Using a screwdriver, push the integrate slide interlock to
the right.
2. Slide the expansion module off towards the right.
3. Insert a screwdriver into the eyelet at the bottom of the
slide
interlock and lever it downward.
4. Swing the expansion module off the profile rail.
Repeat steps 1 to 4 for all other expansion modules.
Note
If you have connected more than one expansion module, it is
advisable to start removal with the last module at the right-hand
side.
Make sure the slide interlock of the module to be installed/removed
is not engaged in the next module.
28IDEC SmartRelay Manual
IDEC SmartRelay installation and wiring
Mounting slides
98 +/– 0.3
1
2
22
+0.2
53.5–0.0
+0.2
35.5–0.0
+0.2
n x 35.5–0.0
2.2.2Wall-mounting
For wall-mounting, first slide the mounting slides on the rear
side of the devices towards the outside. You can now wallmount IDEC SmartRelay by means of two mounting slides
and two
Drilling template for wall-mounting
Before you can wall-mount IDEC SmartRelay, you need to
drill holes
M4 screws (tightening torque 0.8 to 1.2 Nm).
using the template shown below.
All dimensions in mm
Bore hole for
M4 screw, tightening torque 0.8 to 1.2 Nm
1) IDEC SmartRelay base module
2) IDEC SmartRelay expansion modules
IDEC SmartRelay Manual29
IDEC SmartRelay installation and wiring
119.5+0.5mm
78.5+0.5mm
2.2.3Mounting the Text Display
To prepare the mounting surface for the optional Text
Display and mount it, follow these steps:
1. Cut a 119.5 mm x 78.5 mm hole in the mounting surface.
2. Place the included gasket on the frontplate of the Text
Display.
3. Fit the Text Display into the cutout you made in the
mo
unting surface.
4. Attach the mounting brackets (included) to the Text
Display.
5. Tighten the mounting screws on the mounting brackets to
0.
15...0.2 Nm torque to secure the Text Display.
¿
Mounting brackets
¡ Mounting screws
¬ Gasket
Ð Cabinet door or con-
trol panel (Thickness: 1.5 to 4 mm)
You can then use the included cable to connect the Text
Display to the IDEC SmartRelay base module up to a
distance of 2.5 meters. You can extend this distance to up to
ten meters by using a standard Sub-D cable together with
the Text Display cable.
30IDEC SmartRelay Manual
IDEC SmartRelay installation and wiring
Note
The number of supplied mounting screws and brackets on the
FL1E-RD1 text display depends on the version. The version
number of the FL1E-RD1 is found in the lower-right corner on the
back of the module. For identifying the version, see page 5.
For versions 3 and earlier, 2 screws and brackets are provided.
For versions 4 and later, 4 screws and brackets are provided. Listed
by UL type 4x / 12 for a tightening torque of 0.2 Nm.
IDEC SmartRelay Manual31
IDEC SmartRelay installation and wiring
2.3 Wiring IDEC SmartRelay
Wire IDEC SmartRelay using a screwdriver with a 3-mm
blade.
You do not need wire ferrules for the terminals. You can use
conductors with cross-sections of up to the following
thicknesses:
•1 x 2.5 mm
•2 x 1.5 mm2 for each second terminal chamber
Tightening torque: 0.4...0.5 Nm or 3...4 in-lbs.
Recommended ferrules
Ferrules order No.
For 1-cable connection
Cross-section
2
[mm
0.322AI0,5-10WH
0.520AI0,5-10WH
0.7518AI0,75-8GY
1.2518AI1,5-8BK
2.016AI2,5-8BUBT2-9-1
Recommended
crimping tool
AWG
]
2
Phoenix Contact
Ferrule type No.
CRIMPFOX ZA 3
NIC HIFU
Blade Terminals
type No.
BT1.25-10-1
BT1.25-10-1
BT2-9-1
NH1
NH61
NIC HIFU
Insulated Pin Terminals
type No.
TGN-TC-1.25-11T
NH11
NH32
NH65
For 2-cable connection
Cross-section
2
[mm
0.322AI-TWIN2X0,5-8WH
0.520AI-TWIN2X0,5-8WH
0.7518AI-TWIN2X0,75-8GY
1.2518AI-TWIN2X1,5-8BK
Recommended
crimping tool
AWG
]
Phoenix Contact
Ferrule type No.
CRIMPFOX ZA 3
Note
Always cover the terminals after you have completed the
installation. To protect IDEC SmartRelay adequately from
impermissible contact to live parts, comply with local standards.
32IDEC SmartRelay Manual
IDEC SmartRelay installation and wiring
L+
M
ML+I1 I2 I3 I4 I5
IDEC SmartRelay .....
with DC power supply
IDEC SmartRelay .....
with AC power supply
Protection with safety fuse if
required (recommended) for:
FL1E-H12RCE: 0.8 A
FL1E-H12SND: 2.0 A
To suppress surge voltages,
install varistors (MOV) with an
operating voltage at least 20 %
above the rated voltage.
2.3.1Connecting the power supply
IDEC SmartRelays (FL1E-*12RCC, FL1B-M08C2R2) are
suitable for nominal line voltages of 100 V AC/DC and 240 V
AC/DC. IDEC SmartRelays (FL1E-*12RCA, FL1BM08D2R2) are suitable for a supply voltage of 24 V AC/DC.
IDEC SmartRelays (FL1E-H12SND, FL1B-M08B1S2) are
suitable for a supply voltage of 24 V DC. IDEC SmartRelays
(FL1E-*12RCE, FL1B-M08B2R2) are suitable for a supply
voltage of 12 V AC/DC or 24 V AC/DC.
Note the information on connection in the product
infor
mation document shipped with your device and the
technical specifications in Appendix A relating to permissible
voltage tolerances, line frequency and current consumption.
The Text Display must be supplied with a voltage of 12 V DC
or
24 V AC/DC.
Note
A power failure might cause an additional edge triggering signal at
the special functions.
The stored data will be from the last uninterrupted cycle.
Connecting IDEC SmartRelay
To connect IDEC SmartRelay to the power supply:
IDEC SmartRelay Manual33
L1
N
I1 I2 I3 I4L1N
Note
IDEC SmartRelay is a double-insulated switchgear. You do not
need to connect an equipment grounding conductor.
IDEC SmartRelay installation and wiring
Circuit protection with AC voltage
To suppress voltage peaks on the power supply lines, you
can install a metal oxide varistor (MOV). Make sure the
operating voltage of the varistor (MOV) used lies at least
20 % above the rated voltage.
2.3.2Connecting the Text Display power supply
The Text Display must be connected to an external power
supply that supplies a voltage of 12 V DC or 24 V AC/DC. A
power connector is included with the Text Display.
Power supply
Communication interface
The power connection is non-polar. If you connect a DC
p
ower supply to the Text Display, you can connect the
positive supply wire or negative supply wire to either the left
or right side.
Note
IDEC recommends that you protect the Text Display with a 0.5 A
safety fuse on the power supply.
34IDEC SmartRelay Manual
IDEC SmartRelay installation and wiring
2.3.3Connecting IDEC SmartRelay inputs
Requirements
At the inputs you connect sensor elements such as:
momentary pushbuttons, switches, light barriers, daylight
control switches etc.
Signal status 0 < 5 V DC < 5 V DC < 5 V DC < 5 V DC < 5 V DC < 5 V DC
Input current
Signal status 1
Input current
Signal status 0
Input current
Signal status 1
Input current
(1): 1.0 mA (Version 1 to 5 specifications)
(2): 8 V DC (Version 1 to 5 specifications)
(3): 1.0 mA (Version 1 to 4 specifications)
(4): 8 V DC (Version 1 to 4 specifications)
(5): 1.5 mA (Version 1 to 4 specifications)
< 0.85 mA < 0.05 mA < 0.85 mA < 0.05 mA
> 8.5 V DC > 8.5 V DC > 12 V DC > 12 V DC
> 1.5 mA> 0.1 mA> 2 mA> 0.15 mA> 1.5 mA> 2 mA
FL1E-H12RCA/
FL1E-B12RCA
FL1B-
M08D2R2 (AC)
< 5 V AC
< 1.0 mA
> 12 V AC
> 2.5 mA
FL1E-H12RCA/
FL1E-B12RCA
M08D2R2 (DC)
FL1E-H12SNDFL1B-
FL1E-H12RCC/
FL1E-B12RCC
FL1B-
< 5 V DC
< 1.0 mA
> 12 V DC
> 2.5 mA
FL1B-
M08C2R2 (AC)
< 40 V AC
< 0.03 mA
> 79 V AC
> 0.08 mA
M08B2R2
< 0.85 mA
> 8.5 V DC
FL1E-H12RCC/
FL1E-B12RCC
M08C2R2 (AC)
FL1B-
M08B1S2
(1)
< 0.85 mA
(2)
> 12 V DC
FL1B-
< 30 V DC
< 0.03 mA
> 79 V DC
> 0.08 mA
(5)
Note
The digital inputs of FL1E-H12RCC/FL1E-B12RCC are divided into
two groups, each consisting of four inputs. Within the same group,
all inputs must be operated on the same phase. Different phases
are only possible between the groups.
Example: I1 to I4 on phase L1, I5 to I8 on phase L2.
Inputs within the FL1B-M08C2R2 may not be connected to
different phases.
(3)
(4)
IDEC SmartRelay Manual35
IDEC SmartRelay installation and wiring
L1
N
NL1
C
X-capacitor 2.5 kV, 100 nF
Sensor connections
Connecting glow lamps and 2-wire proximity switches
(Bero) to FL1E-H12RCC/FL1E-B12RCC or FL1BM08C2R2 (AC)
The figure below shows how you connect a switch with a
glow lamp
to IDEC SmartRelay. The current that flows
through the glow lamp allows IDEC SmartRelay to detect a
“1” signal even though the switch contact is not closed. If,
however, you use a switch the glow lamp of which is fitted
with a power supply, this response does not occur.
Take into account the quiescent current of any 2-wire
proximity switches used. The level of the quiescent current
of some 2-wire proximity switches is high enough to trigger a
logical ”1” signal at the IDEC SmartRelay input. You should
therefore compare the quiescent current of the proximity
switches with the technical data of inputs in Appendix A.
Remedy
To suppress this response, use an X capacitor rated at
100 nF and 2.5 kV. In a destructive situation, this type of
cap
acitor safely disconnects. You must choose the voltage
level for which the capacitor is rated such that it is not
destroyed in the case of overvoltage!
At 230 V AC, the voltage between N and an input I(n) must
n
ot be greater than 40 V to guarantee a ”0” signal. You can
connect approximately ten glow lamps to the capacitor.
Restrictions
Signal status transitions 0 1 /
After a 0 to 1 or 1 to 0 transition, the signal
1 0:
must remain
constant at the input at least for the duration of one program
cycle, so that IDEC SmartRelay can detect the new signal
status.
The program execution time is determined by the size of the
cir
cuit program. Appendix B contains a benchmark test
routine that you can use to determine the current scan cycle
time.
36IDEC SmartRelay Manual
IDEC SmartRelay installation and wiring
Special features of FL1E-H12RCE/FL1E-B12RCE and FL1E-H12SND
Fast inputs: I3, I4, I5 and I6:
These versions are also equipped with fast inputs (up/down
counters, frequency triggers). The restrictions mentioned
earlier do not apply to these fast inputs.
Note
The fast inputs I3, I4, I5 and I6 are the same as in the previous
versions FL1A to FL1D; therefore, a circuit program that is written
in these versions can be transferred to the new FL1E devices with
the programming software WindLGC, without any changes to these
features. The fast inputs have increased from 2 kHz to 5 kHz with
the FL1E series.
Expansion modules do not have fast inputs.
Analog inputs: I1 and I2, I7 and I8:
The inputs I1, I2, I7 and I8 of IDEC SmartRelay versions
FL1E-H12RCE/FL1E-B12RCE and FL1E-H12SND can be
used as either digital inputs or analog inputs. The input mode
is defined in the IDEC SmartRelay circuit program.
The inputs I1, I2, I7 and I8 provide digital inputs, and the
inputs AI3, AI4, AI1 and AI2 provide analog inputs, as
described in Chapter 4.1. AI3 corresponds to the input
terminal I1; AI4 corresponds to I2; AI1 corresponds to I7; AI2
corresponds to I8. The use of AI3 and AI4 is optional. You
configure your IDEC SmartRelay to use either two or four
analog inputs as described in section 5.2.4.
When using inputs I1, I2, I7 and I8 as analog inputs, only the
range from 0 to 10 V DC is available.
Connecting a potentiometer to inputs I1, I2, I7 and I8
To allow you to achieve 10 V as the maximum value when
you completely turn the potentiometer once, you must
connect a series resistor on the potentiometer’s input side
regardless of the input voltage (see figure below).
We suggest the following sizes of potentiometers and
associated series resistors:
VoltagePotentiometerSeries Resistor
12 V5
24 V5
IDEC SmartRelay Manual37
k-
k6.6 k
IDEC SmartRelay installation and wiring
!
The inputs of these devices are not
isolated and therefore require a
common reference potential (chassis
ground ).
With FL1E-H12RCE / FL1E-B12RCE
and FL1E-H12SND modules, you can
tap analog signals between the
supply voltage and chassis ground
(* = series resistor with 24 V DC).
On the FL1E-H12RCA/-B12RCA, P1 and P2
are indicated in place of L+ and M, respectively
.
L1
N
L3
L2
NL1I1 I2 I3 I4I5 I6
The inputs of these devices are
arranged in 2 groups, each
consisting of 4 inputs. Different
phases are only possible between
blocks, but not within the blocks.
When using a potentiometer and 10 V input voltage as the
maximum value, you must ensure that with a connected
input voltage of 24 V, 14 V must release via the series
resistor so that a maximum of 10 V are supplied when you
turn the potentiometer one full rotation. With a voltage of
12 V, this can be neglected.
Note
The FL1B-J2B2 expansion module provides additional analog
inputs.
Always use twisted and shielded cables for analog signals, and
keep these as short as possible.
Current safety regulations (VDE 0110, ... and IEC 61131-2, ... as
well as cULus) do not permit the connection of different phases to
an AC input group (I1 to I4 or I5 to I8) or to the inputs of a digital
module.
38IDEC SmartRelay Manual
PE terminal for
connecting earth and
shielding the analog
measuring cable
Earth
Cable shielding
DIN rail
PE
RUN/STOP
Current
0...20mA
Reference
Current
Current measurement
Voltage measurement
0-10V
FL1B-J2B2
IDEC SmartRelay installation and wiring
L+
M
ML+
ML+
PE
L+M
M
U1 I2 M2 U2I1 M1
The illustration above shows an example of four–wire
current measurement and two–wire voltage measurement.
Connecting a two–wire sensor to the FL1B-J2B2
Wire up the two–wire sensor’s connecting wires as follows:
1. Connect the sensor’s output to connection U (0 ... 10 V
vo
ltage measurement) or to connection I (0 ... 20 mA
current measurement) of the FL1B-J2B2 module.
2. Connect the plus connector on the sensor to the 24 V
su
pply voltage (L+).
3. Connect the ground connection of the current output M
(o
n the right side of the sensor, as shown in the figure
above) to the corresponding M input (M1 or M2) on the
FL1B-J2B2 module.
IDEC SmartRelay Manual39
IDEC SmartRelay installation and wiring
I1~I8
N
100nF
390kΩ180kΩ270kΩ
47kΩ
Internal Circuit
Digital AC/DC Input
AC
2-wire
Sensor
I1 to I8
R4
100 to 240 V AC
N
L1
When using the AC two-wire sensor
I1~I8
N
100nF
390kΩ390kΩ
62kΩ
Internal Circuit
270kΩ
Digital AC/DC Input
Input Internal Circuit
FL1E-H12RCC / FL1E-B12RCC
FL1B-M08C2R2
40IDEC SmartRelay Manual
FL1E-H12RCA / FL1E-B12RCA
I1~I8
4.3kΩ
+5V
510Ω
150kΩ
100nF
100nF
P2
Internal Circuit
Internal
Circuit
Digital AC/DC Input
AC
2-wire
Sensor
I1 to I8
R3
240 V AC
P1
P2
When using the AC two-wire sensor
I1~I8
4.3kΩ
+5V
510Ω100nF
P2
Internal Circuit
Internal
Circuit
100nF
Digital AC/DC Input
FL1B-M08D2R2
IDEC SmartRelay installation and wiring
IDEC SmartRelay Manual41
IDEC SmartRelay installation and wiring
I1~I8
3.6kΩ270kΩ
2.21kΩ47nF
M
Internal Circuit
Digital DC Input
I1~I8
3.6kΩ
2.2kΩ100nF
M
Internal Circuit
270kΩ
Digital DC Input
I1, I2, I7, I8
M
54kΩ
+5V
18kΩ
10nF
Internal Circuit
Analog Input (0-10V)
U1, U2
M1, M2
38kΩ
+5V
38kΩ
10nF
Internal Circuit
FL1B-J2B2
Analog Input (0-10V)
FL1E-H12RCE / FL1E-B12RCE / FL1E-H12SND
FL1B-M08B2R2/FL1B-M08B1S2
FL1E-H12RCE / FL1E-B12RCE / FL1E-H12SND
42IDEC SmartRelay Manual
FL1B-J2B2
Internal
Circuit
Analog Input (0-20mA)
Note
Fluctuating analog values are due to screening on the connecting
wire from the analog valuator device to the analog FL1B-J2B2
expansion module (encoder wire) that has either been mounted
incorrectly or not at all.
To avoid fluctuating analog values when using these expansion
modules, proceed as follows:
•Use only shielded encoder wires.
•Shorten the encoder wire as much as possible. The encoder
•Clamp the encoder wire on one side only and clamp it only to
•Connect ground on the encoder supply to the PE terminal on the
IDEC SmartRelay installation and wiring
wire must not be more than 10 meters long.
the PE terminal on the FL1B-J2B2 / FL1D-K2B2 / FL1D-K2BM2
expansion module.
The FL1E-H12RCA / FL1E-B12RCA / FL1E-H12RCC /
FL1E-B12RCC /
equipped with relay outputs. The potential of the relay
contacts is isolated from the power supply and the inputs.
Requirements for relay outputs
You can connect various loads to the outputs, e.g. lamps,
fluores
cent lamps, motors, contactor relays etc. For
information on the properties required for the loads
connected to FL1E-H12RCA / FL1E-B12RCA / FL1EH12RCC / FL1E-B12RCC / FL1E-H12RCE / FL1E-B12RCE,
refer to Appendix A.
Connecting
This is how you connect the load to FL1E-H12RCA / FL1EB12RC
A / FL1E-H12RCC / FL1E-B12RCC / FL1E-H12RCE
/ FL1E-B12RCE:
FL1E-H12RCE / FL1E-B12RCE version is
Protection with automatic circuit-breaker, max. 16 A, characteristics
B16, e.g.: Power circuit-breaker 5SX2 116-6 (if required)
IDEC SmartRelay with transistor outputs
IDEC SmartRelay versions with tr
ansistor outputs can be
identified by the fact that the letter R is missing from their
type name. The outputs are short circuit-proof and overloadproof. An auxiliary load voltage supply is not necessary,
because IDEC SmartRelay supplies the load voltage.
44IDEC SmartRelay Manual
IDEC SmartRelay installation and wiring
Load: 24 V DC, 0.3 A max.
LoadLoad
Requirements for transistor outputs
The load connected to IDEC SmartRelay must have the
following characteristics:
•The maximum switched current is 0.3 A per output.
Connecting
This is how you connect the load to an IDEC SmartRelay
with
transistor outputs:
Q5Q6MM
Q1Q2M
M
FL1B-M08
IDEC SmartRelay Manual45
V1, V2: 0 - 10 V DC
V1, V2: 0 - 10 V DC
R1: >= 5 k
I1, I2: 0/4 - 20 mA
R2: <= 250
① Earth② DIN rail
FL1D-K2B2
FL1D-K2BM2
V1, V2: 0 - 10 V DCR1: >= 5 k
I1, I2: 0/4 - 20 mAR2: <= 250
V1 +
V2 +
RU N / ST O P
M2
M1
L
+
M
L+ M
L+ M
OUT P UT 2x (0 .. 10 V)
PE
㨪8
㨪8
2
1
44
V1+
176276 Z8QTO#
L+M
RU N / ST O P
M1PEM2V2+
L+M
I2I1
L
+
M
2
㨪O#
8
4
4
1
The terminal arrangement
on the FL1D-K2BM2 is
different from that of the
FL1D-K2B2.
Check the analog output
terminals on the FL1DK2BM2, and replace the
FL1D-K2B2 with the
FL1D-K2BM2.
FL1D-K2BM2: Voltage output:
IDEC SmartRelay installation and wiring
!
FL1D-K2B2 / FL1D-K2BM2
46IDEC SmartRelay Manual
Note
Caution for wiring the analog output terminals:
Check the analog output terminals, and wire each output terminal
to the external equipment, according to the type of analog
outputs.Incorrect wiring may cause damage to the equipment
connected to the analog output terminals.
The terminal arrangement on the FL1D-K2BM2 is different from
that of the FL1D-K2B2. Check the analog output terminals on the
FL1D-K2BM2, and replace the FL1D-K2B2 with the FL1D-K2BM2.
To set the address of the module on the AS interface bus,
you need an addressing unit.
Valid addresses are in the range of 1 to 31. Use each
ad
dress once only.
You can set the address on the AS interface bus before or
after ins
If the installed module is addressed via the address socket,
the AS-Inter
This is necessary for safety reasons.
tallation.
face voltage must be disconnected beforehand.
Networking on the AS interface bus
To make the connection to the AS interface bus, you need a
commu
•IDEC SmartRelay base module +
nications-capable IDEC SmartRelay variant:
CM AS-I.
To be able to send data across the AS interface bus to IDEC
Smar
tRelay and to receive data from it in the same way, you
also need:
•an AS interface power supply and
•an AS interface master.
IDEC SmartRelay can only be accepted as a slave on the AS
inter
face bus. This means that it is not possible to directly
exchange data between two IDEC SmartRelay devices.
Data is always exchanged across the AS interface master.
IDEC SmartRelay Manual49
IDEC SmartRelay installation and wiring
!
Warning
The AS-Interface and IDEC SmartRelay systems must never be
connected together electrically!
Use safe isolation acc. to IEC 61131-2, EN 50178, UL 508, CSA
C22.2 No. 42.
Logic Assignments
IDEC SmartRelay sys-
tem
InputsOutput data bits
I
n
I
n+1
I
n+2
I
n+3
OutputsOutput data bits
Q
n
Q
n+1
Q
n+2
Q
n+3
AS Interface system
D0
D1
D2
D3
D0
D1
D2
D3
”n” depends on the plug–in position of the expansion module
relative to the IDEC SmartRelay base module. It indicates
the number of the input or output in IDEC SmartRelay
program code.
Note
Ensure that there is enough space for the inputs/outputs of the AS
interface in the IDEC SmartRelay’s address space. If you are
already using more than 12 physical outputs or more than 20
physical inputs, it is no longer possible to operate the CM AS
interface!
50IDEC SmartRelay Manual
IDEC SmartRelay installation and wiring
2.4 Putting into operation
2.4.1Switching on the IDEC SmartRelay/Power On
IDEC SmartRelay does not have a power switch. The
reaction of IDEC SmartRelay during startup depends on the
following:
•Whether a circuit program is stored in IDEC SmartRelay
•Whether a memory cartridge or combined memory/
battery cartridge is inserted
•Whether this is an IDEC SmartRelay version without
display unit (FL1E-B12...)
•The status of IDEC SmartRelay at the time of power
failure.
All possible reactions of IDEC SmartRelay are described on
the following page.
To ensure that the expansion module on IDEC SmartRelay
changes to RUN mode, check the following:
•Has the sliding contact between IDEC SmartRelay and
the expansion module snapped into place properly?
•Is the power supply connected to the expansion module?
•In addition, always ensure that you switch on the power
supply to the expansion module first before activating the
power supply to the IDEC SmartRelay base module (or
activate both power supplies at the same time); if you do
not do this, the system does not detect the expansion
module when you start up the IDEC SmartRelay base
module.
Note
After power-up, the FL1E performs initialization. After completing
initialization, the FL1E is ready to start to run. During initialization,
a sandglass is displayed on the CPU module with display, or the
LED is lit red on the CPU module without display.
Initialization time (regardless of expansion module)
When a memory cartridge or a combined memory/battery cartridge
is installed: Max. 10 sec
When a cartridge is not installed or when a battery cartridge is
installed: Max. 9 sec
*The initialization time depends on the program size.
IDEC SmartRelay Manual51
IDEC SmartRelay installation and wiring
10sec
Power supply
External input signal to base module and expansion modules
I/O signal of base module is reflected
FB process
During the initialization of expansion modules
The initialization period
of base module
I/O signal of expansion modules
I/O signal of expansion modules is reflected
in the user program.
*1
is reflected.
in the user program. *1
Version 7 or earlier *2
Version 8 or later
*1 Output signal of base module and expansion modules
are reflected 1 scan time after each input signal has been reflected.
*2 During the initialization period of expansion I/O modules,
inputs and outputs are off. In addition, the length of initialization period varies with expansion I/O modules , and I/O response depends on the expansion I/O modules.
For further information, see our Internet address
(URL: http://www.idec.com/faq/en/controller/).
Notes for Using Expansion I/O Modules of Version 7 or earlier
When using 3 or more expansion I/O modules including
those of the versions listed below, immediately after powerup, it takes a specific period of time for the base module to
accept input signals from the expansion I/O modules. Until
the output terminals on the expansion I/O module are actu
ally turned on or off.
Expansion I/O Modules
FL1B-M08C2R2(Version 1 to 7),
FL1B-M08B1S2(Version 1 to 7),
FL1B-M08B2R2(Version 1 to 7),
FL1B-M08D2R2(Version 1 to 7),
FL1B-J2B2(Version 1 to 7),
FL1D-K2B2(Version 1)
For identifying the version, see page 5.
-
52IDEC SmartRelay Manual
>Program..
Card..
Setup..
Start
>Program..
Card..
Setup..
Start
2008-05-05
Mo 09:00
>Program..
Card..
Setup..
Start
2002-01-31
&
B1
Q1
2003-01-27
Mo 09:00
No program
Press ESC
No Program
Press ESC
Mo 09:00
I:
0.. 123456789
1..0123456789
2..01234
Q:
0..123456789
1..0123456
0.. 123456789
1..0123456789
2..01234
I:
B3:
Cnt = 0028
Par = 0300
0.. 123456789
1..0123456789
2..01234
I:
Before power off After power on
No program in
memory
or
(empty)
(with program)
IDEC SmartRelay
in RUN mode
or
(empty)
(with program)
with stored program from
IDEC SmartRelay
with a program copied from
the memory cartridge or
combined memory/battery
cartridge in IDEC
SmartRelay
IDEC SmartRelay in
RUN mode
or
(empty)
(with program)
Program in
memory
with stored program from
IDEC SmartRelay
with program copied from
the memory cartridge or
combined memory/battery
cartridge in IDEC
SmartRelay
You can also memorize four simple rules for starting IDEC
SmartRelay :
1. If neither IDEC SmartRelay nor the inserted memory
ca
rtridge or combined memory/battery cartridge contains
a circuit program, IDEC SmartRelay (with display unit)
reports: ’No Program / Press ESC’.
2. A circuit program on the memory cartridge or combined
mem
SmartRelay. The circuit program in IDEC SmartRelay is
overwritten.
3. If there is a circuit program in IDEC SmartRelay or on the
mem
IDEC SmartRelay adopts the operational state it had prior
to POWER-OFF. Versions without display unit (FL1E-
ory/battery cartridge is automatically copied to IDEC
ory cartridge or combined memory/battery cartridge,
B12...) automatically change from STOP to RUN (LED
changes from red to green).
IDEC SmartRelay Manual53
IDEC SmartRelay installation and wiring
IDEC SmartRelay installation and wiring
4. If you have enabled retentivity for at least one function, or
a function is permanently retentive, the current values are
retained at POWER-OFF.
Note
When a power failure occurs while you are entering a circuit
program, the program in IDEC SmartRelay will be deleted after
power is returned.
Before you modify the circuit program, save a backup copy of your
original to a memory cartridge, a combined memory/battery
cartridge or to a computer (WindLGC).
2.4.2Operating states
IDEC SmartRelay base module operating states
IDEC SmartRelay base module/Pure knows has two
operating states: STOP and RUN.
STOPRUN
• The display shows: ’No Program’
(not FL1E-B12...)
• Switching IDEC SmartRelay to
programming mode
(not FL1E-B12...)
•LED is red
(only FL1E-B12...)
Action of IDEC SmartRelay:
• The input data is not read.
• The circuit program is not
executed.
• The relay contacts are
permanently open or the
transistor outputs are switched
off.
• Display: Screen mask for
monitoring I/Os and messages
(after START in the main menu)
(not FL1E-B12...)
• Switching IDEC SmartRelay to
parameter assignment mode
(not FL1E-B12...)
• LED is green
(only FL1E-B12...)
Action of IDEC SmartRelay:
• IDEC SmartRelay reads the
status of the inputs.
• IDEC SmartRelay uses the circuit
program to calculate the status of
the outputs.
• IDEC SmartRelay switches the
relay/transistor outputs on or off.
Note
After switching the power on, the system briefly switches through
the outputs on the FL1E-H12SND. With an open circuit, a voltage
of > 8 V can occur for up to approximately 100 ms; when loaded,
this time reduces to a matter of microseconds.
54IDEC SmartRelay Manual
IDEC SmartRelay installation and wiring
IDEC SmartRelay expansion modules, operating states
IDEC SmartRelay expansion modules have three operating
states: The LED (RUN/STOP) is lit green, red or orange.
LED (RUN/STOP) is lit
Green (RUN)Red (STOP)Orange/Yellow
The expansion module
communicates with the
device to the left.
The expansion module
does not communicate
with the device to its
left.
Initialization phase of
the expansion module
CM AS Interface, communication states
The CM AS Interface has three communication states: The
LED is lit green, red or flashes red/yellow.
LED AS-I is lit
GreenRedRed/Yellow
AS Interface
communication OK
AS Interface
communication failed
Slave has address ”0”.
CM AS Interface, behavior on communication failure
•If the AS Interface voltage fails, communication between
the IDEC SmartRelay system and the expansion
modules, which are arranged to the right of the IDEC
SmartRelay CM AS Interface expansion module, is
interrupted.
Recommendation: Position IDEC SmartRelay CM AS
Interface on the far right side.
•If communication is interrupted, the switching outputs are
reset after about 40 to 100 ms.
IDEC SmartRelay Manual55
IDEC SmartRelay installation and wiring
56IDEC SmartRelay Manual
Programming IDEC SmartRelay
Getting started with IDEC SmartRelay
Programming refers to creating a circuit program from the
IDEC SmartRelay base module.
In this chapter you will learn how to use IDEC SmartRelay to
create the IDEC SmartRelay circuit programs for your
application.
WindLGC is the IDEC SmartRelay programming software
that you can use on your PC to quickly and easily create,
test, modify save and print the circuit programs. The topics
in this manual, however, relate only to the creation of circuit
programs on the actual IDEC SmartRelay base module. The
programming software WindLGC contains extensive online
help. See also Chapter
Note
IDEC SmartRelay versions without a display unit; that is, the FL1EB12RCE, FL1E-B12RCA and FL1E-B12RCC versions, do not have
an operator panel and display unit. They are primarily designed for
use in small machine and process equipment engineering systems
for series production.
FL1E-B12... versions are not programmed directly on the device.
Instead, the circuit program is downloaded to the device from
WindLGC or from memory cartridges or combined memory/battery
cartridges from other IDEC SmartRelay devices.
IDEC SmartRelay versions without a display cannot write data to
memory cartridges or combined memory/battery cartridges.
See Chapters 6, 7 and Appendix C.
7 for additional information.
3
A small example in the first part of this chapter introduces the
operating principles of IDEC SmartRelay:
•You will learn the meaning of two basic terms, namely the
connector and the block.
•As the next step, you will create a circuit program based
on a simple conventional circuit.
•Lastly, you will enter this program directly in IDEC
SmartRelay.
It will take you only a few pages of this manual to store your
first executable circuit program in the IDEC SmartRelay unit.
With suitable hardware (switches etc.), you will then be able
to carry out initial tests.
IDEC SmartRelay Manual57
AI4
1 2 1 2
1 2 1 2
L+ M I13I14 I15I16
Q11Q9Q12
Q10
RUN/STOP
L+ M
AI5
RUN/STOP
L+ M AI3 I3 I4 I5 I6
Q1Q2Q3Q4
AI1 AI2 L+ M I9 I10 I11I12
Q7Q5Q8
Q6
RUN/STOP
M3U3AI6M4 U4
1 2 1 2
1 2 1 2 1 2 1 2
1 2 1 2
PE
INPUT 2x (..10 V/..20 mA)
L+ M
Inputs
OutputsAnalog inputs
Programming IDEC SmartRelay
3.1 Connectors
IDEC SmartRelay is equipped with inputs and outputs
Example of a configuration with several modules:
Each input is identified by the letter I plus a number. When
you look at IDEC SmartRelay from the front, you can see the
input terminals at the top. Only analog modules FL1B-J2B2
have the inputs at the bottom.
Each output is identified by the letter Q plus a number
(
FL1D-K2B2, FL1D-K2BM2: AQ plus number). In the figure,
you can see the output terminals at the bottom.
Note
IDEC SmartRelay can recognize, read and switch the I/O of all
expansion modules regardless of their type. The I/Os are presented
in the installation order of the modules.
The following I/Os and marker blocks are available for creating your
circuit program: : I1 to I24, AI1 to AI8, Q1 to Q16, AQ1 and AQ2,
M1 to M27 and AM1 to AM6. Also available are the shift register bits
S1 to S8, 4 cursor keys: C , C , C and C , four function keys
on the Text Display: F1, F2, F3, and F4 as well as 16 blank outputs
X1 to X16. See Chapter 4.1 for more details.
The following applies to inputs I1, I2, I7 and I8 of FL1E-H12RCE/
FL1E-B12RCE and FL1E-H12SND versions: If you use I1, I2, I7 or
I8 in the circuit program, this input signal is digital. If you use AI3,
AI4, AI1, or AI2, the input signal is analog. The numbering of the
analog inputs is significant: AI1 and AI2 corresponded to I7 and I8
on the FL1D module. With the addition of two new analog inputs for
the FL1E series, these modules optionally use I1 for AI3 and I2 for
AI4. See the graphical representation at 2.1.1. Also note that you
can also use I3, I4, I5, and I6 as fast digital inputs.
The illustration above with numbered AI inputs shows the
conceptual usage of the inputs, not the actual physical
markings on the module.
58IDEC SmartRelay Manual
Programming IDEC SmartRelay
IDEC SmartRelay’s connectors
The term connector refers to all connections and states in
IDEC SmartRelay.
The digital I/O status can be ’0’ or ’1’. Status ’0’ means that
the input does not carry a specific voltage. Status ’1’ means
that the input does carry a specific voltage.
The ’hi’, ’lo’ and ’x’ connectors have been introduced to
make it easier for you to create the circuit program:
’hi’ (high) is assigned the status ’1’,
’lo’ (low) is assigned the status ’0’.
You do not have to use all of the connectors of a block. The
circuit program automatically assigns the unused connectors
a status that ensures proper functioning of the relevant
block. If you prefer to do so, you can identify unused
connectors with an ’x’.
For information on the meaning of the term “block”, refer to
Chapter
3.2.
IDEC SmartRelay has the following connectors:
ConnectorsIDEC SmartRelay base moduleDMAI
I9 ...
InputsFL1E-H12RCC/
FL1E-B12RCC,
FL1E-H12RCA/
FL1E-B12RCA
FL1E-H12RCE/
FL1E-B12RCE,
FL1E-H12SND
OutputsQ1...Q4Q5 ...
loLogical ’0’ signals (off)
hiLogical ’1’ signals (on)
xAn existing connection that is not used
DM: Digital module
AI: Analog input module
AO: Analog output module
Two groups:
I1... I4 and
I5 ... I8
I1,I2, I3-I6, I7, I8
AI3,AI4 ...AI1,
AI2
AI1...
I24
AI8
I9 ...
I24AI5...
AI8
none AQ1,
Q16
AO
none
AQ2
IDEC SmartRelay Manual59
Programming IDEC SmartRelay
I1
I2
x
1
Q
x
Inputs I1 and I2 are here connected to the
OR block. The last two inputs of the block
remain unused and are identified by the
creator of the circuit program with an ‘x’.
3.2 Blocks and block numbers
This chapter shows you how to use IDEC SmartRelay
elements to create complex circuits and how blocks and I/O
are interconnected.
In Chapter 3.3 you will learn how to transform a conventional
circuit into an IDEC SmartRelay circuit program.
Blocks
A block in IDEC SmartRelay represents a function that is
u
sed to convert input information into output information.
Previously you had to wire the individual elements in a
control cabinet or terminal box.
When you create the circuit pr
blocks. To do so, simply select the connection you require
from the Co menu. The menu name Co is an abbreviation of
the term “Connector”.
Logic operations
The most elementary blocks are the logic operations:
•AND
•OR
•...
ogram, you interconnect the
These special functions offer you significantly greater
performance:
•Current impulse relay
•Up/down counter
•On-delay
•Softkey
•...
Chapter 4 gives a full list of the IDEC SmartRelay functions.
60IDEC SmartRelay Manual
Programming IDEC SmartRelay
1
B2
I3
Q1
B1
x
x
View of the IDEC SmartRelay
Input
This connector is
not required
Block
Block number -assigned
by IDEC SmartRelay
Output
Another block is connected
at this point
I1
I2
I3
1
B1
B2
B2
1
B3
Q1
B1
B1
I4
I5
I6
1
B1
Q1
x
B3
x
x
x
Block numbers
These blocks are
interconnected
Scrolling the circuit program using the key
Block representation on the IDEC SmartRelay display
The figure below shows a typical view of the IDEC
SmartRelay display. As you can see, it can show only one
block at a time. We have therefore introduced block numbers
to help you check the circuit structure.
Assigning a block number
IDEC SmartRelay assigns each new block in a circuit
ogram a block number.
pr
IDEC SmartRelay uses these block numbers to indicate the
b
lock interconnections. This means that these numbers are
mainly an aid to your orientation in the circuit program.
IDEC SmartRelay Manual61
The figure above shows you three views of the IDEC
SmartRelay display, which represent the circuit program. As
you can see, IDEC SmartRelay interconnects the blocks
using their numbers.
Programming IDEC SmartRelay
Advantages of block numbers
You can connect almost any block to an input of the current
block by means of its block number. In this way, you can
reuse the interim results of logical or other operations,
reduce programming effort, save memory space and clean
up your circuit layout. To do so, however, you need to know
how IDEC SmartRelay has named the blocks.
Note
We advise you to create an organizational program chart. You will
find this a valuable aid when you create the circuit program
because you can enter in this chart all the block numbers that IDEC
SmartRelay assigns.
By using the WindLGC software to program IDEC SmartRelay, you
can directly create a function chart of your circuit program.
WindLGC also allows you to assign eight-character names to up to
100 blocks, and to view these on the IDEC SmartRelay display in
parameter assignment mode (see Chapter 3.4).
62IDEC SmartRelay Manual
Programming IDEC SmartRelay
K1
S1K1S2
E1
S3
Load E1 is switched on and off by
means of the switches (S1 OR S2)
AND S3.
Relay K1 picks up when condition
(S1 OR S2) AND S3 is met.
S1 ... S3
I3
x
Q1
&
1
I1
I2
x
L1
N
Wiring of the inputs
Circuit program in IDEC SmartRelay
Wiring of the outputs
3.3 From circuit diagram to IDEC SmartRelay
program
View of a circuit diagram
You know, of course, how a circuit logic is represented in a
circuit diagram. Nevertheless, here is an example:
Creating this circuit with IDEC SmartRelay
In IDEC SmartRelay you create a circuit logic by
connecting blocks and connectors:
inter
IDEC SmartRelay Manual63
Programming IDEC SmartRelay
I3
x
Q1
&
I3
x
Q1
&
1
I1
I2
x
Note
Although you have four inputs available for logic operations (Basic
functions, see Chapter 4.2), most of the views will only show three
inputs for reasons of clarity. You program this fourth input and
assign parameters just like you do with the other three inputs.
To create a circuit logic in IDEC SmartRelay, start at the
circuit output.
The output is the load or relay that is to be switched.
Convert the circuit logic into blocks by working through the
circ
uit, starting at the output and ending at the input:
Step 1: The Normally Open Contact S3 is interconnected in
series to output
A series connection corresponds with the AND
block:
Step 2: S1 and S2 are connected in parallel. A parallel circuit
corresponds with the OR block:
Q1 and to a further circuit element.
Unused inputs
The circuit program automatically assigns the unused
co
nnectors a status that ensures proper functioning of the
relevant block. If you like, you can label unused connectors
with an ’x’ identifier.
In our example we shall use only two inputs of the OR block
a
nd two inputs of the AND block; the relevant unused third
and fourth inputs are identified at the connector with an ’x’.
Now connect the I/Os to IDEC SmartRelay.
Wiring
Connect the switches S1 to S3 to the screw terminals of your
IDEC
SmartRelay :
•S1 to connector I1 of IDEC SmartRelay
•S2 to connector I2 of IDEC SmartRelay
•S3 to connector I3 of IDEC SmartRelay
The output of the AND block controls the relay at output Q1.
Th
e load E1 is connected to output Q1.
64IDEC SmartRelay Manual
Wiring example
L1
N
Input wiring
Output wiring
S3S2S1
L1
N
NL1I1 I2 I3 I4
1 2
Q1
Last
The following figure shows you the wiring, based on a 230 V
AC version of IDEC SmartRelay.
Programming IDEC SmartRelay
IDEC SmartRelay Manual65
Programming IDEC SmartRelay
3.4 The four golden rules for operating IDEC
SmartRelay
Rule 1
Changing the operating mode
•You create the circuit program in programming mode.
After power is on, and when the display shows “No
Program / Press ESC”, press the ESC key to select
programming mode.
•Timer and parameter values of an existing circuit
program can be edited both in parameter assignment
mode and in programming mode. During parameter
assignment IDEC SmartRelay is in RUN mode; that is,
it continues executing the circuit program (see Chapter
5). To work in programming mode, you need to
terminate the circuit program by calling the “Stop”
command.
•Select the ’Start’ command on the main menu to set RUN mode.
•When the system is in RUN, you can return to parameter assignment mode by pressing the ESC key.
•When parameter assignment mode is open and you
want to return to programming mode, select the “Stop”
command from the parameter assignment menu, and
confirm “Stop Prg” prompt with “Yes”. To do so, move
the cursor to “Yes” and confirm with OK.
For more details on operating modes, refer to Appendix D.
Rule 2
Outputs and inputs
•Always create your circuit program by working from the
output to the input.
•You can connect an output to several inputs, but not the
same input to several outputs.
•Within the same program path you may not connect an
output to an upstream input. For such internal recursions
you should interconnect memory markers or outputs.
66IDEC SmartRelay Manual
Rule 3
Cursor and cursor movement
The following applies when you edit a circuit program:
•You can mo
ve the cursor when it appears in the form of
an underscore:
-Press
, , or to move the cursor in the circuit
program.
-Press OK
-Press ESC to
•You se
to change to ”Select connector/block”.
exit programming mode.
lect a connector/block
when the cursor appears as a solid square
-Press
or to select a connector or a block.
-Confirm with OK.
-Press ESC t
o return to the previous step.
Rule 4
nning
Pla
•Before you start to create a circuit program, you should
r first create a design on paper or program IDEC
eithe
SmartRelay directly using WindLGC.
•IDEC SmartRelay can only save complete and faultless
c
ircuit programs.
Programming IDEC SmartRelay
IDEC SmartRelay Manual67
Programming IDEC SmartRelay
Main Menu
Programming menu
OK
ESC
OK
ESC
Transfer menu
Setup menu
Note: The ‘BM AI NUM’ selection is
only available on base modules that
support four analog inputs.
OK
ESC
3.5 Overview of IDEC SmartRelay menus
Programming mode
>Program..
Card..
Setup..
Start
= IDEC
SmartRelay
Parameter assignment mode
Parameter assignment menu
>Stop
Set Param
Set..
Prg Name
>Edit..
Clear Prg
Password
Msg Config
>Card
Card
CopyProtect
>Clock
LCD
Menu Lang
BM AI NUM
For more details on these menus, refer to Appendix D.
The Text Display menus provide configuration settings for
Text Display. These menus are a subset of the IDEC
the
SmartRelay menus and are operated in much the same way.
Appendix section D.2 shows the Text Display menus.
68IDEC SmartRelay Manual
Programming IDEC SmartRelay
No Program
Press ESC
>Program..
Card..
Setup..
Start
IDEC SmartRelay’s main menu
>Edit..
Clear Prg
Password
Msg Config
IDEC SmartRelay’s programming
menu
The Edit menu of IDEC SmartRelay
3.6 Writing and starting the circuit program
After you have designed a circuit, you want to write it to your
IDEC SmartRelay. The small example below shows how to
do this.
3.6.1Selecting programming mode
You have connected IDEC SmartRelay to the power supply
and switched it on. The display now shows you the message:
Switch IDEC SmartRelay to programming mode by pressing
ESC. This will take you to the main menu of IDEC
SmartRelay:
IDEC SmartRelay Manual69
The first character in the first line is the ”>” cursor. Press
and
to move the ”>” cursor up and down. Move it to
”Program..” and confirm with OK. IDEC SmartRelay opens
the programming menu.
Here you can also move the ”>” cursor by pressing and .
Move the ”>” cursor to ”Edit..” an
d confirm with OK.
>Edit Prg
Edit Name
AQ
Memory?
Programming IDEC SmartRelay
Q1
The first output of IDEC SmartRelay
The load is switched on
with S1 OR S2. IDEC
SmartRelay interprets this
parallel circuit as an ‘OR’
logic, because S1 OR S2
switches on the output.
Move the ”>” cursor to ”Edit Prg” (for editing the circuit
program) and confirm with OK. IDEC SmartRelay now
shows you the first output:
You are now in programming mode. Press and to select
the other outputs. Now start to edit your circuit program.
Note
Because we have not yet saved a password for the circuit program
in IDEC SmartRelay, you can directly enter editing mode. When
you select “Edit” after you have saved a password-protected circuit
program, you are prompted to enter a password and to confirm it
with OK. You can only edit the program after you have entered the
correct password (see Chapter 3.6.5.).
3.6.2The first circuit program
Let us now take a look at the following parallel circuit
consisting of two switches.
Circuit diagram
The corresponding circuit diagram:
S1
K1
S2
K1
E1
Translated into an IDEC SmartRelay circuit program this
means: Relay K1 is (at output Q1) is controlled by means of
an OR block.
70IDEC SmartRelay Manual
Circuit program
S1 is connected to the I1 and S2 to the I2 input connector of
the OR block.
The corresponding layout of the circuit pr
SmartRelay:
I1
I2
x
Wiring
The corresponding wiring:
L1
N
Programming IDEC SmartRelay
ogram in IDEC
1
Q1
S1
S2
L1 NI4I5 I6 I7 I8
I1I1I3I1I1
I2
1 21 21 21 2
Q1Q2Q3Q4
L
N
S1 switches input I1, while S2 switches input I2. The load is
connected to the relay Q1.
IDEC SmartRelay Manual71
Programming IDEC SmartRelay
The first IDEC SmartRelay output
The cursor indicates your current
position in the circuit program.
The cursor is displayed as a solid
square: You can now select a connector
or a block
The AND is the first block of the basic
functions list. The solid square cursor
prompts you to select a block.
3.6.3Circuit program input
Let us now write the circuit program, starting at the output
and working towards the input. IDEC SmartRelay initially
shows the output:
Q1
You will see an underscore below the Q in Q1, which is the
cursor. The cursor indicates your current position in the
circuit program. You can move the cursor by pressing the
, , and keys. Now press the key. The cursor moves
to the left.
–
At this point you enter only the first (OR) block. Press OK to
select editing mode.
Co
The cursor no longer appears in the form of an underscore;
but instead as a flashing solid square. IDEC SmartRelay
offers you various options here.
Select GF (basic functions) by pressing the
appears, and confirm with OK. IDEC
the first block from the list of basic functions:
Q1
Q1
key until GF
SmartRelay now shows
B1
&
Q1
72IDEC SmartRelay Manual
Programming IDEC SmartRelay
The solid square cursor is still
positioned on the block.
The display now shows:
Block
number
Your complete circuit
program layout
1
B1
Q1
Co
The display now shows:
1
B1
Q1
x
The display now shows:
Now press or until the OR block appears on the display:
B1
1
Q1
Press OK to confirm your entries and exit the dialog.
B1
–
1
Q1
You have now entered the first block. Each new block is
automatically assigned a block number. The only thing left to
do is interconnect the block inputs. This is how it is done:
Press OK.
Select the Co list: Press OK
B1
1
Q1
The first element of the Co list is the ”Input 1” character,
namely ’I1’.
IDEC SmartRelay Manual73
1
Q1
I1
B1
Programming IDEC SmartRelay
1
B1
Q1
1
Q1
I1
I1
B1
–
The display now shows:Your complete circuit program
in IDEC SmartRelay up to now:
1
B1
Q1
1
Q1
I1
I1
B1
I2
I2
The display now shows:Your circuit program layout in
IDEC SmartRelay up to now
Note
Press to go the start of the Co list: I1, I2 .... to lo. Press to go
to the end of the Co list: lo, hi, ..... to I1.
Inputs F1, F2, F3, and F4 are new as of the FL1E device series.
They correspond to the four function keys on the optional Text Display.
Press OK. I1 is now connected to the input of the OR block.
The cursor jumps to the next input of the OR block.
Now you connect input I2 to the input of the OR block. You
already know how to do this:
1. Switch to editing mode:Press OK
2. Select the Co lis
3. Confirm the Co list with:Press OK
4. Select I2:
5. Apply I2:Press OK
I2 is now connected to the input of the OR block:
74IDEC SmartRelay Manual
t:Press or
Press or
Programming IDEC SmartRelay
1
Q1
I1
B1
I2
Q1B1
x
The display now shows:This is the layout of your circuit
program
1
B1
Q1
I2
I3
x
I1
We do not need the last two inputs of the OR block for this
circuit program. You can mark the unused inputs with an ’x’.
Enter the ’x’ character twice:
1. Switch to editing mode:Press OK
2. Select the Co list:
3. Accept the Co list:Press OK
4. Select ’x’:
5. Apply x:Press OK
Note
You can invert individual inputs of the basic and special functions;
that is, if an input carries a logical “1” signal, the circuit program will
output a logical “0”. On the other hand, a logical -0" is inverted into
a logical “1” signal.
To invert an input, move the cursor to the relevant position,
e.g.:
Press or
Press or
Confirm with OK.
Now press
IDEC SmartRelay Manual75
or to invert this input:
Programming IDEC SmartRelay
1
B1
Q1
I2
I3
1
Q1
I2
B1
I3
x
x
I1
I1
Your circuit program layout
Next, press ESC.
You can review your first circuit program by pressing or
to move the cursor through the circuit program.
We shall now exit circuit programming mode. This is how it
is do
ne:
Return to the programming menu:Press ESC
Note
IDEC SmartRelay has now saved your circuit program to
nonvolatile memory. The circuit program remains in the IDEC
SmartRelay memory until you explicitly delete it.
You can save the actual values of special functions in the case of a
power outage assuming that these functions support the
“Retentive” parameter and that the necessary program memory is
available. The Retentive parameter is deactivated when you insert
a function; to use it, you must enable this option.
76IDEC SmartRelay Manual
Programming IDEC SmartRelay
3.6.4Assigning a circuit program name
You can assign your circuit program a name that consists of
up to 16 uppercase/lowercase letters, numbers and special
characters.
In the programming menu:
1. Move the “>” cursor to ’Edit..’:
2. Accept ’Edit’:Press OK
3. Move the “>” cursor to ’Edit Nam
4. Accept ’Edit Name’:Press OK
Press
and to list the alphabet, numbers and special
characters, either in ascending or descending order. You
can sele
ct any letter, number or character.
To enter a space character, simply move the cursor with
to the next position. This character is the first one in the list.
Examples:
Press
once to select an “ A ”
four times to select “ { ”, etc.
The following character set is available:
ABCDEFGH I JKLMNO
PQRSTUVWXYZ a b c d e
f gh i j k lmnopq r s tu
vwxyz0123456789 !
”#$%&’()*+,-./:;
<=>?@[ \ ] ^ _ ‘ { | } ~
Press or
e’: Press or
Let us assume you want to name your circuit program
“ABC”:
5. Select “ A”:
6. Move to the next letter:Press
7. Select “ B”:
8. Move to the next letter:Press
9. Select “ C”:
Press
Press
Press
10.Confirm the complete name: Press OK
Your circuit program is now named “AB
C”, and you are
returned to the programming menu.
To ch
ange the name of your circuit program, proceed in the
same way.
Note
You can change the name of the circuit program only in
programming mode. You can read the name both in programming
and in parameter assignment mode.
IDEC SmartRelay Manual77
Programming IDEC SmartRelay
3.6.5Password
You can protect a circuit program from unauthorized access
by assigning it a password.
You can only assign or deactivate a password from the IDEC
Sm
artRelay Base module or from WindLGC. You can only
change a password from the IDEC SmartRelay Base
module. If you have assigned a password, and are using a
Text Display (version 4 or later) together with an IDEC
SmartRelay Base module (version 4 or later), you must enter
this password if you want to change IDEC SmartRelay from
RUN mode to STOP mode from the Text Display. You can
not stop the execution of the circuit program in IDEC
SmartRelay from the Text Display without entering the
password.
Note
This additional password protection function is only available
in the Text Display with version number 4 or later. This
function is only available under the following conditions:
•The version number of both the IDEC SmartRelay Base
a
nd the Text Display installed is at least version 4
•IDEC SmartRelay is currently in RUN mode and you want
to sw
itch to STOP mode
There is only one password that you can assign for IDEC
Sma
rtRelay. You can only assign it from the IDEC
SmartRelay base module or from WindLGC. To change
IDEC SmartRelay from RUN to STOP from the Text Display,
you must enter the password from the Text Display as
described below in the section “Changing IDEC SmartRelay
from RUN to STOP mode from the Text Display”.
Assigning a password from the IDEC SmartRelay Base module
A password can have a maximum length of 10 characters,
and consists only of uppercase letters. On IDEC
SmartRelay, the password can be assigned, edited or
deactivated only in the “Password” menu.
To enter a password, follow these steps in the programming
m
enu:
1. Move the “>” cursor to ’Password’:
2. Confirm the ’Password’:Press OK
Press
your letters. Becau
78IDEC SmartRelay Manual
or to move up and down the alphabet to select
se IDEC SmartRelay only provides
Press or
Programming IDEC SmartRelay
Old:
No Password
New:
Old:
No Password
New:
AA
uppercase letters for the password, you can quickly access
letters “at the end“ of the alphabet (in this example, English)
by using the
Press
Press
Let us assign the password “AA”
The display now shows:
This procedure is the same as for entering the name of the
circuit program. Select “New” and enter:
3. Select “ A”:
4. Move to the next letter:Press
5. Select “ A”:
The display now shows:
button:
once to select “Z”
twice to select “Y”, etc.
to our first circuit program.
Press
Press
IDEC SmartRelay Manual79
6. Confirm the password:Press OK
Your circuit program is now protected with the password
“AA”, an
Note
You can cancel the input of a new password with ESC. In this case,
IDEC SmartRelay returns to the programming menu without saving
the password.
You can also set your password using WindLGC. You cannot edit
a password-protected circuit program on IDEC SmartRelay or
upload it to WindLGC unless you enter the correct password.
To allow you to create and edit a circuit program for a protected
module (Card), you first need to assign a password to this new
program (see Chapter 6.1).
d you are returned to the programming menu.
Programming IDEC SmartRelay
Old:
AA
New:
Old:
AA
New:
Old:
AA
New:
Z
Z
Changing the password from the IDEC SmartRelay Base module
You must know the current password in order to change it.
In the programming menu:
1. Move the ’>’ cursor to ’Password’: Press or
2. Confirm the ’Password’:Press OK
Select “Old” and enter your old password (in our case: ’AA’) by repeating
steps 3 through 6 as described earlier.
The display now shows:
Now you can select “New” to enter the new password, e.g.
“ZZ”:
3. Select “Z”:
4. Move to the next letter:Press
5. Select “Z”:
The display now shows:
Press
Press
6. Confirm your new password:Press OK
Your new password “ZZ”
the programming menu.
Deactivating the password from the IDEC SmartRelay Base module
To deactivate the password to allow, for example, another
ser to edit your circuit program, you must know your current
u
password (in our example “ZZ”), the same as if you were
changing it.
To deactivate the password, following these steps in the
pr
ogramming menu:
1. Move the ’>’ cursor to ’Pass
2. Confirm the ’Password’:Press OK
Select “Old” and enter your current password as described
steps 3 to 5. Confirm your entries with OK.
in
80IDEC SmartRelay Manual
is now set, and you are returned to
word’: Press or
The display shows:
Old:
Old:
ZZ
ZZ
New:
New:
Clear the password by leaving the input box blank:
3. Confirm the “blank” password:Press OK
The password is ”cleared”, and you are returned to the
ogramming menu.
pr
Note
This action disables the password prompt, and thus permits access
without a password.
Let the password prompt be deactivated for the time being, in
order to accelerate progress in our further exercises and examples.
Password: Wrong Password!
When the user inputs the wrong password and confirms the
input with OK, IDEC SmartRelay does not open editing
mode, but returns to the programming menu. This repeats
itself over and again until you input the correct password.
Programming IDEC SmartRelay
Changing IDEC SmartRelay from RUN to STOP mode from the
T
ext Display
A change from RUN mode to STOP mode from the Text
Dis
play requires password entry if one is assigned. You
must know the existing password if one is assigned. If there
is no password assigned on the IDEC SmartRelay Base
module, the Text Display will not prompt you for password
entry.
To change IDEC SmartRelay
mode from the Text Display when IDEC SmartRelay is
password-protected, follow these steps:
IDEC SmartRelay Manual81
from RUN mode to STOP
Programming IDEC SmartRelay
>Stop
Set Param
Msg Config
Set..
Password?
ZZ
>Setup
Msg Config
Start
1. On the Text Display, press ESC to switch IDEC SmartRelay from RUN mode to STOP mode.
the following menu:
2. Press OK. The Text Display shows you the following display:
Stop Prg
>No
Yes
3. Press to move the cursor to “Yes”, and press OK. Enter
the correct password (in
incorrect password, the Text Display returns to the display in Step 1.
Text Display shows
this case: “ZZ”). If you enter an
82IDEC SmartRelay Manual
4. Press OK to exit the password entry screen form. The
Text Display opens the main menu:
IDEC SmartRelay changes to STOP mode.
Programming IDEC SmartRelay
Note
Whenever the Text Display is initialized, the password needs
to be inputted again. The next time you start it and access
this password-protected function (RUN to STOP), you will be
prompted for password entry on the Text Display.
When IDEC SmartRelay subsequently changes from STOP
to RUN mode, you will again be prompted for password entry
to change IDEC SmartRelay to STOP mode from the Text
Display if more than one minute has elapsed since you
pressed any key on the Text Display.
The Text Display can also change IDEC SmartRelay from
STOP to RUN mode, but no password is required in this
case.
IDEC SmartRelay Manual83
2008-05-26
Mo 09:00
I:
0.. 123456789
1..0123456789
2..01234
Q:
0.. 123456789
1..0123456
AI:
1: 00000
2: 01000
3: 00253
AI:
4: 00010
5: 00000
6: 00005
Start screen: Date and current time-ofday (only for versions with real-time
clock). This element flashes if the date
and time are not set.
Or: Start screen digital inputs (see
Chapter 5.2.5)
Press
Press
Press
Press
Press
Inputs I1 to I9
Inputs I10 to I19
Inputs I20 to I24
Outputs Q1 to Q9
Outputs Q10 to Q16
Analog inputs AI1 to AI3
Analog inputs AI4 to AI6
Programming IDEC SmartRelay
3.6.6Switching IDEC SmartRelay to RUN mode
In the main menu, select RUN to start IDEC SmartRelay.
1. Return to the main menu: Press ESC
2. Move the ’>’ cursor to ’Start’:
3. Confirm ’Start’:Press OK
IDEC SmartRelay runs the circuit program and shows the
following display:
Display field of IDEC SmartRelay in RUN mode
Press or
84IDEC SmartRelay Manual
M:
0.. 123456789
1..0123456789
2..01234567
ESC+C
AI:
7: 00000
8: 00000
AQ:
1: 00000
2: 01000
Analog inputs AI7 to AI8
Analog outputs AQ1 to AQ2
Memory Markers M1 to M9
Memory Markers M10 to M19
Memory Markers M20 to M27
4 cursor keys for manual intervention
in the circuit program (ESC+key)
Press
Press
Press
Programming IDEC SmartRelay
In this example, only the inputs I1, I15, Q8 and Q12 are set “high”.
What is meant by: “IDEC SmartRelay is in RUN”?
In RUN mode, IDEC SmartRelay executes th
e circuit
program. To do so, IDEC SmartRelay first reads the status
at the inputs, determines the status of the outputs by means
of the user program, and switches these on or off according
to your settings.
This is how IDEC SmartRelay indicates the I/O status:
I:
0.. 123456789
1..0123456789
2..01234
IDEC SmartRelay Manual85
Input/output status is ’1’:
inverted
Input/output status is ’0’: not
inverted
Q:
0.. 123456789
1..0123456
I:
0.. 123456789
1..0123456789
2..01234
L1
N
V4V5
=1
L4
L5
T4
Q:
0.. 123456789
1..0123456
Let us examine
this using our
example:
When switch S1 is
closed, the status at
input I1 is hi.
IDEC SmartRelay
computes the output
states by means of the
circuit program.
Output Q1 = ‘1’, in this
case.
When Q1 = ‘1’, IDEC
SmartRelay sets relay
Q1, and the load
L1
N
S1
S2
K1
K1
E1
You already know the first part of
the circuit. S1 and S2 switch a
relay, which is to be used to
switch on the load E1, and to
switch off the load with a delay of
12 minutes.
Programming IDEC SmartRelay
Status indication on the display
3.6.7Second circuit program
Up to this point, you have successfully created your first
circuit and assigned it a name and, if desired, a password. In
this section we will show you how to modify existing circuit
programs and how to use the special functions.
Using this second circuit program, we will show you how to:
•Add a block to an existing circuit program.
•Select a block for a special function.
•Assign parameters.
Modifying circuits
We shall use the first circuit program as a basis for the
nd, with some slight modifications.
seco
First of all take a look at the circuit dia
circuit program:
86IDEC SmartRelay Manual
gram for the second
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.