ICP CCA924GKA100, CCA936GKA100, CCA948GKA100, CCA960GKA100, HCA924GKA100 Installation Guide

...
Theseinstructionsmustbereadand understoodcompletelybeforeattemptinginstallation.
IMPORTANT:Effective January 1,2015, all split system and packaged air conditioners must be installed pursuant to applicable
regional efficiency standards issued by the Department of Energy.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of
hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manuals that may
apply to the product. DANGER - Immediate hazards which will result in
severe personal injury or death. WARNING - Hazards or unsafe practices which
could result in severe personal injury or death. CAUTION - Hazards or unsafe practices which
may result in minor personal injury or product or property damage.
NOTE - Used to highlight suggestions which will result in enhanced installation, reliability, or
operation.
Signal Words in Manuals
The signal word WARNING is used throughout this
manual in the following manner:
The signal word CAUTION is used throughout this
manual in the following manner:
Signal Words on Product Labeling Signal words are used in combination with colors
and/or pictures on product labels.
TABLE OF CONTENTS
Safety Considerations ........................... 2
Installation Recommendations ................... 2
Installation ..................................... 2
Start-up Procedure ............................. 7
System Functions & Sequence of Operation ....... 7
Troubleshooting ................................ 8
Status Codes ................................. 11
R-410A Quick Reference Guides ................ 15
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal
injury and/or death. Before installing, modifying, or servicing system,
main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect
switch. Lock out and tag switch with a suitable warn-
ing label.
CUT HAZARD
Failure to follow this caution may result in personal injury
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
421 01 1702 04 03/16/15
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or
property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The
qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes
and current editions of the National Electrical Code ( NEC ) NFPA
70. In Canada, refer to current editions of the Canadian electrical code CSA 22.1.
Figure 1 [ Connecting Tube Installation
NOTE: Avoid contact between tubing and structure
THROUGH THE WALL
SUSPENSION
Recognize safety information. This is the safety-alert symbol/_
When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand
these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal
injury or death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product
and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
INSTALLATION RECOMMENDATIONS
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate for unit capacity.
3. Run refrigerant tubes as directly as possible by avoiding
unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb vibration.
5.
When passing refrigerant tubes through the wall, seal
opening with RTV or other pliable silicon-based caulk. (See Fig. 1.)
6.
Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.
7.
Do not suspend refrigerant tubing from joists and studs with
a rigid wire or strap which comes in direct contact with tubing. (See Fig. 1.)
8.
Ensure that tubing insulation is pliable and completely
surrounds vapor tube.
9.
When necessary, use hanger straps which are 1 in. (25.4
mm) wide and conform to shape of tubing insulation. (See Fig. 1.)
10.
Isolate hanger straps from insulation by using metal
sleeves bent to conform to shape of insulation.
Outdoor unit contains system refrigerant charge for operation with AHRI rated indoor unit when connected by 15 ft. (4.57 m) of
field-supplied or factory accessory tubing. For proper unit operation, check refrigerant charge using charging information located on control box cover and/or in the Check Charge section
of this instruction. IMPORTANT: Maximum liquid-line size is 3/8-in. OD for all
residential applications including long line. IMPORTANT: Always install the factory-supplied liquid-line filter
drier. Obtain replacement filter driers from your distributor or branch.
INSTALLATION
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
R-410A refrigerant systems operate at higher pressures
than standard R-22 systems. Do not use R-22 service
equipment or components on R-410A refrigerant equipment.
Specifications for this unit in residential new construction market require the outdoor unit, indoor unit, refrigerant tubing sets, metering device, and filter drier listed in presate literature. There
can be no deviation.
Check Equipment and Job Site Unpack Unit
Move to final location. Remove carton taking care not to damage unit.
Inspect Equipment
File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit corner
panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications.
Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad, tie down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 2
to determine base pan size and knockout hole location.
2 specificationssubjectto change without notice. 421 01 1702 04
For hurricane tie downs - contact your local distributor for details
and PE (Professional Certification), if required by local authorities. On rooftop applications, mount on level platform or frame. Place
unit above a load-bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately
support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.
Roof mounted units exposed to winds may require wind baffles.
Consult the Low-Ambient pressure switch installation instructions for wind baffle construction.
NOTE: Unit must be level to within _+2° (+3/8 in./ft..) per
compressor manufacturer specifications. Clearance Requirements
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 30 in. (762 mm) clearance to service end of unit and 48 in. (1219.2 mm) above
unit. For proper airflow, a 6 in. (152.4 mm) clearance on one side of unit and 12 in. (304.8 mm) on all remaining sides must be
maintained. Maintain a distance of 24 in. (609.6 mm) between units. Position so water, snow, or ice from roof or eaves cannot
fall directly on unit.
Figure 2 [
3/8--in. (9.53 ram) Dia. Tiedown Knockouts in
Basepan(2) Places
Tie Down Knockouts
I
View From Top
UNIT BASE PAN TIEDOWN KNOCKOUT LOCATIONS in. (mm)
Dimension A B C
31-1/2 X 31-1/2
(800 X 800) 9-1/8 (231,8) 6-9/16 (166,7) 24-11/16 (627.1)
35 X 35
(889 X 889) 9-1/8 (231,8) 6-9/16 (166,7) 28-7/16 (722,3)
On rooftop applications, locate unit at least 6 in. (152.4 mm) above roof surface.
Operating Ambient The minimum outdoor operating ambient in cooling mode is 55°F
(12.78 °C), and the maximum outdoor operating ambient in
cooling mode is 125°F (51.67°C).
17 SEER product is approved for low ambient cooling operation
down to an ambient as low as 0°F (-17.78°C) with low ambient accessory kits.
19 SEER product is not approved for low ambient cooling
applications.
This unit is not approved for low ambient cooling applications.
Make Piping Connections
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Use all service ports and open all flow-control devices, including solenoid valves.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not leave system open to atmosphere any longer than minimum required for installation. POE oil in compressor is
extremely susceptible to moisture absorption. Always keep ends of tubing sealed during installation.
If ANY refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise at service valve. Refrigerant tubing lengths up to 36 in. (914.4 mm) may be buried without
further special consideration. Do not bury lines more than
36 in. (914.4 mm).
Outdoor units may be connected to indoor section using accessory tubing package or field-supplied refrigerant grade
tubing of correct size and condition. For tubing requirements beyond 80 ft/24.38 m, substantial capacity and performance
losses can occur. Following the recommendations in the Long Line Applications Guideline for Split-System Air Conditioners and
Heat Pumps will reduce these losses. Refer to Table 1 for accessory requirements. Refer to Table 2 for field tubing
diameters. There are no buried-line applications greater than 36 in. (914.4
mm). If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and moisture in the system.
Outdoor Unit Connected to Factory Approved Indoor Unit
Outdoor unit contains correct system refrigerant charge for operation with factory approved AHRI rated indoor unit when
connected by 15 ft. (4.57 m) of field-supplied or factory-accessory tubing, and factory supplied filter drier. Check
refrigerant charge for maximum efficiency.
421 01 1702 04 specificationssubjectto change without notice. 3
Table1- AccessoryUsage
REQUIREDFORLOWAMBIENT
COOLINGAPPLICATIONS
(17SEERProductOnly) REQUIREDFORLONGLINE Requiredfor Sea CoastApplica-
Accessory (Below55°F / 12,8°C) APPLICATIONS*(Over80 ft. / 24,38 m) tion (within2 miles/3,22 km)
Crankcase Heater Yes Standardon some units Yes,standard on some units No
Compressor StartAssist Ca- pacitorand Relay
LiquidLineSolenoid Valve No See Long LineApplications Guideline No
Support Feet Recommended No Recommended
HardShutoff TXV Evaporator Freeze Thermostat Yes No No
Low-Ambient Pressure Switch Yes No No
Winter Start Control Yes No No
For tubing line sets between 80 and 200 ft, (24.38 and 60,96 m) and/or 20 ff, (6.09 m) vertical differential, refer to Long Line Applications Guideline.
Table 2 - Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)
UNIT SIZE Diameter Diameter Diameter
"0A724 3/8 3/4 3/4 "0A924 3/8 7/8 7/8
"0A736, "0A936 3/8 7/8 7/8
"0A748, "0A948 3/8 7/8 1-1/8 "0A760, "0A960 3/8 7/8 1-1/8
Units are rated with 25 ft. (7.6 m) of lineset. See Specification sheet for performance data when using different size and length linesets.
Notes:
1. Do not apply capillary tube or fixed orifice indoor coils to these units.
2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length), refer to the Long Line Applications Guideline.
Install Liquid Line Filter Drier Indoor Refrigerant Tubing Connection Outdoor
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Installation of filter drier in liquid line is required. Filter drier must be wrapped in a heat-sinking material such as a wet cloth while brazing.
Refer to Fig. 3 and install filter drier as follows:
1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to above 5 in. (127 mm) liquid tube. Flow arrow must point towards indoor coil.
4. Connect and braze liquid refrigerant tube to the filter drier.
Figure 3 J Liquid Line Filter Drier
Yes(Standardwith factory approved Yes (Standardwithfactory approved in- Yes (Standardwith factoryap-
No No No
indoorunit) door unit) provedindoor unit)
RATEDVAPOR
LIQUID up to 80ft, (24,38 m)*
Connectionand Tube Connection RatedTube
Connect vapor and liquid tubes to fittings on vapor and liquid
service valves (seeTable 2.) Userefrigerant grade tubing. Sweat Connection
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Service valves must be wrapped in a heat-sinking material such as a wet cloth.
Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, braze sweat connections using industry accepted methods and materials.
Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all
field and factory joints.
Evacuate Refrigerant Tubing and Indoor Coil
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Never use the system compressor as a vacuum pump.
4 specificationssubjectto change without notice. 421 01 1702 04
Refrigeranttubesandindoorcoilshouldbeevacuatedusingthe recommendeddeepvacuummethodof 500microns.Ifdeep
vacuum equipmentis notavailable,thealternatetriple evacuationmethodmaybeusedbyfollowingthespecified
procedure.Ifvacuummustbeinterruptedduringtheevacuation procedure,alwaysbreakvacuumwithdrynitrogen.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of
accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air
and liquid water. (See Fig. 4)
Figure 5 _ Triple Evacuation Sequence
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
Figure 4 [ Deep Vacuum Graph
IN
SYSTEM
VACUUM TIGHT TOO WET
TIGHT DRY SYSTEM
0 1 2 3 4 5 6 7
MINUTES
Triple Evacuation Method The triple evacuation method should only be used when system
does not contain any water in liquid form and vacuum pump is only capable of pulling down to 28 inches of mercury (711mm
Hg). Refer to Fig.5 and proceed is as follows:
1. Pull system down to 28 inches of mercury (711mm Hg) and allow pump to continue operating for an additional 15
minutes.
2. Close manifold valves or valve at vacuum pump and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and fill
with nitrogen until system pressure is 2 psig.
4. Close nitrogen valve and allow system to stand for 1 hour. During this time, dry nitrogen will diffuse throughout the
system absorbing moisture.
5. Repeat this procedure as indicated in Figure 5.
6. After the final evacuate sequence, confirm there are no leaks in the system. If a leak is found, repeat the entire
process after repair is made.
WAIT
EVACUATE
CHECK FOR TIGHT, DRY SYSTEM I
(IF IT HOLDS DEEP VACUUM
CHARGE SYSTEM
Final Tubing Check IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.
Make Electrical Connections
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do not supply power to unit with compressor terminal box cover removed.
Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit
protection device. NOTE: Operation of unit on improper line voltage constitutes
abuse and could affect unit reliability. See unit rating plate. Do not install unit in system where voltage may fluctuate above or below permissible limits.
NOTE: Use copper wire only between disconnect switch and unit. NOTE: Install branch circuit disconnect of adequate size per NEC
to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440-14 of NEC.
Route Ground and Power Wires Remove access panel to gain access to unit wiring. Extend wires
from disconnect through power wiring hole provided and into unit control box.
I
421 01 1702 04 Specifications subject to change without notice. 5
ELECTRICALSHOCKHAZARD
Failure to follow this warning could result in personal injury or death.
The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist
of electrical wire or metal conduit when installed in accordance with existing electrical codes.
Connect Ground and Power Wires
Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig.6.
Figure 6 J
DISCONNECT PER N. E. C. AND/OR LOCAL CODES
Line Power Connections
CONTACTOR
FIELD POWER I
WIRING
@°@
Install Electrical Accessories
Refer to the individual instructions packaged with kits or accessories when installing.
Check OAT Thermistor and OCT Thermistor Attachments
Outdoor Air Temperature (OAT) Thermistor is factory installed by inserting the nibs on either sides of the thermistor body through a
keyhole in the bottom shelf of the control box and locking it in place by turning it 90 degrees, such that the spherical end of a nib faces the front of the control box.
Check to make sure the OAT is locked in place. See Fig. 7.
I
Figure 7 J Outdoor Air Thermistor (OAT) Attachment
OATThermistormust be locked in place with spherical nib end facing
towardsthe front of the control box.
FIELD GROUND
®
WIRING I
Connect Control Wiring This unit is capable of communication with an Observer Wall
Control, or will operate using standard 24v 2-stage thermostat.
Route 24v control wires through control wiring grommet and
connect leads to control board. When an Observer Wall Control is available, connect DX+ and DX- connections only. If additional
grounding is needed connect to C terminal. If a 2-stage thermostat is used, connect to the C, Y1, and Y2 connections.
Refer to the wiring label for further clarification. Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If
thermostat is located more than 100 ft. (30.48 m) from unit, as measured along the control voltage wires, use No. 16 AWG color-coded, insulated wire to avoid excessive voltage drop.
All wiring must be NEC Class 1 and must be separated from
incoming power leads. Use furnace transformer, fan coil transformer, or accessory
transformer for control power, 24-v/40-va minimum.
NOTE: Use of available 24-v accessories may exceed the
minimum 40-va power requirement. Determine total transformer
load and increase the transformer capacity or split the load with
an accessory transformer as required.
Final Wiring Check
IMPORTANT: Check factory wiring and field wire connections to ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing, sheet metal, etc.
Compressor Crankcase Heater
When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit if ambient is less than
65°F (18°C). To furnish power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than 80 ft. (24.38 m). Refer to the Long Line Applications Guidelines.
GROUND LUG
Specifications subject to change without notice. 421 01 1702 04
The Outdoor Coil Temperature (OCT) Thermistor is factory installed on the liquid tube between the coil assembly and the
liquid service valve. See Fig. 8. Check to make sure the thermistor is securely attached on the
liquid tube with the clip as shown in Fig. 8.
Figure 8 J Outdoor Coil Thermistor (OCT) Attachment
OCT Thermistor must be secured tight on the liquid tube.
Airflow Setup with Observer Communicating Furnace or Fan Coil
When using an Observer Communicating Wall Control and communicating indoor equipment, airflow is automatically
selected based on equipment size. See Observer Wall Control Installation Instructions and indoor specification sheet for
available adjustments. Airflow Setup with Non-Communicating Furnace or
Fan Coil Two-stage compressor operation requires two different indoor
airflow settings for proper operation. This outdoor unit is designed for use only with an indoor blower that can be configured for
separate low-stage and high-stage airflow (CFM) levels. Refer to
Product Specifications Sheets for recommended low-stage and high-stage indoor airflow values.
Refer to indoor unit Installation Instructions to set the indoor
blower for the proper low-stage and high-stage airflow values.
NOTE: Optimal comfort, efficiency, and reliability will only be
achieved when the indoor airflow is properly set for both
low-stage and high-stage operation.
START-UP
UNIT OPERATION AND SAFETY HAZARD Failure to follow this caution may result in minor personal
injury, equipment damage or improper operation. To prevent compressor damage or personal injury,
observe the following:
Do not overcharge system with refrigerant.
Do not operate unit in a vacuum or at negative pressure.
Do not disable low pressure switch in scroll compressor applications.
Dome temperatures may be hot.
PERSONAL INJURY HAZARD Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when handling refrigerant and observe the following:
Front seating service valves are equipped with Schrader valves.
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental damage.
Federal regulations require that you do not vent refrigerant to the atmosphere. Recover during system repair or final unit disposal.
Follow these steps to properly start up the system:
1. After system is evacuated, fully open liquid and vapor service valves.
2. Unit is shipped with valve stem(s) front seated (closed) and caps installed.
Replace stem caps after system is opened to refrigerant
flow. Replace caps finger-tight and tighten with wrench an additional 1/12 turn
3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature. Be sure set point is below indoor ambient temperature.
5. Set room thermostat to COOL and fan control to ON or
AUTO mode, as desired. Operate unit for 15 minutes.
Check system refrigerant charge.
Check Charge Two-stage equipment must be charged in high stage compressor
operation only.
Factory charge amount and desired subcooling are shown on unit rating plate. Charging method is shown on information plate
inside unit. To properly check or adjust charge, conditions must
421 01 1702 04
Specifications subject to change without notice. 7
be favorable for subcooling charging. Favorable conditions exist when the outdoor temperature is between 70°F and 100°F
(21.11 °C and 37.78°C), and the indoor temperature is between 70°F and 80°F (21.11°C and 26.67°C). Follow the procedure
below: Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge
by adding or removing 0.6 oz/ft of 3/8 liquid line above or below 15ft (4.57 m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less), allow system to operate in cooling mode at least 15 minutes. When
operating with the Observer Wall Control in communicating mode, make sure that indoor airflow is set to the final operating selection
(Eft 325, Elf 350, Comfort, Maximum) during charging. If conditions are favorable, check system charge by subcooling method. If any adjustment is necessary, adjust charge slowly and
allow system to operate for 15 minutes to stabilize before declaring a properly charged system.
If the indoor temperature is above 80°F (26.67°C), and the outdoor temperature is in the favorable range, adjust system
charge by weight based on line length and allow the indoor temperature to drop to 80°F (26.67°C) before attempting to check
system charge by subcooling method as described above. If the indoor temperature is below 70°F (21.11 °C), or the outdoor
temperature is not in the favorable range, adjust charge for line set length above or below 15ft (4.57 m) only. Charge level should then be appropriate for the system to achieve rated capacity. The
charge level could then be checked at another time when the both indoor and outdoor temperatures are in a more favorable
range. NOTE: The Observer Wall Control has a staging timer, to override
the staging timer for charging in high-stage create at least a 5 degree difference between room and set point temperatures and
hold the "Cool To" button for 10 seconds on the thermostat home screen.
NOTE: If line length is beyond 80 ft (24.38 m) or greater than 20 ft (6.10 m) vertical separation, See Long Line Applications Guideline
for special charging requirements. SYSTEM FUNCTIONS AND SEQUENCE OF
OPERATION The *CA9 and *CA7 models utilize either an Observer
Communicating Wall Control or a 2-stage cooling thermostat. With a call for first stage cooling, the outdoor fan and low-stage
compressor are energized. If low-stage cannot satisfy cooling demand, high-stage is energized by the second stage of the
indoor thermostat. After second stage is satisfied, the unit returns to low-stage operation until first stage is satisfied or until second
stage is required again. When both first stage and second stage cooling are satisfied, the compressor will shut off. When a 2-stage
unit is operating at low-stage, system vapor (suction) pressure will be higher than a standard single-stage system or high-stage operation. When the outdoor ambient is more than 100°F
(37.8°C), the outdoor fan will continue to run for one minute after compressor shuts off, this reduces pressure differential for easier
starting in the next cycle. Communication and Status Function Lights
Green communications (COMM) Light (Only with Observer Communicating Wall Control)
A green LED (COMM light) on the outdoor board indicates successful communication with the other system products. The
green LED will remain OFF until communications is established. Once a valid command is received, the green LED will turn ON
continuously. If no communication is received within 2 minutes, the LED will be turned OFF until the next valid communication.
Amber Status Light (STATUS)
An amber colored STATUS light is used to display the operation mode and fault codes as specified in the troubleshooting section.
See Table 6 for codes and definitions.
NOTE: Only one code will be displayed on the outdoor unit control
board (the most recent, with the highest priority).
Utility Interface with Non-Communicating Thermostat
The utility curtailment relay should be wired in the Y2 thermostat
lead. This allows a power utility device to interrupt high stage
compressor operation during peak load periods. If the utility
requires control of low stage compressor operation a second
utility curtailment relay should be wired in the Y1 lead.
NOTE: Utility curtailment is not available when operating in communicating mode. To apply utility curtailment with the Observer Wall Control you must use a daughter board kit to convert the control signals to standard thermostat signals.
Compressor Operation The basic scroll design has been modified with the addition of an
internal unloading mechanism that opens a by-pass port in the first compression pocket, effectively reducing the displacement of
the scroll. The opening and closing of the by-pass port is controlled by an internal electrically operated solenoid. The
modulated scroll uses a single step of unloading to go from full capacity to approximately 67% capacity. A single speed, high
efficiency motor continues to run while the scroll modulates between the two capacity steps. Modulation is achieved by
venting a portion of the gas in the first suction pocket back to the
low side of the compressor, thereby reducing the effective displacement of the compressor. Full capacity is achieved by
blocking these vents, thus increasing the displacement to 100%. A DC solenoid in the compressor controlled by a rectified 24 volt
AC signal in the external solenoid plug moves the slider ring that covers and uncovers these vents. The vent covers are arranged
in such a manner that the compressor operates at approximately 67% capacity when the solenoid is not energized and 100%
capacity when the solenoid is energized. The loading and unloading of the two step scroll is done "on the fly" without shutting off the motor between steps.
NOTE: 67% compressor capacity translates to approximately 75% cooling capacity at the indoor coil. The compressor will always start unloaded and stay unloaded for five seconds even when the thermostat is calling for high-stage capacity.
Crankcase Heater Operation The crankcase heater is de-energized when the compressor is
running. The crankcase heater is energized when the compressor is off and the ambient is less than 42 ° F. When the
ambient temperature is between 65° F and 42 ° F the crankcase
heater is energized 30 minutes after the compressor is turned off. When the ambient is above 65 ° F the crankcase heater remains
de-energized after the compressor is turned off.
Outdoor Fan Motor Operation
The outdoor unit control energizes the outdoor fan any time the compressor is operating. The outdoor fan remains energized if a
pressure switch or compressor overload should open. Outdoor fan motor will continue to operate for one minute after the
compressor shuts off when the outdoor ambient is greater than or equal to 100°F (37.8°C) to allow for easier starting during next
cooling cycle.
On *CA7 models - The outdoor fan motor is a PSC type. A fan relay on the control board turns the fan off and on by opening and
closing a high voltage circuit to the motor. It does not change speeds between low and high stage operation.
On *CA9 models - The outdoor fan is an ECM type. The motor control is continuously powered with high voltage. The motor
speed is determined by electrical pulses provided by the PWM outputs on the control board. The ECM motor RPM adjusts to
outdoor conditions as described in Table 3. The PWM output can be measured between the PWM1 and PWM2 terminals on the
circuit board with a volt meter set to DC volts.
Table 3 - Outdoor Fan Motor PWM
Outdoor Temp (DC volts, Tolerance +/- 2%)
Model Low-Stage High Stage Low & High Stage
Size OAT _104OF/40oc OAT_ 104OF/40oc OAT> 104OF/40oc
*CA924 9.57 10.88 11.90 *CA936 9.06 10.23 11.90 *CA948 9.91 11.04 11.90 *CA960 10.83 11.70 11.90
Time Delays The unit time delays include:
Five minute time delay to start cooling operation when there is a call from the thermostat or user interface. To
bypass this feature hold the "Cool To" or "Heat To" button on the Observer Wall Control for 10 seconds.
Five minute compressor re-cycle delay on return from a
brown-out condition.
Two minute time delay to return to standby operation from
last valid communication (Observer Communicating Wall Control only).
One minute time delay of outdoor fan at termination of
cooling mode when outdoor ambient is greater than or equal to 100°F (37.8°C).
There is no delay between staging from low to high and from high to low capacity. The compressor will change from
low to high and from high to low capacity "on the fly" to meet
the demand.
TROUBLESHOOTING If the compressor fails to operate with a cooling call, Table 4 can
be used to verify if there is any damage to the compressor windings causing system malfunction.
Table 4 - Winding Resistance
Winding Resistance At 70°F +/- 20°F
(21.11°C +/- 11.11°C)
Winding 24 36 48 60
Start
(S-C) 1.64 1.52 1.86 1.63
Run
(R-C) 1.30 0.88 0.52 0.39
Systems Communication Failure
If communication with the Observer Communicating Wall Control will flash the appropriate fault code. (See Table 6) Check the
wiring to the wall control, indoor and outdoor units.
Model Plug
Each control board contains a model plug. The correct model plug must be installed for or the system to operate properly (see
Table 5).
8 Specifications subject to change without notice. 421 01 1702 04
Table 5 - Model Plug
Pin Resistance
Model
Number
*CA724 *CA736
*CA748 *CA760
*CA924 *CA936
*CA948 *CA960
Model Plug
Number
HK70EZ040 HK70EZ042
HK70EZ044 HK70EZ046
HK70EZ009 HK70EZ011
HK70EZ013 HK70EZ015
The model plug is used to identify the type and size of unit to the control.
On new units, the model and serial numbers are input into the
board's memory at the factory. Ifa model plug is lost or missing at initial installation, the unit wilt operate according to the information
input at the factory and the appropriate error code wilt flash
temporarily. A FAST® Parts replacement board contains no model and serial
information. If the factory control board fails, the model plug must be transferred from the original board to the replacement board
for the unit to operate.
NOTE: The model plug takes priority over factory model information input at the factory. If the model plug is removed after initial power up, the unit will operate according to the last valid model plug installed, and flash the appropriate fault code temporarily.
Pressure Switch Protection
The outdoor unit is equipped with high and low pressure switches.
If the control senses the opening of a high or low pressure switch, it will respond as follows:
1. De-energize the appropriate compressor contactor.
2. Keep the outdoor fan operating for 15 minutes.
3. Display the appropriate fault code (see Table 6).
4. After a 15 minute delay, if there is still a call for cooling and the LPS or HPS is reset, the appropriate compressor
contactor is energized.
5. If LPS or HPS has not closed after a 15 minute delay, the outdoor fan is turned off. If the open switch closes anytime
after the 15 minute delay, then resume operation with a call for cooling.
6. If LPS or HPS trips 3 consecutive cycles, the unit operation is locked out for 4 hours.
7. In the event of a high pressure switch trip or high pressure lockout, check the refrigerant charge outdoor fan operation
and outdoor coil for airflow restrictions.
8. In the event of a low pressure switch trip or low pressure lockout, check the refrigerant charge and indoor airflow.
Control Fault
If the outdoor unit control board has failed, the control will flash
the appropriate fault code. (See Table 6) The control board should be replaced.
Brown Out Protection If the line voltage is less than 187v for at least 4 seconds, the
appropriate compressor contactor and fan relay are de-energized. Compressor and fan operation are not allowed until voltage is a
minimum of 190v. The control will flash the appropriate fault code
(see Table 6) 230 V Brown Out Protection Defeated:
The brownout feature can be defeated if needed for severe noisy
power conditions. This defeat should always be a last resort to
solving the problem. Defeat can be initiated through the forced
421 01 1702 04
(kOhms)
Pin 1-4 Pin 2-3
18 75 18 120
18 180 18 270
5.1 91
5.1 150
5.1 220
5.1 360
Specifications subject to change without notice. 9
defrost pins as follows: The brownout toggle is accomplished by shorting the defrost pins
from power up with the OAT and OCT sensor connector removed. After 3 seconds, the status of the force defrost short and the
OAT/OCT as open will be checked. If correct, then the brownout wilt be toggled.
Status code 6 shows the brownout is disabled.
Status code 5 shows the brownout is active.
After the brownout defeat is set, power down and reinstall the OAT/OCT sensor and remove the short from the forced defrost
pins. As long as the short on the forced defrost remains, the OAT and OCT faults will not be cleared. The code will continue to be
flashed. The control is shipped with the brownout active. The change in
status is remembered until toggled to a new status. A power down/power up sequence will not reset the status. It may be
necessary to do the toggle twice to cycle to the desired state of the defeat.
230V Line (Power Disconnect) Detection
If there is no 230v at the compressor contactor(s) when the indoor unit is powered and cooling demand exists, the appropriate error
code is displayed (see Table 6). Verify that the disconnect is closed and 230v wiring is connected to the unit.
Compressor Voltage Sensing
The control board input terminals labeled VS and L2 (see Fig. 10) are used to detect compressor voltage status, and alert the user of potential problems. The control continuously monitors the high
voltage on the run capacitor of the compressor motor. Voltage should be present any time the compressor contactor is
energized, and voltage should not be present when the contactor is de-energized.
Contactor Shorted Detection
If there is compressor voltage sensed when there is no demand for compressor operation, the contactor may be stuck closed or
there is a wiring error. The control will flash the appropriate fault code.
Compressor Thermal Cutout
If the control senses the compressor voltage after start-up, and is then absent for 10 consecutive seconds while cooling demand
exists, the thermal protector is open. The control de-energizes the compressor contactor for 15 minutes, but continues to operate
the outdoor fan. The control Status LED will flash the appropriate code shown in
Table 6. After 15 minutes, with a call for low or high stage cooling, the compressor contactor is energized. If the thermal protector
has not reset, the outdoor fan is turned off. If the call for cooling continues, the control will energize the compressor contactor
every 15 minutes. If the thermal protector closes, (at the next 15 minute interval check), the unit will resume operation. If the
thermal cutout trips for three consecutive cycles, then unit operation is locked out for 4 hours and the appropriate fault code
is displayed.
No 230V at Compressor
If the compressor voltage is not sensed when the compressor should be starting, the appropriate contactor may be stuck open
or there is a wiring error. The control will flash the appropriate fault code. Check the contactor and control box wiring.
Troubleshooting units for proper switching between low & high stages
Check the suction pressures at the service valves. Suction pressure should be reduced by 3-10% when switching from low
to high capacity.
NOTE: The liquid pressures are very similar between low and high stage operation so liquid pressure should not be used for troubleshooting.
Compressor current should increase 20-45% when switching from low to high stage. The compressor solenoid, when
energized in high stage, should measure 24vac across pin
numbers PL5-2 HI and PL5-5 C. When the compressor is operating in low stage the 24v DC compressor solenoid coil is
de-energized. When the compressor is operating in high stage, the 24v DC solenoid coil is energized. The solenoid plug harness
that is connected to the compressor has an internal rectifier that converts the 24v AC signal to 24v DC.
NOTE: DO NOT INSTALL A PLUG WITHOUT AN INTERNAL RECTIFIER,
Unloader Test Procedure
The unloader is the compressor internal mechanism, controlled by the DC solenoid, that modulates between high and low stage.
If it is suspected that the unloader is not working, the following methods may be used to verify operation.
1. Operate the system and measure compressor amperage. Cycle the unloader on and off at 30 second plus intervals at
the Wall Control (from low to high stage and back to low stage). Wait 5 seconds after staging to high before taking a
reading. The compressor amperage should go up or down
at least 20 percent.
2. If step one does not give the expected results, remove the solenoid plug from the compressor and, with the unit
running and the Wall Control (or Thermostat) calling for high stage, test the voltage output at the plug with a DC
voltmeter. The reading should be 24 volts DC.
3. If the correct DC voltage is at the control circuit molded
plug, measure the compressor unloader coil resistance.
The resistance should be approximately 330 or 1640 ohms
depending on unloader coil supplier. If the coil resistance is infinite or is grounded, the compressor must be replaced.
MAJOR COMPONENTS
2-Stage Control
The 2-stage control board controls the following functions:
-- Compressor high and low stage operation
-- Outdoor fan motor operation
-- Compressor external protection
-- Pressure switch monitoring
-- Time delays
Field Connections
On models with non-communicating (Thermostat other than Observer Wall Control) system, the 2-stage control receives
24vac low-voltage control system inputs through the Y1, and Y2
connections located at the bottom of the control board (see Fig.
10). The OD units can be controlled using a standard 2-stage thermostat or Observer Wall Control.
2-Stage Compressor
The 2-stage compressor contains motor windings that provide 2-pole (3500 RPM) operation. Refer to Table 4 for correct winding resistance.
Compressor Internal Relief
The compressor is protected by an internal pressure relief (IPR) which relieves discharge gas into compressor shell when
differential between suction and discharge pressures exceeds 550 - 625 psig The compressor is also protected by an internal
overload attached to motor windings.
Compressor Control Contactor
The contactor has a 24 volt coil. The electronic control board controls the operation of the appropriate contactor.
TEMPERATURE THERMISTORS
Thermistors are electronic devices which sense temperature. As the temperature increases, the resistance decreases. Thermistors
are used to sense outdoor ambient (OAT) and coil temperature (OCT). Refer to Fig. 9 for resistance values versus temperature. If the outdoor ambient or coil thermistor should fail, the control will
flash the appropriate fault code (see Table 6.)
IMPORTANT: Outdoor air thermistor and coil thermistor are
factory mounted in the final locations. Check to insure thermistors are mounted properly per Fig.7 and Fig.8.
Thermistor Sensor Comparison
The control continuously monitors and compares the outdoor air temperature sensor and outdoor coil temperature sensor to
ensure proper operating conditions. The comparison is:
-- If the outdoor air sensor indicates 10°F (5.56°C) warmer than the coil sensor (or) the outdoor air sensor indicates 20°F (11.1 °C) cooler than the coil sensor, the sensors are out of range.
-- If the sensors are out of range, the control will flash the appropriate fault code as shown in Table 6.
-- The thermistor comparison is not performed during low ambient cooling or defrost operation.
Failed Thermistor Default Operation
Factory defaults have been provided in the event of failure of outdoor air thermistor and/or coil thermistor. If the OAT sensor
should fail, low ambient cooling will not be allowed and the one minute outdoor fan-off delay will not occur. If the OCT sensor
should fail, low ambient cooling will not be allowed.
OAT Thermistor must be locked in place with spherical nib end facing towards the front of the
control box.
10 Specificationssubjectto change without notice. 421 01 1702 04
Table 6 - Status Codes
OPERATION FAULT Possible Cause and Action
Standby- no call for unit operation None On solid, no flash Normal operation Low Stage Cool/Heat Operation None 1, pause Normal operation High Stage Cool/Heat Operation None 2, Pause Normal operation
Brown out protection is Disabled None 5, pause User mode selection, see instructions for more detail Brown out protection is Active None 6, Pause User mode selection, see instructions for more detail
System Communications 16 Communication with Observer Wall Control lost. Check wiring to
Failure Observer Wall Control, indoor and outdoor units
Invalid Model Plug 25
High Pressure 31" High pressure switch trip. Check refrigerant charge, outdoor fan
Switch Open operation and coils for airflow restrictions.
Low Pressure
Switch or Discharge Temp 32* refrigerant charge and indoor air flow
Switch Open
Control Fault 45 replaced.
Brown Out 46 Line Voltage <187v for at least 4 seconds. Compressor and fan
(230 v) operation not allowed until voltage > 190v. Verify line voltage.
No 230v at Unit 47 cooling/heating demand exists. Verify the disconnect is closed and
Outdoor Air Temp Sensor 53 Outdoor air sensor not reading or out of range. Ohm out sensor and
Outdoor Coil Sensor Fault 55 Coil sensor not reading or out of range. Ohm out sensor and check
*Sequence: Compressor contactor is de-energized and outdoor fan is energized for up to 15 minutes. If demand still exists, control will energize compressor.
Fault check wiring
Thermistors out 56 Improper relationship between coil sensor and outdoor air sensor.
of range Ohm out sensors and check wiring.
Low Stage Compressor operation detected then disappears while low stage
Thermal Cutout 71" demand exists. Possible causes are internal compressor overload trip
High Stage Compressor operation detected then disappears while high stage
Thermal Cutout 72* demand exists. Possible causes are internal compressor overload trip
Contactor Shorted 73 operation exists. Contactor may be stuck closed or there is a wiring
No 230V at Compressor voltage not sensed when compressor should be starting.
Compressor wiring error.
Low Stage Thermal 82 Thermal cutout occurs in three consecutive low/high cycles. Low stage
Lockout locked at for 4 hours or until 24v power recycled.
High Stage Thermal 82 Thermal cutout occurs in three consecutive low/high cycles. High
Lockout stage locked out for 4 hours or until 24v power recycled.
Low Pressure Lockout 83
High Pressure 84 High pressure switch trip has occurred during 3 consecutive cycles.
Lockout Unit operation locked out for 4 hours or until 24v power recycled.
AMBER LED
FLASH CODE
Control does not detect a model plug or detects and invalid model
plug. Unit will not operate without correct model plug.
Low pressure switch or discharge temperature switch trip. Check
Outdoor unit control board has failed. Control board needs to be
There is not 230v at the contactor when indoor unit is powered and
230v wiring is connected to the unit.
wiring
or start relay and capacitor held in circuit too long (if installed)
or start relay and capacitor held in circuit too long (if installed)
Compressor voltage sensed when no demand for compressor
error.
74 Disconnect may be open or contactor may be stuck open or there is a
Low pressure switch trip has occurred during 3 consecutive cycles.
Unit operation locked out for 4 hours or until 24v power recycled.
421 01 1702 04 specificationssubjectto change without notice. 11
Figure 9 J
Resistance vs Temperature Chart
THERMISTOR CURVE
90 804
(-17.77) (-6.67) (4.44) (15.56) (26.67) (37.78) (48.89)
4 t I t I
O 20 40 60 80 100 120
Figure 10 J Two-Stage Control Board
] T F F
TEMPERATURE °F (°C)
0,250
0._0
0,0&2 +1- .0075
__J
ALL DIMENSIONS ARE IN INCHES
12 specificationssubjectto change without notice. 421 01 17'02 04
Figure 11
ObserverCommunicatingWallControlFour-WireConnectionWiringDiagrams
(See Thermostat Installation Instructions for specific unit combinations)
Wall Control Furnace/Fan Coil Outdoor
Green
Yellow
White
Red
Room Sensor Humidifier
-- Connection
.Optional Remote .._
Variable Speed
_ Green _
Yellow_,q
HUM
COM
-- 24V FACTORY WIRING
..... 24V FIELD WIRING
FIELD SPLICE CONNECTION
Variable Speed Furnace with
Figure 12 Two-Stage Air Conditioning
Indoor Control Fan Coil
Heat Stage 2 Heat Stage 11_'
Cool Stage 1 f'_"
Cool Stage 2 I--_-_.
Fan
24 VAC Hot
J FVM Fan Coil Wiring With
Two-Stage Air Conditioner
I
Remove J2 Jumper For Heat Staging
I Y/Y2 II
BDD
BDD
-J-_l .4--_1
Figure 13 Two-Stage Air Conditioner
ICP Thermostat
LEGEND
Variable Speed
Furnace
. __1-"_
__1--_-" _ __
--E3
--12D
Two-Stage Heat Pump
Dehumidify fD"_'_.
24 VAC Comm
Humidify
RVS Heatingr__
Outdoor t( _
BDD
BDD
__ Humidifier
__ Outdoor
,-I, H i i
/ (24VAC) /
/ Sensor I J
D HUM
OUTDOOR
SENSOR
421 01 1702 04 specificationssubjectto change without notice. 13
Figure 14 Observer Communicating Wall Control
Non-Communicating Indoor Unit with
Wall
Control
NAXA00101DB
Green
Red ,_
White "C_
Yellow ,_
Communicating
Outdoor
"C_'
----A--
I- q GD
____A__r-
Non-Communicating
Indoor
Note: This installation requires the daugh- ter board accessory, NAXA00101DB. _o
Note: This installation does not allow for OAT communicating feature functionality.
Final Checks
IMPORTANT: Before leaving job, be sure to do the following:
1. Ensure that all wiring is routed away from tubing and sheet metal edges to prevent rub-- through or wire pinching.
2. Ensure that all wiring and tubing is secure in unit before adding panels and covers. Securely fasten all panels and
covers.
3. Tighten service valve stem caps to 1/12--turn past finger tight.
4. Leave Owner's Manual with owner. Explain system
operation and periodic maintenance requirements outlined in manual.
L'O
OAT
Sensor
CARE AND MAINTENANCE
For continuing high performance and to maintain warranty coverage, periodic maintenance must be performed on this
equipment. Frequency of maintenance may vary depending upon geographic areas, such as coastal applications. See
Owner's Manual for information.
14 specificationssubjectto change without notice. 421 01 1702 04
R-410A QUICK REFERENCE GUIDE
R-410A refrigerant operates at 50% - 70% higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with R-410A.
R-410A refrigerant cylinders are rose colored.
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when charging into suction line with compressor operating.
° Manifold sets should be 750 psig high-side and 200 psig low-side with 520 psig low-side retard.
° Use hoses with 750 psig service pressure rating.
° Leak detectors should be designed to detect HFC refrigerant.
° R-410A, as with other HFC refrigerants, is only compatible with POE oils.
° Vacuum pumps will not remove moisture from oil.
° Do not use liquid line filter-driers with rated working pressures less than 600 psig.
° Do not install a suction line filter-drier in liquid line.
° POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
° POE oils may cause damage to certain plastics and roofing materials.
° Wrap all filter-driers and service valves with wet cloth when brazing.
° A liquid line filter-drier is required on every unit.
° Do not use with an R-22 TXV.
° If indoor unit is equipped with an R-22 TXV, it must be changed to an R-410A TXV.
° Never open system to atmosphere while it is under a vacuum.
° When system must be opened for service, break vacuum with dry nitrogen and replace all filter-driers. Evacuate to 500 microns before recharging.
° Do not vent R-410A into the atmosphere.
° Do not use capillary tube indoor coils.
° Observe all WARNINGS, CAUTIONS, NOTES, and bold text.
421 01 1702 04 Specificationssubjectto change without notice. 15
16
Specifications subject to change without notice. Copyright 2015 International Comfort Products
Lewisburg, TN 37091 USA
421 01 1702 04
Loading...