80+ GAS FURNACE
Category I Furnace
*8MPT Two-Stage Heating
*8MPV Variable Speed, Two-Stage Heating & Supports
Two- Stage Cooling Units * Denotes Brands (C, R, T)
See Section 5 for Category ! definition.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or
other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency,
or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits
or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when
installing.
Follow att safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing
operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit. Consult local building codes, the current editions of the National Fuel Gas
Code (NFCG) NFPA 54/ANSI Z223.1, and the National Electrical Code (NEC) NFPA 70.
In Canada refer to the current editions of the National standards of Canada CAN/CSA-B149.1 and .2 Natural Gas and
Propane Installation Codes, and Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety-alert symbol z_. When you see this symbol on the unit and in instructions
or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and
CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will
result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death.
CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage.
NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
International Comfort Products, LLC
Lewisburg, TN.37091
1.SafeInstallationRequirements.................. 4
2.Installation................................. 5
3.SideVenting................................ 8
4.Combustion&VentilationAir ................... 9
5.GasVentInstallation ......................... 12
6.HorizontalVenting ........................... 13
7.ChimneyAdapterVenting...................... 15
8.GasSupplyandPiping........................ 18
9.ElectricalWiring............................. 22
ELECTRIC SHOCK HAZARD
Failure to follow this warning
could result in personal injury
and/or death.
Turn Off All Power Before
Servicing.
Table of Contents
INSTALLER: Affix these instructions on or
adjacent to the furnace.
CONSUMER: Retain these instructions for
future reference.
10. Ductwork and Filter (Upflow/Horizontal) ......... 25
11. DuctworkandFilter(Downflow) ............... 27
12. ChecksandAdjustments .................... 30
13. FurnaceMaintenance....................... 33
14. SequenceofOperation&Diagnostic(*8MPT) ..... 34
15. WiringDiagram(*8MPT) ..................... 36
16. SequenceofOperation&Diagnostic(*8MPV) ..... 37
17. WiringDiagram(*8MPV) ..................... 39
18. ThermostatWiringGuide .................... 40
CARBON MONOXIDE POISONING AND FIRE
HAZARD.
Failure to follow this warning could result in
personal injury, death and/or property dam-
age.
This furnace is not designed for use in mobile
homes, trailers or recreational vehicles.
Portions of the text and tables are reprinted from NFPA 54 / ANSi Z223.1-2006@, with permission of National Fire Protection Association, Quincy, MA 02269 and American Gas Association
Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSi on the referenced subject which is represented only by the standard in its
entirety.
Specificationsare subject to changewithout notice 44101 202301 March2009
START-UP CHECK SHEET
For PSC Models *8MPT
(This sheet is optional. Keep for future reference.)
Date of Start-Up:.
Dealer Name:
Address:
City, State(Province), Zip or Postal Code:
Phone:
Owner Name:
Address:
City, State(Province), Zip or Postal Code:
Model Number:
Serial Number:
Setup Checks
Calculated Input (BTU) Rate: (See Checks and Adjust-
ments Section).
Heating Check
Measured Line Pressure During High Heat:
Measured Manifold Pressure: High Heat
Low Heat
Temperature of Supply Air:
Temperature of Return Air:
Temperature Rise (Supply - Return): High Heat __
In Rise Range (see furnace rating plate)?
Static Pressure (Ducts) High Heat:
The Blower Speed Tap used for:
Optional Check:
Cooling Check
High Heat
Low Heat
Low Heat
Supply
Return
High Heat
Low Heat
CO?
CO2?
Check the box when task is complete.
All Electrical Connections Tight? Lj
Manual Gas Shut-off Upstream of Furnace/Drip LegLU
Gas Valve turned ON? Lj
Type of Gas: Natural: Lj LP: Lj
Filter Type and Size:
Shade in Heating Fan "Time OFF" Setting and Thermo-
stat Type setting:
SWl
44101 202301 Specifications are subject to change without notice 2
Temperature of Supply Air:
Temperature of Return Air:
Temperature Difference:
Static Pressure (Ducts) Cooling:
Dealer Comments:
Supply
Return
CoolingThe Blower Speed Tap used for:
START-UP CHECK SHEET
For Variable Speed Models *8MPV
(This sheet is optional. Keep for future reference.)
Date of Start-Up:.
Dealer Name:
Address:
City, State(Province), Zip or Postal Code:
Phone:
Owner Name:
Address:
City, State(Province), Zip or Postal Code:
Model Number:
Serial Number:
Calculated Input (BTU) Rate: (See Checks and Adjust-
ments Section).
Heating Check
Measured Line Pressure During High Heat:
Measured Manifold Pressure: High Heat
Low Heat
Temperature of Supply Air:
Temperature of Return Air:
Temperature Rise (Supply - Return): High Heat __
In Rise Range (see furnace rating plate)?
Static Pressure (Ducts) High Heat: Supply
Optional Check:
High Heat
Low Heat
Low Heat
Return
CO?
Setup Checks
Check the box when task is complete.
All Electrical Connections Tight? Lj
Manual Gas Shut-off Upstream of Furnace/Drip Leg[--]
Gas Valve turned ON? Lj
Type of Gas: Natural: Lj LP: Lj
Filter Type and Size:
Shade in Final Furnace Settings Below:
SW1 [_
123
I=a D D el J; _-_ AC/HPEfficiencyBLOWER ADJUST HP Comfort
w2looooooDo1
1 234 5 678
J2
liP mode
select
Cooling Check
Temperature of Supply Air:
Temperature of Return Air:
Temperature Difference:
Static Pressure (Ducts) Cooling:
Dealer Comments:
CO2?
Supply
Return
3 Specificationsare subject to changewithout notice 44101 202301
1. Safe Installation Requirements
Seal around supply and return air ducts.
FIRE, EXPLOSION, AND
CARBON MONOXIDE
POISONING HAZARD
Improper adjustment,
alteration, service,
maintenance or installation could result in personal
injury, death and/or property damage.
Installation or repairs made by unqualified persons
could result in hazards to you and others.
Installation MUST conform with local codes or, in
the absence of local codes, with codes of all
governmental authorities having jurisdiction.
The information contained in this manual is
intended for use by a qualified service agency that is
experienced in such work, is familiar with all
precautions and safety procedures required in such
work, and is equipped with the proper tools and test
instruments.
NOTE: This furnace is design-certified by the CSA International
(formerly AGA and CGA) for installation in the United States and
Canada. Refer to the appropriate codes, along with this manual,
for proper installation.
• Use only the Type of gas approved for this furnace (see
Rating Plate on unit). Overfiring wilt result in failure of heat
exchanger and cause dangerous operation. (Furnaces
can be converted to Propane gas with approved kit.)
• Install this furnace only in a location and position as speci-
fied in "Installation" of these instructions.
• Provide adequate combustion and ventilation air to the
furnace as specified in "Combustion and Ventilation Air" of
these instructions.
Combustion products must be discharged outdoors. Con-
nect this furnace to an approved vent system only, as spe-
cified in "Combustion and Ventilation Air, Horizontal
Venting and Chimney Adapter Venting" of these instruc-
tions.
Never test for gas leaks with an open flame. Use a com-
mercially available soap solution made specifically for the
detection of leaks to check all connections, as specified in
"Gas Supply and Piping, Final Gas Piping Check" of these
instructions.
• Always install furnace to operate within the furnace's in-
tended temperature-rise range with a duct system which
has an external static pressure within the allowable range,
as specified in "Technical Support Manual" of these in-
structions. See furnace rating plate. C.
• When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space con-
taining the furnace, the return air shall also be handled by 1.
aduct(s) sealed to the furnace casing and terminating out-
side the space containing the furnace.
• A gas-fired furnace for installation in a residential garage 2.
must be installed as specified in "Installation" of these in-
structions.
• This furnace is not to be used for temporary heating of
buildings or structures under construction. See "Installa-
tion", item 10.
• This furnace is NOT approved for installation in mo-
bile homes, trailers or recreation vehicles.
Install correct filter type and size.
Unit MUST be installed so electrical components are pro-
tected from direct contact with water.
SafetyRules
Your unit is built to provide many years of safe and dependable
service providing itis properly installed and maintained. However,
abuse and!or improper use can shorten the life of the unit and
create hazards for you, the owner.
A,
The U.S. Consumer Product Safety Commission encourages
installation of carbon monoxide alarms. There can be various
sources of carbon monoxide in a building or dwelling. The
sources could be gas-fired clothes dryers, gas cooking
stoves, water heaters, furnaces, gas-fired fireplaces, wood
fireplaces.
Carbon monoxide can cause serious bodily injury and/or
death. Carbon monoxide or "CO" is a colorless and odorless
gas produced when fuel is not burned completely orwhen the
flame does not receive sufficient oxygen.
Therefore, to help alert people of potentially dangerous car-
bon monoxide levels, you should have a commercially avail-
able carbon monoxide alarm that is listed by a nationally
recognized testing agency in accordance with Underwriters
Laboratories Inc. Standard for Single and Multiple Station
Carbon Monoxide Alarms, ANSl/UL 2034 or the CSA 6.19-01
Residential Carbon Alarming Devices installed and main-
tained in the building or dwelling concurrently with the gas-
fired furnace installation (see Note below). The alarm should
be installed as recommended by the alarm manufacturer's
installation instructions.
B,
There can be numerous sources of fire or smoke in a building
or dwelling. Fire or smoke can cause serious bodily injury,
death, and/or property damage. Therefore, in order to alert
people of potentially dangerous fire or smoke, you should
have fire extinguisher and smoke alarms listed by Underwrit-
ers Laboratories installed and maintained in the building or
dwelling (see Note below).
Note: The manufacturer of your furnace does not test any alarms
and makes no representations regarding any brand or type
of alarms.
Toensure safe and efficient operation ofyour unit, you should
do the following:
Thoroughly read this manual and labels on the unit. This
wilt help you understand how your unit operates and the haz-
ards involved with gas and electricity.
Do not use this unit if any part has been under water. Im-
mediately call a qualified service technician to inspect the unit
and to replace any part of the control system and any gas
control which has been under water.
3. Never obstruct the vent grilles, or any ducts that provide
air to the unit. Air must be provided for proper combustion
and ventilation of flue gases.
44101 202301 Specifications are subject to change without notice 4
FrozenWaterPipe Hazard Ifyour furnace remains off for an extended time, the pipes in your
WATER DAMAGE TO PROPERTY HAZARD
Failure to protect against the risk of freezing could
result in property damage.
Do not leave your home unattended for long periods
during freezing weather without turning off water
supply and draining water pipes or otherwise
protecting against the risk of frozen pipes and
resultant damage.
Your furnace isdesigned solely to provide a safe and comfortable
living environment. The furnace is NOT designed to ensure that
water pipes will not freeze. It is equipped with several safety de-
vices that are designed to turn the furnace off and prevent it from
restarting in the event of various potentially unsafe conditions.
home could freeze and burst, resulting in serious water damage.
Ifthe structure wilt be unattended during cold weather you should
take these precautions.
1,
Turn off the water supply to the structure and drain the water
lines if possible and add an antifreeze for potable water to
drain traps and toilet tanks. Open faucets in appropriate
areas.
-or-
2. Have someone check the structure frequently during cold
weather to make sure it is warm enough to prevent pipes
from freezing. Instruct them on a service agency to call to
provide service, if required.
-or-
3. Install a reliable remote sensing device that wilt notify
somebody of freezing conditions within the home.
2. Installation
5,
Do NOT install furnace directly on carpeting, tile or other com-
bustible material other than wood flooring.
6.
CARBON MONOXIDE POISONING HAZARD
Failure to properly vent this furnace or other
appliances could result in personal injury or death.
If this furnace is replacing a previously common-
vented furnace, it may be necessary to resize the
existing vent system to prevent oversizing
problems for the other remaining appliances(s).
See Venting and Combustion Air Check in the Gas
Vent Installation section of this instruction.
Locationand Clearances
If furnace is a replacement, it is usually best to install the furnace
where the old one was. Choose the location or evaluate the exist-
ing location based upon the minimum clearance and furnace di-
mensions (Figure 1).
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in
personal injury or death.
Do NOT operate furnace in a corrosive atmosphere
containing chlorine, fluorine or any other
damaging chemicals, which could shorten furnace
life.
Refer to Combustion & Ventilation Air section,
Contaminated Combustion Air for combustion air
evaluation and remedy.
InstallationRequirements
1. Install furnace level.
2,
This furnace is NOT to be used for temporary heat of build-
ings or structures under construction.
3.
Install furnace as centralized as practical with respect to the
heat distribution system.
4.
Install the vent pipes as short as practical. (See Gas Vent
Installation section).
5 Specifications are subject to change without notice 44101 202301
Maintain clearance for fire safety and servicing. A front clear-
ance of 24" (610 mm) is minimum for access to the burner,
controls and filter. See clearance requirements in Figure 1.
7,
Use a raised base ifthe floor isdamp or wet at times.
8.
Residential garage installations require:
Burners and ignition sources installed at least 18" (457 mm)
above the floor.
Furnace must be located or physically protected from pos-
sible damage by a vehicle.
9,
If the furnace is to be suspended from the floor joists in a
basement or a crawl space or the rafters in an attic, it is nec-
essary to use steel pipe straps or an angle iron frame to rigidly
attach the furnace to prevent movement. These straps
should be attached to the furnace with sheet metal screws
and to the rafters or joists with bolts. The preferred method is
to use an angle iron frame bolted to the rafters or joists.
10. This furnace may be used for construction heat provided that:
The furnace is permanently installed with all electrical
wiring, piping, venting and ducting installed according to
these installation instructions. A return air duct is pro-
vided, sealed to the furnace casing, and terminated out-
side the space containing the furnace. This prevents a
negative pressure condition as created bythe circulating
air blower, causing a flame rollout and/or drawing com-
bustion products into the structure.
The furnace is controlled by a thermostat. It may not be
"hot wired" to provide heat continuously to the structure
without thermostatic control.
Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and
other construction materials. It also prevents the en-
trainment of drywall dust into combustion air, which can
cause fouling and plugging of furnace components.
The temperature of the return air to the furnace is main-
tained between 55 ° F (13 ° C) and 80° F (27 ° C), with no
evening setback or shutdown. The use of the furnace
while the structure is under construction is deemed to be
intermittent operation per our installation instructions.
The air temperature rise is within the rated rise range on
the furnace rating plate, and the firing rate has been set
to the rating plate value.
The filters used to clean the circulating air during the °
construction process must be either changed or thor-
oughly cleaned prior to occupancy.
The furnace, ductwork and filters are cleaned as neces-
sary to remove drywall dust and construction debris from
all HVAC system components after construction is com-
)leted.
After construction is complete,verify proper furnace op-
erating conditions including ignition, gas input rate, air
temperature rise, and venting according to these instal-
lation instructions.
Dimensions and Clearances (*8MPT/*8MPV)
TOP
I , eate *
;iiii!!,i
i
r
.... / ......
5 (127)
.......................................................i
LEFT SIDE
(48)
_-_ 265/8 (676) --_
, BOTTOM
i i J
i , /
J
'_- 231/8 (587) ,_, _- 41/16 (103)
c
(124)i
(25)
DIMENSIONAL INFORMATION
Furnace I Cabinet Top Bottom I ReturnAir
Capacity 15A/2 1B4 6F 1c I o IOpening3/8126/8
*8MPTN050B (76) (356) (1.4) 1(321) 1 H
*8MPTN075F14 191!8 171/2 73/4 21/8 143/4 [
*8MPT100F14 (486) (445) (54) 1(15) I d
*8MPTN100J20 223/4 211/4 91/2 115/16 183/4 j
I I
(152)
(197)
*8MPTN125J20 (578) (540) (241) (49) (476)
* Denotes Brand
Drawingisrepresentative,butsomemodelsmayvary
!
24"(610)min,
ALL DIMENSIONS-IN(MM)
1in =25.4 mm
i _te,_
........................A ..............._
-- B "ii
;J :t /
i ......................................................._
in(mm)
COMBUSTIBLE MATERIALS FOR ALL UNITS
REAR 0
FRONT (combustion air openings in 3" (76 mm)
furnace and in structure)
Required For Service
ALL SIDES Of SUPPLY PLENUM
SIDES
VENT
Single Wall Vent 6" (152 mm)
Type B-1 Double Wall Vent 1" (25 mm)
TOP OF FURNACE 1" (25 mm)
*30" (762ram)clearancerecommendedforfurnaceremoval,
Horizontal)osition:Linecontactispermissibleonlybetweenlines
formedby intersectionsoftopand twosidesof furnacejacket,and
buildingjoists,studsorframing,
MINIMUM CLEARANCES TO
*24" (610 ram)
1" (25 mm)
_o, 281/2 (724) ,_
133/4 (95) _-_ 181/_ 470 _
r_ _ i _ / 3/4 (19)
2 4 /
i ...............................................................................,
(9!o)_
37i
(851)
33 ]i
1) i ...................
3
14 _ I? 1/4-.......................(57!
(749) 1
291/_ Plugged starting hole 131/4 i i i
(440) to cut side duct opening. (337)
i 1'75/16 ....... i i ;
13/4 .... _
(45) _ (124) 261/2 (673)
NOTE:Evaporator"A" coildrainpan dimensions may vary from furnace ductopening size.Always
consultevaporator specificationsfor ductsize requirements.
Furnaceis designedfor bottom return or side return,
Returnairthroughback offurnace isNOT allowed.
7 40
(!7a)_ 0o16)
=47/a _ 215/8 (542) i " 17/8 (48)
0
InstallationPositions
This furnace can be installed in an upflow, horizontal (either teft or
right) or downflow airflow position. DO NOT install this furnace on
its back. For the upflow position, the return air ductwork can be at-
tached to either the left or right side panel and/or the bottom. For
horizontal and downflow positions, the return air ductwork must be
attached to the bottom. The return air ductwork must never be at-
tached to the back of the furnace.
FurnaceInstallation
Inspect the rating plate to be certain the model number begins with
"*8MPV" or "*8MPT'. This identifies the unit as a multi-position
furnace and can be installed in a Upflow, Horizontal Right, Hori-
zontal Left or Downflow position.
Upflow
No modifications are required for upflow installation. (See
Figure 2)
44101 202301 Specifications are subject to change without notice 6
The horizontal furnaces may be installed directly on combustible
iiiiiiiiii!i!i T p,ca,up,,ow,nsta,,a,,on
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
wood flooring or supports, however, it is recommended for further
fire protection cement board or sheet metal is placed between the
furnace and the combustible wood floor and extend 12" (305 mm)
beyond the front of the furnace louver door. (This is a recommen-
dation only, not a requirement).
This furnace MUST NOT be installed directly on carpeting, tile or
other combustible material other than wood flooring or supports.
Downflow
FIRE HAZARD
Failure to install furnace on noncombustible
subbase could result in personal injury, death
Horizontal
If you purchased a multi-position furnace, it can be installed hori-
zontally inan attic, basement, crawl space, alcove, or suspended
from a ceiling in a basement or utility room in either a right or left
airflow position. (see Figure 3)
Horizontally installed furnaces may be vented out the top of the
unit or out the side facing up. See "Side Venting" for instructions
to rotate the vent to the side.
The minimum clearances to combustibles MUST be maintained
between the furnace and adjacent construction, as shown in
Figure 1. ONLY the corner of the cabinet is allowed to contact the
rafters Figure 3. All other clearances MUST be observed as
shown in Figure 1.
i:i iii
_iii_ i_i Typical Horizontal Installation
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
If the furnace is to be suspended from the floor joists in a crawl
space or the rafters in an attic, it is necessary to use steel pipe
straps or an angle iron frame to attach the furnace. These straps
should be attached to the furnace bottom side with sheet metal
screws and to the rafters or joists with bolts. The preferred method
is to use an angle iron frame bolted to the rafters or joists.
If the furnace is to be installed ground level in a crawl space, con-
sult local codes. A concrete pad 1"to 2" (25.4 to 50.8mm) thick is
recommended.
24" (610 mm) is recommended between the front of the furnace
and adjacent construction or other appliances. This should be
maintained for service clearance. 30" (762mm) is required to re-
move furnace.
Keep all insulating materials clear from Iouvered door. Insulating
materials may be combustible.
7 Specifications are subject to change without notice 44101 202301
and/or property damage.
Place furnace on noncombustible subbase on
downflow applications, unless installing on
noncombustible flooring.
The Multi-position furnace (*8MPT or*8MPV) may be installed in
a downflow configuration, (see Figure 4). The minimum clear-
ances to combustion MUST be maintained between the furnace
and adjacent constructions, as shown in Figure 1.
In addition to clearances in Figure 1, clearance for the vent pipe
must be considered.
A subbase for combustible floors MUST be used when the furnace
is installed as a downflow on combustible material. See "Duct-
work and Filter" (Downflow Section). The outlet flange must be
bent flat for downflow installation.
When installing a four-position furnace in the downflow position,
the logo isto be repositioned so that it is right side-up as follows:
T8MPT and T8MPV Model Numbers
1. Find the door hardware kit that is stored inthe furnace and
save it.
2. Carefully remove logo from the outside of burner compart-
ment door and save it.
3. Carefully remove two small plug buttons from outside of
blower compartment door and save them.
4. Remove two thumbscrews from blower compartment door.
Save the two thumbscrews.
5. Install two thumbscrews in holes at other end of blower
compartment door from where thumbscrews were re-
moved.
6. Install new strip of rubber gasket on inside of blower
compartment door on edge that does not already have a
gasket.
7. Install logo retainer pins into holes in blower compartment
door from which plug buttons were removed.
8. Install plug buttons into holes in burner compartment door
from which logo was removed.
9. Install blower compartment door on furnace with bevel
edge and logo at top.
10. Install burner compartment door on furnace with bevel
edge at bottom.
C8MPT, C8MPV, H8MPT, and H8MPV Model Numbers
1. Carefully remove logo from burner compartment door and
save it.
2. Turn the logo rightside-up, and install the logo retainer pins
into holes in burner compartment door
3. New labels for rightside-up application on outside of blower
compartment door may be purchased in akit from your dis-
tributor to cover upside-down labels.
T ,ca,oown.ow.nsta.a.,on
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
Downflow Venting: The combustion venter MUST be rotated to
vent out the side for all downflow installations, (see Figure 4). Bot-
tom venting is not permitted. See "Side venting" for instructions
to rotate the vent to the side. In addition to rotating the vent to the
side, a Vent Pipe Shield (NAHA002VC) is required to shield the
hot vent pipe.
PressureSwitch Relocation
If the furnace is installed in the upflow position, the pressure
switch will remain in the same position as installed by the factory
unless the inducer is rotated. If the furnace is installed in an orien-
tation that places the pressure switch below the pressure tap on
the inducer housing, then the switch MUST be relocated. In order
to relocate the switch, locate 2 mounting holes or drill above the
inducer pressure tap. When drilling the 2 holes make sure to keep
the switch and tubing far enough away from the burners or hot sur-
faces as to not melt the hose, switch, orwires. To prevent possible
kinking of the pressure switch hose, trim the hose to remove ex-
cess length (see Figure 5). If additional wire length is needed, cut
the wire tie.
Pressure Switch Tube Routing
PRESS SW ASSY (DUAL)
SCREW HEX HD (2)
i v
r
!
BURN HAZARD
Vent pipe is HOT and could result in personal
injury.
Hot vent pipe is in reach of small children when
installed in downflow position.
Install vent pipe shield NAHAOO2VC.
3. Side Venting
This furnace isshipped from the factory with the venter assembly
in an upflow configuration (top vent). The venter assembly can
easily be rotated to a side vent configuration for use in upflow, hori-
zontal-flow, or downflow application.
When using a side vent configuration (side outlet instead of top
outlet), it may be necessary to relocate the pressure switch to the
alternate position onthe opposite side ofthe top panel. Two screw
holes are provided at the alternate position. Route the pressure
switch tubing so the tubing is not kinked and not touching the hot
collector box, venter housing, or motor. It may be necessary to
shorten the length of the tubing to properly route the tubing and
eliminate kinks.
TUBTNG
2 STAGE/VARIABLESPEED
Note: When drilling new holes make sure metal shavings do not
fall on or in components, asthis can shorten the life of the furnace.
RotatingtheVenterAssembly
1. If gas and electrical power has already been connected to
unit, shut off gas and remove power from unit. Unscrew
screws on burner compartment door and remove burner
compartment door. (See Figure 6.)
2. Disconnect power leads to the venter motor and hose to pres-
sure switch. Remove four(4) screws which secure the venter
to the collector box. (See Figure 7.)
3. Cut webbing with a pair of snips holding the vent plate to the
cabinet on either the left or right side of unit depending on
right or left venting as desired. Discard vent plate, (see
Figure 6).
44101 202301 Specifications are subject to change without notice 8
iiiiiiii_iiiiii;iii!iiiiiiiiiii;iii_iii1iii_i1iiiii_i;iii!iiiii1iii!!_ii_iiiiIiiiiiiiii!iiiiiiiiiiii_iiii1;i1iiiiiiiiii_!i_iiii;1iii
l li/ l urnacew,t Screws
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
Vent Plate
Venter as et
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii....
4. Replace venter gasket (part # 1013540, if needed) to venter
assembly with adhesive in the same location as the old one.
5. Rotate venter assembly 90° right or left from original location
depending on venting configurations.
6. Tighten the four(4) screws that secure the venter assembly to
the collector box. Do not overtighten. Do tighten screws
enough to compress venter gasket.
7. Replace power leads to venter motor and reconnect hose to
pressure switch.
NOTE: Unused open vent hole must be covered. A Vent Cover is
supplied with Vent Pipe Shield Kit NAHA002VC. A 55/16"
(135mm) diameter Vent Cover can be fabricated with sheet metal
for all side vent installations.
4. Combustion & Ventilation Air
gens that will result in safety and performance related problems
and may harm the furnace. These instances must use only out-
CARBON MONOXIDE POISONING HAZARD
Failure to provide adequate combustion and
ventilation air could result in personal injury or
death.
Use methods described here to provide
combustion and ventilation air.
Furnaces require ventilation openings to provide sufficient air for
proper combustion and ventilation of flue gases. All duct or open-
ings for supplying combustion and ventilation air must comply with
the gas codes, or in the absence of local codes, the applicable na-
tional codes.
Combustion and ventilation air must be supplied in accordance
with one of the following:
1. Section 9.3, Air for Combustion and Ventilation, of the Nation-
al Fuel Gas Code, National Fuel Gas Code (NFGC), NFPA
54/ANSI Z223.1-2006 in the U.S.,
2,
Sections 8.2, 8.3, 8.5, 8.6, 8.7, and 8.8 of National Standard
of Canada, Natural Gas and Propane Installation Code
(NSCNGPIC), CSA B149.1-05 in Canada,
3. Applicable provisions of the local building code.
When the installation is complete, check that all appliances have
adequate combustion air and are venting properly. See Venting
And Combustion Air Check in "Gas Vent Installation" Section in
this manual.
ContaminatedCombustionAir
Installations in certain areas or types of structures could cause ex-
cessive exposure to contaminated air having chemicals or halo-
9 Specifications are subject to change without notice 44101 202301
door air for combustion.
The following areas or types of structures may contain or have ex-
posure to the substances listed below. The installation must be
evaluated carefully as it may be necessary to provide outdoor air
for combustion.
• Commercial buildings.
• Buildings with indoor pools.
• Furnaces installed in laundry rooms.
• Furnaces installed in hobby or craft rooms.
• Furnaces installed near chemical storage areas.
• Permanent wave solutions for hair.
• Chlorinated waxes and cleaners.
• Chlorine based swimming pool chemicals.
• Water softening chemicals.
• De-icing salts or chemicals.
• Carbon tetrachloride.
• Halogen type refrigerants.
• Cleaning solvents (such as perchloroethylene).
• Printing inks, paint removers, varnishes, etc..
• Hydrochloric acid.
• Sulfuric Acid.
• Solvent cements and glues.
• Antistatic fabric softeners for clothes dryers.
• Masonry acid washing materials.
OutdoorCombustionAirMethod
A space having less than 50 cubic feet per 1,000 BTUH (4.8cubic
meters per kW) input rating for all gas appliances installed in the
space requires outdoor air for combustion and ventilation.
Air Openings and Connecting Ducts
Requirements
1. Total maximum input ratings for all gas appliances in the
space MUST be considered when determining free area of
openings.
2. Connect ducts or openings directly to the outdoors.
3. When screens are used to cover openings, the openings
MUST be no smaller than 1/4" (6.4 mm) mesh.
4. The minimum dimension of air ducts MUST NOT be less
1. Provide confined space with sufficient air for proper com-
bustion and ventilation of flue gases using horizontal or ver-
tical ducts or openings.
2. Figure 8 illustrates how to provide combustion and ventila-
tion air when two permanent openings, one inlet and one
outlet, are used.
than 3" (76 mm).
5. When sizing grille, louver or screen, use the free area of a.
opening. If free area is NOT stamped or marked on grill or
louver, assume a 20% free area for wood and 60% for met-
One opening MUST commence within 12" (305 mm) of
the floor and the second opening MUST commence
within 12" (305 mm) of the ceiling.
al. Screens shall have a mesh size not smaller than 1/4"
(76mm). b. Size openings and ducts perTable 1.
Outdoor Air (This is ONLY a guide. Subject to codes of country having jurisdiction.)
ThisinstallationNOTapprovedinCanada
Gas Vent _,.Gable
/Ventilated AtticS.
T9pAbove Insulation_
I I] I sOffitVent
I I _ ITM
OutletAir (1)
JL I Io sl II I Air(l)
_u ,cI LI _t"_" ,._et
3"I I I'_-°'1 _ _ Air (2)
Minimum One Inletand One Outlet Air Supply is Required
Inlet Air Opening Must be Within12"(300mm} of floor
Outlet Air Opening Must be Within12"(300mm} of ceiling
(1} 1 Square Inch per4000 BTUH
(2} 1 Square Inch per2000 BTUH
c. Horizontal duct openings reguire 1 square inch of free
d. Vertical duct openings or openings directly communicat-
3,
When one permanent outdoor opening is used, the opening
requires:
a.
b,
The opening shall commence within 12" (305 mm) of the top ofthe
enclosure. Appliances shall have clearances of at least 1" (25
mm) from the sides and back and 6" (152.4mm) from the front.
May be in and Combination Shown
area per 2,000 BTUH (11 cmZ/kW) of combined input for
all gas appliances in the space (see Table 1).
ing with the outdoors require 1 square inch of free area
per 4,000 BTUH (5.5 cm2/kW) for combined input of all
gas appliances in the space (see Table 1).
1sq. inof free area per 3,000 BTUH (7 cm2/kW) for com-
bined input of all gas appliances in the space (see
Table 1) and
not tess than the sum of the areas of all vent connectors
in the space.
Vent
o°s
Outlet
Inlet
Air (1)
The opening shall directly communicate with the outdoors or shall
communicate through a vertical or horizontal duct to the outdoors
or spaces (crawl or attic) that freely communicate with the out-
doors.
4, Combination of Indoor and Outdoor Air shall have:
a. Indoor openings that comply with the Indoor Combus-
tion Air Method below and
b. Outdoor openings located as required in the Outdoor
Combustion Air Method above and
c. Outdoor openings sized as follows.
1) Calculate the Ratio of all Indoor Space volume
divided by required volume for Indoor Combustion
Air Method.
2) Outdoor opening size reduction Factor is 1 minus
the Ratio in 1) above.
3) Minimum size of Outdoor openings shall be the size
required in Outdoor Combustion Air Method
above multiplied by reduction Factor.
Outlet
_ Air (2)
Air (2)
44101 202301 Specifications are subject to change without notice 10
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
BTUH(kW) TwoVerticalDuctsor RoundDuct
Input TwoHorizontalDucts SingleOpening Openings BTUH(kW)
Rating BTUH(kW) BTUH(kW) BTUH(kW) sq.
50,000 (14.65) 25sq.in.(161 cm2) 16.7sq.in.(108 cm2) 12.5sq.in.(81 cm 2) 4" (101.6mm)
75,000 (21.98) 37.5sq.in.(242 cm2) 25sq.in.(161 cm2) 18.75sq.in.(121 cm2) 5" (127mm)
100,000 (29.31) 50sq.in.(322 cm2) 33.3sq.in.(215 cm2) 25sq.in.(161 cm2) 6" (152.4mm)
125,000 (36.63) 62.50sq.in.(403 cm2) 41.7sq.in.(269 cm2) 31.25sq.in.(202 cm2) 7" (177.8mm)
150,000 75sq.in. 50sq.in. 37.5sq.in. 7" (177.8mm)
EXAMPLE: Determining Free Area
Furnace Water Heater Total Input
100,000 + 30,000 = (130,000 +4,000) = 32.5 Scj. In. Vertical
29.31 8.8 (38.11 + .18) = 210 cmLVertical
Furnace Water Heater Total Input
100,000 + 30,000 = (130,000 +2,000) = 65 Sq. In. Horizontal
29.31 8.8 (38.11 + .09) = 423 cm2 Horizontal
IndoorCombustionAir
Standardand Known-Air-Infiltration Rate Methods
© NFPA & AGA
Indoor air is permitted for combustion and ventilation, if the Stan-
dard or Known-Air-Infiltration Rate Method is used.
CARBON MONOXIDE POISONING HAZARD
Failure to supply adequate combustion air could
result in personal injury or death.
Most homes will require additional air from
outdoors for combustion and ventilation. A space
Free Area
MinimumFreeAreaRequiredfor EachOpeningorDucttoOutdoors
sq.in./2,000(1 cm2/.09) sq. in./3,000 (1 cm2/.135) sq. in./4,000(1 cm2/.18) in./4,000(6.5cm2/.18)
The Standard Method may be used, if the space has no tess vol-
ume than 50 cubic feet per 1,000 BTUH (4.8 cubic meters per kW)
of the maximum input ratings for all gas appliances installed in the
space. The standard method permits indoor air to be used for
combustion and ventilation air.
The Known Air Infiltration Rate Method shall be used if the in-
filtration rate is known to be less than 0.40 air changes per hour
(ACH) and equal to or greater than 0.10 ACH. Infiltration rates
greater than 0.60 ACH shall not be used. The minimum required
volume of the space varies with the number of ACH and shall be
determined per Table 2 or Equations 1 and 2. Determine the
minimum required volume for each appliance in the space, and
add the volumes together to get the total minimum required vol-
ume for the space.
with at least 50 cubic feet per 1,ODDBTUH (4.8 cubic
meters per kW) input rating or homes with tight
construction may need outdoor air, supplied
through ducts, to supplement air infiltration for
proper combustion and ventilation of flue gases.
,::' MINIMUM SPACE VOLUME FOR 100% COMBUSTION AND VENTILATION AIR FROM INDOORS
OtherThanFan-AssistedTotal Fan-assistedTotal
30,000BTU 40,000BTU 50,000BTU 50,000BTU 75,000 100,000BTU 125,000BTU 150,000BTU
ACH (8,790kW) (11,720kW) (14,650kW) (14,650kW) (21,975kW) (29,300kW) (36,625kW) (43,950kW)
ft3(m3)
0.60 1,050 (29.7) 1,400 (39.2) 1,750 (49) 1,250 (35) 1,875 (52.5) 2,500 (70) 3,125 (87.5) 3,750 (105)
0.50 1,260 (35.3) 1,680 (47.04) 2,100 (58.8) 1,500 (42) 2,250 (63) 3,000 (84) 3,750 (105) 4,500 (126)
0.40 1,575 (44.1) 2,100 (58.8) 2,625 (73.5) 1,875 (52.5) 2,813 (78.8) 3,750 (105) 4,688 (131.3) 5,625 (158)
0.30 2,100 (58.8) 2,800 (78.4) 3,500 (98) 2,500 (70) 3,750 (105) 5,000 (140) 6,250 (175) 7,500 (210.6)
0.20 3,150 (88.2) 4,200 (117.6) 5,250 (147) 3,750 (105) 5,625 (157.5) 7,500 (210) 9,375 (262.5) 11,250 (316)
0.10 6,300 (176.4) 8,400 (235.2) 10,500 (294) 7,500 (210) 11,250 (315) 15,000 (420) 18,750 (525) 22,500 (632)
0.00 NP NP NP NP NP NP NP NP
NP = Not Permitted
Table 2 Minimum Space Volumes were determined by using the
following equations from the National Fuel Gas Code NFPA
54/ANSI Z223.1-2006, 9.3.2.2:
1. For other than fan-assisted appliances such as a draft
hood-equipped water heater,
-- ACH 1000 BTUH
°soueOVoumOo,.e>'0''( '°t"er)
-- ACH .293 kW
2. For fan-assisted appliances (such as this furnace), calcu-
late using the following equation:
11 Specifications are subject to change without notice 441 01202301
Required Volume fan_ 15ft3 ( If an )
ACH 1000 BTUH
RequiredV°lume fan_ "42m3 ( If an /
ACH .293 kW
2.
For fan-assisted appliances such as this furnace,
If:
] other = combined inputof all other than fan-assisted
appliances in BTUH
I fan = combined input of all fan-assisted appliances in
BTUH
ACH = air changes per hour (ACH shall not exceed 0.60)
The following requirements apply to the Standard Method and to
the Known Air Infiltration Rate Method.
• Adjoining rooms can be considered part of a space, if there
are no closable doors between rooms.
An attic or crawl space may be considered aspace that freely
communicates with the outdoors provided there are ade-
quate ventilation openings directly to outdoors. Openings
MUST remain open and NOT have any means of being
closed off. Ventilation openings to outdoors MUST be at least
5. Gas Vent Installation
CARBON MONOXIDE POISONING HAZARD
Failure to properly vent this furnace could result
in personal injury or death.
Use methods described here to provide combus-
tion and ventilation air.
Install the vent in compliance with codes of the country having ju-
risdiction, local codes or ordinances and these instructions.
This Category ! furnace is fan-assisted.
Category ! furnace definition: A central furnace which operates
with a non-positive vent static pressure and with a flue loss not
less than 17 percent. These furnaces are approved for common-
venting and multi-story venting with other fan-assisted or draft
hood-equipped appliances in accordance with the NFGC or
NSCNGPIC.
CategoryI SafeVentingRequirements
Category [ furnace vent installations shall be in accordance with
Parts 10 and 13 of the National Fuel Gas Code (NFGC), NFPA
54/ANSI Z223.1-2006; and/or Section 8 and Appendix C of the
CSA B149.1-05, National Standard of Canada, Natural Gas and
Propane Installation Code; the local building codes; furnace and
vent manufacturer's instructions.
NOTE: The following instructions comply with the NFPA 54/ANSI
Z223.1-2006 National Fuel Gas Code and CSA B149.1 Natural
Gas and Propane Installation code, based on the High-Heat
input rate on the furnace rating plate.
1. If a Category ! vent passes through an attic, any concealed
space or floor, use ONLY Type B or Type L double wall vent
pipe. If vent pipe passes through interior wall, use type B vent
pipe with ventilated thimble ONLY.
2. Do NOT vent furnace into any chimney serving an open fire-
place or solid fuel burning appliance.
1square inch of free area per 4,000 BTUH of total input rating
for all gas appliances in the space.
• In spaces that use the Indoor Combustion Air Method, in-
filtration should be adequate to provide air for combustion,
ventilation and dilution of flue gases. However, in buildings
with unusually tight construction, additional air MUST
be provided using the methods described in section
titled Outdoor Combustion Air Method:
• Unusually tight construction is defined as Construction with
1. Wails and ceilings exposed to the outdoors have a con-
tinuous, sealed vapor barrier. Openings are gasketed or
sealed and
2. Doors and openabte windows are weather stripped and
3. Other openings are caulked or sealed. These include
joints around window and door frames, between sole
plates and floors, between walt-ceiling joints, between
wall panels, at penetrations for plumbing, electrical and
gas lines, etc.
VentilationAir
Some provincial codes and local municipalities require ventilation
or make-up air be brought intothe conditioned space as replace-
ment air. Whichever method is used, the mixed return air tempera-
ture across the heat exchanger MUST not fall below 60°
continuously, or 55° on an intermittent basis so that flue gases will
not condense excessively inthe heat exchanger. Excessive con-
densation will shorten the life of the heat exchanger and possibly
void your warranty.
3. Use the same diameter Category ! connector or pipe as per-
mitted by:
• by the National Fuel Gas Code Code (NFGC) NFPA
54/ANSI Z223.1-2006 Sections 12 and 13 venting re-
quirements in the United States
or
• the National Standard of Canada Natural Gas and Pro-
pane Installation Code (NSCNGPIC) CSA B149.1-05
Section 8 and appendix C venting requirements in Cana-
da.
4. Push the vent connector onto the furnace flue collar of the
venter assembly until it touches the bead (at least 5/8" over-
lap) and fasten with at least two field-supplied, corrosion-re-
sistant, sheet metal screws located at least 140° apart.
5. Keep vertical Category ! vent pipe or vent connector runs as
short and direct as possible.
6. Vertical outdoor runs of Type-B or ANY single walt vent pipe
below the roof line are NOT permitted.
7. Slope all horizontal runs upwards from furnace to the vent ter-
minal a minimum of 1/4" per foot (21 mm/m).
8. Rigidly support all horizontal portions of the venting system
every 6' (1.8m)or less using proper clamps and metal straps
to prevent sagging and ensure there is no movement after
installation.
9. Check existing gas vent or chimney to ensure they meet
clearances and local codes. See Figure 1
10. The furnace MUST be connected to afactory built chimney or
vent complying with a recognized standard, or a masonry or
concrete chimney lined with a lining material acceptable to
the authority having jurisdiction. Venting into an unlined
masonry chimney or concrete chimney is prohibited.
See the Masonry Chimney Venting section in these in-
structions.
11. Fan-assisted combustion system Category ! furnaces shall
not be vented into single-wall metal vents.
12. Category ! furnaces must be vented vertically or nearly verti-
cally, unless equipped with a listed mechanical venter.
13. Vent connectors serving Category I furnaces shall not be
connected into any portion of mechanical draft systems oper-
ating under positive pressure.
44101 202301 Specifications are subject to change without notice 12
VentingandCombustionAir Check
NOTE: When an existing Category ! furnace is removed or re-
placed, the original venting system may no longer be sized to
properly vent the attached appliances, and to make sure there is
adequate combustion air for all appliances, MAKE THE FOL-
LOWING CHECK.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed
into operation, could result in carbon monoxide poisoning
or death:
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal
pitch, as required in the National Fuel Gas Code, NFPA
54/ANSI Z223. 1-2006 or CSA B149. 1,Natural Gas and Pro-
pane Installation Code and these instructions. Determine
that there is no blockage or restriction, leakage, corrosion
and other deficiencies which could cause an unsafe condi-
tion.
3. As far as practical, close all building doors and windows and
all doors between the space in which the appliance(s) con-
nected to the venting system are located and other spaces of
the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to
the venting system. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, so they are operating at max-
imum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being in-
spected into operation. Adjust the thermostat so appliance is
operating continuously.
7. Test for spillage from draft hood equipped appliances at the
draft hood relief opening after 5 minutes of main burner op-
eration. Use the flame of a match or candle. (Figure 9)
8. If improper venting is observed, during any of the above
tests, the venting system must be corrected in accordance
with the National Fuel Gas Code, NFPA 54/ANSI
Z223. 1-2006 and/or CSA B149.1, Natural Gas and Propane
Installation Code.
9. After it has been determined that each appliance connected
to the venting system properly vents when tested as outlined
above, return doors, windows, exhaust fans,
fireplace dampers and any other gas-fired burning
appliance to their previous conditions of use.
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii....
Vent Pipe --_ I A/ Draft Hood
Typical Gas
Water Heate_ I I V_('-" Match
NOTE: If flame pulls towards draft ood, this indicates
sufficient infiltration air.
Ventingto ExistingMasonryChimney
NOTE: The tables and notes referred to below are found in the
most recent printing of the NFGC venting tables.
Use the NFGC or NSCNGPIC Tables to size the chimney or vent.
Dedicated venting of one fan assisted furnace into any ma-
sonry chimney is restricted. A chimney must first be lined with
either Type-B vent sized in accordance with NFPA 54/ANSI
Z223.1-2006 tables 13.1 or13.2 or a listed, metal lining system,
sized in accordance with the NFPA 54/ANSI Z223.1-2006 section
13.1.7 for a single appliance or 13.2.19 for multiple appliances or
CSA B149.1-05 Annex C; or venting into a masonry chimney is
permitted as outlined with use of an optional listed masonry chim-
ney kit. (See Section 7. Masonry Chimney Venting of these in-
structions)
Listed, corrugated metallic chimney liner systems in masonry
chimneys shall be sized by using NFPA 54/ANSI Z223.1-2006 or
CSA B149.1-05 tables for dedicated and common venting with
the maximum capacity reduced by 20% (0.80 X maximum capac-
ity) and the minimum capacity as shown in the applicable table.
Corrugated metal vent systems installed with bends or offsets re-
quire additional reduction of 5% of the vent capacity for each bend
up to 45° and 10% of the vent capacity for each bend from 45 ° up
to 90°.
NOTE: Two(2) 45 ° elbows are equivalent to one (1) 90° elbow.
CombinedVentinginto a MasonryChimney
Venting into a masonry or concrete chimney is only per-
mitted as outlined in the NFGC or NSCNGPIC venting tables.
Follow all safe venting requirements.
NOTE: See Masonry Chimney Venting section.
VentCheck
i !
6. Horizontal Venting
CategoryI FurnacesWith ExternalPower
Venters
In order to maintain a Category ! classification of fan-assisted fur-
naces when vented horizontally with sidewall termination, a power
venter is REQUIRED to maintain a negative pressure in the vent-
ing system.
In the U.S.: Per the NFPA 54/ANSI Z223.1-2006, a listed power
venter may be used, when approved by the authority having juris-
diction.
In Canada: Only power venters approved by the power ventor
manufacturer and where allowed by the authority having jurisdic-
tion may be used
Please consult the Fields Controls Co. or Tjernlund Products, Inc.
for power venters certified for use with this furnace.
13 Specifications are subject to change without notice 44101 202301
VentTermination
VentingThrough a Non-Combustible and
Combustible Wall
Consult External Power Venter manufacturer instructions.
Select the power venter to match the Btuh input of the furnace be-
ing vented. Follow all of the manufacturer's installation require-
ments included with the power venter for:
• venting installation,
• vent terminal location,
• preventing blockage by snow,
• protecting building materials from degradation by flue gases,
• see Figure 10 for required vent termination.
NOTE: It is the responsibility of the installer to properly terminate
the vent and provide adequate shielding. This is essential in order
to avoid water/ice damage to building, shrubs and walkways.