Icm controls ICM491 User Manual

ICM491
Single Phase Line Monitor
Reliable line voltage protection for single phase systems
SPECIFICATIONS
Input
Line Voltage: 95-135 VAC or 190-270 VAC (selectable)
Maximum Operating Input: 142-275 VAC
Line Frequency: 50-60 Hz
Output
Type: Relay, energized upon acceptable conditions
Form: SPDT, Single Pole, Double Throw
Ratings: 6A @ 120 VAC resistive
voltage and rapid system
recycling, 95-270 VAC
operation, adjustable
anti-short cycle timer...
DESCRIPTION
The ICM491 was specically designed to guard equipment against damage caused by under/over voltage conditions and/or rapid system recycling.
FEATURES
5-Second Interrogation Delay... helps prevent nuisance tripping
LED Indication... normal run and fault indications
95-270 VAC Operation... in a single model
Integral Anti-Short Cycle Protection... “Delay on break” circuit provides adjustable (.1 to 10 minutes) lockout delay to prevent rapid system recycling; no external ASC timers required
Meets IEEE 587... A&B for transient protection
7313 William Barry Blvd., North Syracuse, NY 13212
(Phone) 315-233-5266 (Toll Free) 800-365-5525
LII114-1
(Fax) 315-233-5276
www.icmcontrols.com
5A @ 240 VAC resistive
Response Times
Line Dropout: .05 seconds (typical)
Line Voltage Sag: 5 seconds (typical)
Turn On (sec): Based on minimum time selected
Lockout Delay Timer
Dry Relay Contacts
Time Delay: Adjusts from 6-600 seconds (+/- 10%)
Under Voltage Protection
Voltage Dropout: Setpoint is -12%
Voltage Pickup: Setpoint is -8%
Over Voltage Protection
Voltage Dropout: Setpoint +12%
Voltage Pickup: Setpoint +8%
Environmental
Operating Temperature: -40°F to +167°F (-40°C to +75°C)
Transient Protection: Meets IEEE 587 Standards for Categories A&B without false output or degradation – (6Kv 0.5 µs x 100 KHz Ring Wave) – (6Kv 1.2 x 50 µs Impulse Wave)
Mechanical
Mounting: Surface mount using (2) #8 screws
Terminations: .25” male quick-connect terminals
MODE OF OPERATION
Upon application of power to the monitor, and provided all voltages and line conditions are acceptable, the green load energized LED indicator will glow. This is an indication that the output contacts have successfully transferred.
Should a High/Low voltage condition exist for longer than the 5 second interrogation delay or a loss of power for more than 50 mS, the relay and green LED shall be de-energized. The red status LED will rapidly ash. Re-energization is automatic upon correction of the fault condition, after the anti-short cycle time delay is complete. Should a fault condition exist upon application of power, the relay will not energize and the red status LED will ash rapidly, indicating power is outside specications. A blinking LED indicates power is good, but unit is still in ASC lockout.
Adjustment: Select the desired operating voltage. If status LED blinks once per second, voltage is within specication and unit is awaiting the end of the ASC delay. If the red status LED rapidly ashes red, adjusting input voltage knob higher or lower should cause a slow blink to result, but ensure input voltage is not beyond motor operating specication. Once input voltage is properly set, adjust “ASC Time Delay” knob to desired ASC delay.
INSTALLATION
1. Determine operating voltage, 95-135 VAC or 190-270 VAC.
2. Disconnect power.
3. Connect the ICM491’s power connections (L1 & L2) to power supply lines L1 & L2 (or N). Ensure there is only one “L2” terminal connected at any time:
OM L1 L2 L2 OM L1 L2 L2
For
95-135 VAC Operation
4. Find a convenient location in control circuit where the ICM491’s on-board relay contacts can make or break the control circuit. The “COM” terminal connects to the “NO” contact when power is within specication, “COM” connects to “NC” when power is outside specication.
5a. With control power off, cut control circuit and
terminate control wires with 1/4” female spade connections. Connect one terminated line to “COM” terminal, the other terminated line to “NO” terminal.
5b. For new installations, where the control circuit
voltage is the same as the voltage being monitored, it may be easier to connect “COM” terminal to “L1” terminal with a jumper wire as shown in ladder diagram. Then, connect control circuit to terminal “NO.”
6. Set the “input voltage” knob to the actual line voltage, or to the motor’s nameplate voltage.
7. Turn the “ASC Time Delay” knob to its minimum position (counter-clockwise).
For
190-270 VAC Operation
8. Apply power. Observe “Load Energized” and “Status” LEDs. If incoming power is within specication, unit will energize load in 6 seconds. The following is a table showing what LED indicators correspond to:
LED STATE INDICATION
Load Energized Off Internal relay is de-energized Load Energized On Internal relay is energized Status Off Voltage is within range Status Blink Voltage is good, unit is in ASC Status Rapid Flash Voltage is out of range
Note: Both LEDs off indicates no power to unit.
9. Set the “ASC Time Delay” to the desired anti­short cycle lockout time.
WIRING DIAGRAM
Typical wiring diagram for 115 VAC system
L1 L2/NFuse
NC COMNO L1 L2 L2
ICM491
115
230
115 VAC Contactor
Motor
Loading...