Ice-O-Matic CIM0320, CIM1136 Technical & Service Manual

ELEVATION SERIES CUBE ICE MAKER
CIM Modular Cubers CIM0320 - CIM1136
Ice-O-Matic 11100 East 45th Avenue Denver, Colorado 80239 1-800-423-3367
1/2018
ELEVATION SERIES CIM CUBERS TABLE OF CONTENTS
AIR AND WATER COOLED UNIT INSTALLATION GUIDELINES ……………………………………………………………….….2
REMOTE UNIT INSTALLATION GUIDELINES ……………………………………………………………………………………… ..…..4
ELECTRICAL AND PLUMBING REQUIREMENTS ……………………………………………………………………………………....7
START‐UP PROCEDURES ………………………………………………………………………………………………………………….….…9
SEQUENCE OF OPERATIONS ………………………………………………………………………………………………………….….….10
CONTROL BOARD …………………………………………………………………………………………………………………………….…..24
CONTROL BOARD LED SEQUENCE …………………………………………………………………………………………………….… .27
BUTTON FUNCTION ………………………………………………………………………………………………………………………….….33
SUMP ……………………………………………………………………………………………………………………………………………….….34
HIGH AND LOW FLOAT SWITCHES AND HOUSING …………………………………………………………………………….…36
WATER PUMP ………………………………………………………………………………………………………………………………….…..39
WATER DISTRIBUTION TUBE ………………………………………………………………………………………………………………..41
WATER INLET VALVE …………………………………………………………………………………………………………………………...43
PURGE VALVE …………………………………………………………………………………………………………………………………......44
HARVEST ASSIST ASSEMBLY / HOT GAS VALVE …………………………………………………………………………………….45
EVAPORATOR …………………………………………………………………………………………………………………………………..….46
MAGNETIC CURTAIN SWITCH ……………………………………………………………………………………………………….…..…50
HIGH PRESSURE CUT‐OUT / FAN CYCLE CINTROL …………………………………………………………………………….…..51
HIGH TEMPERATURE SAFETY ……………………………………………………………………………………………………….……...52
FAN MOTOR (AIR COOLED) ………………………………………………………………………………………………………………....53
REFRIGERATION SECTION ……………………………………………………………………………………………………………….…...54
GENERAL MAINTENANCE ……………………………………………………………………………………………………………….…….56
CLEANING AND SANITIZING ……………………………………………………………………………………………………………….…57
CABINET CARE ……………………………………………………………………………………………………………………………..........59
WINTERIZING ……………………………………………………………………………………………………………………………………….60
TECHNICAL SPECIFICATIONS ………………………………………………………………………………………………………………..61
WIRING DIAGRAMS ……………………………………………………………………………………………………………………………..62
INTRODUCTION …………………………………………………………………………………………………………………………….…….…1
ELEVATION SERIES CIM CUBERS TABLE OF CONTENTS
ELEVATION SERIES CIM CUBERS INTRODUCTION
Energy Efficiency
Ice-O-Matic has partnered with ENERGY STAR since 2004 to ensure our customers receive the most efficient ice machines for your investment dollar. Ice-O-Matic is committed to the continuous improvement in both energy efficiency and productivity thereby delivering the best value in energy efficient ice machines money can buy.
For a detailed list of ENERGY STAR qualified Ice-O-Matic ice machines, go to:
http://www.iceomatic.com/Products/Sales-Literature/#
Freight Claims
Inspect Promptly
This merchandise has been carefully inspected and packed in accordance with the carrier’s packing specifications. Responsibility for safe delivery has been assumed by the carrier. If loss or damage occurs, you as the consignee must file a claim with the carrier and hold the container for carrier’s inspection.
Visible Loss or Damage
Any external evidence of loss or damage must be fully described and noted on your freight bill or express receipt and signed by the carrier’s agent. The claim should be filed on a form available from the carrier.
Concealed Loss or Damage
If loss or damage does not appear until merchandise has been unpacked, make a written request for inspection by the carrier within 5 days of the delivery date, then file a claim on a form from the carrier.
FILE CLAIMS WITHOUT DELAY
DO NOT RETURN DAMAGED GOODS
TO ICE-O-MATIC
How to use this Manual
Ice-O-Matic provides this manual as an aid to the Refrigeration Service Technician for installation and maintenance of the CIM cube ice machines. Do not attempt to perform installation, start-up or maintenance unless you have read and fully understand this manual.
Ice-O-Matic ice-makers and dispensers are not approved for outdoor installation.
CIM Cubers contain R404A Refrigerant.
To find a Service Provider, please reference our “Find a Service Technician” tab at www.iceomatic.com
Keep this manual for future reference.
The CIM Series Service Parts Manuals are available separately.
WARNING
Always disconnect electrical power and shut off water supply whenever maintenance or repairs are
performed on the ice machine and related equipment.
CAUTION
Always wear protective eye wear whenever maintenance or repairs are performed on the ice
machine and related equipment.
Ice-O-Matic Warranty
Every Ice-O-Matic ice maker is backed by a warranty that provides both parts and labor coverage. To view
the warranty details, register products, or check your warranty status visit the “Warranty and Water Filter
Registration” page on www.iceomatic.com
1
ELEVATION SERIES CIM CUBERS INSTALLATION GUIDELINES
Installation Guidelines
For proper operation of the ice machine, the following installation guidelines must be followed by a qualified refrigeration technician
. Failure to do so may result in loss of production capacity, premature part failures, and may void all
warranties.
Reference the installation parameters prior to installing the machine. Ice-O-Matic assumes no responsibility for improperly installed equipment. Excessive time required for service or time for units requiring removal for service of inaccessible equipment will be the sole responsibility of the equipment owner.
Ambient Operating Temperature
Minimum operating temperature: 50°F (10°C) Maximum operating temperature: 100°F (38°C) (60 Hz.), 110°F (43°C) (50 Hz.).
Note: Ice-O-Matic ice-makers and dispensers are not
approved for outdoor installation
Incoming Water Supply
WARNING: Connect to unheated potable water
supply only!
(See Electrical and Plumbing diagrams for line sizing)
Minimum incoming water temperature:
40°F (4.5°C)
Maximum incoming water temperature:
100°F (38°C)
Minimum incoming water pressure:
20 psi (1.4 bar, 0.138MPa)
Maximum incoming water pressure:
80 psi (5.5 bar, 0.552MPa)
machine can be pulled away from the wall if service is needed.
Water Filtration/Treatment
A water filter system should be installed with the ice machine. Refer to Ice-O-Matic water filter specification sheet.
Reverse Osmosis (RO) water can be very acidic and can attack the evaporator and other metal in the ice machine. Because the RO process removes all minerals and metals from the water it can promote the faster growth of microbial mold and slime. If RO water is used, Ice-O-Matic recommends the water pH is verified to be a neutral 7.0 to minimize the corrosive effects. Incorrect cleaners, sanitizers, and RO water that does not have a neutral pH could void
the machine’s warranty.
Drains
All drain lines must be installed per local codes. Flexible tubing is not recommended. Route bin drain, purge drain and water condenser drain individually to a floor drain. The use of condensate pumps for draining water is not recommended. Ice-O-Matic assumes no responsibility for improperly installed equipment.
Note: The Purge Drain Fitting is plastic: DO
NOT apply heat to purge drain area; DO NOT
over-tighten drain connection.
The purge drain should be a minimum of 3/4 inch O.D. tubing. The condenser drain on water cooled units should be 1/2 inch O.D. minimum. The drain line fittings on Ice-O-Matic bins are 3/4 FPT. The bin drain should be a minimum of 3/4 inch O.D. Cold water drains should be insulated to prevent condensation from forming.
Note: if water pressure exceeds 80 psi (5.5 bar), a water
pressure regulator must be installed
All water supply lines must be installed per local codes. Use 3/8 inch O.D. minimum on air cooled machines. On water cooled machines 3/8 inch O.D. minimum tubing must be run to the condenser. The water supply for the machine can “T” off from the condenser line using 3/8 inch O.D. minimum tubing. Make 2 coils of extra tubing so that the
2
ELEVATION SERIES CIM CUBERS INSTALLATION GUIDELINES
Clearance Requirements
Self-contained air-cooled ice machines should have a minimum of 6 inches (15cm) of clearance at the rear, top and sides for proper air circulation and adequate space for serviceability. Self-contained air-cooled ice machines exhaust air out the top and right side. There are two alternative air exhaust options. Option A (top exhaust bias): minimum of 6 inches (15cm) of clearance at the rear and top of the ice machine for proper function at maximum operating conditions. Option B (side exhaust bias): minimum of 6 inches (15cm) of clearance at the rear and right side of the ice machine with a minimum of 3 inches (7.5cm) of clearance at the top for proper function at maximum operating conditions.
Appropriate space should be allowed for proper serviceability of the machine. Excess time to gain
access for serviceability is not covered under
warranty.
Stacking
Ice-O-Matic does not endorse stacking ice machines.
Dispenser Application
A thermostatic bin control kit should be installed if the CIM Cube ice machine is placed on a dispenser. A bin top may or may not be required and should be secured to the dispenser.
Electrical Specifications
Refer to the serial plate at the rear of the ice machine to make sure proper voltage and circuit breaker size have been supplied. Make sure the machine is on a dedicated circuit. European installations require that the electrical supply fixed wiring must be provided with a disconnect means having a separation of at least 3mm in all poles. The ice machines are provided without electrical cord set and are designed and agency approved to be permanently connected.
Units are not approved for GFI outlets.
Caution: Electrical connection must be made or a cord
installed by a qualified electrician
an electrical fire.
or there is danger of
an
Adjustments
Level the machine within 1/8 inch in all directions. Check the water in the Water Sump for proper level. Check the ice bridge for proper thickness and adjust on Float Switch Housing Assembly as needed.
Check the Water Regulating Valve adjustment if water cooled.
Secure the machine on top of the bin or dispenser. Attach the ice machine to the bin with the mounting straps provided with the bin or dispenser. Insure that the back of the ice machine is flush with the back of the bin. Proper functioning of the Bin Door requires the door, when it is opened, to be in a stable position.
If the ice machine is too far forward on the bin, the opened door may not be stable, resulting in an unexpected closing of the bin door. If the ice machine is to be mounted on a bin or dispenser other than an Ice-O-Matic, refer to the manufacturers instructions for machine mounting. Ice-O-Matic will not be responsible for damage or injury that results from unexpected closing of the bin door as a result of the ice machine being too far forward on the bin.
3
ELEVATION SERIES CIM CUBERS REMOTE CONDENSER GUIDELINES
Remote Condenser Installation
For proper operation of the ice machine, the following installation guidelines must be followed. Failure to
do so may result in loss of production capacity, premature part failure, and may void all warranties.
Use the following for planning the placement of the remote condenser relative to the ice machine
Location Limits
Remote condenser location must not exceed ANY of the following:
Maximum rise from the ice machine to the
remote condenser is 35 physical feet.
Maximum drop from the ice machine to
the remote condenser is 10 physical feet. Physical line set maximum length is 75 ft. Calculated
line set length maximum is 100
ft. A m b i en t o p e ra t i n g t e m p e ra t u r e s:
-20°F (-28.9°C) to 120°F (48.9°C)
Install and attach the remote condenser to the roof of the building using the methods and practices of construction that conform to the local building codes, including having a roofing contractor secure the remote condenser to the roof.
Have an electrician connect the remote condenser fan motor wires to the ice machine using the junction box at the back of the machine.
Roof Attachment
Calculation Formula
Drop = dd x 6.6
(dd = drop distance (ft.))
Rise = rd x 1.7
(rd = rise distance (ft.))
Horizontal Run = hd
(hd = horizontal distance (ft.))
Calculated Line Length = Drop + Rise + Horizontal Run
Configurations that do NOT meet these requirements must receive written authorization from Ice-O-Matic. This includes multi-pass or rack system remote condensers.
DO NOT: Route a line set that rises, then falls, then rises or a line set that falls, then rises, then falls.
Remote Condenser Location
Pre-charged line sets are available in 25, 40, 45, 60 or 75 foot length to connect the ice machine to the remote condenser. Select the best available location, protecting the remote condenser from extremes of dirt, dust and sun. Meet all applicable building codes. The services of a licensed electrician may be required.
Pre-charged Line Set Routing
CAUTION: Do not connect the pre-charged tubing until all routing and forming of the tubing has been
completed. See the coupling instructions for
connecting information.
Each set of pre-charged tubing refrigerant lines consists of a 3/8” diameter liquid line and 1/2 inch diameter discharge line. Both ends of each line have quick connect couplings, one end of the line set has a Schrader valve connection.
Note: the openings in the building or ceiling or wall,
listed in the next step, are the minimum sizes
recommended for passing the refrigerant lines through.
Have a roofing contractor cut a minimum hole for the refrigerant lines of 2.50 inch. Check local codes, a separate hole may be required for the electrical power to the condenser.
CAUTION: DO NOT KINK OR CRIMP
REFRIGERANT TUBING WHEN INSTALLING
IT.
NOTE: REMOTE LINES MUST NOT RISE AND
DROP IN THE SAME RUN.
4
ELEVATION SERIES CIM CUBERS REMOTE CONDENSER GUIDELINES
CIM Machine Model Number Remote Condenser Model Number
CIM0520/530 VRC1001B/RCA1001 CIM0525/535 VRC1061B/RCA1061
CIM0636 VRC1061B/RCA1061
CIM1126 VRC1061B/RCA1061 CIM0835/0836/0837 VRC1061B/RCA1061 CIM1135/1136/1137 VRC1061B/RCA1061
Route the refrigerant lines through the roof opening. Follow straight line routing whenever possible. Any excess tubing MUST remain inside the building. Spiral the excess length of pre­charged tubing inside the building. Use a horizontal spiral to avoid any traps in the lines. Have the roofing contractor seal the holes in the roof per local codes.
The following remote ice makers incorporate the Mixing Valve in the Condenser. This configuration allows up to a 100 foot calculated remote line set run. Reference the diagram on the next page to calculate the maximum 100 ft. line set run. Maximum actual line set run is limited to 100 ft. Add 1/4 oz. of refrigerant for each actual foot from 75 to 100 ft. actual line set run.
CAUTION: The couplings on the sets of pre-charged
lines are self sealing when installed properly.
Carefully follow the instructions in the Remote
Condenser manual.
Verify the CIM machine is compatible with the remote condenser.
For more information contact your Ice-O-Matic distributor.
5
ELEVATION SERIES CIM CUBERS REMOTE CONDENSER GUIDELINES
Equivalent Run Calculation Examples
Formula for maximum equivalent run:
(RISE X 1.7) + (DROP X 6.6) + HORIZONTAL RUN = CALCULATED LINE RUN
NOT TO EXCEED 100 CALCULATED FEET
Rise:
(35 ft. x 1.7) + (40 ft.) = 99.5 equivalent feet line run
35 ft. rise
40 ft. horizontal
Drop:
(10 ft. x 6.6) + (34 ft.) = 100 equivalent feet line run
10 ft. drop
34 ft. horizontal
6
ELEVATION SERIES ELECTRICAL AND PLUMBING REQUIREMENTS
Electrical and Plumbing Requirements
22” CIM SERIES Common Connections
(CIM**2
Air Cooled
Please note: air-cooled units require
6”(152mm) for air intake and exhaust.
A. Ice maker potable water in,
3/8” FPT.
B. Ice maker water out,
3/4” FPT.
C. Hole for electrical connections,
7/8”.
D. Electrical junction box,
7/8”.
* A)
Water/Remote Cooled
A. Ice maker potable water in,
3/8” FPT.
B. Ice maker water out,
3/4” FPT.
C. Hole for electrical connections,
7/8”.
D. Electrical junction box,
7/8” (remote).
E. Condenser water in,
3/8” FPT (water only).
Discharge line,
1/2” male quick connect coupling for pre-charged line set (remote only).
F. Condenser water out,
1/2” FPT (water only).
G. Liquid Line,
3/8” male quick connect coupling for pre-charged line set (remote only).
(CIM**2* W/R)
7
ELEVATION SERIES ELECTRICAL AND PLUMBING REQUIREMENTS
Electrical and Plumbing Requirements
30” CIM SERIES Common Connections
(CIM**3
Air Cooled
Please note: air-cooled units require
6”(152mm) for air intake and exhaust.
A. Ice maker potable water in,
3/8” FPT.
B. Ice maker water out,
3/4” FPT.
C. Hole for electrical connections,
7/8”.
D. Electrical junction box,
7/8”.
* A)
Water/Remote Cooled
A. Ice maker potable water in,
3/8” FPT.
B. Ice maker water out,
3/4” FPT.
C. Hole for electrical connections,
7/8”.
D. Electrical junction box,
7/8” (remote).
E. Condenser water in,
3/8” FPT (water only).
Discharge line,
1/2” male quick connect coupling for pre-charged line set (remote only).
F. Condenser water out,
1/2” FPT (water only).
G. Liquid Line,
3/8” male quick connect coupling for pre-charged line set (remote only).
(CIM**3* W/R)
8
ELEVATION SERIES START-UP PROCEDURE
Start-Up Procedure
Note: Before starting the machine, make sure the
machine is level within 1/8 inch in all directions, the
bin or dispenser leg height can be adjusted by
rotating the leg foot
After verifying proper voltage, water supply, drains and breathable air space around the unit, press and quickly release the ON/OFF button behind the unit front panel. The indicator light will change from a solid red to solid blue in color.
Follow the sequence of operation described under “Operation of CIM Series Cuber” in this manual. Check operation of each component through the cycle as explained in this section.
Access to Water Level Adjustment
Bridge Thickness Adjustment
Once the unit has gone through a harvest cycle, verify the bridge thickness (3/16” thick for units less than 400 lbs. and 1/8” for 400 lbs. and above) across the middle of the ice slab on the second batch produced. The ice thickness can be changed on the Float Housing by turning the adjustment clockwise to decrease the bridge thickness and counter-clockwise to increase the bridge thickness. You will hear a “click” with each adjustment. It is recommended adjustments be made one or two “clicks” at a time.
Model Batch Weight
Lowers Float; increases
bridge thickness
Raises Float; decreases
bridge thickness
CIM320/330 2.9-3.15 3.25-3.5 -
CIM430/520/530/630 4.9-5.15 5.5-5.8 -
CIM0830/1120/1130 6.9-7.4 7.9-8.3 8.4-8.8
Half Cube Full Cube Grande Cube
9
ELEVATION SERIES CIM CUBERS SEQUENCE OF OPERATIONS
BROWN
BLUE
VIOLET
BLACK
RED
TAN
PINK
YELLOW
= Illuminated LED
WHIT E
WHIT E
BLUE w/ WHITE
BLUE w/ RED
BLUE
12V DC Switches
Line Voltage Components
R1 R2 R3 R4 R5 R6
SEQUENCE OF OPERATIONS
CONTROL BOARD - OFF STATUS
When power is initially applied to the unit, the LED’s on both the Push Pad and the Board POWER Button will flash in sequence BLUE, then RED, then the WASH Button will flash YELLOW, followed by the POWER Button LED will turn a solid RED, indicating the unit is in the OFF status as shown above.
The LED’s for the Curtain Switches (1 & 2), High Float Switch and Low Float Switch will be illuminated indi‐ cating closed circuits. Should the Curtains or Bin Thermostat (if added) be open, the unit will not start a Freeze Cycle.
From an OFF status, the unit can start a CLEAN cycle, a FREEZE cycle or be put in the DIAGNOSTIC mode. For Cleaning Instructions, see page 56. For more on the DIAGNOSTIC mode see page 30.
10
ELEVATION SERIES CIM CUBERS SEQUENCE OF OPERATIONS
BROWN
BLUE
VIOLET
BLACK
RED
TAN
PINK
YELLOW
= Illuminated LED
WHITE
WHITE
BLUE w/ WHITE
BLUE w/ RED
BLUE
12V DC Switches
Line Voltage Components
R1 R2 R3 R4 R5 R6
CONTROL BOARD - FREEZE CYCLE
A quick press of the POWER button on the Push Pad or Board will start the Freeze cycle. The Water Inlet Valve will be energized (R4 LED on Board illuminated) and water will begin flowing into the Sump. As the water rises, the contacts in the Low Water Float will open (Switch LED off). The Water Inlet Valve will remain energized until the High Water Float contacts open (Switch LED off). The Water inlet Valve will be de‐energized (R4 LED on Board off).
Note: Minimum Freeze Cycle ‐ 5 minutes (from Compressor Start.) Maximum Freeze Cycle ‐ 1 hour.
11
ELEVATION SERIES CIM CUBERS SEQUENCE OF OPERATIONS
BROWN
BLUE
VIOLET
BLACK
RED
TAN
PINK
YELLOW
= Illuminated LED
WHITE
WHITE
BLUE w/ WHITE
BLUE w/ RED
BLUE
12V DC Switches
Line Voltage Components
R1 R2 R3 R4 R5 R6
CONTROL BOARD - COMPRESSOR START
The Hot Gas Valve will be energized (R3 on Board illuminated) for 5 seconds and the system pressures will start to equalize.
12
ELEVATION SERIES CIM CUBERS SEQUENCE OF OPERATIONS
BROWN
BLUE
VIOLET
BLACK
RED
TAN
PINK
YELLOW
= Illuminated LED
WHITE
WHITE
BLUE w/ WHITE
BLUE w/ RED
BLUE
12V DC Switches
Line Voltage Components
R1 R2 R3 R4 R5 R6
CONTROL BOARD - COMPRESSOR START
The Compressor will be energized (R2 on Board illuminated) and the Hot Gas Valve will remain open for 5 more seconds and then de‐energize (R3 on Board off).
13
ELEVATION SERIES CIM CUBERS SEQUENCE OF OPERATIONS
BROWN
BLUE
VIOLET
BLACK
RED
TAN
PINK
YELLOW
= Illuminated LED
WHITE
WHITE
BLUE w/ WHITE
BLUE w/ RED
BLUE
12V DC Switches
Line Voltage Components
R1 R2 R3 R4 R5 R6
CONTROL BOARD - PRE-CHILL
The Compressor and Fan(s)/Liquid Line Solenoid (R1 and R2 LED’s on Board illuminated) are energized and unit is now in a Pre‐Chill for 30 seconds bringing the Evaporator temperature down. Both Curtain Switch LED’s are on showing closed curtain(s). Even though (R1) is energized the Fan Motor will only come on once the Fan Cycle Switch closes at 250 psi of head pressure.
14
ELEVATION SERIES CIM CUBERS SEQUENCE OF OPERATIONS
BROWN
BLUE
VIOLET
BLACK
RED
TAN
PINK
YELLOW
= Illuminated LED
WHITE
WHITE
BLUE w/ WHITE
BLUE w/ RED
BLUE
12V DC Switches
Line Voltage Components
R1 R2 R3 R4 R5 R6
CONTROL BOARD - FREEZE
The Water Pump is energized (R6 LED on Board illuminated) and water is pushed through the Water Pump Tube and flows over the Evaporator. The High Float Switch contacts close as the water level in the Sump drops (High Float Switch LED on Board illuminates).
15
ELEVATION SERIES CIM CUBERS SEQUENCE OF OPERATIONS
BROWN
BLUE
VIOLET
BLACK
RED
TAN
PINK
YELLOW
= Illuminated LED
WHITE
WHITE
BLUE w/ WHITE
BLUE w/ RED
BLUE
12V DC Switches
Line Voltage Components
R1 R2 R3 R4 R5 R6
CONTROL BOARD - ANTI-SLUSH
During the first 3 cycles as the water temperature reaches 36 degrees F. the Water Pump will shut off for 20 seconds to reduce the possibility of slush developing in the Sump. After the first 3 cycles, Anti‐Slush will only occur if the Sump water temperature reaches 28 degrees F.
16
ELEVATION SERIES CIM CUBERS SEQUENCE OF OPERATIONS
BROWN
BLUE
VIOLET
BLACK
RED
TAN
PINK
YELLOW
= Illuminated LED
WHITE
WHITE
BLUE w/ WHITE
BLUE w/ RED
BLUE
12V DC Switches
Line Voltage Components
R1 R2 R3 R4 R5 R6
CONTROL BOARD - WATER PUMP ON
At the end of Anti‐Slush the Water Pump (R6) will be re‐energized and water starts flowing over the Evaporator again. The unit will stay in this mode until the Low Float Switch closes on water level drop, indicating the unit is ready to harvest.
17
ELEVATION SERIES CIM CUBERS SEQUENCE OF OPERATIONS
BROWN
BLUE
VIOLET
BLACK
RED
TAN
PINK
YELLOW
= Illuminated LED
WHITE
WHITE
BLUE w/ WHITE
BLUE w/ RED
BLUE
12V DC Switches
Line Voltage Components
R1 R2 R3 R4 R5 R6
CONTROL BOARD - INITIATING HARVEST
When the water level in the SUMP drops to close the contacts of the Low Float Switch (LED on Board illu‐ minates) after a 5 second de‐bounce of the switch will signal the start of the Harvest Cycle.
18
Loading...
+ 47 hidden pages