Installation Instructions CRD-3XXX, CRD-3XXL &
CRD-700 Series Dampers on Model SP Fans
These installation instructions show recommended
installation procedures. These or other installation
methods may be followed subject to the approval of the
authority having jurisdiction.
Model CRD-310, 320, 350, 360, 310L, 320L and 700 are
specific sizes of Greenheck Model DFD-350 dampers
equipped with hardware to facilitate installation with
Greenheck Model SP ceiling exhaust fans. The
CRD-3XX series and CRD-700 dampers are classified
by UL to function as a heat barrier in air handling
penetrations through fire resistive membrane ceilings.
They are intended to maintain the fire resistive integrity
of the ceiling. They can only be installed in conjunction
with the SP fan models shown and cannot be installed
alone.
Note: Motors for fan models used in conjunction with
CRD shall be equipped with thermal cut-off fuse
control.
Part Number 452832
UL CLASSIFIED (see complete marking on
product)
UL CLASSIFIED to Canadian safety standards (see
complete marking on product)
Standard UL555C
Classifications filed at UL under Listing #R13446
3.69”
SP Fan Size CRD Model
SP-B50, SP-B70, SP-B80,
SP-B90, SP-B110,
SP-B150, SP-B200
SP-A50, SP-A70, SP-A90,
SP-A110, SP-A125,
SP-A190
SP-A250, SP-A290,
SP-A390, SP-A200
SP-A410, SP-A510,
SP-A710, SP-A780
SP-A900, SP-A1050 CRD-360
SP-A1550, SP-A700 CRD-700
CRD-320
CRD-320L
CRD-310
CRD-310L
CRD-320
CRD-350
Damper Installation to a SP fan model
Fan housing fits inside top flange of damper frame.
Observe label on damper indicating top.
Attach damper to fan housing using #10 x 3/4 in. sheet
metal screws on 6 in. maximum centers, minimum two
fasteners per side. See Figure 3.
Figure 1: Isometric view of a CRD-3XX series damper.
Wires to ceiling fan
Do not allow
interference in
this area
Figure 2: Isometric view for wiring the CRD-3XX series
damper to the lighted grille and ceiling fan.
Concrete Floor
#10 x ¾ in. SMS
6 in. Max. Centers,
2 Min./Side
3 in .
Hole Opening Is
“A” x “B”
Figure 3
Ceiling Exhaust Fan Support
The following two mounting methods may be used.
1) Suspend fan/damper assembly using #10 -32
threaded steel rod as shown in Figure 4. Suspend
from joists or cold rolled channels (do not suspend
from beams). If vibration isolators are used, fender
washers must have a larger outside diameter than the
holes in the fan mounting angle.
2) Support fan/damper assembly using (2) minimum 16
ga. x 1 1/2 in. steel channels with 9/16 in. flanges.
Suspend from joists or cold rolled channels (do not
suspend from beams). Alternatively, bolt channels
ends directly to joists or other cold rolled channels
using minimum #10 bolts. See Figure 5.
Do not support fan/damper assembly by ceiling tile
or ceiling grid (Tee) members when using with a
suspended ceiling!
#10 x 3/8 in. SMS,
1 1/2 in. x 9/16 in. x 16 Gauge
(Minimum) Cold Formed Steel
#10 Bolt or #10-32
Threaded Steel Rod
Supports To Joists Or
Other Cold Formed
Channels (By Others)
CRD-XXX
Series Damper
(Minimum) 4 Per Side
#10 Bolt or Sheet Metal Screw
(Minimum) Attached Through
Prepunched Holes In Mounting
Angles Into Channel Brace
Supports, 2 Per Side (By Others)
Figure 5
Grille Installation
Mount grille to underside of ceiling
radiation damper using #10 x 1/2 in.
Phillips head stainless steel sheet metal
screws provided with SP fan.
Grille
SP Fan
#10-32 Threaded
Steel Rod
Hanging Vibration
Isolation
Ceiling Radiation
Damper
Fire Rated Ceiling
Beam
Steel
Joists
Steel Hanger Wires
(12 SWG minimum)
“D”
“E”
Figure 4
Unit Size “D” “E”
B50, B70,
4 1/2 15 5/8
B80, B90,
B110, B150,
B200
A50, A70,
5 1/2 14 5/8
A90, A110,
A125, A190
A250, A290,
6 3/4 15 1/2
A390, A200
A410, A510,
9 1/4 19 5/8
A710, A780
A900, A1050,
9 1/4 25 3/8
A1410, A1550
A700 5 1/2 25 1/8
Copyright © 2010 Greenheck Corporation
452832 CRD-3xx, CRD-700 rev. 5 Nov 2010