TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR
INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in a manner intended by the manufacturer. If you
have questions, contact the manufacturer.
2. Before servicing or cleaning the unit, switch power off at service
panel and lock the service disconnecting means to prevent
power from being switched on accidentally. when the service
disconnecting means cannot be locked, securely fasten a prominent
warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by qualified
person(s) in accordance with all applicable codes and standards,
including fire-rated construction.
4. Sufficient air is needed for proper combustion and exhausting of
gasses through the flue (chimney) of fuel burning equipment to
prevent backdrafting. Follow the heating equipment manufacturer’s
guideline and safety standards, such as those published by the
National Fire Prevention Association (NFPA), and the American
Society for Heating, Refrigeration and Air-Conditioning Engineers
(ASHRAE), and the local code authorities.
5. When cutting or drilling into wall(s) or ceiling, do not
damage electrical wiring or other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. If this unit is to be installed over a tub or shower, it must be marked
as appropriate for the application and be connected to a GFCI
(Ground Fault Circuit Interrupter) - protected branch circuit.
8. Never place a switch where it can be reached from a tub or shower.
9. Install fan at least 5 feet (1.52 m) above the floor.
10. This unit must be grounded.
11. Unit must not be installed in a ceiling thermally insulated to a value
greater than R40.
MAINTENANCE
The motor is permanently lubricated and never needs oiling. If the
motor bearings are making excessive or unusual
noises, replace the motor with the exact service motor. You should
replace the impeller at the same time.
WARNING
!
DISCONNECT ELECTRIC
POWER SUPPLY
AND LOCK OUT
SERVICE PANEL BEFORE
SERVICING UNIT
COOKING AREA
Do Not Install Above
Or Inside This Area
!
1. For general ventilating use only. Do not use to exhaust
hazardous or explosive materials and vapors.
2. To avoid motor bearing damage and noisy/unbalanced
impellers, keep drywall spray, construction dust, etc. off power
unit.
3. DO NOT install this product in a wall. This product is designed
for installation in ceilings up to a 12/12 pitch (45 degrees).
Ductwork must point upward.
4. Please read specification label on product for further
information and requirements.
CAUTION
PREVENTATIVE MAINTENANCE
A clean fan provides better service. Disconnect the power supply and
clean the fan as listed below.
TO CLEAN GRILL : Use a mild detergent, such as
dishwashing liquid, and a soft cloth. DO NOT use abrasive cloths,
steel wool pads or scouring powders.
TO CLEAN FAN ASSEMBLY: Unplug motor cord from receptacle. To
remove motor plate, find the single tab on the motor plate (located
next to the receptacle). Push up rear motor plate tab while pushing out
on the side of the housing or insert a screwdriver into the slot in the
housing (next to tab) and twist screwdriver. Gently vacuum fan, motor
and interior of housing.
METAL AND ELECTRICAL PARTS SHOULD NEVER BE IMMERSED
IN WATER.
45°45°
Floor
Cooking
Equipment
BATHROOM AREA
Bath Fan
8ft. min.
3ft. min.
Tub /
Shower
2
43053-01 - 09/12/2011
95044-01-000
D
95029-01-000
E
77481-01-000
F
03242-07-133
G
98624-01-000
H
Check all the parts. If damaged, call
1-888-830-1326 for replacements.
*
NOTE: Strain relief cable connector must be installed. Not Included.
x4
x2
x2
A
B
B
B
*
*
*
3/8” Cable Connector
*
*
*
C
C
C
x2
I
I
I
Extra Screws
x2
x2
x2
74508-53-000
I
77521-01-000
J
74508-53-000
K
98447-02-000
L
66534-01-000
M
98617-01-000
N
66534-01-000
O
98519-02-000
P
77480-01-218
Q
88401-02-000
R
65517-01-000
S
88432-01-000
T
Not included
Tools Needed.
Estimated assembly time:
30 to 60 minutes
Before Installation
NOTE: Remove all packing materials before installation.
1
3
2
I
H
Turn off the power source.
Loosen screws.
4
H
I
5
E
Remove the motor/blower from the housing.
Remove the pre-loaded screw tip covers.
Remove packing material.
6
Back out the pre-loaded screw tips until flush with the side
of the housing.
4
43053-01 - 09/12/2011
7
8
Remove the wiring cover screw.
9
Pop out the first wiring access slug. Use second if needed.
10
Remove the wiring cover.
B
Insert the strain relief into the housing and
secure with the washer.
Choose Installation Option
For New Construction - attaching to joist go to step A11, page 7
For New Construction - suspended between joists go to step B11, page 9
For Existing Construction - accessible from above go to step C11, page 12
For Existing Construction - accessible only from below go to step D11, page 16
5
43053-01 - 09/12/2011
New constructionattaching to joist
A11
5/8
1/2
Position the correct depth mark at the bottom edge of
the joist based on the thickness of your sheetrock.
A13
A12
Screw pre-loaded screws into joist or framing.
A14
A15
Pull wires through the strain relief.
F1
Go to step F1 on page 20 to connect the wires as shown.
A16
0
Install the wiring cover plate. Make sure all wiring connections
are inside the box or under the wiring cover plate.
Connect 4” duct and vent to the outside. Tape joints.
If ducting does not fit securely, an adapter may need
to be purchased.
6
43053-01 - 09/12/2011
ON
OFF
0000
A17A17
0000
A17
A18
Connect wiring from the motor to the wiring cover plate.
A19
Secure the motor by tightening the 2 screws.
Reinstall the motor by inserting the tabs and pushing up into
position. Make sure the wires are not pinched between the
motor and the housing.
A20
Turn on the power source.
A21
Test the motor. If the motor does not run, check the
plug connection.
A22
E1
Go to step E1 on page 18 to attach grill.
7
43053-01 - 09/12/2011
5/8
1/2
1/8" Bit
New construction suspended between joist
B11
B13
Slide the mounting rails into brackets.
B12
5/8
1/2
Position the correct depth mark at the bottom edge of the
joist based on the thickness of your sheetrock.
B14
Mark position of screws by using holes as a template.
B15
Insert screws, leaving space between the screw head and the
joist. Screws are not provided.
Drill a hole in the center of each outline.
B16
Attach the rails onto the screws.
8
43053-01 - 09/12/2011
B17
B18
Tighten screws.
B19
F1
Go to step F1 on page 20 to connect the wires as shown.
Install the wiring cover plate. Make sure all wiring
connections are inside the box or under the wiring cover plate.
B20
Install the wiring cover plate. Make sure all wiring connections
are inside the box or under the wiring cover plate..
B21
Connect 4” duct and vent to the outside. Tape joints. If ducting
does not fit securely, an adapter may need to be purchased.
B22
Connect wiring from the motor to the wiring cover plate.
9
43053-01 - 09/12/2011
B23
ON
OFF
B24
Reinstall the motor by inserting the tabs and pushing up into
position. Make sure the wires are not pinched between the
motor and the housing.
B25
Turn on the power source.
Secure the motor by tightening the 2 screws.
B26
B26
Test the motor. If the motor does not run, check the
plug connection.
B27
E1
Go to step E1 on page 18 to attach grill.
10
43053-01 - 09/12/2011
Existing construction accessible from above
5/8
1/2
C11
Remove an existing fan and check to make sure the opening is
large enough to accommodate the new motor housing (8”x 8.5”).
EXISTING FAN
NO EXISTING FAN
OR
Use the motor housing as a template to mark position.
C12
C13
8”
8.5”
Cut out an opening for the housing.
5/8
1/2
Slide the mounting rails into brackets.
C14
Position the correct depth mark at the bottom edge of the joist
based on the thickness of your sheetrock.
Mark position of screws by using holes as a template.
11
43053-01 - 09/12/2011
C15
C16
1/8" Bit
C17
Drill a hole in the center of each outline.
Attach the rails onto the screws.
Insert screws, leaving space between the screw head and the
joist. Screws are not provided.
C18
Tighten screws.
C19
Connect 4” duct and vent to the outside. Tape joints. If ducting
does not fit securely, an adapter may need to be purchased.
C20
Pull wires through the strain relief.
12
43053-01 - 09/12/2011
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.