This document is for the person who installs and maintains HP UPS products. HP assumes you are qualified
in the installation of electrical equipment and trained in recognizing hazards in products with hazardous
energy levels.
Part Number: 792523-001
November 17, 2014
Edition: 1
Page 2
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS. This manual contains important instructions
that should be followed during installation and maintenance of the UPS and batteries.
The Tower UPS models that are covered in this manual are intended for installation in an environment
within 0 to 40°C/32 to 100°F, free of conductive contaminant.
For all models:
• FCC/EN55022 Class B IEC62040-2 C1
Certication Standards
• UPS directives: UL 1778 4th edition (UL listed).
• Performance: IEC 62040-3: 2001.
• Radiated emission: FCC CFR 47 part 15 subpart B, Class B, VCCI.
See HP EG regulatory notices at http://www.hp.com/support/Safety-Compliance-EnterpriseProducts.
Special Symbols
The following are examples of symbols used on the UPS or accessories to alert you to important
information:
ENGLISH
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol.
Important instructions that must always be followed.
Do not discard the UPS or the UPS batteries in the trash.
This product contains sealed lead acid batteries and must be disposed as it's explain in this manual.
For more information, contact your local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE)
in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
Page 2
792523-001 Edition 1
Page 3
Personal Safety
• The system has an internal battery as a backup power source. Consequently, the power outlets may be energized,
even if the system is disconnected from the AC power source.
• Dangerous voltage levels are present within the system. It should be opened exclusively by qualied
service personnel.
• The system must be properly grounded.
• There are no user serviceable parts inside except for the replaceable battery.
• The battery supplied with the system contains small amounts of toxic materials.
• To avoid accidents, the directives listed below must be observed:
- Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the
required precautions.
- When replacing batteries, replace with the same type and number of batteries or battery packs.
- Do not dispose of batteries in a re. The batteries may explode.
- Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high.
Precautions must be taken for all handling:
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground.
Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock
can be reduced if such grounds are removed during installation and maintenance (applicable to
equipment and remote battery supplies not having a grounded supply circuit).
ENGLISH
Product Safety
• The UPS connection instructions and operation described in the manual must be followed in
the indicated order.
• A protection circuit breaker must be installed upstream and be easily accessible.
The system can be disconnected from the AC power source by opening this circuit breaker.
• Check that the indications on the rating plate correspond to your AC powered system and to
the actual electrical consumption of all the equipment to be connected to the system.
• For PLUGGABLE EQUIPMENT, the outlet shall be installed near the equipment and shall
be easily accessible.
• Never install the system near liquids or in an excessively damp environment.
• Never let a foreign body penetrate inside the system.
• Never block the ventilation grates of the system.
• Never expose the system to direct sunlight or source of heat.
• If the system must be stored prior to installation, storage must be in a dry place.
• The storage temperature range is -15 to +40ºC/5 to 104°F.
• The system is not for use in a computer room AS DEFINED IN the standard for the Protection
of Information Technology Equipment, ANSI/NFPA 75 (US installations only).
Special Precautions
• All handling operations will require at least two people (unpacking, installation in rack system).
• Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be
energized for a period of 24 hours, at least once every 6 months (for a normal storage temperature
less than 25°C/77°F). This charges the battery, thus avoiding possible irreversible damage.
• During the replacement of the battery module, it is imperative to use the same type and number of
element as the original battery module provided with the UPS to maintain an identical level of
performance and safety. For questions, contact your HP representative.
Page 3
Important: Replace the battery module with the same type battery module, available from HP.
2. User Interface ......................................................................................................................8
2.1 Control panel ................................................................................................................................................................ 8
2.3 UPS setting through the LCD ..................................................................................................................................9
3.3 Communication ports ............................................................................................................................................ 11
4.1 Start-up and normal operation ............................................................................................................................ 12
4.2 Starting the UPS on battery .................................................................................................................................. 12
4.4 Operation on battery power .................................................................................................................................12
4.5 Return of AC input power ......................................................................................................................................12
6.1 HP T750 G4 NA/JP UPS, HP T1000 G4 NA/JP UPS, and HP T1500 G4 NA/JP UPS ..............................16
6.2 HP T750 G4 INTL UPS, HP T1000 G4 INTL UPS, and HP T1500 G4 INTL UPS .........................................17
7. Support and other resources ...................................................................................... 18
Page 4
792523-001 Edition 1
Page 5
1. Overview
PET
Save these instructions. This document contains important safety instructions that should be followed during installation,
operation, and maintenance of the UPS and batteries.
1.1 Environmental protection
Products are developed according to an eco-design approach.
Substances
This product does not contain CFCs, HCFCs, or asbestos.
Packing
To improve waste treatment and facilitate recycling, separate the various packing components.
• The cardboard we use comprises over 50% of recycled cardboard.
• Sacks and bags are made of polyethylene.
• Packing materials are recyclable and bear the appropriate identication symbol
MaterialsAbbreviations
Polyethylene terephthalatPET01
High-density polyethyleneHDPE02
Polyvinyl chloridePVC03
Low-density polyethyleneLDPE04
PolypropylenePP05
PolystyrenePS06
ENGLISH
01
Number in
the identification symbols
Follow all local regulations for the disposal of packing materials.
End of life
HP processes products at the end of their service lives in compliance with local regulations.
HP works with companies in charge of collecting and eliminating our products at the end of
their service lives.
Product
The product is made up of recyclable materials.
Dismantling and destruction must take place in compliance with all local regulations concerning waste.
At the end of its service life, the product must be transported to a processing center for electrical and
electronic waste.
Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations
concerning batteries.
The battery may be removed to comply with regulations and correct disposal.
Page 5
792523-001 Edition 1
Page 6
1. Overview
1.2 Weights and dimensions
D
W
1.3 Rear panels
HP T750 G4 NA/JP UPSHP T1000 G4 NA/JP UPS
DescriptionWeights
(kg/lb)
Dimensions (mm/inch)
D x W x H
HP T750 G4 NA/JP UPS10.9 kg/24 lb. 345 x 150 x 231 mm/13.6 x 5.9 x 9.1 in.
HP T1000 G4 NA/JP UPS 11.3 kg/25 lb. 345 x 150 x 231 mm/13.6 x 5.9 x 9.1 in.
H
HP T1500 G4 NA/JP UPS 16.3 kg/36 lb. 445 x 150 x 231 mm/17.5 x 5.9 x 9.1 in.
HP T750 G4 INTL UPS10.4 kg/23 lb. 345 x 150 x 231 mm/13.6 x 5.9 x 9.1 in.
HP T1000 G4 INTL UPS10.4 kg/23 lb. 345 x 150 x 231 mm/13.6 x 5.9 x 9.1 in.
HP T1500 G4 INTL UPS15.2 kg/33.5 lb. 445 x 150 x 231 mm/17.5 x 5.9 x 9.1 in.
ENGLISH
2
RS232 OR
1
OUTPUT
INPUT
4
HP T1500 G4 NA/JP UPS
2
1
RS232 OR
Refer to the Bottom of
the unit for caution markings!
OUTPUT
Refer to the Bottom of
the unit for caution markings!
OUTPUT
INPUT
5
3
2
RS232 OR
5
1
3
OUTPUT
INPUT
OUTPUT
Refer to the Bottom of
the unit for caution markings!
4
5
3
(1) USB communication port
(2) RS-232 communication port
(3) Outlets for connection of critical equipment
(4) Attached 6-ft. input power cord for AC power source
(5) Ground screw
4
Page 6
792523-001 Edition 1
Page 7
1. Overview
HP T750 G4 INTL UPSHP T1000 G4 INTL UPS
ENGLISH
2
RS232 OR
1
OUTPUT
3
4
INPUT
HP T1500 G4 INTL UPS
2
1
3
4
RS232 OR
Refer to the Bottom of
the unit for caution markings!
Refer to the Bottom of
the unit for caution markings!
OUTPUT
5
2
1
RS232 OR
OUTPUT
OUTPUT
5
3
4
5
(1) USB communication port
(2) RS-232 communication port
INPUT
Refer to the Bottom of
the unit for caution markings!
(3) Outlets for connection of critical equipment
(4) Socket for connection to AC power source
(5) Ground screw
INPUT
Page 7
792523-001 Edition 1
Page 8
2. User Interface
10
2.1 Control panel
The UPS has a three-button control panel.
2.2 LCD window
The LCD window provides useful information about the UPS, load status, events, measurements, and settings.
13
15
16
ENGLISH
On/Off button
6
Scroll
AVR
%
Min
Hz
kVA
kW
6
7
8
11
9
12
14
17
7
Mute alarm
8
UPS on line mode
9
AVR (Automatic Voltage Regulation )
10
mode
Battery mode
11
Internal fault
12
Output load level
13
Battery level
14
Input measurements
15
Output measurements
16
Measuring unit
17
Page 8
792523-001 Edition 1
Page 9
2. User Interface
2.3 UPS setting through the LCD
Tower UPS HP T750 G4 NA/JP UPS, HP T1000 G4 NA/JP UPS, HP T1500 G4 NA/JP UPS
Release the scroll down button to select a menu.
5s
Output voltageSensitivity
Tower UPS HP T750 G4 INTL UPS, HP T1000 G4 INTL UPS, HP T1500 G4 INTL UPS
Release the scroll down button to select a menu.
5s2s
ENGLISH
2s
Alarm
2s
2s
2s
(1)
2s
Output voltageAlarm
Sensitivity
(1)
Note: In Lo (low sensitivity) mode, the UPS will tolerate more uctuations in power and goes on battery power less often.
If the connected load is sensitive to power disturbances, keep the sensitivity as Std (Standard).
Example of setting
10s5s5s
Save the new value
Note: The LCD shuts o if there is no activity for three minutes.
Page 9
792523-001 Edition 1
Page 10
3. Installation
3.1 Unpacking and contents check
1
2
(1) HP Tower UPS
(2) Documentation
(4) Two connection cables for protected equipment (HP T750 G4 INTL UPS, HP T1000 G4 INTL UPS, HP T1500 G4 INTL UPS)
(5) RS-232 communication cable
(6) USB communication cable
ENGLISH
4
5
6
Packing materials must be disposed of in compliance with all local regulations concerning waste.
Recycling symbols are printed on the packing materials to facilitate sorting.
3.2 Battery module connection
This operation must be performed when the UPS is switched o and unplugged from the AC source. In addition, do not
disconnect the connector while the unit is operating from the AC source or in reserve mode.
Note: Before starting the UPS, connect the internal battery. A small amount of arcing may occur when connecting the
batteries. This is normal and does not damage the UPS or present any safety concern.
B
A
A
Remove bezel.
B
Connect the
battery module.
Never pull on the
wires.
Page 10
C
C
Attach the bezel.
792523-001 Edition 1
Page 11
3. Installation
3.3 Communication ports
Connection of RS-232 or USB communication port
The RS-232 and USB communication ports cannot operate simultaneously.
2
1
ENGLISH
A
Connect the RS-232 5 or USB
communication cable to
the serial or USB port on
the computer equipment.
5
B
Connect the other end of the
communication cable to the USB
1
or RS-232 2 communication
6
port on
the UPS.
The UPS can now communicate with
HP power management software.
6
3.4 Ground connection
Page 11
792523-001 Edition 1
Page 12
4. Operation
4.1 Start-up and normal operation
To start the UPS:
1. Verify that the UPS power cord is plugged in.
2. Press the button on the UPS control panel for at least two seconds.
3. Check the UPS LCD window display for active alarms.
If the indicator is on, do not proceed until all alarms are cleared.
Correct the alarms and restart if necessary.
4. Verify that the indicator illuminates, indicating that the UPS is operating normally and any loads are powered and
protected.
4.2 Starting the UPS on battery
Before using this feature, the UPS must have been powered by utility power with output enabled
at least once.
To start the UPS on battery:
1. Press the button on the UPS control panel until the UPS LCD window display illuminates.
The UPS cycles through Standby mode to Battery mode. The indicator illuminates.
The UPS supplies power to your equipment.
2. Check the UPS LCD window display for active alarms. Resolve any active alarms before continuing.
See "5.1 Troubleshooting", page 13.
4.3 UPS shutdown
ENGLISH
To shut down the UPS:
1. Press the button on the UPS control panel for three seconds.
2. The audio alarm beeps and shows a status of "UPS shutting OFF...". The UPS then transfers to Standby mode and the
indicator turns o.
3. The audio alarm stops.
4.4 Operation on battery power
Transfer to battery power
• The connected devices continue to be supplied by the UPS when AC input power is no longer available.
The necessary energy is provided by the battery.
• The indicator illuminates.
• The audio alarm beeps every 10 seconds.
The connected devices are supplied by the battery.
Low-battery warning
• The indicator illuminates solid.
• The audio alarm beeps every three seconds.
• The remaining battery power is low. Shut down all applications on the connected equipment because automatic UPS
shutdown is imminent.
End of battery backup time
• LCD displays "End of backup time."
• All the LEDs go o.
• The audio alarms stops.
4.5 Return of AC input power
Following an outage, the UPS restarts automatically when AC input power returns (unless the restart
function has been disabled) and the load is supplied again.
Page 12
792523-001 Edition 1
Page 13
5. Maintenance
5.1 Troubleshooting
Operation status Possible causeAction
Overload
Short-circuit faultA short-circuit occurred.Check device connection or
Battery faultThe batteries in the UPS are
Fan faultThe UPS has a fan fault.Check that no object is blocking the
Charger faultThe UPS has a charger fault.The UPS does not charge the
Power requirement exceeds the UPS
capacity (greater than 105% of nominal).
disconnected.
The end of battery life is reached.Contact your service representative
Remove some of the equipment from
the UPS. The UPS continues to operate,
but may shutdown if the load increases.
The alarm resets when the condition
becomes inactive.
integrity.
If the error persists, note the alarm
message and the UPS serial number, and
then contact your service representative.
Verify that all batteries are properly
connected.
If the error persists, note the alarm
message and the UPS serial number, and
then contact your service representative.
for battery replacement.
fan.
If the error persists, note the alarm
message and the UPS serial number, and
then contact your service representative.
battery anymore.
ENGLISH
5.2 Updating the UPS rmware
To update the UPS rmware, see the HP website (http://www.hp.com/go/rackandpower).
5.3 Battery module replacement
Safety recommendations
Warning: To prevent personal injury from hazardous energy:
• This operation must be performed when the UPS is switched o and unplugged from the AC source.
• Do not disconnect the connector while the unit is operating from the AC mains or in reserve mode.
• The battery connection must not be disconnected while running in reserve mode.
• The battery can cause electrocution and high short-circuit currents. The following safety precautions
are required before servicing the battery components:
• Remove watches, rings, bracelets, and all other metal objects from the hands and arms.
• Use tools with an insulated handle.
• Do not place tools or metal parts on top of batteries.
Note the alarm message and
the UPS serial number, and then
contact your service representative.
Page 13
792523-001 Edition 1
Page 14
5. Maintenance
Replacing the batteries
• Read and observe the requirements in "Important battery safety information" and "Battery care and
storage guidelines" in this section before battery module replacement.
• Follow the instructions in this section to replace the battery module.
Note: Replace all battery modules at the same time.
Important battery safety information
Warning: The unit contains sealed lead-acid battery modules. To prevent re or chemical burns:
• Do not attempt to recharge batteries after removal from the unit.
• Do not disassemble, crush, or puncture the batteries.
• Do not short the external contacts of the batteries.
• Do not immerse the batteries in water.
• Do not expose to temperatures higher than 60°C (140°F).
Battery care and storage guidelines
Caution: Because of the short shelf life of the batteries, avoid storing a battery spare as a
backup. Do not maintain an inventory of spare batteries on site unless a procedure to keep
these batteries charged while in storage is implemented.
To maintain the batteries:
• Minimize the amount of time the UPS uses battery power by matching the UPS conguration with the utility voltage
(see "6.1 HP T750 G4 NA/JP UPS, HP T1000 G4 NA/JP UPS, and HP T1500 G4 NA/JP UPS", page 16 and "6.2 HP T750
G4 INTL UPS, HP T1000 G4 INTL UPS, and HP T1500 G4 INTL UPS", page 17).
• Keep the area around the UPS clean and dust-free. If the environment is very dusty, clean the outside of the UPS
regularly with a vacuum cleaner.
ENGLISH
Battery module removal
A
Remove the bezel.
A
B
Disconnect the battery
module by separating the
connectors.
B
Never pull on the wires.
Page 14
792523-001 Edition 1
Page 15
5. Maintenance
Battery tray removal (cont.)
ENGLISH
C
Remove the plastic
C
D
protection cover
in front of the battery.
D
Pull the plastic tab to
remove the battery block
and replace the block.
5.4 Spares
Installing the new battery module
Perform the removal instructions in reverse order.
● To ensure safety and high performance, only use batteries supplied by HP.
● Take care to firmly press together the two parts of the connector during remounting.
Ordering Spares
To order a spare, visit the HP website (http://www.hp.com/buy/parts).
To replace parts under warranty, contact an HP authorized service representative.
UPS spare parts list
ItemSpare Part Number
SPS-UPS T750 G4 NA/JP 796774-001
SPS-UPS T750 G4 INTL 796775-001
SPS-UPS T1000 G4 NA/JP
6.1 HP T750 G4 NA/JP UPS, HP T1000 G4 NA/JP UPS, and HP T1500 G4 NA/JP UPS
Filter
Output Power @ 120VNA: 750 VA
Output Power @ 110V NA: 750 VA
Output Power @ 100VJPN: 750 VA
• Rated input voltageSingle phase 100-120V
• Input voltage range96 to 144V
• Input frequency
range
• Voltage100/110/120V (-10% to +5%)
• Frequency50/60 Hz ±0.1 Hz
• Standard
• Operating temperature range
• Storage temperature
range
• Relative humidity
• Noise level
(1) Adjustable to 100/110/120V, but must be set to the identical AC power source value.
Transformer
AVR
ChargerInverter
Battery
HP T750 G4 NA/JP
UPS
HP T1000 G4 NA/JP
UPS
NA: 1000 VA
525W
700W
NA: 1000 VA
525W
700W
JPN: 1000VA
500W
680W
AC Input power
45 to 55 Hz (50 Hz system), 55 to 65 Hz (60 Hz system)
Output on battery power
Battery (sealed lead acid, maintenance free)
2 x 12V
7 Ah
2 x 12V
9 Ah
Environment
0 to 35°C/32 to 95°F
-15 to +40°C/5 to 104°F
0 to 90% (without condensation)
< 40 dBA in normal mode
(1)
ENGLISH
HP T1500 G4 NA/
JP UPS
NA: 1440 VA
1080W
NA: 1440 VA
1080W
JPN: 1200 VA
980W
3 x 12V
9 Ah
Page 16
Caution: To reduce the risk of re, connect only to a circuit provided with 20A maximum branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70.
792523-001 Edition 1
Page 17
6. Technical Specifications
6.2 HP T750 G4 INTL UPS, HP T1000 G4 INTL UPS, and HP T1500 G4 INTL UPS
Filter
Output Power @ 230V750 VA
• Rated input voltage
• Input voltage range
• Input frequency range45 to 55 Hz (50 Hz system), 55 to 65 Hz (60 Hz system)
• Voltage
• Frequency50/60 Hz ±0.1 Hz
• Standard
• Operating temperature
range
• Storage temperature
range
• Relative humidity
• Noise level< 40 dBA in normal mode
(1) Adjustable to 220/230/240V, but must be set to the identical AC power source value.
When the UPS is used in the EU area, use an external circuit breaker in front of the line with rating 16A,
250V which is IEC/EN 60898-1 standard compliant.
When the UPS is used in th NA area, use an external circuit breaker in front of the line with rating 20A, 250V.
Page 17
792523-001 Edition 1
Page 18
7. Support and other resources
Safety and regulatory compliance
For safety, environmental, and regulatory information, see Safety and Compliance Information for Server,
Storage, Power, Networking, and Rack Products, available at the HP website
(http://www.hp.com/support/Safety-Compliance-EnterpriseProducts).
Warranty information
HP ProLiant and X86 Servers and Options (http://www.hp.com/support/ProLiantServers-Warranties)
Before you contact HP
Be sure to have the following information available before you call HP:
• Active Health System log (HP ProLiant Gen8 or later products)
• Download and have available an Active Health System log for 7 days before the failure was detected. For more
information, see the HP iLO 4 User Guide or HP Intelligent Provisioning User Guide on the HP website (http://www.
hp.com/go/ilo/docs).
• Onboard Administrator SHOW ALL report (for HP BladeSystem products only)
• For more information on obtaining the Onboard Administrator SHOW ALL report, see the HP website (http://www.
hp.com/go/OAlog).
• Technical support registration number (if applicable)
• Product serial number
• Product model name and number
• Product identication number
• Applicable error messages
• Add-on boards or hardware
• Third-party hardware or software
• Operating system type and revision level
ENGLISH
HP contact information
For United States and worldwide contact information, see the Contact HP website (http://www.hp.com/go/assistance).
In the United States:
• To contact HP by phone, call 1-800-334-5144. For continuous quality improvement, calls may be recorded or monitored.
• If you have purchased a Care Pack (service upgrade), see the Support & Drivers website (http://www8.hp.com/us/
en/support-drivers.html). If the problem cannot be resolved at the website, call 1-800-633-3600. For more information about Care Packs, see the HP website (http://pro-aq-sama.houston.hp.com/services/cache/10950-0-0-225-121.
html).
Product QuickSpecs
For more information about product features, specications, options, congurations, and compatibility, see the product
QuickSpecs on the HP website (http://www.hp.com/go/qs).
Documentation feedback
HP is committed to providing documentation that meets your needs. To help us improve the documentation, send any
errors, suggestions, or comments to Documentation Feedback (mailto: docsfeedback@hp.com). Include the document
title and part number, version number, or the URL when submitting your feedback.
Page 18
792523-001 Edition 1