General characteristics
Power rating (non-redundant)
Power rating N+1
Efficiency
Heat dissipation
Cooling
Altitude before derating
Input characteristics
Input connection
Input voltage
Voltage range
Frequency range
Input current distortion
Input power factor
Inrush current
Input requirements
Bypass source
Generator compatibility
Output characteristics
Output connection
Rated output voltage
Output configuration
Output frequency (nominal)
Frequency regulation
Load power factor range
Total output voltage distortion
Battery characteristics
Battery type
Battery run time (internal)
Battery string voltage
Battery test
Battery recharge profile
Battery cut-off voltage
Battery low condition
Extended battery capability
36 kW / 36 kVA
24 kW / 24 kVA
>97%
<1113 W / 3800 BTU/hr. at 100% rated load
Fan-cooled, temperature microprocessor monitored; front air entry, rear exhaust
1000 meters (3300 ft. ASL)
Hard-wired from facility power
208 VAC and 400 VAC models
208V model: 180 to 265 VAC (N.A.)
400V model: 311 to 519 VAC (Intl.)
50 or 60 Hz, ±5 Hz (auto-sensing)
<5% with IT loads (PFC power supplies)
>.99 with IT loads (PFC power supplies)
Load dependent
Hard-wired, three-phase, wye (5 wire, 4 pole)
Same as input (single-feed)
Fast sync slew rate for generator synchronization
Hard-wired from power bus bar or uses optional output modules
208V model: 180 to 255 VAC, Ph to Ph
400V model: 180 to 240 VAC, Ph to N
Three-phase, wye. Three-phase Delta can be provided by optional
output modules
50 or 60 Hz auto-detection on startup
0.1 Hz free-running
Lagging: 0.7
Leading: 0.9
<3% with IT loads (PFC power supplies)
<5% with non-linear or non-PFC power supplies
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
>5 minutes at 100% load
240 VDC
Automatic battery test standard
Manual battery test from front display
Enhanced Battery Management three-stage charging technology
Variable from 1.67 VPC at <5 min. run time to 1.75 VPC at >90 min. run time
Announced with alarm
Yes, add up to four additional 3U battery enclosures per RP12000/3
UPS Module
12 kW / 12 kVA
60 kW / 60 kVA maximum configuration
>97%
<371 W / 1266 BTU/hr. at 100% rated load
Fan-cooled, temperature microprocessor monitored; front air entry, rear exhaust
1000 meters (3300 ft. ASL)
Connects to power bus bar
208 VAC and 400 VAC models
208V model: 180 to 265 VAC (N.A.)
400V model: 311 to 519 VAC (Intl.)
50 or 60 Hz, ±5 Hz (auto-sensing)
<5% with IT loads (PFC power supplies)
>.99 with IT loads (PFC power supplies)
Load dependent
Hard-wired, three-phase, wye (5 wire, 4 pole)
Same as input (single-feed)
Fast sync slew rate for generator synchronization
Hard-wired from power bus bar or uses optional output modules
208V model: 180 to 255 VAC, Ph to Ph
400V model: 180 to 240 VAC, Ph to N
Three-phase, wye. Three-phase Delta can be provided by optional
output modules
50 or 60 Hz auto-detection on startup
0.1 Hz free-running
Lagging: 0.7
Leading: 0.9
<3% with IT loads (PFC power supplies)
<5% with non-linear or non-PFC power supplies
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
>5 minutes at 100% load
240 VDC
Automatic battery test standard
Manual battery test from front display
Enhanced Battery Management three-stage charging technology
Variable from 1.67 VPC at <5 min. run time to 1.75 VPC at >90 min. run time
Announced with alarm
Yes, add up to four additional 3U battery enclosures per RP12000/3
UPS Module
RP36000/3 (base unit) RP12000/3 (optional UPS expansion module)
Technical specifications
3