The information contained herein is subject to change without notice. The only warranties for HP products and
services are set forth in the express warranty statements accompanying such products and services. Nothing
herein should be construed as constituting an additional warranty. HP shall not be liable for technical or
editorial errors or omissions contained herein.
Audience assumptions
This guide is for the person who operates, configures, maintains, and troubleshoots UPSs. HP
assumes you are qualified in the servicing of high-voltage equipment and trained in recognizing
hazards in products with hazardous energy levels.
Class A EMC Statements
EN 62040-2
Some configurations are classified under EN 62040-2 as “Category C2 UPS.” For these configurations, the following applies:
WARNING This is a category C2 UPS product. In a residential environment, this product may cause radio interference, in which case the
user may be required to take additional measures.
Special Symbols
The following are examples of symbols used on the UPS or accessories to alert you to important information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol.
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for additional
information, such as important operating and maintenance instructions.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. This product contains
sealed, lead-acid batteries and must b e disposed of properly. For more information, contact your local
recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash.
For proper disposal, contact your local recycling/reuse or hazardous waste center.
National Electrical Code and NEC are registered trademarks of National Fire Protection Association, Inc. Phillips is a registered trademark of
Phillips Screw Company. All other trademarks are property of their respective companies.
Typical Alarms and Conditions37........................................................
Silencing the Alarm38.................................................................
Service and Support38................................................................
One Year Limited Warranty39..........................................................
ii
HP R3000v UPS User Guide S 164201731 Rev 1
Chapter 1Introduction
The HP R3000v Uninterruptible Power System (UPS) protects your sensitive electronic
equipment from the most common power problems, including power failures, power sags,
power surges, brownouts, line noise, high voltage spikes, frequency variations, switching
transients, and harmonic distortion.
Power outages can occur when you least expect them, and power quality can be erratic.
These power problems have the potential to corrupt critical data, destroy unsaved work
sessions, and damage hardware — causing hours of lost productivity and expensive
repairs.
With the HP R3000v UPS, you can safely eliminate the effects of power disturbances and
guard the integrity of your equipment. Providing outstanding performance and reliability, the
HP R3000v UPS’s unique benefits include:
S True online double-conversion technology with high power density, utility frequency
independence, and generator compatibility.
S Space-optimizing 2U size that fits any standard 48 cm (19”)rack.
S Standard communication options: one RS-232 communication port and one USB
communication port.
S Extended runtime with up to four Extended Runtime Modules (ERMs) per UPS.
S Firmware that is easily upgradable without a service call.
Figure 1 shows the HP R3000v UPS, and Figure 2 shows the optional ERM.
Figure 1 The HP R3000v UPS
Figure 2 The HP R3000v ERM
HP R3000v UPS User Guide S 164201731 Rev 1
1
INTRODUCTION
2
HP R3000v UPS User Guide S 164201731 Rev 1
Chapter 2Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the
equipment and save this manual for future reference.
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS
inside the UPS.
S This UPS contains its own energy source (batteries). The UPS output may carry live voltage
even when the UPS is not connected to an AC supply.
S To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature must
not exceed 40°C (104°F). Do not operate near water or excessive humidity
(90% maximum).
S To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent
protection in accordance with the National Electrical Code
S Output overcurrent protection and disconnect switch must be provided by others.
S To comply with international standards and wiring regulations, the sum of the leakage
current of the UPS and the total equipment connected to the output of this UPS must not have
an earth leakage current greater than 3.5 milliamperes.
S If installing an optional rackmount Extended Runtime Module, install the ERM or ERMs
directly below the UPS so that all wiring between the cabinets is installed behind the front
bezels and is inaccessible to users. The maximum number of ERMs per UPS is four.
DANGER
WARNING
®
(NEC®), ANSI/NFPA 70.
CAUTION
S Batteries can present a risk of electrical shock or burn from high short-circuit current. Observe
proper precautions. Servicing should be performed by qualified service personnel
knowledgeable of batteries and required precautions. Keep unauthorized personnel away
from batteries.
S Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
S Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
S Replace batteries with the same number and type of batteries as originally installed in the
UPS.
S If the UPS requires any type of transportation, disconnect the UPS internal batteries before
transporting (see page 26).
HP R3000v UPS User Guide S 164201731 Rev 1
3
SAFETY WARNINGS
4
HP R3000v UPS User Guide S 164201731 Rev 1
Chapter 3Installation
This section explains:
S Equipment inspection
S Unpacking the cabinet
S Checking the accessory kit
S Cabinet installation
S Wiring installation
S Initial startup
S UPS rear panel
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping cartons and
packing materials for the carrier or place of purchase and file a claim for shipping damage.
If you discover damage after acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier within
15 days of receipt of the equipment; 2) Send a copy of the damage claim within 15 days
to your service representative.
Unpacking the Cabinet
NOTE: Check the battery recharge date on the shipping carton label. If the date has expired
and the batteries were never recharged, do notusetheUPS.Contactyourservice
representative.
CAUTION
S Unpacking the cabinet in a low-temperature environment may cause condensation to occur
in and on the cabinet. Do not install the cabinet until the inside and outside of the cabinet
are absolutely dry (hazard of electric shock).
S The cabinet is heavy (see page 35). Use caution to unpack and move the cabinet.
Use care when moving and opening the carton. Leave the components packaged until you
are ready to install.
To unpack the cabinet and accessories:
1. Open the outer carton and remove the accessories packaged with the cabinet.
2. Carefully lift the cabinet out of the outer carton.
3. Discard or recycle the packaging in a responsible manner, or store it for future use.
Place the cabinet in a protected area that has adequate airflow and is free of humidity,
flammable gas, and corrosion.
HP R3000v UPS User Guide S 164201731 Rev 1
5
INSTALLATION
Checking the Accessory Kit
Verify that the following additional items are included with the UPS:
S UPS user guide
S CD with HP Value UPS Manager
S USB cable
S Serial cable
S Two power cords (one for India and one for China)
If you ordered an optional Extended Runtime Module, verify that an ERM user guide is
included with the ERM.
NOTE: Discard the ERM user guide if you are installing the ERM with a new UPS at the same
time. Use the UPS user guide to install both the UPS and the ERM.
Rackmount Installation
The HP R3000v UPS rackmount cabinet comes with all of the hardware required for
installation in a standard EIA or JIS seismic rackmount configuration with square and round
mounting holes. The rail assemblies adjust to mount in 48-cm (19-inch) racks with front to
rear rail distances from 61 to 76 cm (24 to 30 inches) deep.
Checking the Rail Kit Accessories
Verify that the following rail kit items are included for each cabinet:
S Left rail assembly:
-Leftrail
-Rearrail
-(3)M4
×8 pan-head screws
S Right rail assembly:
- Right rail
-Rearrail
-(3)M4
×8 pan-head screws
S Rail hardware kit:
- (10) M6
- (10) M6 hex cage nuts
- (10) M6 square cage nuts
- (2) rear stop brackets
-(6)M3
×16 pan-head screws
×8 pan-head screws
S Mounting bracket kit:
- (2) mounting brackets
-(8)M4
×6flat-headscrews
6
HP R3000v UPS User Guide S 164201731 Rev 1
INSTALLATION
Tools Required
To assemble the components, the following tools may be needed:
S Medium flat-bladed screwdriver
S Phillips
®
#2 screwdriver
S 7 and 8 mm wrench or socket
Rackmount Setup
CAUTION
S The cabinet is heavy (see page 35). A minimum of two people are required to remove the
cabinet from its carton.
S If installing optional ERM(s), install the ERM(s) directly below the UPS so that all wiring
between the cabinets is installed behind the front bezels and is inaccessible to users.
NOTE: Mounting rails are required for each individual cabinet.
To install the rail kit:
1. Attach the left and right rails to the rear rails as shown in Figure 3. Do not tighten the
screws.
Adjusteachrailsizeforthedepthofyourrack.
Rear Rails
M4
×8Pan-Head
Screws (6 places)
Left Rail
Figure 3 Attaching the Rails
Right Rail
HP R3000v UPS User Guide S 164201731 Rev 1
7
INSTALLATION
2. SelecttheproperholesintherackforpositioningtheUPSintherack(seeFigure4).
The rails occupy four positions on the front and rear of the rack.
3. Secure one rail assembly to the front of the rack with one M6
and one M6 cage nut.
4. Using two M6 cage nuts and two M6
×16 pan-head screws, attach the rail assembly
to the rear of the rack.
Position 4
Position 1
M6 Cage Nuts
(6 places)
Tighten
adjustment
screws after rail
attachment
(3 places each rail).
M6×16 Pan-Head
Screws (6 places)
Figure 4 Securing the Rails
×16 pan-head screw
Front of Rack
5. Repeat Steps 3 and 4 for the other rail assembly.
6. Tighten the three adjustment screws on each rail assembly.
7. If installing optional cabinets, repeat Step 1 through Step 6 for each rail kit.
8. Place the UPS on a flat, stable surface with the front of the cabinet facing you.
9. Align the mounting brackets with the screw holes on each side of the UPS and secure
with the supplied M4
×6 flat-head screws (see Figure 5).
NOTE: There are two sets of four mounting holes on each side of the UPS: a forward position
and a middle position. Choose the position that meets your configuration needs.
Mounting
Bracket
M4×6Flat-Head
Screws (4 places)
Figure 5 Installing the Mounting Brackets (Forward Position Shown)
10. If installing optional cabinets, repeat Steps 8 and 9 for each cabinet.
8
HP R3000v UPS User Guide S 164201731 Rev 1
INSTALLATION
CAUTION
The ERM is heavy (see page 35). A minimum of two people are required to lift the cabinet into
the rack.
11. Slide the UPS and any optional cabinets into the rack.
12. Secure the front of the UPS to the rack using two M6
×16 pan-head screws and two
M6 cage nuts on each side (see Figure 6). Install the bottom screw on each side
through the bottom hole of the mounting bracket and the bottom hole of the rail
assembly.
Repeat for any optional cabinets.
M6 Cage Nuts
(4 places)
M6×16 Pan-Head
Screws (4 places)
Figure 6 Securing the Front of the Cabinet
13. Optional. Insert a rear stop bracket through the inside of each rail assembly behind the
UPS. Rotate each bracket and slide the bracket until it fits tightly against the UPS’s rear
panel. Secure each bracket to the UPS with one M3
×8 pan-head screw. See
Figure 7.
Rear Stop Bracket
Repeat for any optional cabinets.
Figure 7 Securing the Back of the Cabinet (Optional)
14. Continue to “Rackmount Wiring Installation” on page 10.
HP R3000v UPS User Guide S 164201731 Rev 1
M3
×8 Pan-Head Screw
9
INSTALLATION
Rackmount Wiring Installation
This section explains:
S Installing the UPS, including connecting the UPS internal batteries
S Connecting any optional ERMs
Installing the UPS
NOTE: Do not make unauthorized changes to the UPS; otherwise, damage may occur to your
equipment and void your warranty.
NOTE: Do not plug the UPS power cord into a power outlet until after the installation is
completed.
To install the UPS:
1. RemovetheUPSrightfrontbezel.SeeFigure8.
To remove the bezel, loosen the two captive screws on the right side of the bezel.
Grasp the top and bottom of the bezel and slide the bezel to the right.
NOTE: A ribbon cable connects the control panel to the UPS. Do not pull on the cable or
disconnect it.
NOTE: Leave
ribbon cable
connected.
Figure 8 Removing the UPS Right Front Bezel
10
HP R3000v UPS User Guide S 164201731 Rev 1
INSTALLATION
NOTE: A small amount of arcing may occur when connecting the internal batteries. This is
normal and will not harm personnel. Connect the cables quickly and firmly.
2. Connect the internal battery connector (see Figure 9).
Connect red to red, and black to black. Press the two parts tightly together to ensure a
proper connection.
Figure 9 Connecting the UPS Internal Batteries
3. If you are installing ERMs, see the section, “Connecting the ERM(s),” before continuing
with the UPS installation.
4. Replace the UPS right front bezel.
To replace the bezel, verify that the ribbon cable is protected and (if ERMs are
installed) the ERM cable is routed through the knockout on the bottom of the bezel.
Slide the bezel to the left until it aligns with the left front bezel. Tighten the two captive
screws on the right side of the right front bezel.
5. If you are installing power management software, connect your computer to one of the
communication ports using the appropriate cable (supplied). See page 21 for more
information.
6. If your rack has conductors for grounding or bonding of ungrounded metal parts,
connect the ground cable (not supplied) to the ground bonding screw. See Figure 13
on page 15 for the location of the ground bonding screw.
7. Continue to “UPS Initial Startup” on page 14.
HP R3000v UPS User Guide S 164201731 Rev 1
11
INSTALLATION
Connecting the ERM(s)
To install the optional ERM(s) for a UPS:
1. On the bottom of the UPS right front bezel, remove the knockout for the ERM cable.
SeeFigure10.
NOTE: Use care to protect the control panel and the connected ribbon cable from damage.
ERM Cable Knockout
Figure 10 Removing the Knockout
2. Remove the front bezel of each ERM. See Figure 11.
To remove the bezel, loosen the two captive screws on the right side of the bezel.
Grasp the sides of the bezel. Slide the bezel to the left and then away from the
cabinet.
Top ERM Cable Knockout
ERM Bezel Hook
12
HP R3000v UPS User Guide S 164201731 Rev 1
Bottom ERM Cable Knockout
(underneath bezel)
Figure 11 Removing the ERM Front Bezel
INSTALLATION
3. For the bottom (or only) ERM, remove the ERM cable knockout on the top of the ERM
front bezel. See Figure 11 for the location of the top ERM cable knockout.
4. If you are installing more than one ERM, for each additional ERM remove the ERM
cable knockout on the top and bottom of the ERM front bezel. See Figure 11 for the
location of the ERM cable knockouts.
NOTE: A small amount of arcing may occur when connecting an ERM to the UPS. This is
normal and will not harm personnel. Insert the ERM cable into the UPS battery connector quickly
and firmly.
5. Plug the ERM cable(s) into the battery connector(s) as shown in Figure 12. Up to four
ERMs may be connected to the UPS.
Connect red to red, black to black, and green to green. Press the two parts tightly
together to ensure a proper connection.
To connect a second ERM, unclip the ERM connector on the first ERM and pull gently to
extend the wiring to the ERM connector on the second ERM. Repeat for any additional
ERMs.
6. Verify that the ERM connections are tight and that adequate bend radius and strain
relief exist for each cable.
Figure 12 Typical ERM Installation
7. Replace the ERM front bezel.
To replace the bezel, verify that the ERM cables are routed through the ERM cable
knockouts. Slide the bezel from the left to the right until it connects with the bezel hook
near the left side of the ERM cabinet. Tighten the two captive screws on the right side
of the front bezel. For reference, see Figure 11 on page 12.
Repeat for each additional ERM.
8. Verify that all wiring connecting the UPS and ERM(s) is installed behind the front bezels
and is inaccessible to users.
NOTE: To ensure maximum battery runtime, configure the UPS for the correct number of ERMs
through the HP Value UPS Manager software. Refer to the HP Value UPS Manager manual.
9. Return to Step 4 on page 11 to continue the UPS installation.
HP R3000v UPS User Guide S 164201731 Rev 1
13
INSTALLATION
UPS Initial Startup
To start up the UPS:
NOTE: Verify that the total equipment ratings do not exceed the UPS capacity to prevent an
overload alarm.
1. Verify that the internal batteries are connected. See “Installing the UPS” on page 10.
2. If optional ERMs are installed, verify that the ERMs are connected to the UPS. See
“Connecting the ERM(s)” on page 12.
3. Plug the equipment to be protected into the UPS, but do not turn on the protected
equipment.
4. Make any necessary provisions for cord retention and strain relief.
5. Plug the detachable UPS power cord into the input connector on the UPS rear panel.
6. Plug the UPS power cord into a power outlet.
7. Press the
(Output On) button on the UPS front panel for at least one second.
8. Check the UPS front panel for active alarms. Resolve any active alarms before
continuing. See “Troubleshooting” on page 39.
If the
(Alarm) indicator is on, do not proceed until all alarms are clear. Check the
UPS status from the front panel to view the active alarms. Correct the alarms and
restart, if necessary.
9. Verify that the
(Power On) indicator is illuminated, indicating that the UPS is
operating normally and any loads are powered.
The UPS should be in Normal mode.
10. If optional ERMs are installed, see “Configuring the UPS for ERMs” on page 20 to set
thenumberofinstalledERMs.
NOTE: The batteries charge to 90% capacity in less than 3 hours. However, to fully charge, HP
recommends that the batteries charge for 48 hours after installation or long-term storage.
NOTE: Verify that the UPS firmware is updated. See “Updating the UPS Firmware” on
page 33.
14
HP R3000v UPS User Guide S 164201731 Rev 1
Rear Panel
INSTALLATION
(8) IEC 320-10A
Output Receptacles
IEC C20-16A Input Connector
(1) IEC 320-16A
Output Receptacle
Ground Bonding Screw
Figure 13 HP R3000v UPS
RS-232 Communication
Port
USB Port
HP R3000v UPS User Guide S 164201731 Rev 1
15
INSTALLATION
16
HP R3000v UPS User Guide S 164201731 Rev 1
Chapter 4Operation
This chapter contains information on how to use the HP R3000v UPS, including front panel
operation, operating modes, UPS startup and shutdown, and battery settings.
Control Panel Functions
The UPS has two buttons and four LEDs on the right front bezel (see Figure 14).
Power On Indicator (green)
On Battery Indicator (yellow)
Bypass Indicator (yellow)
Alarm Indicator (red)
Output On/Alarm
Silence Button
Output Off Button
Figure 14 HP R3000v UPS Control Panel
Table 1 shows the indicator status and description.
Table 1. Indicator Descriptions
IndicatorStatusDescription
OnThe UPS is operating normally.
Green
OnThe UPS is in Battery mode.
Yellow
Yellow
Red
FlashingThe battery voltage is below the warning level.
OnThe UPS is in Bypass mode.
OnThe UPS has an active alarm or fault. See “Troubleshooting” on
page 39 for additional information.
HP R3000v UPS User Guide S 164201731 Rev 1
17
OPERATION
Operating Modes
The HP R3000v UPS front panel indicates the UPS status through the UPS indicators (see
Figure 14 on page 17).
Normal Mode
During Normal mode, the(Power On) indicator illuminates and the UPS is powered
from the utility. The UPS monitors and charges the batteries as needed and provides filtered
powerprotectiontoyourequipment.
Battery Mode
When the UPS is operating during a power outage, the alarm beeps once every five
seconds and the
When the utility power returns, the UPS transfers to Normal mode operation while the
battery recharges.
(On Battery) indicator illuminates.
If battery capacity becomes low while in Battery mode, the
(On Battery) indicator
flashes slowly and the audible alarm beeps once every second. If the Battery Low alarm is
set, the
(Alarm) indicator also illuminates. This warning is approximate, and the actual
time to shutdown may vary significantly.
NOTE: Depending on the UPS load and the number of Extended Runtime Modules (ERMs)
connected, the Battery Low warning may occur before the batteries reach 25% capacity. See
Table 9 on page 37 for estimated runtimes.
When utility power is restored after the UPS shuts down, the UPS automatically restarts.
NOTE: You can configure the auto-restart option through the HP Value UPS Manager software
(see page 23).
Bypass Mode
NOTE: You can manually transfer the UPS to Bypass mode by pressing the(Output Off)
button once within four seconds. If Bypass mode is not available, the UPS returns to its original
operating mode.
NOTE: You can configure Bypass mode options through the HP Value UPS Manager software
(see page 23).
In the event of a UPS overload or internal failure, the UPS transfers your equipment to utility
power. Battery mode is not available and your equipment is not protected; however, the
utility power continues to be passively filtered by the UPS. The
illuminates.
(Bypass) indicator
The UPS remains in Bypass mode for at least five seconds (if the bypass source remains
acceptable). If three transfers to bypass occur within 10 minutes for any reason other than
user command, the UPS locks in Bypass mode for one hour or until any control button is
pressed.
18
HP R3000v UPS User Guide S 164201731 Rev 1
OPERATION
The UPS transfers to Bypass mode when:
S The UPS detects an internal failure.
S The UPS has an overtemperature condition.
S The UPS has an overload condition listed in Table 7 on page 36.
NOTE: The UPS shuts down after a specified delay for overload conditions listed in Table 7 on
page 36. The UPS logic power remains on to alarm the fault.
Standby Mode
When the UPS is turned off and remains plugged into a power outlet, the UPS is in Standby
mode. The
equipment. The battery recharges when necessary.
If utility fails and output turns off due to drained batteries or UPS internal failure, the UPS is in
Standby mode.
(Power On) indicator is off, indicating that power is not available to your
UPS Startup and Shutdown
If the UPS is waiting on commands and utility fails, unit and logic power turn off in
approximately 30 seconds.
To start up or shut down the UPS, see:
S “Starting the UPS” below
S “Starting the UPS on Battery” on page 20
S “UPS Shutdown” on page 20
Starting the UPS
To start the UPS:
1. Verify that the UPS power cord is plugged in.
2. Press the
3. Check the UPS front panel for active alarms. Resolve any active alarms before
continuing. See “Troubleshooting” on page 39.
If the
UPS status from the front panel to view the active alarms. Correct the alarms and
restart, if necessary.
(Output On) button on the UPS front panel for at least one second.
(Alarm) indicator is on, do not proceed until all alarms are clear. Check the
4. Verify that the
operating normally and any loads are powered.
The UPS should be in Normal mode.
(Power On) indicator is illuminated, indicating that the UPS is
HP R3000v UPS User Guide S 164201731 Rev 1
19
OPERATION
Starting the UPS on Battery
NOTE: Before using this feature, the UPS must have been powered by utility power with output
enabled at least once.
To start the UPS on battery:
Configuring the UPS for ERMs
1. Press the
The UPS cycles through Standby mode to Battery mode. The
illuminates. The UPS supplies power to your equipment.
2. Check the UPS front panel for active alarms. Resolve any active alarms before
continuing. See “Troubleshooting” on page 39.
(Output On) button on the UPS front panel for at least one second.
(On Battery) indicator
UPS Shutdown
To shut down the UPS,
1. Press the
The UPS then transfers to Standby mode (if utility power is available) and the
(Power On) indicator turns off.
NOTE: Pressing the(Output Off) button once within four seconds transfers the UPS to Bypass
mode, if available. If Bypass mode is not available, the UPS returns to its original operating
mode.
2. Unplug the UPS from the power outlet.
To ensure maximum battery runtime, configure the UPS for the correct number of ERMs
through the HP Value UPS Manager software.
(Output Off) button on the UPS front panel twice within four seconds.
Battery Tests
Automatic battery tests run approximately every 30 days. You can also manually perform a
battery test by pressing the
During the battery test, the UPS transfers to Battery mode and discharges the batteries for
25 seconds under the existing load.
To run a battery test:
S The UPS must be in Normal mode, with no active alarms.
S The batteries must be fully charged.
S The bypass voltage must be acceptable.
S No manual battery test was initiated previously in the same charging cycle.
To pass the battery test, the battery voltage must remain above the threshold value during
discharge.
20
HP R3000v UPS User Guide S 164201731 Rev 1
(Output On) button for half a second.
Chapter 5Communication
This section describes the:
S Communication ports (RS-232 and USB)
S HP Value UPS Manager software
Figure 15 shows the location of the communication options on a typical UPS.
Figure 15 Communication Options
RS-232
USB
RS-232 and USB Communication Ports
NOTE: The communication speed of the USB port is fixed at 2400 bps.
To establish communication between the UPS and a computer, connect your computer to
one of the UPS communication ports using an appropriate communication cable (supplied).
See Figure 15 for the communication port locations.
When the communication cable is installed, power management software can exchange
data with the UPS. The software polls the UPS for detailed information on the status of the
power environment. If a power emergency occurs, the software initiates the saving of all
data and an orderly shutdown of the equipment.
HP R3000v UPS User Guide S 164201731 Rev 1
21
COMMUNICATION
ThecablepinsfortheRS-232communicationport are identified in Figure 16 and the pin
functions are described in Table 2.
5
9
4
8
3
7
2
6
1
Figure 16 RS-232 Communication Port (DB-9 Connector)
Table 2 RS-232 Communication Port Pin Assignment
Pin NumberSignal NameFunctionDirection from the UPS
1DCDNot used—
2RxDTransmit to external deviceOut
3TxDReceive from external deviceIn
4DTRNot used—
5GNDSignal common (tied to chassis)—
6DSRNot used—
7RTSNot used—
8CTSNot used—
9RINot used—
22
HP R3000v UPS User Guide S 164201731 Rev 1
HP Value UPS Manager Software
Each HP R3000v UPS ships with HP Value UPS Manager software. To install the HP Value
UPS Manager software, see the instructions accompanying the CD.
After installing the HP Value UPS Manager software, you can configure UPS parameters:
1. Select UPS Control Parameters from the Device menu.
2. Modify the parameters (see Table 3).
3. Click OK to save any modified parameters. Click Cancel to ignore any changes.
COMMUNICATION
The UPS Control Parameters dialog appears (see Figure 17).
Click Default to revert all settings to the default values.
Figure 17 UPS Control Parameters Dialog
HP R3000v UPS User Guide S 164201731 Rev 1
23
COMMUNICATION
Table 3 UPS Control Parameters
Parameter
UnitMaximum MinimumDefaultAction
Input Frequency Range%102Low limit: 10
High limit: 10
Voltage Range on Bypass%204Low limit: 15
High limit: 10
ERM number—40—
Allow ON-Key to Enable/Disable Audible
———YesWhen the UPS is in Bypass mode, users can
Warning When UPS Works on Bypass
Allow ON-Key to Enable/Disable Audible
———YesWhen the UPS is in Battery mode, users can
Warning When UPS Works on Battery
Mode
If the utility power frequency is out of range
(2–10%) while the UPS is in Bypass mode, the
UPS transfers to Battery mode. Enter a low limit
and a high limit for the input frequency range.
If the utility power voltage is out of range
(4–20%) while the UPS is in Bypass mode, the
UPS transfers to Battery mode.
Set the number of Extended Runtime Modules
according to the number of ERMs installed with
the UPS (0–4 ERMs).
turn off the audible a larm (the UPS beeps once
every five seconds) by pressing the(Output
On) button once. To recover the audible alarm,
press the(Output On) button once.
Select “No” to disable the front panel control;
thealarmcannotbeturnedoffwhiletheUPSis
in Bypass mode.
turn off the audible a larm (the UPS beeps once
every five seconds) by pressing the(Output
On) button once. To recover the audible alarm,
press the(Output On) button once.
Select “No” to disable the front panel control;
thealarmcannotbeturnedoffwhiletheUPSis
in Battery mode.
Bypass Audible Warning———OnWhen the UPS is in Bypass mode, the audible
alarm will sound.
Select “Silent” to disable the audible alarm
when the UPS is in Bypass mode. When
“Silent” is selected, the(Output On) button
cannot turn on the audible alarm.
Battery Mode Audible Warning———OnWhen the UPS is in Battery mode, the audible
alarm will sound.
Select “Silent” to disable the audible alarm
when the UPS is in Battery mode. When
“Silent” is selected, the(Output On) button
cannot turn on the audible alarm.
Work On Bypass When UPS Turned Off———NoWhen the UPS is off, Bypass mode is not
available.
Select “Yes” to allow the UPS to provide
bypass power when the UPS is turned off.
Auto Reboot UPS When AC Input Restored———YesIf the battery runtime is depleted, the UPS shuts
down. The UPS automatically restarts when
utility power is restored.
Select “No” to stop the UPS from restarting
automatically. The UPS can be manually started
from the front panel only.
24
HP R3000v UPS User Guide S 164201731 Rev 1
Loading...
+ 68 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.