HP R8000/3, R12000/3 Quickspecs

Crowded data centers and racks filled to capacity with storage devices, monitors, servers communications devices, and other equipment are driving the need for uninterruptible power with increased power density and power efficiency. The HP 3 Phase Uninterruptible Power Systems provide just that. These rack-mountable Uninterruptible Power Systems provide up to 12,000 watts (W) of power in a 6-U rack form factor. This equates to 2 KW per U space, which leads the industry in power density. The UPS R8000/3 and the R12000/3 use digital signal processing and a new On-line On Demand hybrid technology to answer the demands for increased power density and power efficiency.
UPS R8000/3 and R12000/3 front view
UPS R8000/3 and R12000/3 front viewUPS R8000/3 and R12000/3 front view
UPS R8000/3 and R12000/3 front view
UPS R8000/3 and R12000/3 rear view
UPS R8000/3 and R12000/3 rear viewUPS R8000/3 and R12000/3 rear view
UPS R8000/3 and R12000/3 rear view
1.
Battery compartment (behind bezel)
1.
Communications terminal block
2.
Menu navigation buttons
2.
Output circuit breaker
3.
Status and alarm LED display
3.
Input circuit breaker
4.
Electronics module compartment (behind bezel)
4.
Battery circuit breaker
5.
Input/output location R8000/3, input location R12000/3 1
6.
ERM connector
7.
Option card slots
8.
Output connector R12000/3
9.
Ground bonding screw
10.
DB9 Service port
11.
REPO port
Models
ModelsModels
Models
HP R8000/3
HP R8000/3HP R8000/3
HP R8000/3
HP R8000/3 8000kVA Three Phase 6U Rackmount Uninterruptible Power System
AF431A
HP R12000/3
HP R12000/3HP R12000/3
HP R12000/3
HP R12000/3 12000VA Three Phase 6U Rackmount Uninterruptible Power System
AF429A
QuickSpecs
HP Rackmountable 3 Phase Uninterruptible Power
HP Rackmountable 3 Phase Uninterruptible PowerHP Rackmountable 3 Phase Uninterruptible Power
HP Rackmountable 3 Phase Uninterruptible Power
Systems
SystemsSystems
Systems
Overview
DA - 12857 North America — Version 8 — June 20, 2011
Page 1
Key Features
Key FeaturesKey Features
Key Features
Unity Rated, volt amperage out equals wattage out Highest wattage per U space. Up to 12000 VA/12KW in only 6U Industry leading efficiency with On-line On Demand hybrid technology Attached line cords for easier and faster connection to your facility power Hot-swappable battery and electronics modules provide ease of maintenance and faster time to repair (MTTR) Industry leading efficiency with On-line On Demand hybrid technology Attached line cords for easier and faster connection to your facility power Extra long battery life with Enhanced Battery Management (EBM) Extended battery run time with optional Extended Runtime Modules (ERMs) Easy configuration through enhanced front panel display or HP UPS Management Module (included) Backed by a limited three-year warranty, HP's pre-failure warranty and a load protection guarantee
Superior Battery
Superior BatterySuperior Battery
Superior Battery Management
ManagementManagement
Management
HP UPS HP 3 Phase UPS incorporates Enhanced Battery Management: an exclusive, patented technology that doubles battery service life, optimizes battery recharge time, and provides advance notice of pending battery failure. With Enhanced Battery Management, you have a lower total cost of ownership and receive the best in the industry protection for your critical equipment.
Ease of serviceability
Ease of serviceabilityEase of serviceability
Ease of serviceability through hot-swappable
through hot-swappablethrough hot-swappable
through hot-swappable batteries and electronics
batteries and electronicsbatteries and electronics
batteries and electronics modules.
modules.modules.
modules.
The HP 3 Phase UPSs have a modular design architecture, consisting of separate, hot swappable battery and electronics modules. Further, a built-in intelligent automatic bypass feature ensures continuous power to your connected load even while the modules are being replaced. Ease of maintenance and serviceability
Faster time to repair (MTTR) Automatic and manual bypass Increased flexibility through modular design
Increase battery back-up
Increase battery back-upIncrease battery back-up
Increase battery back-up time with up to four
time with up to fourtime with up to four
time with up to four Extended Runtime
Extended RuntimeExtended Runtime
Extended Runtime Modules
ModulesModules
Modules
HP 3 Phase UPS supports a maximum of four Extended Runtime Modules (ERM), to further increase your battery back-up time, should you have a sudden brief power outage. Each ERM is 3U high and can be automatically detected and configure when attached to the UPS. For more information on battery back up times, please refer to the Back-up Times Chart.
Multiple management
Multiple managementMultiple management
Multiple management options increase flexibility
options increase flexibilityoptions increase flexibility
options increase flexibility
The HP 3 Phase UPS systems can bee fully configured and monitored from the front management LCD. For remote management the HP UPS Management Module is included at no charge and provides additional features such as out of band communications with up to 5 servers and UPS clustering for redundancy.
Remote Emergency Power
Remote Emergency PowerRemote Emergency Power
Remote Emergency Power Off Feature
Off FeatureOff Feature
Off Feature
The HP 3 Phase UPS includes an isolated REPO (Remote Emergency Power Off) port. The REPO feature allows the power to the UPS outlets to be switched off from a remote location. For more information, refer the HP 3 Phase UPS users manual.
QuickSpecs
HP Rackmountable 3 Phase Uninterruptible Power
HP Rackmountable 3 Phase Uninterruptible PowerHP Rackmountable 3 Phase Uninterruptible Power
HP Rackmountable 3 Phase Uninterruptible Power
Systems
SystemsSystems
Systems
Standard Features
DA - 12857 North America — Version 8 — June 20, 2011
Page 2
UPS Management Module
UPS Management ModuleUPS Management Module
UPS Management Module
The HP UPS Management Module enables you to monitor and manage power environments through comprehensive control of HP UPSs. The HP UPS Management Module can support either a single UPS configuration or provides additional power protection with support for dual redundant UPS configuration for no-single-point-of-failure. The additional serial ports will provide greater power management control and flexible monitoring.
The management module can be configured to send alert traps to HP Systems Insight Manager and other SNMP management programs or used as a standalone management system. This flexibility enables you to monitor and manage UPSs through the network. To facilitate day-to-day maintenance tasks, the embedded management software provides detailed system logs.
The HP UPS Management Module provides remote management of a UPS by connecting the UPS directly to the network. Configuration & Management of the UPS from anywhere and at anytime via a standard web browser.
NOTE:
NOTE: NOTE:
NOTE:
For more information on the UPS Management Module please see:
http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/software/module/ups/ index.html
Warranty
WarrantyWarranty
Warranty
Standard three year warranty with first year including parts and labor. HP UPSs are backed by a standard three year limited warranty; 3 year parts, 1 year Labor, 1 year onsite. Optional UPS HP Care Pack and packaged services are also available for purchase. You can choose the precise level of support based on your needs, from basic to business critical. Pre-Failure Battery Warning and its associated Warranty. The Pre-Failure Battery Warning is proactively detected and notified by a LED indicator light, showing that the battery needs to be replaced. This notice is given 30 days prior to the battery failure. This indicator provides ample time to order a spare battery (1-800-HP-INVENT). Avoid storing battery spares as a back up because of short shelf life of the battery. The battery warranty coverage is 3 years for parts. The warranty for the first year of ownership includes parts and labor.
Warranty, standard on all HP Uninterruptible Power System (UPS) units, extends the advantage of a HP three-year limited warranty by applying it to the battery before it actually fails. Specifically, the Pre-Failure Battery Warranty ensures that when customers receive the notification from their HP UPS that the battery may fail, the battery is replaced free of charge under the warranty. HP maintains the highest standards in the industry, as evidenced by the HP Pre-Failure Battery Warranty. In addition, HP UPSs are covered by a $250,000 equipment protection guarantee. Should your connected equipment get damaged due to a UPS failure, then your damaged equipment is covered to up to $250,000.
QuickSpecs
HP Rackmountable 3 Phase Uninterruptible Power
HP Rackmountable 3 Phase Uninterruptible PowerHP Rackmountable 3 Phase Uninterruptible Power
HP Rackmountable 3 Phase Uninterruptible Power
Systems
SystemsSystems
Systems
Standard Features
DA - 12857 North America — Version 8 — June 20, 2011
Page 3
HP Care Pack Services
HP Care Pack ServicesHP Care Pack Services
HP Care Pack Services
HP Care Pack Services include HP branded hardware options qualified for the server, purchased at the same time or afterwards, internal to the enclosure, as well as 22" and smaller external monitors and rack mounted UPS options. HP Uninterruptible Power Systems will be covered at the same service level and coverage period as the server. For servers or storage systems installed within a rack, service also covers all HP qualified rack options installed within the same rack.
NOTE:
NOTE: NOTE:
NOTE:
For more information on HP Care Pack services, contact any of our worldwide sales offices or resellers or visit our worldwide Web site on the internet at:
http://www.hp.com/hps/carepack
NOTE:
NOTE: NOTE:
NOTE:
For more complete information on HP Services offerings, customers and resellers, please visit us at:
http://www.hp.com/hps
NOTE:
NOTE: NOTE:
NOTE:
Additional information regarding worldwide limited warranty and technical support is available at:
http://h18004.www1.hp.com/products/servers/platforms/warranty/index.html
NOTE:
NOTE: NOTE:
NOTE:
The information contained herein is subject to change without notice and is provided "as is" without warranty of any kind. NOTE:
NOTE: NOTE:
NOTE:
The warranties for HP products and services are set forth in the express limited warranty statements accompanying such products and services.
QuickSpecs
HP Rackmountable 3 Phase Uninterruptible Power
HP Rackmountable 3 Phase Uninterruptible PowerHP Rackmountable 3 Phase Uninterruptible Power
HP Rackmountable 3 Phase Uninterruptible Power
Systems
SystemsSystems
Systems
Service and Support
DA - 12857 North America — Version 8 — June 20, 2011
Page 4
Extended Runtime Module
Extended Runtime ModuleExtended Runtime Module
Extended Runtime Module
HP UPS R8000/3 R12000/3 Extended Runtime Module
NOTE:
NOTE: NOTE:
NOTE:
HP 3 PHASE UPS supports a maximum of four Extended Runtime Modules (ERM), to further increase your battery back-up time. Each ERM is 3U high and can be automatically detected and configure when attached to the UPS. For more information on battery back up times, please refer to the Back-up Times Chart.
AF434A
Serial Adapters for UPS
Serial Adapters for UPSSerial Adapters for UPS
Serial Adapters for UPS Management Module
Management ModuleManagement Module
Management Module
HP RJ45-DB89 DCE Female 5 Pack Serial Adapter
NOTE:
NOTE:NOTE:
NOTE:
The serial adapters allow direct (serial) connections to up to 5 servers with the UPS Management Module for out of band communications in the event of a power failure.
AF402A
Rackmount Power
Rackmount PowerRackmount Power
Rackmount Power Distribution Units (PDUs)
Distribution Units (PDUs)Distribution Units (PDUs)
Distribution Units (PDUs) and PDU options
and PDU optionsand PDU options
and PDU options
HP 24A 3PH Modular Power Distribution Unit
AF512A
HP Single Input 3 Phase 24A Monitored Power Distribution Unit
AF504A
HP Dual Input 3 Phase 24A Monitored Power Distribution Unit
AF503A
NOTE:
NOTE: NOTE:
NOTE:
The HP R8000/3 UPS can support one AF512A or AF504A. The HP
R12000/3 UPS can support two AF512A or AF504A or one AF503A.
HP PDU Management Module
NOTE:
NOTE: NOTE:
NOTE:
For more information on the PDU Management Module please see
http://h18004.www1.hp.com/products/servers/proliantstorage/ powerprotection/pdu.html
AF400A
PDU Extension Bars
PDU Extension BarsPDU Extension Bars
PDU Extension Bars
(PDU
options)
HP Two C13 PDU Extension Bars
NOTE:
NOTE:NOTE:
NOTE:
Each extension bar has a C-20 input cord and 7 x C-13 receptacles.
AF500A
HP Fixed Cord Extension Bars
NOTE:
NOTE:NOTE:
NOTE:
Each extension bar has a C-20 input cord and 7 attached 13 inch C-13
power cords for use with 1U servers
351655-B21
NOTE:
NOTE: NOTE:
NOTE:
Extension bars may be used with any HP PDU that has C-19 outlets
HP Power Cables
HP Power CablesHP Power Cables
HP Power Cables
HP IEC320-C14 to C13 10A/4.5ft/1.37m/ 15 PDU Cable
142257-007
HP IEC320-C14 to C13 (10A/4.5ft/1.37m) PDU Cable
142257-006
HP IEC C13-C14 Cable Option Kit
142257-B28
HP 1xC19-C120 16A 2.5m Cable
295633-B22
HP 2m 16A C19-C20 Redundant Jumper Cord
AF574A
HP 1.2m 16A C19-C20 Redundant Jumper Cord
AF575A
HP IEC320-C20 Power Cord
E7798A
NOTE:
NOTE: NOTE:
NOTE:
For more information on HP power cords please go to:
ftp://ftp.compaq.com/pub/products/servers/ProLiantstorage/power-protection/power­cord-option-kits.pdf
HP Care Pack Services
HP Care Pack ServicesHP Care Pack Services
HP Care Pack Services
HP Install Universal Power Supply 6KVA or Greater Service
U4696E
QuickSpecs
HP Rackmountable 3 Phase Uninterruptible Power
HP Rackmountable 3 Phase Uninterruptible PowerHP Rackmountable 3 Phase Uninterruptible Power
HP Rackmountable 3 Phase Uninterruptible Power
Systems
SystemsSystems
Systems
Related Options
DA - 12857 North America — Version 8 — June 20, 2011
Page 5
R8000/3
R8000/3R8000/3
R8000/3
R12000/3
R12000/3R12000/3
R12000/3
Electrical Output
Electrical OutputElectrical Output
Electrical Output
Power Output
Power OutputPower Output
Power Output
8kVA/8KW @ 208v 3F Delta
12kVA/12KW @ 208v 3F Delta
Nominal output frequency
Nominal output frequencyNominal output frequency
Nominal output frequency
50-60 Hz auto-detection (Normal mode) 50 or 60 Hz (Battery mode)
Output Frequency
Output FrequencyOutput Frequency
Output Frequency Variation
VariationVariation
Variation
Synchronized (Normal mode) ±0.1 when not synchronized with source (Battery mode)
Output overload
Output overloadOutput overload
Output overload
100–110%: load transfers to Bypass mode after 10 minutes 110–125%: load transfers to Bypass mode after 1 minute 125–150%: load transfers to Bypass mode after 5 seconds >150%: load transfers to Bypass mode after 300 ms
Voltage wave form
Voltage wave formVoltage wave form
Voltage wave form
Sine wave; 2% THD with typical PFC load
Surge suppression
Surge suppressionSurge suppression
Surge suppression
High-energy 6500 A peak
Noise filtering
Noise filteringNoise filtering
Noise filtering
MOVs and line filter
Output Connections
Output ConnectionsOutput Connections
Output Connections
One NEMA L15-30R
Two NEMA L15-30R
Electrical Input
Electrical InputElectrical Input
Electrical Input
Voltage Range
Voltage RangeVoltage Range
Voltage Range
200-240 v 3F Wye
208v 3F Wye
Nominal voltage
Nominal voltageNominal voltage
Nominal voltage
208v 3F Wye 208v 3F Wye
Nominal frequency
Nominal frequencyNominal frequency
Nominal frequency
50/60 Hz 50/60 Hz
Frequency range
Frequency rangeFrequency range
Frequency range
45-65 Hz 45-65 Hz
Rated input current
Rated input currentRated input current
Rated input current Maximum input current at
Maximum input current atMaximum input current at
Maximum input current at nominal voltage
nominal voltagenominal voltage
nominal voltage Efficiency
EfficiencyEfficiency
Efficiency
97% @ 40-100% load 97% @ 40-100% load
Input connector
Input connectorInput connector
Input connector
NEMA L21-30 (30A)
IEC309 560P9 (60A)
Operating Temperature
Operating TemperatureOperating Temperature
Operating Temperature Operating Temperature
Operating TemperatureOperating Temperature
Operating Temperature
50° F to 104° F (10° C to 40° C)
Optimal battery
Optimal batteryOptimal battery
Optimal battery performance
performanceperformance
performance
41° F to 77° F (5° C to 25° C)
Non-operating
Non-operatingNon-operating
Non-operating Temperature
TemperatureTemperature
Temperature
-13°F to 131°F (-25°C to 55°C)
Relative Humidity
Relative HumidityRelative Humidity
Relative Humidity
Operating
OperatingOperating
Operating
5% to 95% non-condensing
Operating Altitude
Operating AltitudeOperating Altitude
Operating Altitude
Up to 3300 ft (1,000 meters) above sea level; up to 6600 ft (2,000 meters) with 1% derating per +330 ft (100 meters)
Transit Altitude
Transit AltitudeTransit Altitude
Transit Altitude
Up to 49,212 ft (15,000 meters) above sea level
Heat Dissipation
Heat DissipationHeat Dissipation
Heat Dissipation
1266 BTU/hr maximum at 100% rated load (High Efficiency mode)
Audible Noise
Audible NoiseAudible Noise
Audible Noise
Less than 50 dBA at 1 meter (Normal mode) Less than 55 dBA at 1 meter (Battery mode)
Leakage Current
Leakage CurrentLeakage Current
Leakage Current
< 3.5 mA
Surge suppression
Surge suppressionSurge suppression
Surge suppression
ANSI C62.41 Category B3
Safety Conformance
Safety ConformanceSafety Conformance
Safety Conformance
UL 1778 4th edition; CSA C22.2, No. 107.3
UL 1778 4th edition; CSA C22.2, No. 107.3
EMC
EMCEMC
EMC
(Class A)
FCC Part 15
FCC Part
Unit Dimensions
Unit DimensionsUnit Dimensions
Unit Dimensions
(WxDxH)
14.4 x 26 x 10.3 in (441 x 660 x 261 mm) 6U
QuickSpecs
HP Rackmountable 3 Phase Uninterruptible Power
HP Rackmountable 3 Phase Uninterruptible PowerHP Rackmountable 3 Phase Uninterruptible Power
HP Rackmountable 3 Phase Uninterruptible Power
Systems
SystemsSystems
Systems
Technical Specifications
DA - 12857 North America — Version 8 — June 20, 2011
Page 6
Shipping Dimensions
Shipping DimensionsShipping Dimensions
Shipping Dimensions (WxDxH)
25 x 38 x 46 in (635 x 965 x 1169 mm)
Unit Weight
Unit WeightUnit Weight
Unit Weight
Without batteries
Without batteriesWithout batteries
Without batteries
135 lb (61 kg)
With batteries installed
With batteries installedWith batteries installed
With batteries installed
307 lb (140 kg)
Shipping Weight
Shipping WeightShipping Weight
Shipping Weight
400 lbs (182 kg)
Extended Runtime Module
Extended Runtime ModuleExtended Runtime Module
Extended Runtime Module (ERM)
Unit Dimensions
Unit Dimensions Unit Dimensions
Unit Dimensions
(WxDxH)
17.2 x 26 x 5.2 in (438 x 660 x 131 mm) 3U
Shipping Dimensions
Shipping DimensionsShipping Dimensions
Shipping Dimensions (WxDxH)
47.25 x 31.5 x 37 in (1207 x 800 x 940 mm)
Unit Weight
Unit WeightUnit Weight
Unit Weight
170 lbs (77 kg)
Shipping Weight
Shipping WeightShipping Weight
Shipping Weight
185 lb (84 kg)
Estimated Backup Times Chart (Minutes) R8000/3
Estimated Backup Times Chart (Minutes) R8000/3Estimated Backup Times Chart (Minutes) R8000/3
Estimated Backup Times Chart (Minutes) R8000/3
Load %
Load %Load %
Load %
With Internal Battery
With Internal BatteryWith Internal Battery
With Internal Battery
With 1 ERM
With 1 ERMWith 1 ERM
With 1 ERM
With 2 ERMs
With 2 ERMsWith 2 ERMs
With 2 ERMs With 3 ERMs
With 3 ERMsWith 3 ERMs
With 3 ERMs With 4 ERMs
With 4 ERMsWith 4 ERMs
With 4 ERMs
20%
55
118 183 253 329
50%
23 46 69 94
120
80%
12 27 41 55 70
100%
9
21 32 43 54
Estimated Backup Times Chart (Minutes) R12000/3
Estimated Backup Times Chart (Minutes) R12000/3Estimated Backup Times Chart (Minutes) R12000/3
Estimated Backup Times Chart (Minutes) R12000/3
20%
37 78
119 163 211
50%
13 30 44 59 76
80%
6
17 26 34 44
100%
5
12 20 27 34
NOTE:
NOTE: NOTE:
NOTE:
Backup times are estimated for typical applications. Actual performance will depend on load and battery conditions.
Environment-friendly
Environment-friendlyEnvironment-friendly
Environment-friendly Products and Approach
Products and ApproachProducts and Approach
Products and Approach
End-of-life Management
End-of-life ManagementEnd-of-life Management
End-of-life Management and Recycling
and Recyclingand Recycling
and Recycling
Hewlett-Packard offers end-of-life HP product return, trade-in, and recycling programs in many geographic areas. For trade-in information, please go to
http://www.hp.com/go/green
. To recycle your product, please go to:
http://www.hp.com/go/green
or contact your nearest HP sales office. Products returned to HP will be recycled, recovered or disposed of in a responsible manner.
The EU WEEE directive (2002/95/EC) requires manufacturers to provide treatment information for each product type for use by treatment facilities. This information (product disassembly instructions) is posted on the Hewlett Packard web site at:
http://www.hp.com/go/green
. These instructions may be used by recyclers and other WEEE treatment facilities as well as HP OEM customers who integrate and re-sell HP equipment.
© Copyright 2011 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice.
The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.
QuickSpecs
HP Rackmountable 3 Phase Uninterruptible Power
HP Rackmountable 3 Phase Uninterruptible PowerHP Rackmountable 3 Phase Uninterruptible Power
HP Rackmountable 3 Phase Uninterruptible Power
Systems
SystemsSystems
Systems
Technical Specifications
DA - 12857 North America — Version 8 — June 20, 2011
Page 7
Loading...